USED FOR CONSTRUCTION 13.8KV CT ADEQUACY CALCULATION
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED UPGRADING OVER CURRENT PROTECTION AT MEDSO SUBSTATION X CE-XXXXXX 01 OF 04 A
AND DATED
AP
APPR'D
KR
1 SYSTEM PARAMETERS
CHK'D
MD
where:
ρ20 Resistivity of the copper at 20 deg c = 0.01786 Ωmm2/m
Copper Prperties
Resitivity of Copper at 20oC, ρ 17.2 nΩm
Temperature Coefficient of Copper, α 0.0039
First Temperature 20 o
C
Second Temperature 75 o
C
Change in Temperature, ∆t 55 o
C
SHF
BY
Size
DATE
First Teperature, T1 20 OC
REVISIONS Second Teperature, T2 75 OC
DRAWN Difference in Temperaturwe, ∆t = T2 - T1 55 OC
BY:- Resistance at 75oC, R75 = R20 x ( 1 + α x ∆t ) 0.00522235 Ω
DATE:-
CHECKED
BY:-
DATE:-
AS BUILT BY DATE
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION 13.8KV CT ADEQUACY CALCULATION
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED UPGRADING OVER CURRENT PROTECTION AT MEDSO SUBSTATION P 02 OF 04 A
AND DATED
AP
APPR'D
KR
MD
System Data
20
Accuracy limitig factor (ALF)
DESCRIPTION
132kV SWGR CT
CT Ratio 600-300 A
CT used tap 600 A
Class 5P 20
CT resistance (Rct) 2.967 Ω
CT secondary 1 A
CT knee voltage 655 V
CT Burden 30 VA
Rb = CT Burden / Current2 30 Ω
Cable data
Size 4 mm2
Lead Resistance per meter 0.005310801 Ω / meter
SEPT.2021
Relay data
NO.
DATE:-
CHECKED
BY:-
DATE:-
OPRG. DEPT
BY
BY:-
DATE:-
CERTIFIED.
BY:-
DATE:-
AS BUILT BY DATE
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION 13.8KV CT ADEQUACY CALCULATION
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED UPGRADING OVER CURRENT PROTECTION AT MEDSO SUBSTATION P 03 OF 04 A
AND DATED
AP
APPR'D
KR
CT Calculations:
MD
with
l = Single conductor length from CT to relay in m
ρ = Specifi c resistance = 0.0175 Ωmm2 / m (copper wires)
SEPT.2021
(from Relay manufacturer manual formula taken) (Received from CT Test Report)
A
AS BUILT BY DATE
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION 13.8KV CT ADEQUACY CALCULATION
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED UPGRADING OVER CURRENT PROTECTION AT MEDSO SUBSTATION P 04 OF 04 A
AND DATED
AP
APPR'D
KR
MD
Where,
I pickup : is the primary pickup current setting of the IED. Is normally from ( 1.5 to 2) In. ,
So, we can consider it 2In is a maximum
I pickup = 1200 A
Fa > 20*Ipickup/In
3
0A > 40 A
SHF
BY
SEPT.2021
DATE
NO.
REVISIONS
DRAWN
BY:-
DATE:-
CHECKED
BY:-
DATE:-
OPRG. DEPT
BY
DATE:-
ENG'G. DEPT.
BY:-
DATE:-
CERTIFIED.
BY:-
DATE:-
AS BUILT BY DATE
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION 13.8KV CT ADEQUACY CALCULATION
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED UPGRADING OVER CURRENT PROTECTION AT MEDSO SUBSTATION P 01 OF A
AND DATED