Professional Documents
Culture Documents
1Abstract— This paper presents a model of the first CIGRE discussed in [4] by the CIGRE Working Group. The capabilities
benchmark HVDC system in PSS/E. The model was composed of and limitations of the EMTP and NETOMAC programs for
three parts which: equation converting, DC line, and the control HVDC system simulation were investigated in [5], where the
mode selection. The equation conversion uses different equations
fundamental differences between the two programs and the new
to calculate the dc voltage and dc power according to normal and
abnormal conditions. The DC line calculates the dc current at both advanced stability feature of provided by NETOMAC have
dc transmission lines using the dc voltage derived by the equation been discussed. In addition, custom power devices, such as
conversion. The ABB and AREVA control selections are DSTATCOM and DVR, have been simulated using
investigated to determine the control mode selection model. PSCAD/EMTDC and MATLAB/SIMULINK. This allows for
Simulation studies have been carried out in PSCAD as well as the analysis of advantages and disadvantages during the
PSS/E to confirm the performance. The simulation results of
transient situation described in [6]. The elaborate control model
PSS/E are similar to those of PSCAD. PSS/E cannot analyze the
valve state or firing level such as the harmonic instability or the and control technique for the 4-terminal Pacific Intertie HVDC
firing control of the converter. transmission scheme using EMTP have been presented in [7].
More recently, a comparative study of the CIGRE HVDC
Index Terms— HVDC transmission, CIGRE HVDC benchmark benchmark system model and simulation using
model, modeling, PSS/E PSCAD/EMTDC, PSB/SIMULINK, and PSCAD/SIMULINK
interface have been reported in [8]. Furthermore, the CIGRE
HVDC benchmark system has been modeled using
I. INTRODUCTION MATLAB/SIMULINK in [9].
II. CIGRE BENCHMARK SYSTEM IN PSCAD III. SIMULATION AND MODELING ENVIRONMENT IN PSS/E
Fig. 1 shows the CIGRE benchmark HVDC system which is a PSS/E is a package of programs that study the power system
mono-polar 500-kV, 1000-MW HVDC link with 12-pulse transmission network and generation performance in both
converters on the rectifier side in PSCAD. The inverter side is steady-state and dynamic conditions. The process of solving the
similar to the rectifier side and both are connected to the weak algebraic equations for given loads and generator power outputs
ac system, which has a short circuit ratio of 2.5 at a 50Hz rated is referred to as the Power Flow Calculation and requires an
frequency. There are the low and high filters that compensate for iterative procedure. Dynamic simulation is the process of
a portion of, or all of, the reactive power absorbed by the integrating the differential equations to produce transient
converter, to limit the current distortion caused by the converter variation plots of quantities like rotor angle or power flow [10].
harmonics to an acceptable level. The capacitive reactive The HVDC system can be modeled at various simulation time
compensation are also provided at both sides to supply the steps depending on the simulation tools used from PSS/E,
reactive power. The full three-phase model of the CIGRE PSCAD, and RTDS. PSS/E can be used to simulate system
benchmark HVDC system is available as an example file in phenomenon at a fundamental frequency or below, i.e.
PSCAD Version 4.2.0. The CIGRE benchmark HVDC system phenomena like low-frequency resonances or oscillation
data [3], [4] is given in Table I. The detailed power circuits of damping. Fig. 3 indicates the various kinds of control that can
the converter and power circuit models like converter, converter occur in a power system.
transformer, supplying voltage source, and dc line are reported Because the PSS/E simulation time step is longer than the
in [8]. time to analyze the interactions between HVDC and ac systems
The control system model has the following three controllers at 1kHz or higher, such as harmonic instability, the modeling
in PSCAD Version 4.0.2: scopes of HVDC in PSS/E are at constant current loop level,
Extinction Angle (γ) Controller VDCOL, and over as shown in Fig. 4. It is assumed that a firing
DC Current Controller angle such that the minimum γ of thyristor valves at the inverter
Voltage Dependent Current Limiter (VDCOL) side is ideal in PSS/E while the minimum γ of thyristor valves is
The rectifier side controls only the constant DC current while considered in PSCAD as shown in Fig. 2.
the inverter side can control the extinction angle (γ) or the DC
current with Voltage Dependent Current Limiter (VDCOL). The Turbine and boiler control
detailed information on control at both sides is provided in [8].
