Connected Burden
Diff. relay (Micom P546): 0.10 VA Micom P546 Burden: (VA/I2) = (0.1 /1^2)
0.1000 Ohms
Rb = 0.0300 Ohms
Relay (Micom P546) constants
Factors: K 65
Kmax: 1.40
KRPA: 0.60
The CT Accuracy Limiting Voltage (Ual) shall meet the following requirements.
æ Xö
B) Ual2 K xI x çç 1 + ÷÷ x (Rct + Rl + Rr + Rb )
RPA FZ1 è Rø
Kmax x I x (Rct + Rl + Rr + Rb )
C) Ual3 F max
K: Dimensioning factor
'K' is dependent on If (Max. through fault current) & system X/R ratio and 'K'is determined as follows.
For relays set at Is1 = 20%, Is2 = 2 In, K1 = 30%, K2 = 150%:
K > 40 + (0.07 x (If x X/R)) AND: K = 65
This is valid for (If x X/R) < 1000 In
A) CT Ual1 Calculation
= 313.69 V - RESULT - A1
B) CT Ual2 Calculation
æ Xö
K x I x çç1 + ÷ x (Rct + Rl/2 + Rr + Rb)
Ual2(PF) RPA FZ1 è R ÷ø -B1
= 425.85 V - RESULT - B1
æ Xö
K xI x ç1 + ÷ x (Rct + Rl + Rr + Rb )
Ual2(EF) RPA FZ1 çè R ÷ø -B2
= 177.79 V - RESULT - B2
C) CT Ual3 Calculation
= 212.83 V - RESULT - C
Result B1 is higher than other Results, hence CT sizing is calculated based on result B1.
Since the available Ual (3700) volts is higher than (512) volts, the CT is suitably sized.