Project: AS-BUILT PLAN MACAO IMPERIAL TEA-AYALA MALLS THE 30TH
Owner: Location: 30 MERALCO AVENUE, PASIG CITY. 1605 METRO MANILA
1.0. Load Calculation
PANEL: LP circuit no.1 1 - Spare (Exhaust Blower) x 6045 VA ---------------------------------------- 6045 VA *use: 30AT, 50AF, 3Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 3-5.5mm2 copper wire + 1-5.5mm2 copper wire (GND) in 20mm Ø conduit PVC circuit no.2 1 - Spare (Fresh Air Blower) x 3825 VA ---------------------------------------- 3825 VA *use: 30AT, 50AF, 3Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 3-5.5mm2 copper wire + 1-5.5mm2 copper wire (GND) in 20mm Ø conduit IMC/RSC circuit no.3 1 - Lighting Dining x 650 VA ---------------------------------------- 650 VA *use: 20AT, 50AF, 1Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 2-3.5mm2 copper wire + 1-3.5mm2 copper wire (GND) in 20mm Ø conduit IMC/RSC circuit no.4 1 - Lighting Dining x 350 VA ---------------------------------------- 350 VA *use: 20AT, 50AF, 1Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 2-3.5mm2 copper wire + 1-3.5mm2 copper wire (GND) in 20mm Ø conduit IMC/RSC circuit no.5 1 - Lighting Counter x 390 VA ---------------------------------------- 390 VA *use: 20AT, 50AF, 1Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 2-3.5mm2 copper wire + 1-3.5mm2 copper wire (GND) in 20mm Ø conduit IMC/RSC circuit no.6 1 - Lighting Lkitchen x 175 VA ---------------------------------------- 175 VA *use: 20AT, 50AF, 1Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 2-3.5mm2 copper wire + 1-3.5mm2 copper wire (GND) in 20mm Ø conduit IMC/RSC circuit no.7 1 - TV Menu x 1200 VA ---------------------------------------- 1200 VA *use: 20AT, 50AF, 1Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 2-3.5mm2 copper wire + 1-3.5mm2 copper wire (GND) in 20mm Ø conduit IMC/RSC circuit no.8 1 - Signage x 1000 VA ---------------------------------------- 1000 VA *use: 20AT, 50AF, 1Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 2-3.5mm2 copper wire + 1-3.5mm2 copper wire (GND) in 20mm Ø conduit IMC/RSC circuit no.9 1 - AC Kitchen x 1127 VA ---------------------------------------- 1127 VA *use: 20AT, 50AF, 1Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 2-3.5mm2 copper wire + 1-3.5mm2 copper wire (GND) in 20mm Ø conduit IMC/RSC circuit no.10 1 - AC Dining x 1127 VA ---------------------------------------- 1127 VA *use: 20AT, 50AF, 1Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 2-3.5mm2 copper wire + 1-3.5mm2 copper wire (GND) in 20mm Ø conduit IMC/RSC circuit no.11 1 - AC Dining x 1840 VA ---------------------------------------- 1840 VA *use: 32AT, 50AF, 1Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 2-5.5mm2 copper wire + 1-5.5mm2 copper wire (GND) in 20mm Ø conduit IMC/RSC circuit no.12 1 - AC Dining x 1840 VA ---------------------------------------- 1840 VA *use: 32AT, 50AF, 1Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 2-5.5mm2 copper wire + 1-5.5mm2 copper wire (GND) in 20mm Ø conduit IMC/RSC circuit no.13 1 - Convenience outlet Sofa and Toilet x 1790 VA ---------------------------------------- 1790 VA *use: 32AT, 50AF, 1Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 2-5.5mm2 copper wire + 1-5.5mm2 copper wire (GND) in 20mm Ø conduit IMC/RSC circuit no.14 1 - Cake Chiller x 1150 VA ---------------------------------------- 1150 VA *use: 32AT, 50AF, 1Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 2-5.5mm2 copper wire + 1-5.5mm2 copper wire (GND) in 20mm Ø conduit IMC/RSC circuit no.15 1 - Computer / POS Counter x 600 VA ---------------------------------------- 600 VA *use: 32AT, 50AF, 1Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 2-5.5mm2 copper wire + 1-5.5mm2 copper wire (GND) in 20mm Ø conduit IMC/RSC circuit no.16 1 - Coffee Maker / Blender x 1500 VA ---------------------------------------- 1500 VA *use: 32AT, 50AF, 1Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 2-5.5mm2 copper wire + 1-5.5mm2 copper wire (GND) in 20mm Ø conduit IMC/RSC circuit no.17 1 - Convenience outlet / Water heaterx 2500 VA ---------------------------------------- 2500 VA *use: 32AT, 50AF, 1Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 2-5.5mm2 copper wire + 1-5.5mm2 copper wire (GND) in 20mm Ø conduit IMC/RSC circuit no.18 1 - Ice maker x 1000 VA ---------------------------------------- 1000 VA *use: 32AT, 50AF, 1Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 2-5.5mm2 copper wire + 1-5.5mm2 copper wire (GND) in 20mm Ø conduit IMC/RSC circuit no.19 1 - Chiller x 1150 VA ---------------------------------------- 1150 VA *use: 32AT, 50AF, 1Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 2-5.5mm2 copper wire + 1-5.5mm2 copper wire (GND) in 20mm Ø conduit IMC/RSC circuit no.20 1 - Ice maker and convenience outletx 1150 VA ---------------------------------------- 1150 VA *use: 32AT, 50AF, 1Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 2-5.5mm2 copper wire + 1-5.5mm2 copper wire (GND) in 20mm Ø conduit IMC/RSC circuit no.21 1 - Chiller x 1150 VA ---------------------------------------- 1150 VA *use: 32AT, 50AF, 1Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 2-5.5mm2 copper wire + 1-5.5mm2 copper wire (GND) in 20mm Ø conduit IMC/RSC circuit no.22 1 - Refrigerator x 1250 VA ---------------------------------------- 1250 VA *use: 32AT, 50AF, 1Ø, 60Hz, 10KAIC over current protection device (circuit breaker) *use: 2-5.5mm2 copper wire + 1-5.5mm2 copper wire (GND) in 20mm Ø conduit IMC/RSC Total connected load: ---------------------------------------- 32809 VA
1.1. Service Entrance Conductor and Equipment
Maximum Current Rating of Protective Device (I) Inverse Time Circuit Breaker First 10,000 VA at 100% ---------------------------------------- 10000 VA Remainder at: 50% ---------------------------------------- 11405 VA Total connected load: ---------------------------------------- 26756 VA 26755.625 VA ÷ 230 V ---------------------------------------- 83.95 A size of protection device = (100% noncontinuous load + 125% continuous load) / Supply voltage over current protection device: 160AT, 225AF, 3Ø, 60Hz, 22KAIC feeder size: 3- 60 mm2 copper wire THHN (L) 1- 60 mm2 copper wire THHN (N) *if applicable 1- 14 mm2 copper wire THHN (GND) size of conduit: 50 mm Ø conduit IMC/RSC
In compliance with DILG-Memorandum Circular 2016-23 and PEC-Article 1.3.2.1 (f)
● Memorandum Circular 2016-23 Department of the Interior and Local Government. Reiteration of Certain Provision of the Pgilippine Electrrical Code Relative to the Issuance of Building and Construction Permit. ● Philippine Electrical Code 2017, Article 1.3.2.1 (f). Requires the Inclusion of a Design Analysis. Prepared on: Changes in load, equipment settings or system configuration will invalidate the 8/15/2019 calculated values with a validity for (1) year, unless specfied by the attached documents.