RELAY SETTING CALCULATIONS AND PARAMETER SET SHEET

SUBSTATION BANG KLA PANEL BAK2YB-01

SUBSTATION BANG KLA


PANEL BAK2YB-01
RELAY TYPE P443
MANUFACTURER Alstom

CONTENTS PAGE

RELAY SETTING CALCULATION 2 - 19

Distance Protection (21/21N) 2 - 17


Directional overcurrent Protection (67/67N) 18 - 19

PARAMETER SET SHEET 20 - 27


2 OF 27

RELAY SETTING CALCULATIONS

SUBSTATION BANG KLA PANEL BAK2YB-01

RELAY SETTING CALCULATION


P443
Distance Protection (21/21N)
3 OF 27

RELAY SETTING CALCULATIONS

SUBSTATION BANG KLA PANEL BAK2YB-01

SUBSATION : BANG KLA


LINE PROTECTION : BAK2YB-01 TO : HSR1YB-01 HUA SOMRONG
RELAY TYPE : P443 S/N :
MANUFACTURER : Alstom
PANAL : BAK2YB-01
FUNCTION : 21/21N

BANG KLA HUA SOMRONG CHACHOENGSAO


SUBSTATION SUBSTATION SUBSTATION (EGAT)
BAK2YB‐01 HSR1YB‐01

SD 2×400 = 2.1 km HSR3YB‐01 SD 2×400 = 25.1 km CS70XX


SD 2×400 = 17.3 km

TOYOTA GATEWAY PHANOM SARAKHAM
SUBSTATION SUBSTATION
SD 2×400 = 33 km
1YB‐01

600 ms
ZONE3 100% OF SECTION1 + 120% OF SECTION2 TIME OPERATE = 600 ms
300 ms
ZONE2 100% OF SECTION1+ 50% OF SECTION2 TIME OPERATE = 300 ms
0 ms
ZONE1 85% OF SECTION1 TIME OPERATE = 0 ms

Figure.1 Transmision line data BAK2YB-01

SYSTEM DATA

Base MVA : 100 MVA


Max MVA : 320 MVA
Base voltage : 115 kV
Base impredance : 132.25 Ohm
CT Ratio : 1200 / 1 A
VT Ratio : 115 / 115 kV
CTR/VTR : 1.2
4 OF 27

RELAY SETTING CALCULATIONS

SUBSTATION BANG KLA PANEL BAK2YB-01

LINE IMPENDANCE

Line type R1 (Ohm/km) X1 (Ohm/km) R0 (Ohm/km) X0 (Ohm/km)


SS
SD 0.042936 0.2677 0.21347 1.3294

Line length section I : 19.40 km


Line length section II (Shortest line section II) : 25.1 km
Line length section II (Longest line section II) : 33 km

Positive sequence line impedance Z1 = R1 + jX1 Ohm/km

Z1 = 0.042936 + 0.2677 Ohm/km

Z1 = 0.271121357 Ohm/km

Zero sequence line impedance Z0 = R0 + jX0 Ohm/km

Z0 = 0.21347 + 1.3294 Ohm/km

Z0 = 1.346430021

Earth fault residual compensation K0 = Z0-Z1


3Z1
K0 = (0.21347 + j1.3294) - (0.042936 + j0.2677)
3 × (0.042936 + j0.2677)

So earth fault residual compensation K0 = 1 / 0 ° Ohm sec


(PEA requirement)
LINE IMPENDANCE SECTION I

Line length section I = 19.4 km

Z1 = 0.8329584 + 5.19338 Ohm

Positive sequence line impedance section Z1 = 5.259754321 Ohm

Z1 = 6.3117052 / 80.9 ° Ohm sec

Zero sequence line impedance section I Z0 = 4.141318 + 25.7904 Ohm

Z0 = 26.1207424 Ohm

Z0 = 31.344891 / 80.9 ° Ohm sec


5 OF 27

RELAY SETTING CALCULATIONS

SUBSTATION BANG KLA PANEL BAK2YB-01

LINE IMPENDANCE SECTION II (Shortest line section II)

Line length section II (Shortest line section II) = 25.1 km

Z1 = 1.0776936 + 6.71927 j Ohm

Positive sequence line impedance section Z1 = 6.8051461 / 80.9 ° Ohm

Z1 = 8.1661753 / 80.9 ° Ohm sec

Zero sequence line impedance section II Z0 = 5.358097 + 33.36794 j Ohm

Z0 = 33.795394 / 80.9 ° Ohm

Z0 = 40.55447223 / 80.9 ° Ohm sec

LINE IMPENDANCE SECTION II (Longest line section II)

