R1 +jX1 R0+JX0
Panther 0.1603+0.408j 0.480+1.216j Conductor Selected Panther
Zebra(132KV) 0.0793+0.3975j 0.2702+1.2936j
Moose 0.0299+0.3068j 0.3603+1.3478j
Deer 0.0804+0.4100j 0.2814+1.4350j
IMPEDANCE Z = R + X j Ω
Positive Secquence Impedance Z₁primary = 0.1603+0.408j Ω/K.M.
Zero Secquence Impedance Z₀primary = 0.480+1.216j Ω/K.M.
Arc Resistance (Primary value) = 5 Ω
Tower Foot Resistance (Primary value) = 10 Ω
CTR/PTR 0.6667
ZONE 1
ZONE 1 80.00% of Protected Line Length
ZONE 1 REACH IMPEDANCE = ZONE 1 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE
Z₁ = 2.4263+6.1755j Z₀ 7.2653+18.4054j
R₁ = 2.4263 R₀ 7.2653
X₁ = 6.1755 X₀ 18.4054
ZONE 2
ZONE 2 = 100.00% of Protected Line Length + 50.00% Adjacent Longest Line Length
ZONE 2 REACH IMPEDANCE = ZONE 2 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE
ZONE 3 REACH IMPEDANCE = ZONE 3 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE
Z₁ 7.4967+19.0808j Z₀ 22.448+56.8683j
R₁ 7.4967 R₀ 22.448
X₁ 19.0808 X₀ 56.8683
Phase to Phase Blinder Calculation
Quad Right Blinder 18.3267 2*R₁+Arc resistance
Quad Left Blinder 9.163366666667 (2*R₁+Arc resistance)/2
Phase to GROUND Blinder Calculation
Quad Right Blinder 47.4414 2*R₁+R₀+ArcResistance+TowerFootResistance
Quad Left Blinder 23.7207 (2*R₁+R₀+ArcResistance+TowerFootResistance)/2
ZONE 4
ZONE 4 25.00% of Zone1 Distance
ZONE 4 DISTANCE 5.676 K.M.
ZONE 4 REACH IMPEDANCE = ZONE 4 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE
Z₁ = 0.6066+1.5439j Z₀ 1.8163+4.6013j
R₁ = 0.6066 R₀ 1.8163
X₁ = 1.5439 X₀ 4.6013
FAULT REPORT
SETTING PARAMETER
Fault Report 1 Source SRC 1 (SRC1)
Fault Report 1 Trigger FINAL TRIP
Fault Report 1 Positive Seq (Z1) Mag 8.29
Fault Report 1 Positive Seq (Z1) Angle ∠68.5505
Fault Report 1 Zero Seq (Z0) Mag 24.73
Fault Report 1 Zero Seq (Z0) Angle ∠68.459
Fault Report 1 Line Length Units K.M.
