Name of Customer POWER TRANSMISSION CORPORATION OF UTTARAKHAND LIMITED

Name of SubStation 132kV S/S Laltappar, Ddun


Feeder Name 132kV Laltappar-Majra Line
Panel Serial No
RELAY Serial No
RELAY Order Code
RELAY Make GE Date of Commissioning

R1 +jX1 R0+JX0
Panther 0.1603+0.408j 0.480+1.216j Conductor Selected Panther
Zebra(132KV) 0.0793+0.3975j 0.2702+1.2936j
Moose 0.0299+0.3068j 0.3603+1.3478j
Deer 0.0804+0.4100j 0.2814+1.4350j

132KV Majra-Kulhal Line


41.77 KM

132KV Laltappar-Majra Line


28.38 KM

132KV Majra-Bindal Line


8.54 KM
132kV S/S Laltappar, Ddun 132kV Sub station Majra

Protected Line Length 28.38 KM 132KV Laltappar-Majra Line


Adjacent Longest Line Length 41.77 KM 132KV Majra-Kulhal Line
Adjacent Shortest Line Length 8.54 KM 132KV Majra-Bindal Line
Adjacent Sub Station Name 132kV Sub station Majra

C.T.Primary = 800 A P.T.Primary = 132000 V


C.T.Secondary = 1 A P.T.Secondary = 110 V

IMPEDANCE Z = R + X j Ω
Positive Secquence Impedance Z₁primary = 0.1603+0.408j Ω/K.M.
Zero Secquence Impedance Z₀primary = 0.480+1.216j Ω/K.M.
Arc Resistance (Primary value) = 5 Ω
Tower Foot Resistance (Primary value) = 10 Ω

ZONE 1 = 80.00% of Protected Line Length


ZONE 2 = 100.00% of Protected Line Length + 50.00% Adjacent Shortest Line Length
ZONE 3 = 100.00% of Protected Line Length + 100.00% Adjacent Longest Line Length
ZONE 4 = 25.00% of Zone1 Distance

CT RATIO 800 PT RATIO 1200

CTR/PTR 0.6667

Arc Resistance(Secondary) 3.333 Ω


Tower Foot Resistance(Secondary) 6.667 Ω
Converting Impedance value Rectangular form to Polarform

Positive Secquence Impedance Z₁primary 0.4384 ∠68.5505


Zero Secquence Impedance Z₀primary 1.3073 ∠68.459

Converting Primary Impedance value to Secondary Impedance value


Per K.M. SECONDARY IMPEDANCE =Per K.M. Primary Impedance * (CTR/PTR)

Positive Secquence Impedance Z₁secondary 0.2922 ∠68.5505


Zero Secquence Impedance Z₀secondary 0.8715 ∠68.459
TOTAL IMPEDANCE VALUE= PROTECTED LINE LENGTH K.M.*Per K.M. Secondary Impedance

Total Positive Secquence Impedance Z ₁secondary 8.2938 ∠68.5505


Total Zero Secquence Impedance Z ₀secondary 24.7343 ∠68.459

Z₀/Z₁ Magnitude 2.982267185605 Ω Z₀/Z₁ Angle -.0915 Deg.

Converting Polar to Rectangular Form

Z₁ 0.1069+0.272j Ω/K.M. Z₀ 0.32+0.8107j Ω/K.M.


R₁ 0.1069 Ω/K.M. R₀ 0.32 Ω/K.M.
X₁ 0.272 Ω/K.M. X₀ 0.8107 Ω/K.M.

ZONE 1
ZONE 1 80.00% of Protected Line Length

ZONE 1 DISTANCE 22.704 K.M.

ZONE 1 REACH IMPEDANCE = ZONE 1 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE

ZONE 1 Positive Secquence IMPEDANCE Z₁ = 6.6350 ∠68.5505


ZONE 1 Zero Secquence IMPEDANCE Z₀ = 19.7874 ∠68.459

Z₁ = 2.4263+6.1755j Z₀ 7.2653+18.4054j
R₁ = 2.4263 R₀ 7.2653
X₁ = 6.1755 X₀ 18.4054

Phase to Phase Blinder Calculation


Quad Right Blinder 8.1859 2*R₁+Arc resistance
Quad Left Blinder 4.093 (2*R₁+Arc resistance)/2

Phase to GROUND Blinder Calculation


Quad Right Blinder 22.1179 2*R₁+R₀+ArcResistance+TowerFootResistance
Quad Left Blinder 11.059 (2*R₁+R₀+ArcResistance+TowerFootResistance)/2

ZONE 2
ZONE 2 = 100.00% of Protected Line Length + 50.00% Adjacent Longest Line Length

ZONE 2 DISTANCE = 32.65 K.M.

ZONE 2 REACH IMPEDANCE = ZONE 2 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE

ZONE 2 Positive Secquence IMPEDANCE Z₁ = 9.5417 ∠68.5505


ZONE 2 Zero Secquence IMPEDANCE Z₀ = 28.4558 ∠68.459
Z₁ 3.4892+8.8808j Z₀ 10.448+26.4683j
R₁ 3.4892 R₀ 10.448
X₁ 8.8808 X₀ 26.4683

Phase to Phase Blinder Calculation


Quad Right Blinder 10.3117 2*R₁+Arc resistance
Quad Left Blinder 5.1559 (2*R₁+Arc resistance)/2

Phase to GROUND Blinder Calculation


Quad Right Blinder 27.4264 2*R₁+R₀+ArcResistance+TowerFootResistance
Quad Left Blinder 13.7132 (2*R₁+R₀+ArcResistance+TowerFootResistance)/2
ZONE 3
ZONE 3 = 100.00% of Protected Line Length + 100.00% Adjacent Longest Line Length

ZONE 3 DISTANCE 70.15 K.M.

ZONE 3 REACH IMPEDANCE = ZONE 3 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE

ZONE 3 Positive Secquence IMPEDANCE Z₁ = 20.5 ∠68.5505


ZONE 3 Zero Secquence IMPEDANCE Z₀ = 61.1385 ∠68.459

Z₁ 7.4967+19.0808j Z₀ 22.448+56.8683j
R₁ 7.4967 R₀ 22.448
X₁ 19.0808 X₀ 56.8683
Phase to Phase Blinder Calculation
Quad Right Blinder 18.3267 2*R₁+Arc resistance
Quad Left Blinder 9.163366666667 (2*R₁+Arc resistance)/2
Phase to GROUND Blinder Calculation
Quad Right Blinder 47.4414 2*R₁+R₀+ArcResistance+TowerFootResistance
Quad Left Blinder 23.7207 (2*R₁+R₀+ArcResistance+TowerFootResistance)/2

ZONE 4
ZONE 4 25.00% of Zone1 Distance
ZONE 4 DISTANCE 5.676 K.M.