Line length section II (Longest line section II) = 33 km

Z1 = 1.416888 + 8.8341 j Ohm

Positive sequence line impedance section Z1 = 8.947004773 / 80.9 ° Ohm

Z1 = 10.73640573 / 80.9 ° Ohm sec

Zero sequence line impedance section II Z0 = 7.04451 + 43.8702 j Ohm

Z0 = 44.43219069 / 80.9 ° Ohm

Z0 = 53.31862882 / 80.9 ° Ohm sec


6 OF 27

RELAY SETTING CALCULATIONS

SUBSTATION BANG KLA PANEL BAK2YB-01

MINIMUM LOAD CHECK

Capacity of Protected Line = 320 MVA

= 1606.5 A

CT Rated Primary = 1200 A


Use Capacity of Protected Line for minimum load check because Capacity of Protected Line less than
CT Rated
Minimum Load ( Zmin ) = 41.33 Ohm pri

= 49.59 Ohm sec

Load angle = 45 deg.

50 % of Minimum Load = 24.80 Ohm sec

60 % of Minimum Load = 29.76 Ohm sec

LOAD BLINDING

Z< Blinder Imp = 24.80 Ohm sec

Load/B Angle = 45 deg.

CRITERIA FOR RESISTIVE REACH

Max Rph = 60 % of Minimum Load Ohm sec

R3ph-R4ph = 30 Ohm sec

R2ph = 24 Ohm sec

R1ph = 19 Ohm sec

Max RG = 40 Ohm pri

R3G-R4G,R2G,R1G = 48 Ohm sec


7 OF 27

RELAY SETTING CALCULATIONS

SUBSTATION BANG KLA PANEL BAK2YB-01

ZONE 1 REACH

Zone 1 Reach setting = 85 % of section 1

Positive reactive reach (X1) = 4.414373 j Ohm

Positive reactive reach secondary (X1) = 5.2972476 j Ohm sec

Positive resistance reach (R1) = 0.70801464 Ohm

Positive resistance reach secondary (R1) = 0.849617568 Ohm sec

Positive impedance reach (Z1) = 4.470791173 / 80.9 ° Ohm

Positive impedance reach secondary (Z1) = 5.364949408 / 80.9 ° Ohm sec

Zero reactive reach (X0) = 21.921806 j Ohm

Zero reactive reach secondary (X0) = 26.3061672 j Ohm sec

Zero resistance reach (R0) = 3.5201203 Ohm

Zero resistance reach secondary (R0) = 4.22414436 Ohm sec

Zero impedance reach (Z0) = 22.20263104 / 80.9 ° Ohm

Zero impedance reach secondary (Z0) = 26.64315725 / 80.9 ° Ohm sec


8 OF 27

RELAY SETTING CALCULATIONS

SUBSTATION BANG KLA PANEL BAK2YB-01

So set :
GROUP 1 DIST. ELEMENTS

Z1 Ph. Reach = 5.36 Ohm sec

Z1 Ph. Angle = 80.90 deg

R1 Ph. Resistive = 19 Ohm

Z1 Tilt Top Line = 0 deg

Z1 Sensit. Iph>1 = 250 mA

Z1 Gnd. Reach = 5.36 Ohm sec

Z1 Gnd. Angle = 80.9 deg

Z1 Dynamic Tilt = Disabled

Z1 Tilt Top Line = 0 deg

kZN1 Res. Comp. = 1.00

kZN1 Res. Angle = 0 deg

R1 Gnd Resistive = 48 Ohm

Z1 Sensit Ignd>1 = 150 mA

GROUP 1 SCHEME LOGIC

Zone1 Tripping = Phase And Ground

tZ1 Ph. Delay = 0 s

tZ1 Gnd. Delay = 0 s


9 OF 27

RELAY SETTING CALCULATIONS

SUBSTATION BANG KLA PANEL BAK2YB-01

ZONE 2 REACH

Zone 2 Reach setting = 100 % of section I + 50 % Short line sec II

Positive reactive reach (X1) = 8.553015 j Ohm

