Protective Relay Co-ordination
February – 2006
By
1. Introduction 1
2. Executive Summary 2
7. Relay Catalogues
6.1. Single line Diagram Showing Over Current Relay Setting &
Timings. (Drg.No: EPPPL/1188/ITC/001)
6.2. Single line Diagram Showing Earth Fault Relay Setting &
Timings. (Drg.No: EPPPL/1188/ITC/002)
1. INTRODUCTION
1. INTRODUCTION
Elsytec Power Projects Pvt Ltd Chennai was asked to study the protective relaying at ITC
Kovai Unit in the wake of recent disturbances in grid and local faults in the plant which caused
tripping of their in plant turbine as well as Utility supply. Also any addition /alteration required to
protective relaying scheme were asked to be identified in the light of their proposed export of
power from in plant generator to Grid.
A snap study was undertaken by Elsytec Power Projects Pvt Limited by making a visit to
their plant on 16th and 17th of Jan 2006 and Electrical system details along with protection scheme
were studied by holding discussions with their engineers.
Following are the high lights of discussion and study.
• Three major tripping that happened recently were discussed in depth and details analyzed
• The analysis revealed serious shortcomings in the maintenance of system which led to the
faulty tripping of in plant generator and Grid
• Failure to connect/test certain protective relays
• Necessity to tighten the preventive maintenance checks which are vulnerable in nature
• Necessity to check the relay co-ordination as well as test and calibrate the relays
• Necessity check and revamp earthing system
This report details the present settings and analyses the tripping scenarios in the faults that
affected the plants as well as scenarios faults at various levels. The report also details the existing
settings, their tripping times, previous consultant’s settings and their tripping time and under
various scenarios and Elsytec’s suggested modification in settings where necessary.
Report is divided in to following sections:
• Fault level calculations
• Existing settings and tripping times and sequence during 3.0kV fault which crippled the
mill
• Tripping times for faults at various buses
• Elsytec’s suggested settings for proper Co-ordination with various settings in tabular
format and setting marked in SLD for easy reference
2.EXECUTIVE SUMMARY
2. EXECUTIVE SUMMARY
Protection scenario:
• All 11kV switchgear are provided with IDMTL electromagnetic relays of Type TJM
Easun Reyrolle make for their associated feeder protection with two over current and one
earth fault element
• Sensitive earth fault relays type MIT Easun Reyrolle make are also seen to be
provided in SB1 and appear to have not been connected and they appear to be in
service in Generator panel
• Vector surge relay of type MICOM GE Alstom make is in service at 11kV incomer
breaker of grid at SB1 and appears to be operating effectively
Recommendation and comments:
Elsytec Power projects Pvt Ltd has carried out detailed fault calculation study
and arrived at appropriate settings for the relay coordination consistent with plant
scenarios.
1. Basically the presents settings need adjustments to the new values indicated in the report
as present settings lack co ordination as given in Section-3.
2. It may be noted that incoming fault level and equivalent line impedance is ignored in this
fault calculations, as it is less than 10% of the available impedances of the mill circuits.
Also the cable impedances are not taken into consideration as these values are very small
to have any effect in the calculations.
3. Neutral CT and sensitive earth fault relay in 433 volts transformer neutral is to be
provided.
4. Sensitive earth fault relay in SB1 to be put in service. It should be noted that certain faults
in the system like 3.0 kV bus faults will not operate the O/C element of 11kV switchgear
as the fault current will not be sufficient to operate these relays and residual current in
sensitive earth fault relay can only serve as back up for 3kV system protective relays.
5. Please note Instantaneous settings in present settings are 99.99%, may be this is to be
switched off.
6. Reverse power element in MICOM relay to be disabled as and when the generator is
connected for export of power after discussing with TNEB for any other requirements for
export of power.
7. It is imperative D.C trip supply is maintained in healthy condition to avoid repetition of
failures and prevent fire risks and burn outs in future Possibly Trip supply supervision
relay and alarm at central place like T.G control panel can be installed apart from daily
check of “trip circuit healthy” lamp check manually on daily basis.
8. Earthing system integrity and maintain earth grid resistance with in 1ohm is a basic
requirement.
9. Relay and meter testing shall be carried out at periodic interval not exceeding 2 year is a
must.
3.RELAY SETTINGS & TIMINGS
Project : ITC Ltd PSPD - Kovai Unit ELSYTEC POWER PROJECTS PVT LTD,
CHENNAI.
