Professional Documents
Culture Documents
This part of the course covers application of Ohm’s Law and Kirchhoff’s Laws in in analyzing
relationships between currents and voltages, calculation of electric power and phasor analysis for a
balanced three-phase system.
Learning Outcomes:
Analyze and apply Ohm’s Law to determine currents and voltages, relationships
between voltages and currents, and calculate electric power in a three-phase balanced
wye (Y) connected system.
Analyze and apply Ohm’s Law to determine currents and voltages, relationships
between voltages and currents, and calculate electric power in a three-phase balanced
delta (∆) connected system.
Pre-Test:
Instructions: Answer the each question/problem quietly and encircle the letter of the correct answer.
3. A (n) _______ stores and returns energy to a circuit while a(n) ________ dissipates energy.
(a) resistance, impedance (b) resistor, inductor
(c) inductor, resistor (d) inductor, reactance
4. For an RL circuit, the power factor cannot be less than ______ or greater than
_______.
(a) 1, 0 (b) 0, -1 (c) 0, 1 (d) -1, 0
5. The advantage of using static capacitor to improve the power factor is because they
(a) are not variable
(b) are almost loss free
(c) provide continuous charge of power factor
(d) none of these
6. The advantage of the star-connections over the delta connections for the same phase
voltage is that it gives
(a) step-down current (b) extra step-up voltage
(c) extra step-up current (d) extra step-up power
7. The inductance is responsible for the current to _____ the applied voltage.
(a) lag (b) be in phase with (c) lead (d) be opposite
power. C C’
(a) 13.86 A & 1,536 Watts (b) 13.86 Amp. & 4,608 Watts
(c) 24.0 Amp. & 4,608 Watts (d) 24.0 Amp. & 1,536 Watts
(a) 13.31 A & 1,772 Watts (b) 13.31 Amp. & 5,318 Watts
(c) 23.05 Amp. & 1,772 Watts (d) 23.05 Amp. & 5,318 Watts
10. In the circuit shown, the
magnitude of the voltages VL = A’
120 Volts and the load A ZL=24+j0 Ω
impedance ZL = 24+j0.Ω. If VAB ZL=24+j0 Ω
is taken as reference and the
C B’ C’
phase sequence is CBA. B ZL=24+j0 Ω
Determine line currents and
power.
(a) 8.66 Amp. & 1,800 Watts (b) 8.66 Amp. & 600 Watts
(c) 5.0 Amp. & 1,800 Watts (d) 5.0 Amp. & 600 Watts
CONTENT
THREE-PHASE SYSTEM
V (Volts)
ea ec
Em
t (seconds)
f (Hertz)
1200 1200
2400
Figure 7.1.1 Three phase voltage waves of a three-phase system. The three phase voltages (emf
waves) ea, eb and ec respectively are out-of-phase by 120 degrees.
Ec Eb
1200 1200
Ea (Reference) Ea (Reference)
0 0
120 120
Eb Ec
(a) abc, bca, cab - Sequence (b) cba, bac, acb - Sequence
123, 231, 312 321, 213, 132
Figure 7.1.2 The three phase effective voltages Ea, Eb and Ec of a three-phase system. The three phase
effective voltages Ea, Eb and Ec respectively are out-of-phase by 120 degrees. With Ea
taken as reference, equivalent phasor diagrams are shown below: (a) abc sequence; (b)
cba sequence.
a
Phase Voltages (VФ): Line Voltages (VL):
Vb Van Vab
Vbn Vbc
Va
Vcn Vca
n b
Vc Van Vbn Vcn V Vab Vbc Vca VL
Figure 7.1.3 Balanced Wye (Y) – Connected Source with terminals a, b and c, and common junction n
(Neutral).
Applying KVL in the circuit of Figure 2.3 to find the line voltages in terms of phase voltages
Vab Van Vnb Van Vbn Eq. 7.1
Applying the principle of double subscript notations for AC circuits: To omit the negative sign, we
simply interchanged the subscripts, or
Vnb Vbn Vnb
Equation 7.1 through Equation 7.3 show that line voltage is equal to the phasor sum of two phase
voltages. These are illustrated in the phasor diagrams in Figure 7.4: (a) for abc-sequence; (b) for cba-
sequence.