Positive reactive reach secondary (X1) = 10.263618 j Ohm sec

Positive resistance reach (R1) = 1.3718052 Ohm

Positive resistance reach secondary (R1) = 1.64616624 Ohm sec

Positive impedance reach (Z1) = 8.662327349 / 80.9 ° Ohm

Positive impedance reach secondary (Z1) = 10.39479282 / 80.9 ° Ohm sec

Zero reactive reach (X0) = 42.47433 j Ohm

Zero reactive reach secondary (X0) = 50.969196 j Ohm sec

Zero resistance reach (R0) = 6.8203665 Ohm

Zero resistance reach secondary (R0) = 8.1844398 Ohm sec

Zero impedance reach (Z0) = 43.01843916 / 80.9 ° Ohm

Zero impedance reach secondary (Z0) = 51.622127 / 80.9 ° Ohm sec


10 OF 27

RELAY SETTING CALCULATIONS

SUBSTATION BANG KLA PANEL BAK2YB-01

So set :
GROUP 1 DIST. ELEMENTS

Z2 Ph. Reach = 10.39 Ohm sec

Z2 Ph. Angle = 80.90 deg

R2 Ph. Resistive = 24 Ohm

Z2 Tilt Top Line = 0 deg

Z2 Sensit. Iph>2 = 250 mA

Z2 Gnd. Reach = 10.39 Ohm sec

Z2 Gnd. Angle = 80.9 deg

Z2 Dynamic Tilt = Disabled

Z2 Tilt Top Line = 0 deg

kZN2 Res. Comp. = 1.00

kZN2 Res. Angle = 0 deg

R2 Gnd Resistive = 48 Ohm

Z2 Sensit Ignd>1 = 150 mA

GROUP 1 SCHEME LOGIC

Zone2 Tripping = Phase And Ground

tZ2 Ph. Delay = 300 ms

tZ2 Gnd. Delay = 300 ms


11 OF 27

RELAY SETTING CALCULATIONS

SUBSTATION BANG KLA PANEL BAK2YB-01

ZONE 3 REACH

Zone 3 Reach setting = 100 % of section I + 120 % Long line sec


II
Positive reactive reach (X1) = 15.7943 j Ohm

Positive reactive reach secondary (X1) = 18.95316 j Ohm sec

Positive resistance reach (R1) = 2.533224 Ohm

Positive resistance reach secondary (R1) = 3.0398688 Ohm sec

Positive impedance reach (Z1) = 15.99616005 / 80.9 ° Ohm

Positive impedance reach secondary (Z1) = 19.19539206 / 80.9 ° Ohm sec

Zero reactive reach (X0) = 78.4346 j Ohm

Zero reactive reach secondary (X0) = 94.12152 j Ohm sec

Zero resistance reach (R0) = 12.59473 Ohm

Zero resistance reach secondary (R0) = 15.113676 Ohm sec

Zero impedance reach (Z0) = 79.43937123 / 80.9 ° Ohm

Zero impedance reach secondary (Z0) = 95.32724547 / 80.9 ° Ohm sec


12 OF 27

RELAY SETTING CALCULATIONS

SUBSTATION BANG KLA PANEL BAK2YB-01

So set :
GROUP 1 DIST. ELEMENTS

Z3 Ph. Reach = 19.20 Ohm sec

Z3 Ph. Angle = 80.90 deg

R3 Ph. Resistive = 30 Ohm

Z3 Tilt Top Line = 0 deg

Z3 Sensit. Iph>3 = 250 mA

Z3 Gnd. Reach = 19.20 Ohm sec

Z3 Gnd. Angle = 80.9 deg

Z3 Dynamic Tilt = Disabled

Z3 Tilt Top Line = 0 deg

kZN3 Res. Comp. = 1.00

kZN3 Res. Angle = 0 deg

R3 Gnd Resistive = 48 Ohm

Z3 Sensit Ignd>1 = 150 mA

GROUP 1 SCHEME LOGIC

Zone3 Tripping = Phase And Ground

tZ3 Ph. Delay = 600 ms

tZ3 Gnd. Delay = 600 ms


13 OF 27

RELAY SETTING CALCULATIONS