Fault Report 1 Line Length 28.38
Fault Report 1 VT Substitution None
Fault Report 1 System Z0 Mag 2.00 ohms
Fault Report 1 System Z0 Angle 75 deg
PARAMETER CT F1
Phase CT Primary 800 A
Phase CT Secondary 1 A
Ground CT Primary 800 A
Ground CT Secondary 1 A
PARAMETER VT F5
Phase VT Connection Wye
Phase VT Secondary 63.5 V
Phase VT Ratio 1200.00 : 1
Auxiliary VT Connection Vag
Auxiliary VT Secondary 63.5 V
Auxiliary VT Ratio 1200.00 : 1
SETTING PARAMETER
Nominal Frequency 50 Hz
Phase Rotation ABC
Frequency And Phase Reference SRC 1 (SRC 1)
Frequency Tracking Function Enabled
PHASE DISTANCE
GROUND DISTANCE
R1 X1
2 Conductor ACSR Panther 0.1603 0.4080
ACSR Zebra 0.0793 0.3975
MOOSE 0.0299 0.3068
DEER
(PTCUL) 0.0804 0.4100
5 Fault Mva
6 Fault Mva Other end
7 CTR 800 /1A CTR/PTR
8 PTR 1200 0.666667
9 Shortest line from Bus KM
Tower Footing Resistance in
10 Ohms 10
11 Arc Resistance in Ohms 5
BLINDERS
RpH LPH RG
Z1 8.19 4.09 20.31
Z2 10.31 5.16 24.82
Z3 19.54 9.77 44.42
Z4 4.55 2.27 12.58
PSB when locus travels from Outer to Inner but locus is between Inner and Outer locus for this much specified time
SB will be in hold condition for this much specified time
B Trip when locus is present in the Inner region for this much of time
ar
Angle
69.2281
68.8567
LG
10.15
12.41
22.21
6.29
Name of Customer POWER TRANSMISSION CORPORATION OF UTTARAKHAND LIMITED
Name of SubStation 132kV S/S Laltappar, Ddun
Feeder Name 132kV Laltappar-Rishikesh Line
Panel Serial No
RELAY Serial No
RELAY Order Code
RELAY Make GE Date of Commissioning
R1 +jX1 R0+JX0
Panther 0.1603+0.408j 0.480+1.216j Conductor Selected Panther
Zebra(132KV) 0.0793+0.3975j 0.2702+1.2936j
Moose 0.0299+0.3068j 0.3603+1.3478j
Deer 0.0804+0.4100j 0.2814+1.4350j
IMPEDANCE Z = R + X j Ω
Positive Secquence Impedance Z₁primary = 0.1603+0.408j Ω/K.M.
Zero Secquence Impedance Z₀primary = 0.480+1.216j Ω/K.M.
Arc Resistance (Primary value) = 5 Ω
Tower Foot Resistance (Primary value) = 10 Ω
CTR/PTR 0.6667
ZONE 1
ZONE 1 80.00% of Protected Line Length
ZONE 1 REACH IMPEDANCE = ZONE 1 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE
Z₁ = 1.3705+3.4881j Z₀ 4.1037+10.396j
R₁ = 1.3705 R₀ 4.1037
X₁ = 3.4881 X₀ 10.396
ZONE 2
ZONE 2 = 100.00% of Protected Line Length + 50.00% Adjacent Longest Line Length
Z₁ 2.9404+7.4841j Z₀ 8.8048+22.3055j
R₁ 2.9404 R₀ 8.8048
X₁ 7.4841 X₀ 22.3055
ZONE 3
ZONE 3 = 100.00% of Protected Line Length + 100.00% Adjacent Longest Line Length
ZONE 3 REACH IMPEDANCE = ZONE 3 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE
Z₁ 10.0487+25.5762j Z₀ 30.0896+76.227j
R₁ 10.0487 R₀ 30.0896
X₁ 25.5762 X₀ 76.227
Phase to Phase Blinder Calculation
Quad Right Blinder 23.4307 2*R₁+Arc resistance
Quad Left Blinder 11.71536666667 (2*R₁+Arc resistance)/2
Phase to GROUND Blinder Calculation
Quad Right Blinder 60.187 2*R₁+R₀+ArcResistance+TowerFootResistance
Quad Left Blinder 30.0935 (2*R₁+R₀+ArcResistance+TowerFootResistance)/2
ZONE 4
ZONE 4 25.00% of Zone1 Distance
ZONE 4 DISTANCE 3.206 K.M.
ZONE 4 REACH IMPEDANCE = ZONE 4 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE
Z₁ = 0.3426+0.872j Z₀ 1.0259+2.599j
R₁ = 0.3426 R₀ 1.0259
X₁ = 0.872 X₀ 2.599
FAULT REPORT
SETTING PARAMETER
Fault Report 1 Source SRC 1 (SRC1)
Fault Report 1 Trigger FINAL TRIP
Fault Report 1 Positive Seq (Z1) Mag 4.68
Fault Report 1 Positive Seq (Z1) Angle ∠68.5505
Fault Report 1 Zero Seq (Z0) Mag 13.97
Fault Report 1 Zero Seq (Z0) Angle ∠68.459
Fault Report 1 Line Length Units K.M.