Vca Vbc
Vcn
30 0 Vbn Van
300
Vab (Reference) Vab (Reference)
300
300
300
Vbn Van 300
Vcn
Vbc Vca
(a) abc, bca, cab - Sequence (b) cba, bac, acb - Sequence
123, 231, 312 321, 213, 132
abc – sequence: phase voltage lags 300 with corresponding line voltage
cba – sequence: phase voltage leads 300 with corresponding line voltage
Figure 7.1.4 Relationships between line voltages and phase voltages of a balanced wye (Y)-connected source.
With Vab taken as reference, equivalent phasor diagrams: (a) abc sequence; (b) cba sequence.
Figure 7.1.5 Magnitude of line voltage in terms of phase voltages for balanced wye (Y) – connected
source
Balanced Wye (Y) – Connected Source with Balanced Wye (Y) – Connected Load: Three-Phase
Three-Wire System
Iaa’
Wye (Y) System:
a b b’ Ib’n’ a’
Inb ZL Voltage:
Ina Ibb’ n’ Ia’n’ VL 3 V
ZL
n
Inc Ic’n’ Current: By Ohm’s Law
ZL
Icc’ V
c c’ I I L
ZL
Figure 7.1.6 Balanced wye (Y) – connected source with balanced wye (Y) – connected load.
Voltages:
Phase Voltages (VФ): Source Side = Phase Voltages (VФ): Load Side
Van Vbn Vcn V = Va 'n ' Vb 'n ' Vc 'n ' V
Line Voltages (VL): Source Side = Line Voltages (VL): Load Side
Vab Vbc Vca VL = Va 'b ' Vb 'c ' Vc 'a ' VL
Currents:
Phase Currents (IФ): Source Side = Line Currents (IL): = Phase Currents (IФ): Load Side
I na I aa' I a 'n' I I L
I nb Ibb' Ib'n' I I L
I nc I cc' I c 'n' I I L
3 V I Cos 3 VL I L Cos
S Cos Watts
Total Reactive Power : Q 3 I X
2
3 V I Sin 3 VL I L Sin
S Sin VARs
Illustrative Problem 7.1
In the circuit shown, the magnitude
of the voltages VL = 240 Volts and A B B’ ZL=10/36.870Ω A’
the load impedance ZL = ZL=10/36.870Ω
10/36.870Ω. If VAB is taken as N’
N
reference and the phase sequence
is ABC. Determine (a) line ZL=10/36.870Ω
Phasor diagram - ABC sequence (From Figure 7.4a), showing voltages with VAB taken as reference
VCA = VC’A’ Line Voltages (VL): From Phasor Diagram
V AB V A'B ' 240 / 0 V
0
VBC = VB’C’
Required:
(a) line currents:
Line Currents (IL) = Phase currents (IФ):
I I L ; By Ohm’s Law
138 .564 / 30
o
V A' N '
I AA' I A' N ' 13.856 / 66.87 A
o
I NA o
ZL 10 / 36.87
138 .564 / 150
o
VB ' N '
I BB' I B ' N ' 13.856 / 173 .13 A
o
I NB o
ZL 10 / 36.87
o
VC ' N ' 138 .564 / 90
I CC ' I C ' N ' 13.856 / 53.13 A
o
I NC o
ZL 10 / 36.87
(b) power
Power per Phase:
True Power per phase : 2
P I R V I Cos Watts
P 13.856 8 138 .56 13.856 0.80
2
1,919.887 / 36.87 VA
0
5,759.66 / 36.87 VA
0
or
3 V I Cos 3 V L I L Cos
3 138 .56 13.856 0.80 3 240 13.856 0.80
4,607 .73 Watts
or
S Cos 5,759 .66 0.80 4,607 .73 Watts
or
3 V I Sin 3 V L I L Sin
3 138 .56 13.856 0.7071 3 240 13.856 0.7071
3,455 .80 VARs Inductive
or
S Sin 5,759 .83 0.7071 3,455 .80 VARs Inductive
(c) Phasor Diagram:
Phasor diagram - ABC sequence (From Figure 7.4a) with currents indicated as shown.