Generator control
Every controller uses the PI controller to produce the required
order. The γ controller selects the minimum value of γ of each System stabilizing control
thyristor valve in the converter at the inverter side during the Protective relay system
one cycle in PSCAD, as shown in Fig. 2. If γ is selected for
HVDC, SVC
another value, such as the average value of all thyristor valves in
the converter, then commutation failure can occur due to the γ,
which is larger than the average value. The minimum γ is 10-4 10-3 10-2 10-1 1 101 102 103 104
considered the firing control region, because the PSCAD Time period (s)
simulation time step is shorter than 10ms, as shown in Fig. 4.
Fig. 3. Power system control and time period
methods for control mode selections are described in following When the rectifier controls the dc voltage due to the ac
subcircuits. voltage drop at the rectifier side, the dc current controller will
decrease αorder to the minimum and increase the dc current since
Id_measured is near Id_order at the inverter end, which is smaller than
A. ABB Control Mode Selection Method
Id_order at the rectifier end. This means that the rectifier control
The ABB HVDC system model control mode selection can mode is the dc voltage control, as αorder is the output from the dc
be achieved by changing the maximum or minimum limit of the voltage controller.
PI controller in the dc current controller. Fig. 5 shows the simple The normal αmin is 5 degrees to ensure adequate voltage
diagram for the control mode selection at the rectifier and across the valve before firing, αmax_voltage and αmax_current are
inverter sides. Every voltage and current controller at both sides normally between 90 and 140 degrees in the inverter region to
is composed of the PI controller. There are two control modes: assist the system under certain fault conditions.
dc voltage and current control at the rectifier converter. The dc In the detailed ABB HVDC model, the minimum limit of the
voltage controller output goes to the dc current controller and dc voltage controller is the maximum value among αmin, and,
the minimum dc current controller is shown in Fig. 5(a). The αmin_RAML from the Rectifier Alpha Min Limiter, αmin_OVL which
minimum dc current controller limit is selected to be the larger considered the over voltage limit, and αmin_refVARC calculated by
αmin, which is pre-determined, or the dc voltage controller the voltage and angle reference calculator [11].
output. Fig. 5(b) shows the simple diagram for control mode
If the rectifier controls the dc current in normal operations, selection at the inverter end, which is composed of the dc
the dc voltage controller will decrease αorder_vol which is the voltage controller, the dc current controller, and the alphamax
minimum limit of the dc current controller since Vdc_order is inverter controller. The output from the dc voltage controller
larger than Vdc_measured. Because the difference between Idc_order goes into the dc current controller as the maximum limit of the
and Idc_measured is small in the steady state, the dc current dc current controller. This is the smaller αmax value, which is
controller output is near the measured α, which is normally pre-determined as the output from the dc voltage controller.
within 15 and 20 degrees. This means that the rectifier control In normal operations, the dc current controller increases αorder
mode is the dc current control since αorder is the output from the to the maximum limit to increase the inverter dc voltage since
dc current controller. Id_measured is larger than the Id_order of the inverter. This means that
the inverter control mode is the dc voltage control since αorder is
DC Voltage DC Current the output from the dc voltage controller.
Controller Controller The maximum limit of the dc voltage controller is determined
by the alphamax inverter controller which is nothing but
αmax_voltage αmax_current
constant beta control to have a positive slope in the current
margin region increase the stability of the current controller. If
Vdc_order Ki αorder_vol Idc_order Ki
there is no positive slope, sudden changes in the current cause
Vdc_measured Kp +
s Idc_measured Kp +
s
αorder power oscillations in the system during mode shifting. The
constant beta for positive slopes and αmax are given in (1) and (2).
The normal αmin at the inverter is 110 degrees for the inverter
αmin_voltage Maximum and does not operate as the rectifier.
Select αmin_current
αmin I o Vd
=β arccos cos γ − 2 ⋅ X c ⋅ ⋅ (1)
(a) I dN Vdio
α max= π − β (2)
DC Voltage DC Current
αmax
Controller Controller
B. AREVA Control Mode Selection Method
γref
Alphamax αmax_voltage Minimum αmax_current The AREVA HVDC system model selects the control mode
Inverter
Select
controller composed of the PD controllers and integrator by using the
minimum and maximum selection at both converter sides, as
Vdc_order Idc_order shown in Fig. 6. A basic mode selection principle in AREVA is
Ki Ki
Vdc_measured Kp +
s αorder_vol Idc_measured Kp +
s
αorder to select the control mode with the smallest difference between
the set-point and measured value.