SB-2 (11kV)
Transformer (10MVA) = 9.61 %
TG (8MW) = 12 % SOURCE CURRENT
T/F || TG = 5.33641832 % T/F 5.462
%Zeq = 5.33641832 % TG 4.374
Fault MVA = 187.392 MVA 9.836
Short Circuit Current Isc = 9.836 kA
SB-3 (11kV)
Transformer (10MVA) = 9.61 % SOURCE CURRENT
TG(8MW) = 12 % T/F 5.462
T/F || TG = 5.33641832 % TG 4.374
%Zeq = 5.33641832 % 9.836
Fault MVA = 187.392 MVA
Short Circuit Current Isc = 9.836 kA
SB-4 (11kV)
Transformer (10MVA) = 9.61 % SOURCE CURRENT
TG(8MW) = 12 % T/F 5.462
T/F || TG = 5.33641832 % TG 4.374
%Zeq = 5.33641832 % 9.836
Fault MVA = 187.392 MVA
Short Circuit Current Isc = 9.836 kA
SB-5 (3kV)
a Transformer (10MVA) = 9.61 % SOURCE CURRENT
b TG(8MW) = 12 % T/F 0.5266985
c Tr-2 (1MVA) = 50 % TG 0.422
d a || b = 5.336 % 0.948
e %Zeq = c+d = 55.336 %
Fault MVA = 18.071 MVA
Short Circuit Current Isc = 3.478 kA
TG-PMCC-3 (3.3kV)
a Transformer (10MVA) = 9.61 % SOURCE CURRENT
b TG(8MW) = 12 % T/F 0.9300875
c Aux.Tr-3 (2.5MVA) = 26 % TG 0.745
d a || b = 5.33641832 % 1.675
e %Zeq = c+d = 31.3364183 %
Fault MVA = 31.912 MVA
Short Circuit Current Isc = 5.583 kA
4
Project : ITC Ltd PSPD - Kovai Unit ELSYTEC POWER PROJECTS PVT LTD,
CHENNAI.
TG - PMCC1 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Aux.Tr-1 (2MVA) = 40 % T/F 0.6428741
d a || b = 5.33641832 % TG 0.515
e %Zeq = c+d = 45.3364183 % 1.158
Fault MVA = 22.057 MVA
Short Circuit Current Isc = 29.411 kA
PMCC-1 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Tr-1 (2.5MVA) = 28 % T/F 0.8742874
d a || b = 5.33641832 % TG 0.700
e %Zeq = c+d = 33.3364183 % 1.574
Fault MVA = 29.997 MVA
Short Circuit Current Isc = 39.997 kA
PMCC-3 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Tr-3 (2MVA) = 33.00 % T/F 0.7602591
d a || b = 5.33641832 % TG 0.609
e %Zeq = c+d = 38.3364183 % 1.369
Fault MVA = 26.085 MVA
Short Circuit Current Isc = 34.781 kA
PMCC-4 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Tr-4 (2MVA) = 32.8 % T/F 0.7642462
d a || b = 5.33641832 % TG 0.612
e %Zeq = c+d = 38.1364183 % 1.376
Fault MVA = 26.222 MVA
Short Circuit Current Isc = 34.963 kA
PMCC-5 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Tr-5 (2MVA) = 33.15 % T/F 0.757296
d a || b = 5.33641832 % TG 0.606
e %Zeq = c+d = 38.4864183 % 1.364
Fault MVA = 25.983 MVA
Short Circuit Current Isc = 34.645 kA
5
Project : ITC Ltd PSPD - Kovai Unit ELSYTEC POWER PROJECTS PVT LTD,
CHENNAI.