INB = IBB’ = IB’N’
VCA = VC’A’
VBC = VB’C’
Solution:
Given Data:
V L V A' B ' V B 'C ' VC ' A' 440 Volts IAA’
V V A' N ' VB ' N ' VC ' N '
A B B’ IB’N’ A’
VL INB ZL
254.03 Volts IBB’
3 INA ZL N’ IA’N’
12 / 25.84 10.80 j 5.23 N
0
ZL
INC IC’N’
Load is capacitive, so p.f is Leading: ZL
ϴ = 25.840 ICC’
= Power Factor angle C C’
= Angle between phase voltage and phase current
Cos ϴ = Power Factor = 0.90 Leading Balanced wye (Y) – connected source with balanced
wye (Y) – connected load.
Sin ϴ = Reactive Factor = 0.436
Phasor diagram - CBA sequence (From Figure 7.4b), showing voltages with VAB taken as reference
VBC = VB’C’ Line Voltages (VL): From Phasor Diagram
V AB V A'B' 440 / 0 V
0
VCA = VC’A’
Required:
(a) line currents:
Line Currents (IL) = Phase currents (IФ):
I I L
o
V A' N ' 254 .03 / 30
I A' N ' 21.17 / 55.84 A
o
I NA I AA'
12 / 25.84
o
ZL
o
VB 'N ' 254 .03 / 150
I B'N ' 21.17 / 175 .84 A
o
I NB I BB'
12 / 25.84
o
ZL
254 .03 / 90
o
VC ' N '
I C 'N ' 21.17 / 64.16 A
o
I NC I CC '
12 / 25.84
o
ZL
(b) power
Power per Phase:
True Power per phase : 2
P I R V I Cos Watts
P 21.17 10.8 254 .0321.17 0.90
2
5,377.82 / 25.84 VA
0
16,133.71 / 25.84 VA
0
or
3 V I Cos 3 V L I L Cos
3 254 .0321.17 0.90 3 440 21.17 0.80
14,520 .67 Watts
or
S Cos 16,133 .71 0.90 14,520 .67 Watts
or
3 V I Sin 3 V L I L Sin
3 254 .0321.17 0.436 3 440 21.17 0.436
7,031 .77 VARs Capacitive
or
S Sin 14,520 .67 0.436 7,031 .77 VARs Capacitive
(c) Phasor Diagram:
Phasor diagram - CBA sequence (From Figure 7.4b) with currents indicated as shown.
INA = IAA’ = IA’N’
VBC = VB’C’
ϴ = 25.840
= Power Factor angle
= Angle between phase voltage and phase current
VBN = VB’N’ Note: Phase current leads phase voltage by an angle ϴ = 25.840
25.840= VAN = VA’N’
INB = IBB’ = IB’N’ 300 ϴ
25.840 = ϴ (Reference)
300
VAB = VA’B’
300
ϴ = 25.840
VCN = VC’N’
VCA = VC’A’
I. Direction Analyze and identify data given on the following problems and employ related
equations to determine the corresponding required data for each problem.
a’
Phase Voltages (VФ): Line Voltages (VL):
a Vab Va’b’
Vca
Vab Vbc = Vb’c’
b’ Vca Vc’a’
c
Vbc
b Vab Vbc Vca V = Va 'b ' Vb 'c ' Vc 'a ' VL
c’
VL V
Figure 7.2.1 Balanced Delta (∆) – Connected Source with terminals a, b and c on the supply side, and
line terminals a’, b’ and c’ respectively.
Applying KVL in the circuit of Figure 7.2.1 to find the line voltages in terms of phase voltages
Vab Va 'b' Eq. 7.4
Equation 7.4 through Equation 7.6 show that line voltage is equal to the phase voltage. These are
illustrated in the phasor diagrams in Figure 7.2.2: (a) for abc-sequence; (b) for cba-sequence.