There are two control modes: dc voltage and current control
αmin_voltage αmin_current at the rectifier converter. The dc voltage controller is comprised
(b) of Vdc control and αmin control, as shown in Fig. 6(a). If the
Fig. 5. Simple diagram for ABB HVDC system model control mode selection at (a) rectifier controls the dc current in normal operations, the
rectifier and, (b) inverter difference between Idc_order and Idc_measured is so small that output
4
αorder_current from the PD controller is near measured α while Vdc The control mode selection of the inverter side is similar to
control and αmin control decrease αorder_voltage and αorder_αmin since that of the rectifier side except for the minimum selection as
each set-point value is larger than each measured value. shown in Fig. 6(b). If the inverter controls the dc voltage in
Therefore, the dc current control mode is selected among the normal operations, αorder_current is increased by the dc current
control modes, because the larger value of the two outputs, controller to increase the dc voltage of the inverter side since
αorder_voltage or αorder_αmin, is smaller than αorder_current. Idc_order is smaller than Idc_measured. αorder_γ and αorder_voltage are
When the rectifier controls the dc voltage due to the ac small since γmeasured is near γset point and the difference between
voltage drop, αorder_current is decreased by the dc current Vdc_set point and Vdc_measured is very small. Therefore, the dc voltage
controller and rectifier dc voltage increased to increase dc controller, Vdc control or αmin control, is selected by minimum
current to Idc_order. The αmin controller make αorder_αmin into αmin selection.
and αorder_voltage is near αmeasured due to the small difference When the inverter controls the dc current due to the ac
between Vdc_set point and Vdc_measured. Therefore, αorder is selected voltage drop in the rectifier side, the difference between Idc_order
from the dc voltage controller, which is Vdc control or αmin and Idc_measured is so small that αorder_current is near zero while
control. αorder_voltage and αorder_γ increase since Vdc_set point is larger than
After the control mode is chosen by maximum selection, the Vdc_measured and γset point is smaller than γmeasured. This means that
αorder passes through the integrator and the PD controller αorder_current is selected by minimum selection rather than by
function becomes the PI controller. This means that the AREVA αorder_voltage or αorder_γ. Additionally γset point can be increased to
HVDC system model can have the same results as the ABB have a positive slope in the current margin region.
HVDC system model using the PD controller, the maximum In the detailed AREVA HVDC model, the Vac control for
selector, and the integrator. The normal αmin_set point is 5 degrees preventing overvoltage of ac system, αmax and γrec control for
so that there is a certain voltage across the valve before firing operating the inverter mode of the rectifier during the dc fault
and Vdc_set point is larger than 1.0 pu at the rectifier. are also implemented.
DC Current Controller
αorder_current
V. CIGRE HVDC SYSTEM MODEL IN PSS/E
Idc_order - Σ Kp + sKd
+ The CIGRE HVDC system model in PSS/E is comprised of
Idc_measured 179° three parts: the converting equation, the dc line, and the control.
The control is implemented using the PI controllers and the
Maximum 2πf00
DC Voltage Controller Select s
αorder minimum and maximum selection. This is similar to the AREVA
αorder_voltage
HVDC system model and VDCOL at the inverter side.
Vdc_set point - 1°
+
Σ Kp + sKd
The converting equation calculates the dc voltage and dc real
Maximum power in addition to ac active and reactive power and certain
Vdc_measured Select
additional quantities like converter transformer secondary
αmin_set point +
Σ Kp + sKd
αorder_αmin voltage. These values are derived using ac and dc converting
- equations in transient conditions as well as steady state
αmeasured conditions after the control the calculates the firing angle of
(a)
both converters at each time step.
The converting equation initializes the present dc quantities
from the load flow. During the dynamic run, the firing angle
DC Current Controller
updated by the control part enables the converting equation to
- αorder_current calculate the dc voltages at both sides of the link. The dc line
Idc_order Σ Kp + sKd
+ part updates the dc current at each time step using the firing
Idc_measured 179°
angle and dc voltage at both converter ends. These dc voltage
Minimum 2πf00
and current updates can calculate the dc and ac active power at
αorder
DC Voltage Controller Select s both converter sides. The reactive power of the ac system at the
αorder_voltage converter is found by calculating the power factor angle in terms
Vdc_set point +
Σ Kp + sKd 1°
- of firing angle and overlap angle.
Maximum When the firing angle is derived by the control, Vdcc, μc,
Vdc_measured Select
power factor angle, Pdcc, and Pacc can be expressed as (3)-(7).