ZONE 4 REACH IMPEDANCE = ZONE 4 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE

ZONE 4 Positive Secquence IMPEDANCE Z₁ = 1.6588 ∠68.5505


ZONE 4 Zero Secquence IMPEDANCE Z₀ = 4.9469 ∠68.459

Z₁ = 0.6066+1.5439j Z₀ 1.8163+4.6013j
R₁ = 0.6066 R₀ 1.8163
X₁ = 1.5439 X₀ 4.6013

Phase to Phase Blinder Calculation


Quad Right Blinder 4.546533333333 2*R₁+Arc resistance
Quad Left Blinder 2.273266666667 (2*R₁+Arc resistance)/2

Phase to GROUND Blinder Calculation


Quad Right Blinder 13.0295 2*R₁+R₀+ArcResistance+TowerFootResistance
Quad Left Blinder 6.5148 (2*R₁+R₀+ArcResistance+TowerFootResistance)/2

FAULT REPORT
SETTING PARAMETER
Fault Report 1 Source SRC 1 (SRC1)
Fault Report 1 Trigger FINAL TRIP
Fault Report 1 Positive Seq (Z1) Mag 8.29
Fault Report 1 Positive Seq (Z1) Angle ∠68.5505
Fault Report 1 Zero Seq (Z0) Mag 24.73
Fault Report 1 Zero Seq (Z0) Angle ∠68.459
Fault Report 1 Line Length Units K.M.
Fault Report 1 Line Length 28.38
Fault Report 1 VT Substitution None
Fault Report 1 System Z0 Mag 2.00 ohms
Fault Report 1 System Z0 Angle 75 deg

PARAMETER CT F1
Phase CT Primary 800 A
Phase CT Secondary 1 A
Ground CT Primary 800 A
Ground CT Secondary 1 A

PARAMETER VT F5
Phase VT Connection Wye
Phase VT Secondary 63.5 V
Phase VT Ratio 1200.00 : 1
Auxiliary VT Connection Vag
Auxiliary VT Secondary 63.5 V
Auxiliary VT Ratio 1200.00 : 1

SETTING PARAMETER
Nominal Frequency 50 Hz
Phase Rotation ABC
Frequency And Phase Reference SRC 1 (SRC 1)
Frequency Tracking Function Enabled

PARAMETER SOURCE 1 SOURCE 2


Name SRC 1 SRC 2
Phase CT F1 None
Ground CT F1 None
Phase VT F5 None
Aux VT F5 None

PHASE DISTANCE

PARAMETER ZONE 1 ZONE 2 ZONE 3 ZONE 4


Function Enabled Enabled Enabled Enabled
Direction Forward Forward Forward Reverse
Shape
Xfmr Vol Connection None None None None
Xfmr Curr Connection None None None None
Reach 6.64 9.54 20.5 1.66
RCA 68.55 68.55 68.55 68.55
Rev Reach 1.6588 1.6588 1.6588 1.6588
Rev Reach RCA 68.55 68.55 68.55 68.55
Comp Limit 90 90 90 90
DIR RCA 68.55 68.55 68.55 68.55
DIR Comp Limit 90 90 90 90
Quad Right Blinder 8.19 10.31 18.33 4.55
Quad Right Blinder RCA 68.55 68.55 68.55 68.55
Quad Left Blinder 4.09 5.16 9.16 2.27
Quad Left Blinder RCA 68.55 68.55 68.55 68.55
Supervision 0.200 pu 0.200 pu 0.200 pu 0.200 pu
Volt Level 0.000 pu 0.000 pu 0.000 pu 0.000 pu
Delay 0.000 s 0.350 s 0.800 s 1.000 s
Block
Target Latched Latched Latched Latched
Events Enabled Enabled Enabled Enabled

GROUND DISTANCE

PARAMETER ZONE 1 ZONE 2 ZONE 3 ZONE 4


Function Enabled Enabled Enabled Enabled
Direction Forward Forward Forward Reverse
Shape
Z0/Z1 Mag 2.98 2.98 2.98 2.98
Z0/Z1 Ang -0.09 -0.09 -0.09 -0.09
Z0M/Z1 Mag 0 0 0 0
Z0M/Z1 Ang 0 deg 0 deg 0 deg 0 deg
Reach 6.64 9.54 20.5 1.66
RCA 68.55 68.55 68.55 68.55
Rev Reach 1.6588 1.6588 1.6588 1.6588
Rev Reach RCA 68.55 68.55 68.55 68.55
POL Current Zero-seq Zero-seq Zero-seq Zero-seq
Non-Homogen Ang 0.0 deg 0.0 deg 0.0 deg 0.0 deg
Comp Limit 90 90 90 90
DIR RCA 68.55 68.55 68.55 68.55
DIR Comp Limit 90 90 90 90
Quad Right Blinder 22.12 27.43 47.44 13.03
Quad Right Blinder RCA 68.55 68.55 68.55 68.55
Quad Left Blinder 11.06 13.71 23.72 6.51
Quad Left Blinder RCA 68.55 68.55 68.55 68.55
Supervision 0.200 pu 0.200 pu 0.200 pu 0.200 pu
Volt Level 0.000 pu 0.000 pu 0.000 pu 0.000 pu
Delay 0.000 s 0.350 s 0.800 s 1.000 s
Block
Target Latched Latched Latched Latched
Events Enabled Enabled Enabled Enabled

POWER SWING SETTING IN GE


SETTING PARAMETER
Function Enabled
Source SRC1
Shape Quad Shape
Mode Two Step
Supv 0.6 PU
Fwd Reach 24.6 Ohms
Quad Fwd Out 29.52 Ohms
Fwd RCA 68.55052576507 deg
Rev Reach 4.92 Ohms
Quad Rev Mid 60 Ohms
Quad Rev Out 5.904 Ohms
Rev RCA 68.55052576507 deg
Outer Limit Angle 120 deg
Middle Limit Angle 90 deg
Inner Limit Angle 60 deg
Outer Right Blinder 27.495 Ohms
Outer Left Blinder 4.58 Ohms
Middle Right Blinder 24.7455 Ohms
Middle Left Blinder 3.206 Ohms
Inner Right Blinder 21.996 Ohms
Inner Left Blinder 1.832 Ohms
Delay 1 Pickup 0.1 seconds time required to declare PSB when locus travels from Outer to
Delay 1 Reset 0.05 seconds Once PSB is declared PSB will be in hold condition for this m
Delay 2 Pickup 0.017 seconds only for three step mode:
Delay 3 Pickup 2 seconds time delay to declare PSB Trip when locus is present in the Inn
Delay 4 Pickup 0.017 seconds only for delayed tripping mode
Seal-In-Delay 0.4 seconds
Trip Mode Early Mode
Block OFF
Target Latched
Events Enabled
TANTRANSCO
MADHYA PRADESH POWER TRANSMISSION
HARYANA
POWER TRANSMISSION
VIDYUT
COMPANY
BIHAR
PRASARAN
CORPORATION
STATE
LIMITED
NIGAM
POWERLIMITED
TRANSMISSION
OF UTTARAKHA
TANTRANSCO MPPTCL HVPNL PTCUL BSPTCL
ZONE2 TANTRANSCO 0.300 s 0.350 s 0.350 s 0.300 s
ZONE3 TANTRANSCO 0.700 s 1.000 s 0.800 s 0.700 s
ZONE4 TANTRANSCO 1.000 s 1.000 s 1.000 s 1.000 s