SUBSTATION BANG KLA PANEL BAK2YB-01

ZONE 4 REACH

Zone 1 Reach setting = 15 % of ZONE 1

Positive reactive reach (X1) = 0.66215595 j Ohm

Positive reactive reach secondary (X1) = 0.79458714 j Ohm sec

Positive resistance reach (R1) = 0.106202196 Ohm

Positive resistance reach secondary (R1) = 0.127442635 Ohm sec

Positive impedance reach (Z1) = 0.670618676 / 80.9 ° Ohm

Positive impedance reach secondary (Z1) = 0.804742411 / 80.9 ° Ohm sec

Zero reactive reach (X0) = 3.2882709 j Ohm

Zero reactive reach secondary (X0) = 3.94592508 j Ohm sec

Zero resistance reach (R0) = 0.528018045 Ohm

Zero resistance reach secondary (R0) = 0.633621654 Ohm sec

Zero impedance reach (Z0) = 3.330394656 / 80.9 ° Ohm

Zero impedance reach secondary (Z0) = 3.996473588 / 80.9 ° Ohm sec


14 OF 27

RELAY SETTING CALCULATIONS

SUBSTATION BANG KLA PANEL BAK2YB-01

So set :
GROUP 1 DIST. ELEMENTS

Z4 Ph. Reach = 0.80 Ohm sec

Z4 Ph. Angle = 80.90 deg

R4 Ph. Resistive = 30 Ohm

Z4 Tilt Top Line = 0 deg

Z4 Sensit. Iph>1 = 250 mA

Z4 Gnd. Reach = 0.80 Ohm sec

Z4 Gnd. Angle = 80.9 deg

Z4 Dynamic Tilt = Disabled

Z4 Tilt Top Line = 0 deg

kZN4 Res. Comp. = 1.00

kZN4 Res. Angle = 0 deg

R4 Gnd Resistive = 48 Ohm

Z4 Sensit Ignd>1 = 150 mA

GROUP 1 SCHEME LOGIC

Zone4 Tripping = Phase And Ground

tZ4 Ph. Delay = 600 ms

tZ4 Gnd. Delay = 600 ms


15 OF 27

RELAY SETTING CALCULATIONS

SUBSTATION BANG KLA PANEL BAK2YB-01

ZONE PSB

Zone 5 Reach setting = 130 % of Z3 Ph. Reach

Positive impedance reach (Z5) = 20.795 / 81 ° Ohm

Positive impedance reach secondary (Z5) = 24.954 / 81 ° Ohm sec

Zone 6 Reach setting = 150 % of Z3 Ph. Reach

Positive impedance reach (Z6) = 23.994 / 81 ° Ohm

Positive impedance reach secondary (Z6) = 28.793 / 81 ° Ohm sec

Zone 5 Reach setting = 40 % of Minimum Load

Positive resistance reach (R5) = 16.531 Ohm

Positive resistance reach secondary (R5) = 19.838 Ohm sec

Zone 6 Reach setting = 60 % of Minimum Load

Positive resistance reach (R6) = 24.797 Ohm

Positive resistance reach secondary (R6) = 29.756 Ohm sec


16 OF 27

RELAY SETTING CALCULATIONS

SUBSTATION BANG KLA PANEL BAK2YB-01

Synchronize Relay Protection (25)

Setting live line voltage = 80 % Un

So,Setting live line voltage = 53.12 VL-N

Setting dead line voltage = 30 % % Un

So,Setting dead line voltage = 19.92 VL-N

Setting differential voltage = 20 % Un

So, Setting differential voltage = 13.28 VL-N

Setting differential angle = 25 deg

So, Setting differential angle = 25 deg

Setting differential frequency = 0.2 Hz

So, Setting differential frequency = 200 mHz

CB Fail (CB FAIL & P.DEAD)