PMCC-6 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Tr-6 (315kVA) = 147.301587 % T/F 0.190946
d a || b = 5.33641832 % TG 0.153
e %Zeq = c+d = 152.638006 % 0.344
Fault MVA = 6.551 MVA
Short Circuit Current Isc = 8.736 kA
PMCC-7 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Tr-7 (1.6MVA) = 41.9375 % T/F 0.6165262
d a || b = 5.33641832 % TG 0.494
e %Zeq = c+d = 47.2739183 % 1.110
Fault MVA = 21.153 MVA
Short Circuit Current Isc = 28.205 kA
PMCC-8 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Tr-8 (1.6MVA) = 40.4375 % T/F 0.6367297
d a || b = 5.33641832 % TG 0.510
e %Zeq = c+d = 45.7739183 % 1.147
Fault MVA = 21.847 MVA
Short Circuit Current Isc = 29.130 kA
PMCC-9 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Tr-9 (1.6MVA) = 41.5625 % T/F 0.6214559
d a || b = 5.33641832 % TG 0.498
e %Zeq = c+d = 46.8989183 % 1.119
Fault MVA = 21.322 MVA
Short Circuit Current Isc = 28.431 kA
DCD-10 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Tr-10 (1.6MVA) = 41.875 % T/F 0.6173424
d a || b = 5.33641832 % TG 0.494
e %Zeq = c+d = 47.2114183 % 1.112
Fault MVA = 21.181 MVA
Short Circuit Current Isc = 28.243 kA
DCD- 11 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Tr-11 (1.6MVA) = 41.625 % T/F 0.6206289
d a || b = 5.33641832 % TG 0.497
e %Zeq = c+d = 46.9614183 % 1.118
Fault MVA = 21.294 MVA
Short Circuit Current Isc = 28.393 kA
6
Primary
Fault Current in Tripping Time
S.No SB No Description Relay Type Current in PS TMS I//Ipu
kA (Sec)
CT(A)
252-3 SB-1 TIE TO TG-1 SG CDD 31 4.374 500 1 0.7 8.75 0.98
252-26 TG-1 TIE TO SB-1 CDD 31 4.374 500 1 0.7 8.75 0.98
252-21 TG-1 I/C FROM TG CDG 31 4.374 600 1 0.85 7.29 1.3
8
Primary
Fault Current in Tripping Time
S.No SB No Description Relay Type Current in PS TMS I//Ipu
kA (Sec)
CT(A)
252-1 SB-1 I/C FOR SB-1 TJM 10 0.616 800 1 0.4 0.77 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 0.062 75 1 0.85 0.82 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 0.616 500 1 0.7 1.23 5
252-26 TG-1 TIE TO SB-1 CDD 31 0.616 500 1 0.7 1.23 5
9
Primary
Fault Current in Tripping Time
S.No SB No Description Relay Type Current in PS TMS I//Ipu
kA (Sec)
CT(A)
Fault at PMCC-5 (433V)
452-14 PMCC-5 I/C FROM TR-5 CDG 31 34.645 3000 1 0.15 11.55 0.19
252-13 SB-3 OG TO TR-5 TJM 10 1.364 125 1 0.1 10.91 0.31
252-9 SB-3 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-3 TJM 10 1.364 400 1 0.3 3.41 2.6
252-1 SB-1 I/C OF SB-1 TJM 10 0.757 800 1 0.4 0.95 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 0.076 75 1 0.85 1.01 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 0.757 500 1 0.7 1.51 4.5
252-26 TG-1 TIE TO SB-1 CDD 31 0.757 500 1 0.7 1.51 4.5
252-21 TG-1 I/C FROM TG CDG 31 0.606 600 1 0.85 1.01 6
10
Primary
Fault Current in Tripping Time
S.No SB No Description Relay Type Current in PS TMS I//Ipu
kA (Sec)
CT(A)
Fault at PMCC-8 (433V)
452-18 PMCC-8 I/C FROM TR-8 CDG 31 29.130 2500 1 0.15 11.65 0.18
252-18 SB-4 OG TO TR-7 TJM 10 1.147 100 1 0.1 11.47 0.3
252-9 SB-4 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-4 TJM 10 1.147 500 1 0.3 2.29 2.6