Zone setting Selection


Z1 Z2 (KM) Z3 (KM)
22.70 34.06 75.83
32.65 80.59
whichever is higher whichever is lower
34.06 75.83
us travels from Outer to Inner but locus is between Inner and Outer locus for this much specified time
hold condition for this much specified time

ocus is present in the Inner region for this much of time


TRANSMISSION COMPANY LIMITED
P442 Setting Calculation for 132KV

R1 X1
2 Conductor ACSR Panther 0.1603 0.4080
ACSR Zebra 0.0793 0.3975
MOOSE 0.0299 0.3068

DEER
(PTCUL) 0.0804 0.4100

System Voltage 132 KV


1 Line Length 28.38 KM 132KV Laltappar-Majra Line
2 conductor Panther 0.1603 0.4080
3 Adjacent Shortest Line 8.54 KM 132KV Majra-Bindal Line

4 Adjacent Longest Line 41.77 KM 132KV Majra-Kulhal Line

5 Fault Mva
6 Fault Mva Other end
7 CTR 800 /1A CTR/PTR
8 PTR 1200 0.666667
9 Shortest line from Bus KM
Tower Footing Resistance in
10 Ohms 10
11 Arc Resistance in Ohms 5

DPR Calculations Positive Seq.Primary Impedances


km R X Impedanc Angle
Zone1 80% 22.70 3.64 9.26 9.95 68.55

Zone2 100% LL + 50% OF SL 32.65 5.23 13.32 14.31 68.55


Zone3 120% LL + 100% OF LL 75.83 12.15 30.94 33.24 68.55
Zone4 25% of Z1 5.68 0.91 2.32 2.49 68.55

------> Values to be entered

-------> Calculated Values

-------> Values to be entered to relay


POWER SWING SETTING IN GE
SETTING PARAMETER
Function Enabled
Source SRC1
Shape Quad Shape
Mode Two Step
Supv 0.6 PU
Fwd Reach 26.5913098300155 Ohms
Quad Fwd Out 31.9095717960186 Ohms
Fwd RCA 68.5505257650744 deg
Rev Reach 5.31826196600311 Ohms
Quad Rev Mid 60 Ohms
Quad Rev Out 6.38191435920373 Ohms
Rev RCA 68.5505257650744 deg
Outer Limit Angle 120 deg
Middle Limit Angle 90 deg
Inner Limit Angle 60 deg
Outer Right Blinder 29.3098156 Ohms
Outer Left Blinder 4.88496926666667 Ohms
Middle Right Blinder 26.37883404 Ohms
Middle Left Blinder 3.41947848666667 Ohms
Inner Right Blinder 23.44785248 Ohms
Inner Left Blinder 1.95398770666667 Ohms
Delay 1 Pickup 0.1 seconds time required to declare PSB when locus travels from Outer to Inner b
Delay 1 Reset 0.05 seconds Once PSB is declared PSB will be in hold condition for this much spe
Delay 2 Pickup 0.017 seconds only for three step mode:
Delay 3 Pickup 2 seconds time delay to declare PSB Trip when locus is present in the Inner regio
Delay 4 Pickup 0.017 seconds only for delayed tripping mode
Seal-In-Delay 0.4 seconds
Trip Mode Early Mode
Block OFF
Target Latched
Events Enabled
g Calculation for 132KV Laltappar-Majra Line at 132KV S/S Laltappar

Z1 Angle R0 X0 Z0 Angle Rm Xm Zm0


0.4384 68.5505 0.3603 1.3478 1.3951 75.0334 0.2049 0.5402 0.5778
0.4053 78.7178 0.2702 1.2936 1.3215 78.2020 0.1907 0.4931 0.5287
0.3083 84.4400 0.2936 1.1034 1.1418 75.1000

0.4178 78.9052 0.2814 1.4350 1.4623 78.9052

132KV Laltappar-Majra Line


0.4384 68.5505 0.3603 1.3478 1.3951 75.0334
132KV Majra-Bindal Line

132KV Majra-Kulhal Line

EARTH COMPENSATION Fault Report


Z0/Z1 Angle 100% Line TOTAL Z1 8.29 68.55
3.18 6.48 Length TOTAL Z0 26.40 75.03

Zero seq.Pri. Impedances Positive Seq.Sec. Impedances Zero seq.Sec. Impedances


R0 X0 Z0 Angle R X Impedan Angle R0
8.18 30.60 31.67 75.03 2.43 6.18 6.64 68.55 5.45

11.76 44.01 45.55 75.03 3.49 8.88 9.54 68.55 7.84


27.32 102.20 105.79 75.03 8.10 20.62 22.16 68.55 18.21
2.05 7.65 7.92 75.03 0.61 1.54 1.66 68.55 1.36

BLINDERS
RpH LPH RG
Z1 8.19 4.09 20.31
Z2 10.31 5.16 24.82
Z3 19.54 9.77 44.42
Z4 4.55 2.27 12.58
PSB when locus travels from Outer to Inner but locus is between Inner and Outer locus for this much specified time
SB will be in hold condition for this much specified time

B Trip when locus is present in the Inner region for this much of time
ar

Angle
69.2281
68.8567

Zero seq.Sec. Impedances


X0 Z0 Angle
20.40 21.12 75.03

29.34 30.37 75.03


68.13 70.52 75.03
5.10 5.28 75.03

LG
10.15
12.41
22.21
6.29
Name of Customer POWER TRANSMISSION CORPORATION OF UTTARAKHAND LIMITED
Name of SubStation 132kV S/S Laltappar, Ddun
Feeder Name 132kV Laltappar-Rishikesh Line
Panel Serial No
RELAY Serial No
RELAY Order Code
RELAY Make GE Date of Commissioning

R1 +jX1 R0+JX0
Panther 0.1603+0.408j 0.480+1.216j Conductor Selected Panther
Zebra(132KV) 0.0793+0.3975j 0.2702+1.2936j
Moose 0.0299+0.3068j 0.3603+1.3478j
Deer 0.0804+0.4100j 0.2814+1.4350j

132KV Rishikesh-Shrinagar Line


78 KM

132KV Laltappar-Rishikesh Line


16.03 KM

132KV Rishikesh-Jwalapur Line


22.97 KM
132kV S/S Laltappar, Ddun 220kV Substation Rishikesh

Protected Line Length 16.03 KM 132KV Laltappar-Rishikesh Line


Adjacent Longest Line Length 78.00 KM 132KV Rishikesh-Shrinagar Line
Adjacent Shortest Line Length 22.97 KM 132KV Rishikesh-Jwalapur Line
Adjacent Sub Station Name 220kV Substation Rishikesh
4
C.T.Primary = 800 A P.T.Primary = 132000 V
C.T.Secondary = 1 A P.T.Secondary = 110 V

