7 K-Factor Harmonic Transformers

K-Factor Harmonic Transformers

In today’s industrial workplace, the proliferation of solid


state devices (lighting ballasts, motor drives and controls,
communications equipment, and other DC-powered loads)
has created a major problem for specifying engineers,
contractors and building owners. The non-linear nature of
their switch mode power supplies generate harmonic
currents that cause transformers and system neutrals
to overheat and destroy themselves.

K-Factor transformers are designed to reduce the heating


effects of harmonic currents created by loads like those
shown in Chart A. The K-Factor rating is an index of the
transformer’s ability to withstand harmonic content while
operating within the temperature limits of its insulating
system. Sola/Hevi-Duty K-Factor transformers have
UL ratings of K-4, K-13 and K-20.
Listed Certified
The Sola/Hevi-Duty K-Factor design is a specialized
transformer that offers these benefits:
• Conductors capable of carrying the harmonic currents Accessories and Optional Design Styles
of non-linear loads without exceeding the temperature • Wall mounting brackets (through 45 KVA only).
rating of the insulation system. Paralleled conductors • Weather Shields (UL-3R).
are used to reduce and control skin effect losses.
• Stainless Steel Enclosures.
• A transformer design that takes into account the • Totally enclosed non-ventilated designs.
increase in naturally occurring “stray” losses caused • Low temperature rise units available.
by non-linear loads. These losses cause standard • Open core and coil designs.
transformers to dramatically overheat and substan-
tially shorten design life. The K-Factor is designed to • Copper Wound designs.
function within safe operating temperatures.

• A core and coil design that manages the DC flux Chart A: Typical Load K-Factors
caused by triplen harmonics*. As these harmonics
Load K-Factor
increase, they cause additional current to circulate in
Electric discharge lighting ............................................................ K-4
the delta winding. This produces a DC flux in the core UPS with optional input filtering .................................................. K-4
which leads to core saturation, voltage instability and Welders ........................................................................................ K-4
overheating. Induction heating equipment ....................................................... K-4
PLCs and solid state controls
(other than variable speed drives) .............................................. K-4
• K-Factor transformers are UL 1561 listed. Telecommunications equipment (e.g.. PBX) ............................ K-13
UPS without input filtering ......................................................... K-13
• Designed to supply non-linear loads without Multiwire receptacle circuits in general care
overheating the windings or saturating the core. areas of health care facilities and classrooms
of schools, etc. ........................................................................... K-13
Multiwire receptacle circuits supplying
• All Sola/Hevi-Duty K-Factor transformers have inspection or testing equipment on an
a rated temperature rise of 150oC. assembly or production line ....................................................... K-13
Mainframe computer loads ........................................................ K-20
Solid state motor drives
Contact Technical Services for weather shield (variable speed drives) .............................................................. K-20
information. Multiwire receptacle circuits in critical care areas and
operating/recovery rooms of hospitals ...................................... K-20
* Triplen harmonics are those harmonics which are odd multiples
of third harmonic (9th, 15th, 21st, etc.). REPRINTED WITH PERMISSION FROM EDI MAGAZINE

Visit our website at www.solaheviduty.com or


174 contact Technical Services at (800) 377-4384 with any questions.
K-Factor Harmonic Transformers 7
Features
• Conductors to carry harmonics of a K-rated load • Basic design takes “stray losses” into account and
without exceeding insulation temperature ratings. functions within safe operating temperatures.
• UL 1561 listed up to K-20 rated protection. • Core and coil design engineered to manage the zero
• Rated temperature rise of 150oC, 220oC insulation. sequence flux caused by triplen harmonics.
• Shielded for quality power. • Provides 100% rated current without overheating the
windings or saturating the core.

Selection Tables: Three Phase


Group A – K-4 Rated 480 D Primary, 208Y/120 Secondary, 60 Hz Listed Certified

NEMA 3R Ship
Catalog Height Width Depth Primary Secondary
KVA Weather Weight
Number (inch) (inch) (inch) Amps Amps
Shield* (lbs)
15 3H4T2H15S WS-02 23 18 14 180 18.1 41.7
30 3H4T2H30S WS-14 28 23 16 329 36.1 83.4
45 3H4T2H45S WS-14 28 23 16 357 54.2 125
75 3H4T2H75S WS-30 34 28 22 647 90.3 208
112.5 3H4T2H112S WS-10 44 33 21 890 135 313
150 3H4T2H150S WS-10 44 33 21 1045 181 417
225 3H4T2H225S WS-11 46 36 24 1230 271 625
300 3H4T2H300S WS-11 46 36 24 1420 361 834
500 3H4T2H500S WS-12 65 45 35 2400 602 1390
*Weather shields (set of two) must be ordered separately.

Group B – K-13 Rated 480 D Primary, 208Y/120 Secondary, 60 Hz

NEMA 3R Ship
Catalog Height Width Depth Primary Secondary
KVA Weather Weight
Number (inch) (inch) (inch) Amps Amps
Shield* (lbs)
15 3H13T2H15S WS-14 28 23 16 239 18.1 41.7
30 3H13T2H30S WS-30 34 28 22 409 36.1 83.4
45 3H13T2H45S WS-30 34 28 22 480 54.2 125
75 3H13T2H75S WS-30 34 28 22 647 90.3 208
112.5 3H13T2H112S WS-10 44 33 21 972 135 313
150 3H13T2H150S WS-11 46 36 24 1210 181 417
225 3H13T2H225S WS-11 46 36 24 1230 271 625
300 3H13T2H300S WS-11 46 36 24 1420 361 834
500 3H13T2H500S WS-12 65 45 35 2400 602 1390

*Weather shields (set of two) must be ordered separately.

Visit our website at www.solaheviduty.com or


contact Technical Services at (800) 377-4384 with any questions. 175
7 K-Factor Harmonic Transformers

Selection Tables: Three Phase

Group C – K-20 Rated 480 D Primary, 208Y/120 Secondary, 60 Hz Listed Certified

NEMA 3R Ship
Catalog Height Width Depth Primary Secondary
KVA Weather Weight
Number (inch) (inch) (inch) Amps Amps
Shield* (lbs)
15 3H20T2H15S WS-14 28 23 16 239 18.1 41.7
30 3H20T2H30S WS-30 34 28 22 422 36.1 83.4
45 3H20T2H45S WS-30 34 28 22 532 54.2 125
75 3H20T2H75S WS-30 34 28 22 654 90.3 208
112.5 3H20T2H112S WS-10 44 33 21 980 135 313
150 3H20T2H150S WS-11 46 36 24 960 181 417
225 3H20T2H225S WS-11 46 36 24 1230 271 625
300 3H20T2H300S WS-12 65 45 35 1420 361 834
500 3H20T2H500S WS-12 65 45 35 2400 602 1390

*Weather shields come in a set of two and need to be ordered separately.

Electrical Connection
Tap Information
480 D Primary 208Y/120 Volt Secondary
TAPS: 2, 2½% FCAN; 4, 2½% FCBN All Sola/Hevi-Duty non-linear load transformers are provided with two
2½% FCAN and four 2½% FCBN taps in addition to the nominal rating
tap. For actual tap voltages, refer to the Electrical Connection Diagram.

Primary H1-H2-H3 Secondary Voltage

@ Tap Voltage X 1, X 2, X 3 X0-X1, X2, X3


1 504
2 492
3 480
4 468 208 120
5 456
6 444
7 432

Visit our website at www.solaheviduty.com or


176 contact Technical Services at (800) 377-4384 with any questions.