Vca = Vc’a’
(a) abc, bca, cab - Sequence (b) cba, bac, acb - Sequence
123, 231, 312 321, 213, 132
Figure 7.2.2 Relationships between line voltages and phase voltages of a balanced delta (∆)-connected
source. With Vab taken as reference, equivalent phasor diagrams (a) abc sequence; (b) cba sequence.
Balanced Delta (∆) – Connected Source with Balanced Delta (∆) – Connected Load:
Iaa’
Figure 7.2.3 Balanced delta (∆) – connected source with balanced delta (∆) – connected load.
Voltages:
VФ = VL: Source Side = VФ = VL: Load Side
I aa' I ba I ac I ba I ca
I bb' I cb I ba I cb I ab
I cc' I ac I cb I ac I bc
3 V I Cos 3 VL I L Cos
S Cos Watts
Total Reactive Power : Q 3 I X
2
3 V I Sin 3 VL I L Sin
S Sin VARs
Illustrative Problem 7.3:
In the circuit shown, the
magnitude of the voltages VL = A’
240 Volts and the load A ZL=18.03/-56.310 Ω
impedance ZL = 18.03/- ZL=18.03/-56.310 Ω
56.31 .Ω. If VAB is taken as
0
C B’ C’
reference and the phase B ZL=18.03/-56.310 Ω
sequence is ABC. Determine
(a) line currents; (b) power; (c)
draw phasor diagram; (d) phase currents from the supply mains.
Solution:
Given Data:
Load Side:
VL V V A'B ' VB 'C ' VC ' A' 240 Volts
Z L 18.03 / 56.31 10 j 15
0
IAA’
Load is capacitive, so p.f is Leading:
ϴ = 56.310 A’
= Power Factor angle A IA’B’ IC’A’
= Angle between phase voltage and IAC IBA IBB’ ZL
phase current ZL ZL
Cos ϴ = Power Factor B B’ C’
= 0.555 Leading ICB ICC’ IB’C’
Sin ϴ = Reactive Factor = 0.832 C
Phasor diagram - ABC sequence (From Figure 7.2.2a), showing voltages with VAB taken as reference
VCA = VC’A’
1200
(Reference)
VAB = VA’B’
1200
Line Voltages (VL) =Phase Voltage (VФ): From Phasor Diagram
V AB V A'B ' 240 / 0 V
0
VBC = VB’C’
VCA VC ' A'' 240 / 120 V
0
Required:
(a) line currents: (Considering Load Side)
By Ohm’s Law
Phase currents:
o
V A' B ' 240 / 0
I A' B ' 13.31 / 56.31 A
o
18.03 / 56.31
o
ZL
240 / 120
o
VB 'C '
I B 'C ' 13.31 / 63.69 A
o
18.03 / 56.31
o
ZL
o
VC ' A ' 240 / 120
I C ' A' 13.31 / 176 .31 A
o
18.03 / 56.31
o
ZL
Note: The three phase currents are equal in magnitude and exactly out-of phase by 1200.
By KCL:
Line currents:
I AA' I A'B ' I C ' A' 13.31 / 56.31 13.31 / 176 .31 23.05 / 26.31 A
o o o
I BB' I B 'C ' I A'B ' 13.31 / 63.69 13.31 / 56.31 23.05 / 93.69 A
o o o
I CC ' I C ' A' I B 'C ' 13.31 / 176 .31 13.31 / 63.69 23.05 / 146 .31 A
o o o
IL 3 I 3 13.31 23.05 A
Note: The three line currents are equal in magnitude and exactly out-of phase by 1200.
Magnitude of each line current is equal to square-root of 3 times the magnitude of
phase-current.