IMPEDANCE Z = R + X j Ω
Positive Secquence Impedance Z₁primary = 0.1603+0.408j Ω/K.M.
Zero Secquence Impedance Z₀primary = 0.480+1.216j Ω/K.M.
Arc Resistance (Primary value) = 5 Ω
Tower Foot Resistance (Primary value) = 10 Ω

ZONE 1 = 80.00% of Protected Line Length


ZONE 2 = 100.00% of Protected Line Length + 50.00% Adjacent Shortest Line Length
ZONE 3 = 100.00% of Protected Line Length + 100.00% Adjacent Longest Line Length
ZONE 4 = 25.00% of Zone1 Distance

CT RATIO 800 PT RATIO 1200

CTR/PTR 0.6667

Arc Resistance(Secondary) 3.333 Ω


Tower Foot Resistance(Secondary) 6.667 Ω

Converting Impedance value Rectangular form to Polarform

Positive Secquence Impedance Z₁primary 0.4384 ∠68.5505


Zero Secquence Impedance Z₀primary 1.3073 ∠68.459

Converting Primary Impedance value to Secondary Impedance value


Per K.M. SECONDARY IMPEDANCE =Per K.M. Primary Impedance * (CTR/PTR)

Positive Secquence Impedance Z₁secondary 0.2922 ∠68.5505


Zero Secquence Impedance Z₀secondary 0.8715 ∠68.459
TOTAL IMPEDANCE VALUE= PROTECTED LINE LENGTH K.M.*Per K.M. Secondary Impedance

Total Positive Secquence Impedance Z ₁secondary 4.6846 ∠68.5505


Total Zero Secquence Impedance Z ₀secondary 13.9708 ∠68.459

Z₀/Z₁ Magnitude 2.982267185605 Ω Z₀/Z₁ Angle -.0915 Deg.

Converting Polar to Rectangular Form

Z₁ 0.1069+0.272j Ω/K.M. Z₀ 0.32+0.8107j Ω/K.M.


R₁ 0.1069 Ω/K.M. R₀ 0.32 Ω/K.M.
X₁ 0.272 Ω/K.M. X₀ 0.8107 Ω/K.M.

ZONE 1
ZONE 1 80.00% of Protected Line Length

ZONE 1 DISTANCE 12.824 K.M.

ZONE 1 REACH IMPEDANCE = ZONE 1 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE

ZONE 1 Positive Secquence IMPEDANCE Z₁ = 3.7477 ∠68.5505


ZONE 1 Zero Secquence IMPEDANCE Z₀ = 11.1766 ∠68.459

Z₁ = 1.3705+3.4881j Z₀ 4.1037+10.396j
R₁ = 1.3705 R₀ 4.1037
X₁ = 3.4881 X₀ 10.396

Phase to Phase Blinder Calculation


Quad Right Blinder 6.0743 2*R₁+Arc resistance
Quad Left Blinder 3.0372 (2*R₁+Arc resistance)/2

Phase to GROUND Blinder Calculation


Quad Right Blinder 16.8447 2*R₁+R₀+ArcResistance+TowerFootResistance
Quad Left Blinder 8.4224 (2*R₁+R₀+ArcResistance+TowerFootResistance)/2

ZONE 2
ZONE 2 = 100.00% of Protected Line Length + 50.00% Adjacent Longest Line Length

ZONE 2 DISTANCE = 27.515 K.M.


ZONE 2 REACH IMPEDANCE = ZONE 2 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE

ZONE 2 Positive Secquence IMPEDANCE Z₁ = 8.0410 ∠68.5505


ZONE 2 Zero Secquence IMPEDANCE Z₀ = 23.9804 ∠68.459

Z₁ 2.9404+7.4841j Z₀ 8.8048+22.3055j
R₁ 2.9404 R₀ 8.8048
X₁ 7.4841 X₀ 22.3055

Phase to Phase Blinder Calculation


Quad Right Blinder 9.2141 2*R₁+Arc resistance
Quad Left Blinder 4.6071 (2*R₁+Arc resistance)/2

Phase to GROUND Blinder Calculation


Quad Right Blinder 24.6856 2*R₁+R₀+ArcResistance+TowerFootResistance
Quad Left Blinder 12.3428 (2*R₁+R₀+ArcResistance+TowerFootResistance)/2

ZONE 3
ZONE 3 = 100.00% of Protected Line Length + 100.00% Adjacent Longest Line Length

ZONE 3 DISTANCE 94.03 K.M.

ZONE 3 REACH IMPEDANCE = ZONE 3 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE

ZONE 3 Positive Secquence IMPEDANCE Z₁ = 27.48 ∠68.5505


ZONE 3 Zero Secquence IMPEDANCE Z₀ = 81.9508 ∠68.459

Z₁ 10.0487+25.5762j Z₀ 30.0896+76.227j
R₁ 10.0487 R₀ 30.0896
X₁ 25.5762 X₀ 76.227
Phase to Phase Blinder Calculation
Quad Right Blinder 23.4307 2*R₁+Arc resistance
Quad Left Blinder 11.71536666667 (2*R₁+Arc resistance)/2
Phase to GROUND Blinder Calculation
Quad Right Blinder 60.187 2*R₁+R₀+ArcResistance+TowerFootResistance
Quad Left Blinder 30.0935 (2*R₁+R₀+ArcResistance+TowerFootResistance)/2

ZONE 4
ZONE 4 25.00% of Zone1 Distance
ZONE 4 DISTANCE 3.206 K.M.

ZONE 4 REACH IMPEDANCE = ZONE 4 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE

ZONE 4 Positive Secquence IMPEDANCE Z₁ = 0.9369 ∠68.5505


ZONE 4 Zero Secquence IMPEDANCE Z₀ = 2.7942 ∠68.459

Z₁ = 0.3426+0.872j Z₀ 1.0259+2.599j
R₁ = 0.3426 R₀ 1.0259
X₁ = 0.872 X₀ 2.599

Phase to Phase Blinder Calculation


Quad Right Blinder 4.018533333333 2*R₁+Arc resistance
Quad Left Blinder 2.009266666667 (2*R₁+Arc resistance)/2
Phase to GROUND Blinder Calculation
Quad Right Blinder 11.7111 2*R₁+R₀+ArcResistance+TowerFootResistance
Quad Left Blinder 5.8556 (2*R₁+R₀+ArcResistance+TowerFootResistance)/2

FAULT REPORT

SETTING PARAMETER
Fault Report 1 Source SRC 1 (SRC1)
Fault Report 1 Trigger FINAL TRIP
Fault Report 1 Positive Seq (Z1) Mag 4.68
Fault Report 1 Positive Seq (Z1) Angle ∠68.5505
Fault Report 1 Zero Seq (Z0) Mag 13.97
Fault Report 1 Zero Seq (Z0) Angle ∠68.459
Fault Report 1 Line Length Units K.M.
Fault Report 1 Line Length 16.03
Fault Report 1 VT Substitution None
Fault Report 1 System Z0 Mag 2.00 ohms
Fault Report 1 System Z0 Angle 75 deg

PARAMETER CT F1
Phase CT Primary 800 A
Phase CT Secondary 1 A
Ground CT Primary 800 A
Ground CT Secondary 1 A