CB Fail 1 Timer = 200 ms

UNDER CURRENT

I< Current Set (3I0) = 30 % In

So, Setting I< Current Set (3I0) = 300 mA

ISEF< Current (I0) = 10 % In

So, Setting ISEF< Current (I0) = 100 mA

POLEDEAD VOLTAGE

V< (3V0) = 30 % Un

So, Setting V< (3V0) = 34.5 V


17 OF 27

RELAY SETTING CALCULATIONS

SUBSTATION BANG KLA PANEL BAK2YB-01

AUTORECLOSE

Three Pole Shot = 1

Dead Time 1 = 1 S

AR CBHealthyTime = 5 S

Reclaim Time = 5 S

AR Inhibit Time = 10 S

AR CheckSyncTime = 10 S

VT Fail

VT Fail Timer = 5 s

V0 detaction = 10 % Un

So, Setting V0 detact = 11.5 V

3V0 detaction = 30 % Un

So, Setting V0 detact = 34.5 V

SOTF

SOTF Delay = 10 s

SOTF Tripping = All zone


18 OF 27

RELAY SETTING CALCULATIONS

SUBSTATION BANG KLA PANEL BAK2YB-01

RELAY SETTING CALCULATION


P443
Directional overcurrent Protection (67/67N)
19 OF 27

RELAY SETTING CALCULATIONS

SUBSTATION BANG KLA PANEL BAK2YB-01

SUBSTATION : BANG KLA


LINE PROTECTION : BAK2YB-01 TO : HSR1YB-01 HUA SOMRONG
RELAY TYPE : P443 S/N :
MANUFACTURER : Alstom
PANAL : BAK2YB-01
FUNCTION : 67/67N

SYSTEM DATA

CAPACITY OF PROTECTED LINE = 1800 A


PT RATIO = 115 / 115 kV/V
CT RATIO = 1200 / 1 A

PHASE DIRECTIONAL OVERCURRENT PROTECTION RELAY (67)

Select minimum pick up = 100 % CAPACITY OF PROTECTED LINE

Primary current = 1800 A pri

Secondary current = 1.50 A sec

Time characterristic cure = DT

Operating time = 0.5 s

Direction = forward

GROUND DIRECTIONAL OVERCURRENT PROTECTION RELAY (67N)

Select minimum pick up = 30 % CAPACITY OF PROTECTED LINE

Primary current = 540 A pri

Secondary current = 0.45 A sec

Time characterristic cure = DT

Operating time = 0.5 s

Direction = forward
20 OF 27

PARAMETER SET SHEET

SUBSTATION BANG KLA PANEL BAK2YB-01

PARAMETER SET SHEET


P443
21 OF 27

PARAMETER SET SHEET

SUBSTATION BANG KLA PANEL BAK2YB-01


PARAMETER SETTING
SYSTEM DATA
Description MiCOM P443
Plant Reference BAK2YB-01
Sys Fn Links 0
Language English
Frequency 50 Hz
CONFIGURATION
Setting Group Select via Menu
Active Settings Group 1
Setting Group 1 Enabled
Setting Group 2 Disabled
Setting Group 3 Disabled
Setting Group 4 Disabled
Distance Disabled
Directional E/F Disabled
Phase Diff Disabled
Overcurrent Disabled
Neg Sequence O/C Disabled
Broken Conductor Disabled
Earth Fault Disabled
SEF/REF Prot'n Disabled
Residual O/V NVD Disabled
Thermal Overload Disabled
PowerSwing Block Disabled
Volt Protection Disabled
Freq Protection Disabled
df/dt Protection Disabled
CB Fail Disabled
Supervision Enabled
System Checks Enabled
Auto-Reclose Enabled
Input Labels Visible
Output Labels Visible
CT & VT Ratios Visible
Record Control Visible
Disturb Recorder Visible
Measure't Setup Visible
Comms Settings Visible
Commission Tests Visible
Setting Values Secondary
Control Inputs Visible
Ctrl I/P Config Visible
Ctrl I/P Labels Visible
Direct Access Enabled
Function Key Visible
22 OF 27

PARAMETER SET SHEET

SUBSTATION BANG KLA PANEL BAK2YB-01


RP1 Read Only Disabled
NIC Read Only Disabled

CT AND VT RATIOS
Main VT Primary 115 kV
Main VT Sec'y 115 V
CS VT Primary 115 kV
CS VT Secondary 115 V
Phase CT Primary 1200 A
Phase CT Sec'y 1 A
SEF CT Primary 1200 A
SEF CT Secondary 1 A
MComp CT Primary 1200 A
MComp CT Sec'y 1 A
CS Input BN
Main VT Location Line
CT Polarity Standard
SEF CT Polarity Standard
M CT Polarity Standard
VT Connected Yes

GROUP 1 LINE PARAMETERS


Line Length 19.40 km
Line Impedance 6.312 Ohm
Line Angle 80.9 deg
kZN Res Comp 1
kZN Res Angle 0 deg
Mutual Comp Disabled
Phase Sequence Standard ABC
Tripping Mode 3 Pole
Line Charging Y 10 s
GROUP 1 DISTANCE SETUP
Setting Mode Advanced
Phase Chars. Mho
Zone 1 Ph Status Enabled
Zone 2 Ph Status Enabled
Zone 3 Ph Status Enabled
Zone 3 Ph Offset Disabled
Zone P Ph Status Disabled
Zone 4 Ph Status Enabled
Ground Chars. Quad
Zone 1 Gnd Stat. Enabled
Zone 2 Gnd Stat. Enabled
Zone 3 Gnd Stat. Enabled
Zone3 Gnd Offset Disabled
Zone P Gnd Stat. Disabled
23 OF 27