252-1 SB-1 I/C FOR SB-1 TJM 10 0.617 800 1 0.4 0.77 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 0.062 75 1 0.85 0.82 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 0.530 500 1 0.7 1.06 Infinity
252-26 TG-1 TIE TO SB-1 CDD 31 0.530 500 1 0.7 1.06 Infinity
252-21 TG-1 I/C FROM TG CDG 31 0.530 600 1 0.85 0.88 Infinity
11
Primary
Fault Current in Tripping Time
S.No SB No Description Relay Type Current in PS TMS I//Ipu
kA (Sec)
CT(A)
Fault at DCD 11 (433V)
452-15 DCD-11 I/C FROM TR-11 CDG 31 28.393 2500 1 0.15 11.36 0.18
252-15 SB-4 OG TO TR-11 TJM 10 1.118 100 1 0.1 11.18 0.3
252-9 SB-4 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-4 TJM 10 1.118 500 1 0.3 2.24 2.6
252-1 SB-1 I/C FOR SB-1 TJM 10 0.621 800 1 0.4 0.78 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 0.062 75 1 0.85 0.83 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 0.497 500 1 0.7 0.99 Infinity
252-26 TG-1 TIE TO SB-1 CDD 31 0.497 500 1 0.7 0.99 Infinity
252-21 TG-1 I/C FROM TG CDG 31 0.497 600 1 0.85 0.83 Infinity
12
3.1.3. Existing Relay Settings for Over Current
Primary
Fault Current Tripping
S.No SB No Description Relay Type Current in PS TMS I//Ipu
in kA Time (Sec)
CT(A)
Fault at SB-1 (11kV)
1 SB-1 OG TO SB-2 TJM 10 9.836 150 1 0.5 65.57 1.2
2 SB-1 I/C FOR SB-1 TJM 10 5.462 800 0.75 0.7 9.10 2.1
3 SB-1 I/C FROM 110kV Line ICM 21 0.546 75 0.75 0.8 9.71 2.4
4 SB-1 TIE TO TG-1 SG CDD 31 4.374 500 1.25 0.95 7.00 1.3
5 TG-1 TIE TO SB-1 CDD 31 4.374 500 1 0.65 8.75 0.84
6 TG-1 I/C FROM TG CDG 31 4.374 600 1 0.4 7.29 0.58
Fault at TG PMCC-3(3.3kV)
352-2 SB-6 I/C FROM AUX.TR-3 CDG 31 100 500 0.1 0.1 2.00 0.26
SB-6 AUX.TR NUTRAL MIT 161 100 500 0.1 0.075 2.00 0.75
252-25 SB-1 OG TO AUX.TR-3 CDG 31 100 200 0.25 0.3 2.00 0.92
252-21 SB-1 I/C FROM TG CDG 31 100 600 0.1 0.45 1.67 1.80
252-1 SB-1 I/C FOR SB-1 MIT 161 100 800 0.075 0.15 1.67 2.05
152-1 SB-1 I/C FROM 110kV Line ICM 21 100 75 0.75 0.2 1.78 2.30
252-3 SB-1 TIE TO TG-1 SG MIT 161 100 500 0.1 0.15 2.00 1.51
252-26 TG-1 TIE TO SB-1 MIT 161 100 500 0.1 0.15 2.00 1.51
Fault at TG PMCC-3(3.3kV)
352-2 SB-6 I/C FROM AUX.TR-3 500 CDG 31 0.1 0.1 0.26 CDG 31 0.1 0.1 0.26
SB-6 AUX.TR NUTRAL 500 - - - MIT 161 0.1 0.075 0.75
252-25 SB-1 OG TO AUX.TR-3 200 CDG 31 0.1 0.1 0.16 CDG 31 0.25 0.3 0.92
252-21 SB-1 I/C FROM TG 600 CDG 31 0.1 0.3 1.1 CDG 31 0.1 0.45 1.80
252-1 SB-1 I/C FOR SB-1 800 TJM 10 0.2 0.2 7 MIT 161 0.075 0.15 2.05
152-1 SB-1 I/C FROM 110kV Line 75 ICM 21 0.1 0.1 0.27 ICM 21 0.75 0.2 2.30
252-3 SB-1 TIE TO TG-1 SG 500 MIT 161 0.005 0.7 1.28 MIT 161 0.1 0.15 1.51
252-26 TG-1 TIE TO SB-1 500 MIT 161 0.005 0.25 0.458 MIT 161 0.1 0.15 1.51
1. GT
2. Tr-1
3. Tr-2
4. Tr-3
5. Tr-4
6. Tr-5
7. Tr-6
8. Tr-7
9. Tr-8
10. Tr-9
11. Tr-10
12. Tr-11
13. Aux.Tr-1
14. Aux.Tr-2
15. Aux.Tr-3 and also
252-1 Incoming from 10/12.5MVA Transformer
252-4 Outgoing to SB-3 from SB-1.
252-5 Outgoing to SB-4 from SB-1
252-3 Tie feeder from SB-1 to TG
252-26 Tie feeder from TG to SB-1
In the above places MIT 161 type of relays is recommended to installed and CT
ratios to match with LT side CT’s respective Breakers. (Refer 3.2.1.)