PARAMETER VT F5
Phase VT Connection Wye
Phase VT Secondary 63.5 V
Phase VT Ratio 1200.00 : 1
Auxiliary VT Connection Vag
Auxiliary VT Secondary 63.5 V
Auxiliary VT Ratio 1200.00 : 1

SETTING PARAMETER
Nominal Frequency 50 Hz
Phase Rotation ABC
Frequency And Phase Reference SRC 1 (SRC 1)
Frequency Tracking Function Enabled

PARAMETER SOURCE 1 SOURCE 2


Name SRC 1 SRC 2
Phase CT F1 None
Ground CT F1 None
Phase VT F5 None
Aux VT F5 None
PHASE DISTANCE

PARAMETER ZONE 1 ZONE 2 ZONE 3 ZONE 4


Function Enabled Enabled Enabled Enabled
Direction Forward Forward Forward Reverse
Shape
Xfmr Vol Connection None None None None
Xfmr Curr Connection None None None None
Reach 3.75 8.04 27.48 0.94
RCA 68.55 68.55 68.55 68.55
Rev Reach 0.9369 0.9369 0.9369 0.9369
Rev Reach RCA 68.55 68.55 68.55 68.55
Comp Limit 90 90 90 90
DIR RCA 68.55 68.55 68.55 68.55
DIR Comp Limit 90 90 90 90
Quad Right Blinder 6.07 9.21 23.43 4.02
Quad Right Blinder RCA 68.55 68.55 68.55 68.55
Quad Left Blinder 3.04 4.61 11.72 2.01
Quad Left Blinder RCA 68.55 68.55 68.55 68.55
Supervision 0.200 pu 0.200 pu 0.200 pu 0.200 pu
Volt Level 0.000 pu 0.000 pu 0.000 pu 0.000 pu
Delay 0.000 s 0.350 s 1.000 s 1.000 s
Block
Target Latched Latched Latched Latched
Events Enabled Enabled Enabled Enabled

GROUND DISTANCE

PARAMETER ZONE 1 ZONE 2 ZONE 3 ZONE 4


Function Enabled Enabled Enabled Enabled
Direction Forward Forward Forward Reverse
Shape
Z0/Z1 Mag 2.98 2.98 2.98 2.98
Z0/Z1 Ang -0.09 -0.09 -0.09 -0.09
Z0M/Z1 Mag 0 0 0 0
Z0M/Z1 Ang 0 deg 0 deg 0 deg 0 deg
Reach 3.75 8.04 27.48 0.94
RCA 68.55 68.55 68.55 68.55
Rev Reach 0.9369 0.9369 0.9369 0.9369
Rev Reach RCA 68.55 68.55 68.55 68.55
POL Current Zero-seq Zero-seq Zero-seq Zero-seq
Non-Homogen Ang 0.0 deg 0.0 deg 0.0 deg 0.0 deg
Comp Limit 90 90 90 90
DIR RCA 68.55 68.55 68.55 68.55
DIR Comp Limit 90 90 90 90
Quad Right Blinder 16.84 24.69 60.19 11.71
Quad Right Blinder RCA 68.55 68.55 68.55 68.55
Quad Left Blinder 8.42 12.34 30.09 5.86
Quad Left Blinder RCA 68.55 68.55 68.55 68.55
Supervision 0.200 pu 0.200 pu 0.200 pu 0.200 pu
Volt Level 0.000 pu 0.000 pu 0.000 pu 0.000 pu
Delay 0.000 s 0.350 s 1.000 s 1.000 s
Block
Target Latched Latched Latched Latched
Events Enabled Enabled Enabled Enabled

POWER SWING SETTING IN GE


SETTING PARAMETER
Function Enabled
Source SRC1
Shape Quad Shape
Mode Two Step
Supv 0.6 PU
Fwd Reach 32.976 Ohms
Quad Fwd Out 39.5712 Ohms
Fwd RCA 68.55052576507 deg
Rev Reach 6.5952 Ohms
Quad Rev Mid 60 Ohms
Quad Rev Out 7.91424 Ohms
Rev RCA 68.55052576507 deg
Outer Limit Angle 120 deg
Middle Limit Angle 90 deg
Inner Limit Angle 60 deg
Outer Right Blinder 35.145 Ohms
Outer Left Blinder 5.86 Ohms
Middle Right Blinder 31.6305 Ohms
Middle Left Blinder 4.102 Ohms
Inner Right Blinder 28.116 Ohms
Inner Left Blinder 2.344 Ohms
Delay 1 Pickup 0.1 seconds time required to declare PSB when locus travels from Oute
Delay 1 Reset 0.05 seconds Once PSB is declared PSB will be in hold condition for thi
Delay 2 Pickup 0.017 seconds only for three step mode:
Delay 3 Pickup 2 seconds time delay to declare PSB Trip when locus is present in the
Delay 4 Pickup 0.017 seconds only for delayed tripping mode
Seal-In-Delay 0.4 seconds
Trip Mode Early Mode
Block OFF
Target Latched
Events Enabled
TANTRANSCO
MADHYA PRADESH POWER TRANSMISSION
HARYANA
POWER TRANSMISSION
VIDYUT
COMPANY
PRASARAN
CORPORATION
LIMITED
NIGAM LIMITED
OF UTTARAKH
TANTRANSCO MPPTCL HVPNL PTCUL
ZONE2 TANTRANSCO 0.300 s 0.350 s 0.350 s
ZONE3 TANTRANSCO 0.700 s 1.000 s 1.000 s
ZONE4 TANTRANSCO 1.000 s 1.000 s 1.000 s

Zone setting Selection


Z1 Z2 (KM) Z3 (KM)
12.82 19.24 97.24
27.52 113.53
whichever is higher whichever is lower
27.52 97.24
NCE IMPEDANCE
NCE IMPEDANCE

NCE IMPEDANCE
n locus travels from Outer to Inner but locus is between Inner and Outer locus for this much specified time
in hold condition for this much specified time

en locus is present in the Inner region for this much of time


STATE POWER TRANSMISSION COMPANY LIMITED
BSPTCL
0.300 s
0.700 s
1.000 s
P442 Setting Calculation for 132KV L

R1 X1
2 Conductor ACSR Panther 0.1603 0.4080
ACSR Zebra 0.0793 0.3975
MOOSE 0.0299 0.3068

DEER
(PTCUL) 0.0804 0.4100

System Voltage 132 KV


1 Line Length 16.03 KM 132KV Laltappar-Rishikesh Line
2 conductor Panther 0.1603 0.4080
3 Adjacent Shortest Line 22.97 KM 132KV Rishikesh-Jwalapur Line

4 Adjacent Longest Line 78 KM 132KV Rishikesh-Shrinagar Line

5 Fault Mva
6 Fault Mva Other end
7 CTR 800 /1A CTR/PTR
8 PTR 1200 0.666667
9 Shortest line from Bus KM
Tower Footing Resistance in
10 Ohms 10
11 Arc Resistance in Ohms 5

