SHORT CIRCUIT ANALYSIS

RESISTANCE PER
WIRE GAUGE LENGTH(ft) RESISTANCE
1000 ft

#6 AWG 0.491 SERVICE DROP 49.216 0.024165056


FEEDER 49.216 0.024165056

VA base 30000
V base 220

COMPUTE FOR FAULT AT MAIN (XFA)


PER UNIT Z OF CABLE

XFA PU Z cable = VA base x Z cable x 2


(V base)2

Z cable 0.024165056

PU Z cable = 0.029956681

SYMMETRICAL FAULT CURRENT AT PANEL BOARD

XFB ISC = VA base


( V base x PU Z cable )

ISC = 4552.027523 A

THEREFORE USE DISCONNECT WITH RATING GREATER THAN 4552.027523 AIC

COMPUTE FOR FAULT AT MAIN (XFB)


PER UNIT Z OF CABLE

PU Z cable = VA base x Z cable x 2


(V base)2

Z cable 0.048330112

PU Z cable = 0.059913362

SYMMETRICAL FAULT CURRENT AT BUS BAR TAP POINT

ISC = VA base
( V base x PU Z cable )

ISC = 2276.013761 A
THEREFORE USE CIRCUIT BREAKER GREATER THAN 2276.013761 A
VOLTAGE DROP ANALYSIS

LENGTH(ft) RESISTANCE

SERVICE DROP 49.216 0.024165056


FEEDER CONDUCTOR 49.216 0.024165056

Demand Current = 55.22

VD = (SERVICE DROP RESISTANCE + FEEDER CONDUCTOR RESISTANCE) X DEMAND CURRENT

VD = 2.668789 V

220 v x 0.03 = 6.6 V

Therefore 2.67 V < 6.6 V and and less than 3% VD