γset point - αorder_γ
Σ Kp + sKd
+
3 2 3X I
γmeasured Vdcc = Nc Eacc cos α c − cc dc − 2 Rcc I dc (3)
π π
(b) 2 I dc X cc
µ= arccos
cos α − −
c α (4)
Eacc
c c
Fig. 6. Simple diagram for the control mode selection of the AREVA HVDC system
model at the (a) rectifier and, (b) inverter
5
G2
+
2 1 Vdl2 1
3N c Eacc E − 06
( cos ( 2α c ) − cos 2 ( µc + α c ) ) 1.0SBASE 1 Σ G2 Idi
Pacc = (7) G2
1+sT2
1+sT2
-
1+sT2
4π X cc
=
γ c arccos cos (α c − 30 ) −
6 I dc X cc VI. CASE STUDIES AND RESULTS
− 30 (11)
Eacc
2µc + sin ( 2 (α c − 30 ) ) − sin ( 2 ( γ c + α c ) ) A. Test System and Simulation Conditions
tan (φc ) = (12)
cos ( 2 (α c − 30 ) ) − cos ( 2 ( γ c + 30 ) ) The test system for the PSS/E CIGRE HVDC system model is
3N c E 2
1.0 E − 06 a four bus system, which has two buses for the ac system at the
Pacc =
4π X cc
acc
(
cos ( 2 (α c − 30 ) ) − cos 2 ( γ c + 30 )
SBASE
) (13)
rectifier and inverter sides and two buses for the HVDC rectifier
2
3N c Eacc 1.0 E − 06 and inverter. The ac base voltage of the two buses at the rectifier
Qacc
=
4π X cc
(
2µc + sin ( 2 (α c − 30 ) ) − sin ( 2 ( γ c + 30 ) )
SBASE
) (14)
side is 345kV. A generator connected to the ac system bus
supplies 1,000MW of power to the rectifier bus as shown in Fig.
8. The 500kV HVDC transmission system supplies 1,000MW
The transformer open circuit secondary voltage magnitude, Eacc,
to the inverter side; this is similar to the rectifier side, but has a
and the transformer valve winding secondary voltage under load
980MW load with 230kV ac base voltage. The rectifier and
conditions, Vacs, can be calculated by
inverter bus have a 600MVar shunt capacitor to supply reactive
power. Filters are assumed to be ideal due to the PSS/E
TRc ⋅ EBASE simulation time step.
=Eacc Vac ⋅1.0 E + 03
TAPc (15)
The GIGRE HVDC system has been simulated in both
Vacs=
Vac ( R + jX cc ) ⋅ SBASE
− I ac ⋅ TAPc ⋅ cc PSCAD and PSS/E to confirm the model’s performance. The
TAPc N c ⋅ TRc2 ⋅ EBASE 2 (16)
HVDC system was simulated for 5s to analyze the steady-state
and transient results. The simulation was run without any faults
for the steady-state analysis, then a three-phase ground fault at
The dc line section calculates the dc current at both sides of a
the rectifier or inverter side occurred for 0.1s at 1s for the
dc transmission line using dc voltage derived by the converting
transient analysis. The CIGRE HVDC system model should be
equation at each time step. The line is modeled as shown in Fig.
loaded before the dynamic simulations in PSS/E, as shown in
7. Vdl1 and Vdl2 are the voltage drops given as (17) and (18) in
Fig. 9.
Fig. 7(b).
R1 L1 L2 R2
Rectifier C ic Inverter
Reactive power
Fig. 8. Simplified diagram of test system at the rectifier side in PSS/E
(a)
6
Dynamic Simulation
Second Action 1.6
1 Fault
1.1 Clear Fault
5 Run
p.u
1
Fig. 9. Loading HVDC model and operation for dynamic simulation in PSS/E
p.u
linearly due to the VDCOL after fault clearing in PSS/E, as 1
shown in Fig. 10(b).