DPR Calculations Positive Seq.Primary Impedances


km R X Impedanc Angle
Zone1 80% 12.82 2.06 5.23 5.62 68.55

Zone2 100% LL + 50% OF SL 27.52 4.41 11.23 12.06 68.55


Zone3 120% LL + 100% OF LL 97.24 15.59 39.67 42.62 68.55
Zone4 25% of Z1 3.21 0.51 1.31 1.41 68.55

------> Values to be entered

-------> Calculated Values

-------> Values to be entered to relay


POWER SWING SETTING IN GE
SETTING PARAMETER
Function Enabled
Source SRC1
Shape Quad Shape
Mode Two Step
Supv 0.6 PU
Fwd Reach 34.0995516396934 Ohms
Quad Fwd Out 40.9194619676321 Ohms
Fwd RCA 68.5505257650744 deg
Rev Reach 6.81991032793868 Ohms
Quad Rev Mid 60 Ohms
Quad Rev Out 8.18389239352642 Ohms
Rev RCA 68.5505257650744 deg
Outer Limit Angle 120 deg
Middle Limit Angle 90 deg
Inner Limit Angle 60 deg
Outer Right Blinder 36.1738616 Ohms
Outer Left Blinder 6.02897693333333 Ohms
Middle Right Blinder 32.55647544 Ohms
Middle Left Blinder 4.22028385333333 Ohms
Inner Right Blinder 28.93908928 Ohms
Inner Left Blinder 2.41159077333333 Ohms
Delay 1 Pickup 0.1 seconds time required to declare PSB when locus travels from Outer to Inner b
Delay 1 Reset 0.05 seconds Once PSB is declared PSB will be in hold condition for this much spe
Delay 2 Pickup 0.017 seconds only for three step mode:
Delay 3 Pickup 2 seconds time delay to declare PSB Trip when locus is present in the Inner regio
Delay 4 Pickup 0.017 seconds only for delayed tripping mode
Seal-In-Delay 0.4 seconds
Trip Mode Early Mode
Block OFF
Target Latched
Events Enabled
Calculation for 132KV Laltappar-Rishikesh Line at 132KV S/S Laltappar

Z1 Angle R0 X0 Z0 Angle Rm Xm Zm0


0.4384 68.5505 0.3603 1.3478 1.3951 75.0334 0.2049 0.5402 0.5778
0.4053 78.7178 0.2702 1.2936 1.3215 78.2020 0.1907 0.4931 0.5287
0.3083 84.4400 0.2936 1.1034 1.1418 75.1000

0.4178 78.9052 0.2814 1.4350 1.4623 78.9052

132KV Laltappar-Rishikesh Line


0.4384 68.5505 0.3603 1.3478 1.3951 75.0334
132KV Rishikesh-Jwalapur Line

132KV Rishikesh-Shrinagar Line

EARTH COMPENSATION Fault Report


Z0/Z1 Angle 100% Line TOTAL Z1 4.68 68.55
3.18 6.48 Length TOTAL Z0 14.91 75.03

Zero seq.Pri. Impedances Positive Seq.Sec. Impedances Zero seq.Sec. Impedances


R0 X0 Z0 Angle R X Impedan Angle R0
4.62 17.28 17.89 75.03 1.37 3.49 3.75 68.55 3.08

9.91 37.08 38.39 75.03 2.94 7.48 8.04 68.55 6.61


35.03 131.05 135.66 75.03 10.39 26.45 28.42 68.55 23.36
1.16 4.32 4.47 75.03 0.34 0.87 0.94 68.55 0.77

BLINDERS
RpH LPH RG
Z1 6.07 3.04 15.82
Z2 9.21 4.61 22.49
Z3 24.12 12.06 54.14
Z4 4.02 2.01 11.46
PSB when locus travels from Outer to Inner but locus is between Inner and Outer locus for this much specified time
SB will be in hold condition for this much specified time

B Trip when locus is present in the Inner region for this much of time
ppar

Angle
69.2281
68.8567

Zero seq.Sec. Impedances


X0 Z0 Angle
11.52 11.93 75.03

24.72 25.59 75.03


87.37 90.44 75.03
2.88 2.98 75.03

LG
7.91
11.24
27.07
5.73
GRID DIAGRAM O
CHIBRO (4x60 MW)
MAJRI 83 84
5.77kM 8.59 kM
86 81 82 KHODRI (4X30MW)
83 84 885
100 MVA T/F
83.5 kM 81.04 kM
785
73
SAHARANPUR 8.835kM
71 DHAKRANI (3X11.2MW)
73
5.60kM
71 DHALIPUR (3X17MW)
74 73
5.591 k.m
72 KULHAL (3X10MW) 26.474kM
71 74

31.97kM

41.769 k.m

15.98kM

77 132KV MAJRA 78
73

28.382 k.m

132KV LALTAPPAR 71
73
16.028kM

71
77 73

132KV 78
SHRINAGAR 22.97

104
SHATPULI
132KV JWALAPUR
46.7
132KV KOTDWAR
D DIAGRAM OF PTCUL DEHRADUN AREA

DRI (4X30MW)
87

400/220kV S/S PGCIL

27.532 kM

ANI (3X11.2MW) 6.110 kM

83 220KV S/S JHAJHRA 87


881 882
2 x 160MVA
26.474kM
781 782
71 72 73 74 132KV S/S JHAJHRA

21.292kM

132KV PURKUL 78 220kV IIP Dehradun


73

22.772kM
71
74

8.54kM
72 132KV BINDAL
74
44.778 K.m

72 132KV RISHIKESH
76

220KV
53 RISHIKESH
87 86 82

132KV BPT 104.5kM 40.5KM


WALAPUR

MANERIBHALI-II MANERIBHALI-I CHAMBA


20kV S/S PGCIL

6.110 kM

89
81

26kM

83
81

31kM
83
81

21.2 kM
220KV HARIDWAR SDCUL
BASIS

ZONE I =
ZONE II(min) =
ZONE II(max) =

ZONE III
CHECK I
CHECK I I
80% OP PRINCIPAL LINE
120% OF PRINCIPAL LINE
80% {PRINCIPAL LINE+80% SHORTEST LINE}
CHECK THAT ZONE IInd SHOULD NOT CROSS THE Ist ZONE
SETTING OF THE ADJACENT LINE.