PARAMETER SET SHEET

SUBSTATION BANG KLA PANEL BAK2YB-01


Zone 4 Gnd Stat. Enabled
Digital Filter Standard
CVT Filters Disabled
Load Blinders Disabled
Dist. Polarizing 1
GROUP 1 DIST. ELEMENTS
Z1 Ph. Reach 5.36 Ohm
Z1 Ph. Angle 80.90 deg
R1 Ph. Resistive 19 Ohm
Z1 Tilt Top Line 0 deg
Z1 Sensit. Iph>1 250 mA
Z2 Ph. Reach 10.39 Ohm
Z2 Ph. Angle 80.90 deg
R2 Ph. Resistive 24 Ohm
Z2 Tilt Top Line 0 deg
Z2 Sensit. Iph>2 250 A
Z3 Ph. Reach 19.20 Ohm
Z3 Ph. Angle 80.90 deg
R3 Ph. Res. Fwd. 30 Ohm
Z3 Tilt Top Line 0 deg
Z3 Sensit. Iph>3 250 A
Z4 Ph. Reach 0.80 Ohm
Z4 Ph. Angle 80.90 deg
R4 Ph. Resistive 30 Ohm
Z4 Tilt Top Line 0 deg
Z4 Sensit. Iph>4 250 A
Z1 Gnd. Reach 5.36 Ohm
Z1 Gnd. Angle 80.9 deg
Z1 Dynamic Tilt Disabled
Z1 Tilt Top Line 0 deg
kZN1 Res. Comp. 1.00
kZN1 Res. Angle 0 deg
R1 Gnd Resistive 48.00 Ohm
Z1 Sensit Ignd>1 150 A
Z2 Gnd. Reach 10.39 Ohm
Z2 Gnd. Angle 80.9 deg
Z2 Dynamic Tilt Disabled
Z2 Tilt Top Line 0 deg
kZN2 Res. Comp. 1.00
kZN2 Res. Angle 0 deg
R2 Gnd Resistive 48.00 Ohm
Z2 Sensit Ignd>2 150 A
Z3 Gnd. Reach 19.20 Ohm
Z3 Gnd. Angle 80.90 deg
Z3 Dynamic Tilt Disabled
Z3 Tilt Top Line 0.00 deg
24 OF 27

PARAMETER SET SHEET

SUBSTATION BANG KLA PANEL BAK2YB-01


kZN3 Res. Comp. 1.00
kZN3 Res. Angle 0.00 deg
R3 Gnd. Res. Fwd 48.00 Ohm
Z3 Sensit Ignd>3 150.00 A
Z4 Gnd. Reach 0.80 Ohm
Z4 Gnd. Angle 80.90 deg
Z4 Dynamic Tilt Disabled
Z4 Tilt Top Line 0.00 deg
kZN4 Res. Comp. 1.00
kZN4 Res. Angle 0.00 deg
R4 Gnd Resistive 48.00 Ohm
Z4 Sensit Ignd>4 150.00 A
GROUP 1 SCHEME LOGIC
BASIC SCHEME
Zone1 Tripping Phase And Ground
tZ1 Ph. Delay 0 s
tZ1 Gnd. Delay 0 s
Zone2 Tripping Phase And Ground
tZ2 Ph. Delay 300 ms
tZ2 Gnd. Delay 300 ms
Zone3 Tripping Phase And Ground
tZ3 Ph. Delay 600 ms
tZ3 Gnd. Delay 600 ms
ZoneP Tripping Phase And Ground
tZP Ph. Delay 600 ms
tZP Gnd. Delay 600 ms
Zone4 Tripping Phase And Ground
tZ4 Ph. Delay 600 ms
tZ4 Gnd. Delay 600 ms
AIDED SCHEME 1
Aid. 1 Selection POR
Aid 1 Distance Phase And Ground
Aid.1 Dist. Dly 0 s
Aid. 1 DEF Disabled
Aid. 1 Delta Disabled
tRev. Guard 20 ms
Send On Trip Aided / Z1
Weak Infeed Disabled
AIDED SCHEME 2
Aid. 2 Selection Disabled
Trip On Close
SOTF Status Enabled PoleDead
SOTF Delay 10 s
SOTF Tripping 00010111
TOR Status Enabled
TOR Tripping 00000001
25 OF 27

PARAMETER SET SHEET

SUBSTATION BANG KLA PANEL BAK2YB-01


TOC Reset Delay 500 ms
TOC Delay 200 ms
Z1 Extension
Z1 Ext Scheme Disabled
Loss Of Load
LOL Scheme Disabled

GROUP 1 POWER SWING BLK.