The dc current at the rectifier side increased to 1.6pu rapidly
due to the voltage difference between the rectifier side and the 0.4
middle of the dc line. This increased rapidly as the inverter dc
1 1.2 1.4 2
voltage dropped to zero due to the three-phase ground fault at
Time (s)
the inverter side in PSCAD, as shown in Fig. 11(a). the dc
current decreased rapidly once more after the fault clearing due (b)
Fig. 11. Rectifier DC current when 3-phase ground fault occurs at the inverter side in
to the voltage difference between the rectifier side and middle of (a) PSCAD and, (b) PSS/E
the dc line, which decreased as the inverter dc voltage increased
dramatically, as shown in Fig. 10(a). Fig. 11(b) indicates that
similar results appeared in PSS/E. 1
Fig. 12(a) and (b) show that the simulation results of the dc
p.u
0
p.u
-1
-1.5 0
1 1.2 1.4 2
Time (s) 1 1.2 1.4 2
(a) Time (s)
(b)
1 Fig. 12. Inverter DC voltage when 3-phase ground fault occurs at the inverter side in
(a) PSCAD and, (b) PSS/E
p.u
0
The dc current at the inverter side increased to 2.5pu, which is
-1 higher than the peak value of dc current at the rectifier side, and
-1.5
rapidly goes to the right after the fault in PSCAD, as shown in
1 1.2 1.4 2 Fig. 13(a). This is due to the voltage difference in the middle of
Time (s)
the dc line. The inverter side is also bigger than the rectifier and
(b) the middle of the dc line. Similar results appeared in PSS/E, but
Fig. 10. Rectifier DC voltage when 3-phase ground fault occurs at the inverter side
there was a little AC component during the fault, as shown in
in (a) PSCAD and, (b) PSS/E
7
TABLE I
1 CIGRE HVDC BENCHMARK SYSTEM DATA
Parameter Rectifier Inverter
0 AC Base Voltage 345 kV 230 kV
Base MVA 100 MVA 100 MVA
1 1.2 1.4 2 Transf. tap (HV side) 1.01 pu 0.989 pu
Time (s) Voltage Source 1.088∠22.18° 0.935∠-23.14°
(a) Nominal DC Voltage 500 kV 500 kV
Nominal DC Current 2 kA 2 kA
Transf. Xl 0.18 pu 0.18 pu
Source Impedance R = 3.737Ω R = 0.7406 Ω
2.5 L= 0 H L = 0.0365 H
System Frequency 50 Hz 50 Hz
Minimum Angle α = 15° γ = 15°
p.u
0 REFERENCES
1 1.2 1.4 2 [1] D.Madhan Mohan, Bhim Singh, B.K Panigrahi, “HVDC Technology for
Time (s) Power Transmission,” July 2008, Electrical India.
[2] J. D. Ainsworth, “Proposed benchmark model for study of HVDC con-
(b) trols by simulator or digital computer,” in Proc. CIGRE SC-14 Colloq.
Fig. 13. Inverter DC current when 3-phase ground fault occurs at the inverter side in HVDC With Weak AC Systems, Maidstone, U.K., Sep. 1985.
(a) PSCAD and, (b) PSS/E [3] M. Szechtman, T. Wess, and C. V. Thio, “First benchmark model for
HVDC control studies,” Electra, no. 135, pp. 54-67, Apr. 1991.
[4] ----------, “A benchmark model for HVDC system studies,” in Proc. Int.
1 Conf. AC/DC Power Transmission, Sep. 17-20, 1991, pp. 374-378
[5] P. Lehn, J. Rittiger, and B. Kulicke, “Comparison of the ATP version of
the EMTP and the NETOMAC program for simulation of HVDC
p.u
systems,” IEEE Trans. Power Del., vol. 10, no. 4, pp. 2048-2053, Oct.
1995.
[6] W. Freitas and A. Morelato, “Comparative study between power system
blockset and PSCAD/EMTDC for transient analysis of custom power
0
devices based on voltage source converter,” in Proc. Int. Conf. Power
1 1.2 1.4 2 Systems Transients, New Orleans, LA, 2003, pp. 91-96.
[7] A. Hammad, R. Minghetti, J. Hasler, P. Eicher, R. Bunch, and D.
Time (s)
Goldsworthy, “Controls modeling and verification for the Pacific Intertie
(a) HVDC 4-terminal scheme,” IEEE Trans. Power Del, vol. 8, no. 1, pp.
367-375, Jan. 1993.
[8] M. O. Faruque, Y. Zhang, and V. Dinavahi, “Detailed modeling of
1.6 CIGRE HVDC benchmark system using PSCAD/EMTDC and
PSB/SIMULINK,” IEEE Trans. Power Del., vol. 21, no. 1, pp. 378-387,
Jan. 2006.
1
p.u
Do-Hoon Kwon (S’15) received his B.S. and M.S. degree in Electrical
Engineering from Seoul National University in 2010 and 2012, respectively.
He is currently a Ph.D. candidate in Electrical Engineering at Seoul Nation
University. His research fields of interest include HVDC, EMS and Smart
distribution system.
Rae-Gyun Kim (S’14) received his B.S. degree in electrical engineering from
Seoul National University in 2014. He is currently a M.S. candidate in
Electrical Engineering at Seoul Nation University. His research fields of
interest include HVDC, ESS and Fault Current Detection.