120% {PRINCIPAL LINE+ADJACENT LONGEST LINE}


ZONE IIIrd < {ZLT+ZT} ZT = EQUIVALLENT IMP. OF T/F IN 11
ZONE IIIrd SHOULD NOT CROSS ZONE IInd OF THE ADJ. SECTION.
Name of Customer
Name of SubStation UJVNL Dhakrani Power house
Feeder Name 132kV Dhakrani Dhalipur Line
Panel Serial No
RELAY Serial No
RELAY Order Code
RELAY Make GE Date of Commissioning

R1 +jX1 R0+JX0
Panther 0.1603+0.408j 0.480+1.216j Conductor Selected Panther
Zebra(132KV) 0.0793+0.3975j 0.2702+1.2936j
Moose 0.0299+0.3068j 0.3603+1.3478j
Deer 0.0804+0.4100j 0.2814+1.4350j

132KV Dhalipur-Jhajhara Line


26.47 KM

132KV Dhakrani -Dhalipur


5.6 KM

132KV Dhalipur-Kulhal Line


5.59 KM
UJVNL Dhakrani Power house 132kV Substation Dhakrani

Protected Line Length 5.6 KM 132KV Dhakrani -Dhalipur


Adjacent Longest Line Length 26.47 KM 132KV Dhalipur-Jhajhara Line
Adjacent Shortest Line Length 5.59 KM 132KV Dhalipur-Kulhal Line
Adjacent Sub Station Name 132kV Substation Dhakrani
4
C.T.Primary = 400 A P.T.Primary = 132000 V
C.T.Secondary = 1 A P.T.Secondary = 110 V

IMPEDANCE Z = R + X j Ω
Positive Secquence Impedance Z₁primary = 0.1603+0.408j Ω/K.M.
Zero Secquence Impedance Z₀primary = 0.480+1.216j Ω/K.M.
Arc Resistance (Primary value) = 5 Ω
Tower Foot Resistance (Primary value) = 10 Ω

ZONE 1 = 80.00% of Protected Line Length


ZONE 2 = 100.00% of Protected Line Length + 50.00% Adjacent Shortest Line Length
ZONE 3 = 100.00% of Protected Line Length + 100.00% Adjacent Longest Line Length
ZONE 4 = 25.00% of Zone1 Distance

CT RATIO 400 PT RATIO 1200

CTR/PTR 0.3333

Arc Resistance(Secondary) 1.667 Ω


Tower Foot Resistance(Secondary) 3.333 Ω

Converting Impedance value Rectangular form to Polarform

Positive Secquence Impedance Z₁primary 0.4384 ∠68.5505


Zero Secquence Impedance Z₀primary 1.3073 ∠68.459

Converting Primary Impedance value to Secondary Impedance value


Per K.M. SECONDARY IMPEDANCE =Per K.M. Primary Impedance * (CTR/PTR)

Positive Secquence Impedance Z₁secondary 0.1461 ∠68.5505


Zero Secquence Impedance Z₀secondary 0.4358 ∠68.459
TOTAL IMPEDANCE VALUE= PROTECTED LINE LENGTH K.M.*Per K.M. Secondary Impedance

Total Positive Secquence Impedance Z ₁secondary 0.8183 ∠68.5505


Total Zero Secquence Impedance Z ₀secondary 2.4403 ∠68.459

Z₀/Z₁ Magnitude 2.982267185605 Ω Z₀/Z₁ Angle -.0915 Deg.

Converting Polar to Rectangular Form

Z₁ 0.0534+0.136j Ω/K.M. Z₀ 0.16+0.4053j Ω/K.M.


R₁ 0.0534 Ω/K.M. R₀ 0.16 Ω/K.M.
X₁ 0.136 Ω/K.M. X₀ 0.4053 Ω/K.M.

ZONE 1
ZONE 1 80.00% of Protected Line Length

ZONE 1 DISTANCE 4.48 K.M.

ZONE 1 REACH IMPEDANCE = ZONE 1 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE

ZONE 1 Positive Secquence IMPEDANCE Z₁ = 0.6546 ∠68.5505


ZONE 1 Zero Secquence IMPEDANCE Z₀ = 1.9522 ∠68.459

Z₁ = 0.2394+0.6093j Z₀ 0.7168+1.8159j
R₁ = 0.2394 R₀ 0.7168
X₁ = 0.6093 X₀ 1.8159

Phase to Phase Blinder Calculation


Quad Right Blinder 2.1455 2*R₁+Arc resistance
Quad Left Blinder 1.0727 (2*R₁+Arc resistance)/2

Phase to GROUND Blinder Calculation


Quad Right Blinder 6.1956 2*R₁+R₀+ArcResistance+TowerFootResistance
Quad Left Blinder 3.0978 (2*R₁+R₀+ArcResistance+TowerFootResistance)/2

ZONE 2
ZONE 2 = 100.00% of Protected Line Length + 50.00% Adjacent Longest Line Length

ZONE 2 DISTANCE = 8.395 K.M.


ZONE 2 REACH IMPEDANCE = ZONE 2 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE

ZONE 2 Positive Secquence IMPEDANCE Z₁ = 1.2267 ∠68.5505


ZONE 2 Zero Secquence IMPEDANCE Z₀ = 3.6583 ∠68.459

Z₁ 0.4486+1.1417j Z₀ 1.3432+3.4028j
R₁ 0.4486 R₀ 1.3432
X₁ 1.1417 X₀ 3.4028

Phase to Phase Blinder Calculation


Quad Right Blinder 2.5639 2*R₁+Arc resistance
Quad Left Blinder 1.2819 (2*R₁+Arc resistance)/2

Phase to GROUND Blinder Calculation


Quad Right Blinder 7.2404 2*R₁+R₀+ArcResistance+TowerFootResistance
Quad Left Blinder 3.6202 (2*R₁+R₀+ArcResistance+TowerFootResistance)/2

ZONE 3
ZONE 3 = 100.00% of Protected Line Length + 100.00% Adjacent Longest Line Length

ZONE 3 DISTANCE 32.07 K.M.

ZONE 3 REACH IMPEDANCE = ZONE 3 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE

ZONE 3 Positive Secquence IMPEDANCE Z₁ = 4.69 ∠68.5505


ZONE 3 Zero Secquence IMPEDANCE Z₀ = 13.9751 ∠68.459

Z₁ 1.7136+4.3615j Z₀ 5.1312+12.999j
R₁ 1.7136 R₀ 5.1312
X₁ 4.3615 X₀ 12.999
Phase to Phase Blinder Calculation
Quad Right Blinder 5.0939 2*R₁+Arc resistance
Quad Left Blinder 2.546933333333 (2*R₁+Arc resistance)/2
Phase to GROUND Blinder Calculation
Quad Right Blinder 13.5584 2*R₁+R₀+ArcResistance+TowerFootResistance
Quad Left Blinder 6.7792 (2*R₁+R₀+ArcResistance+TowerFootResistance)/2

ZONE 4
ZONE 4 25.00% of Zone1 Distance
ZONE 4 DISTANCE 1.12 K.M.