Fault Report 1 Line Length 16.03
Fault Report 1 VT Substitution None
Fault Report 1 System Z0 Mag 2.00 ohms
Fault Report 1 System Z0 Angle 75 deg
PARAMETER CT F1
Phase CT Primary 800 A
Phase CT Secondary 1 A
Ground CT Primary 800 A
Ground CT Secondary 1 A
PARAMETER VT F5
Phase VT Connection Wye
Phase VT Secondary 63.5 V
Phase VT Ratio 1200.00 : 1
Auxiliary VT Connection Vag
Auxiliary VT Secondary 63.5 V
Auxiliary VT Ratio 1200.00 : 1
SETTING PARAMETER
Nominal Frequency 50 Hz
Phase Rotation ABC
Frequency And Phase Reference SRC 1 (SRC 1)
Frequency Tracking Function Enabled
GROUND DISTANCE
NCE IMPEDANCE
n locus travels from Outer to Inner but locus is between Inner and Outer locus for this much specified time
in hold condition for this much specified time
R1 X1
2 Conductor ACSR Panther 0.1603 0.4080
ACSR Zebra 0.0793 0.3975
MOOSE 0.0299 0.3068
DEER
(PTCUL) 0.0804 0.4100
5 Fault Mva
6 Fault Mva Other end
7 CTR 800 /1A CTR/PTR
8 PTR 1200 0.666667
9 Shortest line from Bus KM
Tower Footing Resistance in
10 Ohms 10
11 Arc Resistance in Ohms 5
BLINDERS
RpH LPH RG
Z1 6.07 3.04 15.82
Z2 9.21 4.61 22.49
Z3 24.12 12.06 54.14
Z4 4.02 2.01 11.46
PSB when locus travels from Outer to Inner but locus is between Inner and Outer locus for this much specified time
SB will be in hold condition for this much specified time
B Trip when locus is present in the Inner region for this much of time
ppar
Angle
69.2281
68.8567
LG
7.91
11.24
27.07
5.73
GRID DIAGRAM O
CHIBRO (4x60 MW)
MAJRI 83 84
5.77kM 8.59 kM
86 81 82 KHODRI (4X30MW)
83 84 885
100 MVA T/F
83.5 kM 81.04 kM
785
73
SAHARANPUR 8.835kM
71 DHAKRANI (3X11.2MW)
73
5.60kM
71 DHALIPUR (3X17MW)
74 73
5.591 k.m
72 KULHAL (3X10MW) 26.474kM
71 74
31.97kM
41.769 k.m
15.98kM
77 132KV MAJRA 78
73
28.382 k.m
132KV LALTAPPAR 71
73
16.028kM
71
77 73
132KV 78
SHRINAGAR 22.97
104
SHATPULI
132KV JWALAPUR
46.7
132KV KOTDWAR
D DIAGRAM OF PTCUL DEHRADUN AREA
DRI (4X30MW)
87
27.532 kM
21.292kM
22.772kM
71
74
8.54kM
72 132KV BINDAL
74
44.778 K.m
72 132KV RISHIKESH
76
220KV
53 RISHIKESH
87 86 82
6.110 kM
89
81
26kM
83
81
31kM
83
81
21.2 kM
220KV HARIDWAR SDCUL
BASIS
ZONE I =
ZONE II(min) =
ZONE II(max) =
ZONE III
CHECK I
CHECK I I
80% OP PRINCIPAL LINE
120% OF PRINCIPAL LINE
80% {PRINCIPAL LINE+80% SHORTEST LINE}
CHECK THAT ZONE IInd SHOULD NOT CROSS THE Ist ZONE
SETTING OF THE ADJACENT LINE.
