Professional Documents
Culture Documents
Multiphase A.C. Emfs (Produced by Multiple Windings)
Multiphase A.C. Emfs (Produced by Multiple Windings)
Circuits
8.1 Single–Phase A.C. Generators: the principles 8.2 Three–Phase Balanced A.C. Generators
A single–phase alternating sinusoidal voltage can be A three–phase supply uses the same principle as the
generated by rotating with constant angular velocity single–phase, where three coils angularly displaced
ω a single winding aa′ in a constant magnetic field B. between each other around the same axis of rotation
are used, instead of one coil.
As aa ′ rotates anticlockwise in the magnetic field B its
sides a and a ′ cut the magnetic flux and emf is Each coil is called phase winding. The three phases
induced in them by motional induction. The induced are usually given the names
emf at both sides of the winding at time t is
• red phase (R–phase), or A–phase
eaa′ (t ) = 2 Blvh = 2 Blrω sinϑ = 2 Blrω sinωt (8.1) • yellow phase (Y–phase), or B–phase and
• blue phase (B–phase), or C–phase
the motion referred from the horizontal position at
time t = 0 . A balanced or symmetrical three–phase supply
consists of three identical coils displaced by 120° in
space from each other. Therefore, a balanced or
v = ω ×r symmetrical three–phase supply has sinusoidal
ω winding alternating phase voltages (or currents), which are
N vh
B r
i(t ) l ϑ • equal in magnitude and
B ω
• displaced in time from one another by a phase of
a′ e a 120° .
aa ′ −v h
S
−v It is assumed that the load at each phase is also
balanced (see later), or well buffered.
Cross section perpendicular
to the axis of rotation If either of the above conditions do not apply, the
supply is said to be imbalanced.
An elementary three–phase, two–pole generator is The voltage signals from a balanced emf generator
shown bellow. are given by
• It has three identical stator coils ( aa′, bb′, and cc′ ), eaa′ = V ph sin(ωt )
U|
of one or more turns, displaced by 120° in space ||
|
from each other and ebb = V ph sin(ωt −120° )|V (8.2)
′ ||
• The rotor carries a field winding excited by the |
d.c. supply through brushes and slip rings and is ecc′ = V ph sin(ωt − 240° )|
|W
driven at an angular velocity ω in such a way that
the flux is distributed sinusoidally over the poles.
Using the spatial geometry of the coils in the
Here the phase windings are static within a rotating armature, the phasor diagram in polar form of the
magnetic field, but the principle of induction is the above signals is the following
same as in the single–phase generator.
a
A–Phase
Field Armature Eaa′
winding a or 120°
stator a′ b′
Ecc′ c′ Ebb
c′ ′
b′
b
c
N S
120°
Armature Note that
Field system c Rotation b Coil sides
or Eaa′ + Ebb + Ecc′ = 0 or eaa′ (t ) + ebb (t ) + ecc′ (t ) = 0 (8.3)
rotor ′ ′
a′
8.2.1 Winding Connections for A.C. Balanced Voltage phasor diagram in the WYE connection
Generators
IL
The phase windings may be connected in either wye A
I ph
or delta connections.
ean V ph
Balanced WYE Supply Connection V L− L , or V L
A wye or star connection (represented as Y) results n
ecn N
by connecting together all three primed or unprimed
terminals to form a common terminal known as the ebn
B
neutral of the wye. If a neutral conductor is used, the C
system is known as
• a four–wire, three–phase system, otherwise it is A
• a three–wire, three–phase system.
IL
A I L = I ph
I ph VCA V AN V (8.4)
AB
a V L = 3V ph
N
V ph VBN
V L− L VCN
a′
n C B
c′ N VBC
b′
c
b B VL
C VBC = V L∠0° V AN = V ph∠90°= ∠90°
3
V
where V AB = V L∠120° VBN = V ph∠− 30°= L ∠− 30° (8.5)
− ph stands for phase quantities, and 3
V
− L, and L-L stands for line, and line-to-line VCA = V L∠240° VCN = V ph∠−150°= L ∠−150°
3
quantities respectively.
Dr. E. Milonidis 8-7 EE1.15 Dr. E. Milonidis 8-8 EE1.15
Three – Phase A.C. Circuits Three – Phase A.C. Circuits
IB
Example 8.1
V AB = VBC = VCA = V L− L = 3V ph
(8.8)
I A = I B = IC = I L = I ph
I N = I A + I B + IC = 0
I AB = I BC = ICA = I L = I ph (8.9)
I A = I B = IC = I L = 3I ph
Z AB ZCA Z AZB + ZB ZC + ZC Z A
ZA = Z AB =
Z AB + ZBC + ZCA ZC
Z AB ZBC Z AZB + ZB ZC + ZC Z A
ZB = ZBC =
Z AB + ZBC + ZCA ZA
ZCAZBC Z Z +Z Z +Z Z IL
ZC = ZCA = A B B C C A
Z AB + ZBC + ZCA ZB
(8.10) V L− N ∠0° Z∆−Y
where
S = P + jQ (8.15)
V ph is the phase voltage
I ph is the phase current
The total apparent power (in VAs) is then
cosϕ is the load power factor
ϕ is the phase difference between V ph and I ph
(positive for leading V ph ). S = S = P2 + Q2 = 3V ph I ph = 3V L I L (8.16)
P = 3V L I L cosϕ (8.13)
Example 8.2 IA
A
A balanced 433 V, wye–connected, three–phase,
four–wire supply is connected to the following four–
ean V AN ZA
wire, wye–connected load:
N IN
• A–phase: a 10 Ω resistor ecn
• B–phase: an 8 Ω resistor in series with a 2 Ω VBN
ZB ZC
inductive reactance ebn IB
• C–phase: a 4 Ω resistor in series with a 5 Ω B VCN
capacitive reactance. IC
C
Determine the current in each phase of the load and
in the neutral wire.
Z A = 10 Ω , So I A = V AN / Z A = 250∠0° = 25∠0° A
10∠0°
Solution
ZB = 8 + 2 j = 825
. ∠14° Ω , So
Conventionally, it is assumed that 433 V is the rms I B = VBN / ZB = 250∠−120° = 303
. ∠−134° A
. ∠14°
825
value of the line – to – line voltage of the supply
system. Therefore, the magnitude of the phase
ZC = 4 − 5 j = 64
. ∠− 513
. ° Ω , So
voltage is
V ph = V L / 3 = 433 / 3 = 250 V IC = VCN / ZC = 250∠− 240° = 391 . ∠−1887
.°A
. ∠− 513
64 .°
Example 8.3
A three–phase, 440 V a.c. motor provides a full–load (3) Since the power factor is 0.8, then
mechanical output of 10 kW when its power factor is
0.8 (lagging) and its efficiency is 90 per cent. ϕ = cos−1(08
. ) = 3687
. ° lagging. So
Calculate at full load
Apparent power:
(1) the power consumed by the motor,
(2) its line current, and S = 3V L I L = 3 × 440 ×1822
. = 139
. kVA
(3) the apparent and reactive power consumed.
Reactive power:
Solution S = 3V L I L sinϕ = 3 × 440 ×1822
. × sin(3687
. ° ) = 833
. kVAR
(1) The input power to the motor is