ZONE 4 REACH IMPEDANCE = ZONE 4 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE

ZONE 4 Positive Secquence IMPEDANCE Z₁ = 0.1637 ∠68.5505


ZONE 4 Zero Secquence IMPEDANCE Z₀ = 0.4881 ∠68.459

Z₁ = 0.0598+0.1523j Z₀ 0.1792+0.454j
R₁ = 0.0598 R₀ 0.1792
X₁ = 0.1523 X₀ 0.454

Phase to Phase Blinder Calculation


Quad Right Blinder 1.786266666667 2*R₁+Arc resistance
Quad Left Blinder 0.893133333333 (2*R₁+Arc resistance)/2
Phase to GROUND Blinder Calculation
Quad Right Blinder 5.2988 2*R₁+R₀+ArcResistance+TowerFootResistance
Quad Left Blinder 2.6494 (2*R₁+R₀+ArcResistance+TowerFootResistance)/2

FAULT REPORT

SETTING PARAMETER
Fault Report 1 Source SRC 1 (SRC1)
Fault Report 1 Trigger FINAL TRIP
Fault Report 1 Positive Seq (Z1) Mag 0.82
Fault Report 1 Positive Seq (Z1) Angle ∠68.5505
Fault Report 1 Zero Seq (Z0) Mag 2.44
Fault Report 1 Zero Seq (Z0) Angle ∠68.459
Fault Report 1 Line Length Units K.M.
Fault Report 1 Line Length 5.6
Fault Report 1 VT Substitution None
Fault Report 1 System Z0 Mag 2.00 ohms
Fault Report 1 System Z0 Angle 75 deg

PARAMETER CT F1
Phase CT Primary 400 A
Phase CT Secondary 1 A
Ground CT Primary 400 A
Ground CT Secondary 1 A

PARAMETER VT F5
Phase VT Connection Wye
Phase VT Secondary 63.5 V
Phase VT Ratio 1200.00 : 1
Auxiliary VT Connection Vag
Auxiliary VT Secondary 63.5 V
Auxiliary VT Ratio 1200.00 : 1

SETTING PARAMETER
Nominal Frequency 50 Hz
Phase Rotation ABC
Frequency And Phase Reference SRC 1 (SRC 1)
Frequency Tracking Function Enabled

PARAMETER SOURCE 1 SOURCE 2


Name SRC 1 SRC 2
Phase CT F1 None
Ground CT F1 None
Phase VT F5 None
Aux VT F5 None
PHASE DISTANCE

PARAMETER ZONE 1 ZONE 2 ZONE 3 ZONE 4


Function Enabled Enabled Enabled Enabled
Direction Forward Forward Forward Reverse
Shape
Xfmr Vol Connection None None None None
Xfmr Curr Connection None None None None
Reach 0.65 1.23 4.69 0.16
RCA 68.55 68.55 68.55 68.55
Rev Reach 0.1637 0.1637 0.1637 0.1637
Rev Reach RCA 68.55 68.55 68.55 68.55
Comp Limit 90 90 90 90
DIR RCA 68.55 68.55 68.55 68.55
DIR Comp Limit 90 90 90 90
Quad Right Blinder 2.15 2.56 5.09 1.79
Quad Right Blinder RCA 68.55 68.55 68.55 68.55
Quad Left Blinder 1.07 1.28 2.55 0.89
Quad Left Blinder RCA 68.55 68.55 68.55 68.55
Supervision 0.200 pu 0.200 pu 0.200 pu 0.200 pu
Volt Level 0.000 pu 0.000 pu 0.000 pu 0.000 pu
Delay 0.000 s 0 0 0
Block
Target Latched Latched Latched Latched
Events Enabled Enabled Enabled Enabled

GROUND DISTANCE

PARAMETER ZONE 1 ZONE 2 ZONE 3 ZONE 4


Function Enabled Enabled Enabled Enabled
Direction Forward Forward Forward Reverse
Shape
Z0/Z1 Mag 2.98 2.98 2.98 2.98
Z0/Z1 Ang -0.09 -0.09 -0.09 -0.09
Z0M/Z1 Mag 0 0 0 0
Z0M/Z1 Ang 0 deg 0 deg 0 deg 0 deg
Reach 0.65 1.23 4.69 0.16
RCA 68.55 68.55 68.55 68.55
Rev Reach 0.1637 0.1637 0.1637 0.1637
Rev Reach RCA 68.55 68.55 68.55 68.55
POL Current Zero-seq Zero-seq Zero-seq Zero-seq
Non-Homogen Ang 0.0 deg 0.0 deg 0.0 deg 0.0 deg
Comp Limit 90 90 90 90
DIR RCA 68.55 68.55 68.55 68.55
DIR Comp Limit 90 90 90 90
Quad Right Blinder 6.2 7.24 13.56 5.3
Quad Right Blinder RCA 68.55 68.55 68.55 68.55
Quad Left Blinder 3.1 3.62 6.78 2.65
Quad Left Blinder RCA 68.55 68.55 68.55 68.55
Supervision 0.200 pu 0.200 pu 0.200 pu 0.200 pu
Volt Level 0.000 pu 0.000 pu 0.000 pu 0.000 pu
Delay 0.000 s 0 0 0
Block
Target Latched Latched Latched Latched
Events Enabled Enabled Enabled Enabled

POWER SWING SETTING IN GE


SETTING PARAMETER
Function Enabled
Source SRC1
Shape Quad Shape
Mode Two Step
Supv 0.6 PU
Fwd Reach 5.628 Ohms
Quad Fwd Out 6.7536 Ohms
Fwd RCA 68.55052576507 deg
Rev Reach 1.1256 Ohms
Quad Rev Mid 60 Ohms
Quad Rev Out 1.35072 Ohms
Rev RCA 68.55052576507 deg
Outer Limit Angle 120 deg
Middle Limit Angle 90 deg
Inner Limit Angle 60 deg
Outer Right Blinder 7.635 Ohms
Outer Left Blinder 1.275 Ohms
Middle Right Blinder 6.8715 Ohms
Middle Left Blinder 0.8925 Ohms
Inner Right Blinder 6.108 Ohms
Inner Left Blinder 0.51 Ohms
Delay 1 Pickup 0.1 seconds time required to declare PSB when locus travels from Oute
Delay 1 Reset 0.05 seconds Once PSB is declared PSB will be in hold condition for thi
Delay 2 Pickup 0.017 seconds only for three step mode:
Delay 3 Pickup 2 seconds time delay to declare PSB Trip when locus is present in the
Delay 4 Pickup 0.017 seconds only for delayed tripping mode
Seal-In-Delay 0.4 seconds
Trip Mode Early Mode
Block OFF
Target Latched
Events Enabled
TANTRANSCO
MADHYA PRADESH POWER TRANSMISSION
HARYANA
POWER TRANSMISSION
VIDYUT
COMPANY
PRASARAN
CORPORATION
LIMITED
NIGAM LIMITED
OF UTTARAKH
TANTRANSCO MPPTCL HVPNL PTCUL
ZONE2 TANTRANSCO 0.300 s 0.350 s 0.350 s
ZONE3 TANTRANSCO 0.700 s 1.000 s 1.000 s
ZONE4 TANTRANSCO 1.000 s 1.000 s 1.000 s

Zone setting Selection


Z1 Z2 (KM) Z3 (KM)
4.48 6.72 33.19
8.40 38.69
whichever is higher whichever is lower
8.40 33.19
NCE IMPEDANCE
NCE IMPEDANCE

NCE IMPEDANCE
n locus travels from Outer to Inner but locus is between Inner and Outer locus for this much specified time
in hold condition for this much specified time

en locus is present in the Inner region for this much of time


STATE POWER TRANSMISSION COMPANY LIMITED
BSPTCL
0.300 s
0.700 s
1.000 s