(b) power
Power per Phase:
True Power per phase : 2
P I R V I Cos Watts
P 13.31 10 240 13.310.555
2
1,772 Watts
Reactive Power per phase : 2
Q I X V I Sin VARs
Q 13.31 15 240 13.310.832
2
3,195 / 36.87 VA
0
9,583 / 56.31 VA
0
or
3 V I Cos 3 V L I L Cos
3 240 13.310.555 3 240 23.050.555
5,318 Watts
or
S Cos 9,583 0.80 5,318 Watts
Total Reactive Power X 3 13.31 15 7,973 VARs Capacitive
2
: Q 3 I
2
or
3 V I Sin 3 V L I L Sin
3 240 13.310.832 3 240 13.310.832
7,973 VARs Capacitive
or
S Sin 9,583 0.832 7,973 VARs Capacitive
ϴ = 56.310 ϴ = 56.310
300
IC’A’’ 300 (Reference)
VAB = VA’B’
300
ϴ = 56.310
ϴ = 56.310
IB’C’ = Power Factor angle
= Angle between phase voltage and phase current
I CC ' I AC I BC
I ? I AA' I BA I CA
I ? 300
300 ϴ = 56.310
(Reference)
VAB = VA’B’
300
I ?
I BB' I CB I AB
Based on the preceding phasor diagram, we can now write/indicate the phase currents from the source
in the phasor diagram that corresponds to the component currents of the line currents.
I CC ' I AC I BC
300
ICB = IB’C’
I BB' I CB I AB
Phasor diagram - CBA sequence (From Figure 7.2.2b), showing voltages with VAB taken as reference
VBC = VB’C’
1200
(Reference)
VAB = VA’B’
1200
Line Voltages (VL) =Phase Voltage (VФ): From Phasor Diagram
VAB VA'B ' 120 / 0 V
0
Required:
(a) line currents: (Considering Load Side)
By Ohm’s Law
Phase currents:
o
V A'B ' 120 / 0
I A'B ' 5/ 0 A
o
o
ZL 24 / 0
o
VB 'C ' 120 / 120
I B 'C ' 5 / 120 A
o
o
ZL 24 / 0
120 / 120
o
VC ' A'
I C ' A' 5 / 120 A
o
o
ZL 24 / 0
Note: The three phase currents are equal in magnitude and exactly out-of phase by 1200.
By KCL:
Line currents:
I AA' I A'B ' I C ' A' 5 / 0 5 / 120 8.66 / 30 A
o o o
IL 3 I 3 5 8.66 A
Note: The three line currents are equal in magnitude and exactly out-of phase by 1200.
Magnitude of each line current is equal to square-root of 3 times the magnitude of
phase-current.
(b) power
Power per Phase:
True Power per phase : 2
P I R V I Cos Watts
P 5 24 120 51
2
600 Watts
600 / 0 VA
0
1,800 / 0 VA
0
or
3 V I Cos 3 VL I L Cos
3 120 51 3 120 8.66 1
1,800 Watts
or
S Cos 1,800 1 1,800 Watts
Total Reactive Power Q 3 I X 3 5 0 0 VARs
2
: 2
or
3 V I Sin 3 VL I L Sin
3 120 50.0 3 120 8.66 0.0
0 VARs
or
S Sin 1,800 0.0 0 VARs
I BB' I B 'C ' I A'B ' I AA' I A'B ' I C ' A'
IB’C’ ϴ=0 0
300
1200
300 IA’B’ (Reference)
ϴ=0 0 VAB = VA’B’
1200
ϴ = 00
IC’A’’ 300
ϴ = 00
= Power Factor angle
= Angle between phase voltage and phase current
Note: Phase current and phase voltage are in phase (angle
VCA = VC’A’ ϴ = 00)
I CC ' I C ' A' I B 'C '
Learning Activity 7.2 Self-Assessment:
Balanced Three-Phase Delta (∆) – Connected System
I. Direction Analyze and identify data given on the following problems and employ related
equations to determine the corresponding required data for each of the problems.
Pre-Test
1. a 6. b
2. b 7. a
3. c 8. b
4. c 9. d
5. b 10. a
P 14.52 kW
Q 7.03 kVARs Capacitive
P 4.608 kW
Q 3.456 kVARs Inductive
I AA' 34.641 / 60 A
o
I CC ' 34.641 / 60 A
o
P 22.863 kW
Q 13.2 kVARs Capactive
TO BE CONTINUED
7.3
&
7.4