R1 +jX1 R0+JX0
Panther 0.1603+0.408j 0.480+1.216j Conductor Selected Panther
Zebra(132KV) 0.0793+0.3975j 0.2702+1.2936j
Moose 0.0299+0.3068j 0.3603+1.3478j
Deer 0.0804+0.4100j 0.2814+1.4350j
IMPEDANCE Z = R + X j Ω
Positive Secquence Impedance Z₁primary = 0.1603+0.408j Ω/K.M.
Zero Secquence Impedance Z₀primary = 0.480+1.216j Ω/K.M.
Arc Resistance (Primary value) = 5 Ω
Tower Foot Resistance (Primary value) = 10 Ω
CTR/PTR 0.3333
ZONE 1
ZONE 1 80.00% of Protected Line Length
ZONE 1 REACH IMPEDANCE = ZONE 1 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE
Z₁ = 0.2394+0.6093j Z₀ 0.7168+1.8159j
R₁ = 0.2394 R₀ 0.7168
X₁ = 0.6093 X₀ 1.8159
ZONE 2
ZONE 2 = 100.00% of Protected Line Length + 50.00% Adjacent Longest Line Length
Z₁ 0.4486+1.1417j Z₀ 1.3432+3.4028j
R₁ 0.4486 R₀ 1.3432
X₁ 1.1417 X₀ 3.4028
ZONE 3
ZONE 3 = 100.00% of Protected Line Length + 100.00% Adjacent Longest Line Length
ZONE 3 REACH IMPEDANCE = ZONE 3 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE
Z₁ 1.7136+4.3615j Z₀ 5.1312+12.999j
R₁ 1.7136 R₀ 5.1312
X₁ 4.3615 X₀ 12.999
Phase to Phase Blinder Calculation
Quad Right Blinder 5.0939 2*R₁+Arc resistance
Quad Left Blinder 2.546933333333 (2*R₁+Arc resistance)/2
Phase to GROUND Blinder Calculation
Quad Right Blinder 13.5584 2*R₁+R₀+ArcResistance+TowerFootResistance
Quad Left Blinder 6.7792 (2*R₁+R₀+ArcResistance+TowerFootResistance)/2
ZONE 4
ZONE 4 25.00% of Zone1 Distance
ZONE 4 DISTANCE 1.12 K.M.
ZONE 4 REACH IMPEDANCE = ZONE 4 DISTANCE * PER KM SECONDARY POSITIVE SECQUENCE IMPEDANCE
Z₁ = 0.0598+0.1523j Z₀ 0.1792+0.454j
R₁ = 0.0598 R₀ 0.1792
X₁ = 0.1523 X₀ 0.454
FAULT REPORT
SETTING PARAMETER
Fault Report 1 Source SRC 1 (SRC1)
Fault Report 1 Trigger FINAL TRIP
Fault Report 1 Positive Seq (Z1) Mag 0.82
Fault Report 1 Positive Seq (Z1) Angle ∠68.5505
Fault Report 1 Zero Seq (Z0) Mag 2.44
Fault Report 1 Zero Seq (Z0) Angle ∠68.459
Fault Report 1 Line Length Units K.M.
Fault Report 1 Line Length 5.6
Fault Report 1 VT Substitution None
Fault Report 1 System Z0 Mag 2.00 ohms
Fault Report 1 System Z0 Angle 75 deg
PARAMETER CT F1
Phase CT Primary 400 A
Phase CT Secondary 1 A
Ground CT Primary 400 A
Ground CT Secondary 1 A
PARAMETER VT F5
Phase VT Connection Wye
Phase VT Secondary 63.5 V
Phase VT Ratio 1200.00 : 1
Auxiliary VT Connection Vag
Auxiliary VT Secondary 63.5 V
Auxiliary VT Ratio 1200.00 : 1
SETTING PARAMETER
Nominal Frequency 50 Hz
Phase Rotation ABC
Frequency And Phase Reference SRC 1 (SRC 1)
Frequency Tracking Function Enabled
GROUND DISTANCE
NCE IMPEDANCE
n locus travels from Outer to Inner but locus is between Inner and Outer locus for this much specified time
in hold condition for this much specified time