PSB Status Blocking
Zone 1 Ph. PSB Blocking
Zone 2 Ph. PSB Allow Trip
Zone 3 Ph. PSB Allow Trip
Zone P Ph. PSB Allow Trip
Zone 4 Ph. PSB Allow Trip
Zone 1 Gnd. PSB Blocking
Zone 2 Gnd. PSB Allow Trip
Zone 3 Gnd. PSB Allow Trip
Zone P Gnd. PSB Allow Trip
Zone 4 Gnd. PSB Allow Trip
Slow PSB Enabled
PSB Unblocking Disabled
PSB Reset Delay 200 ms
OST Mode OST Disabled
Z7 24.95 Ohm
Z8 28.79 Ohm
Z7' -24.95 Ohm
Z8' -28.79 Ohm
R7 19.84 Ohm
R8 29.76 Ohm
R7' -19.84 Ohm
R8' -29.76 Ohm
Blinder Angle 81 deg
delta T 40 ms
Tost 0 s
GROUP 1 CB FAIL & P.DEAD
BREAKER FAIL
CB Fail 1 Status Enabled
CB Fail 1 Timer 200 ms
CB Fail 2 Status Disabled
Volt Prot Reset I< Only
Ext Prot Reset I< Only
WI Prot Reset Disabled
UNDER CURRENT
I< Current Set 300 mA
26 OF 27

PARAMETER SET SHEET

SUBSTATION BANG KLA PANEL BAK2YB-01


ISEF< Current 300 mA
POLEDEAD VOLTAGE
V< 30 V
I< 300 mA
GROUP 1 SUPERVISION
VTS Mode Measured + MCB
VTS Status Blocking
VTS Reset Mode Auto
VTS Time Delay 5 s
VTS I> Inhibit 1.2 A
VTS I2> Inhibit 50 mA
Inrush Detection Disabled

WI Inhibit Disabled

CTS Mode Disabled

GROUP 1 SYSTEM CHECKS


VOLTAGE MONITORS
Live Live 53 V
Dead Live 20 V
Live Bus 53 V
Dead Bus 20 V
CS UV 53 V
CS OV 73 V
System Checks Enabled
CS Voltage Block V< >V and Vdiff >
CS1 Status Enabled
CS1 Angle 25 deg
CS1VDiff 13 V
CS1 Slip Ctrl Enabled
CS1 SlipFreq 200 mHz
SS Status Disabled
GROUP 1 AUTORECLOSE
AR Mode AR Opto
AR Shots 1
AR Skip Shot 1 Disabled
Mult Phase AR AIIow Autoclose
Discrim Time 100 ms
CB IS Time 5 s
CB IS MemoryTime 500 ms
DT Start By Prot Protection Reset
3PDTStart WhenLD Disabled
DTStart by CB Op Disabled
SP AR Dead Time 1 s
3P AR DT Shot 1 1 s
27 OF 27

PARAMETER SET SHEET

SUBSTATION BANG KLA PANEL BAK2YB-01


3P AR DT Shot 2 60 s
3P AR DT Shot 3 60 s
3P AR DT Shot 4 60 s
SPAR ReclaimTime 5 s
3SPAR ReclaimTime 5 s
AR CBHealthyTime 5 s
AR CheckSyncTime 5 s
Z1 AR Initiate AR
Dist Aided AR Initiate AR
Z2T AR Block AR
Z3T AR Block AR
ZPT AR Block AR
Z4T AR Block AR
DEF Aided AR Block AR
TOR AR Block AR
I>1 AR Block AR
IN>1 AR Block AR
AR SYS CHECKS
CB SC All Enabled
CB SC Shot 1 Enabled
CB SC ClsNoDly Disabled
CB SC CS1 Enabled
CB SC CS2 Disabled
CB SC DLLB Enabled
CB SC LLDB Enabled
CB SC DLDB Disabled