5. RECOMMENDED SETTINGS
FOR OVER CURRENT &
EARTH FAULT
RECOMMENDED SETTINGS FOR OVER CURRENT AND EARTH FAULT BY ELSYTEC
RECOMMENDED SETTINGS FOR OVER CURRENT
Plug
Device No Device Location Relay Type CT Ratio TMS
Settings
152-1 I/C FROM 110kV LINE ICM 21 75/1A 1 0.85
252-1 I/C FOR SB-1 TJM 10 800/1A 1 0.4
252-2 OG TO SB-2 FROM SB-1 TJM 10 150/1A 1 0.3
252-3 TIE TO SB-1 TO TG1 CDD 31 500/1A 1 0.7
252-4 OG TO SB-3 FROM SB-1 TJM 10 400/1A 1 0.3
252-5 OG TO SB-4 FROM SB-1 TJM 10 500/1A 1 0.3
252-7 I/C FROM SB-1 IN SB-2 TJM 10 150/1A 1 0.3
252-8 OG TO TR-1 FROM SB-2 - - - -
252-9 I/C FROM SB-1 IN SB-3 - - - -
252-10 OG TO TR-2 FROM SB-3 TJM 10 100/1A 0.75 0.1
252-11 OG TO TR-3 FROM SB-3 TJM 10 125/1A 1 0.1
252-12 OG TO TR-4 FROM SB-3 TJM 10 125/1A 1 0.1
252-13 OG TO TR-5 FROM SB-3 TJM 10 125/1A 1 0.1
252-14 I/C FROM SB-1 IN SB-4 - - - -
252-15 OG TO TR-11 FROM SB-4 TJM 10 100/1A 1 0.1
252-16 OG TO TR-10 FROM SB-4 TJM 10 100/1A 1 0.1
252-17 OG TO TR-9 FROM SB-4 TJM 10 100/1A 1 0.1
252-18 OG TO TR-8 FROM SB-4 TJM 10 100/1A 1 0.1
252-19 OG TO TR-7 FROM SB-4 TJM 10 100/1A 1 0.1
252-20 OG TO TR-6 FROM SB-4 TJM 10 100/1A 1 0.1
252-21 I/C FROM TG IN TG SG CDG 31 600/1A 1 0.85
252-22 OG TO Aux.TR-1 FROM TG1 CDG 31 200/1A 1 0.3
252-23 OG TO Aux.TR-2 FROM TG1 CDG 31 200/1A 1 0.3
252-25 OG TO Aux.TR-3 FROM TG1 CDG 31 200/1A 1 0.3
252-26 TIE TO TG1 TO SB-1 CDD 31 500/1A 1 0.7
352-1 I/C FROM TR-2 IN SB-5 TJM 10 200/1A 1 0.1
352-2 I/C FROM Aux.TR-3 IN TG PMCC-3 CDG 31 500/1A 1 0.1
452-1 I/C FROM Aux.TR-1 IN TG PMCC-1 CDG 31 3000/1A 1 0.1
452-2 I/C FROM Aux.TR-2 IN TG PMCC-2 CDG 31 3000/1A 1 0.1
452-11 I/C FROM TR-1 IN PMCC-1 CDG 31 4000/1A 1 0.15
452-12 I/C FROM TR-3 IN PMCC-3 CDG 31 3000/1A 1 0.15
452-13 I/C FROM TR-4 IN PMCC-4 CDG 31 3000/1A 1 0.15
452-14 I/C FROM TR-5 IN PMCC-5 CDG 31 3000/1A 1 0.15
452-15 I/C FROM TR-11 IN DCD-11 CDG 31 2500/1A 1 0.15
452-16 I/C FROM TR-10 IN DCD-10 CDG 31 2500/1A 1 0.15
452-17 I/C FROM TR-9 IN PMCC-9 CDG 31 2500/1A 1 0.15
452-18 I/C FROM TR-8 IN PMCC-8 CDG 31 2500/1A 1 0.15
452-19 I/C FROM TR-7 IN PMCC-7 CDG 31 2500/1A 1 0.15
452-20 I/C FROM TR-6 IN PMCC-6 CDG 31 600/1A 1 0.15
49
RECOMMENDED SETTINGS FOR EARTH FAULT
Plug
Device No Device Location Relay Type CT Ratio Settings TMS
152-1 I/C FROM 110kV LINE ICM 21 75/1A 0.75 0.2
252-1 I/C FOR SB-1 MIT 161 800/1A 0.075 0.15
252-2 OG TO SB-2 FROM SB-1 TJM 10 150/1A 0.3 0.1
252-3 TIE TO SB-1 TO TG1 MIT 161 500/1A 0.1 0.15
252-4 OG TO SB-3 FROM SB-1 MIT 161 400/1A 0.125 0.125
252-5 OG TO SB-4 FROM SB-1 MIT 161 500/1A 0.1 0.125
252-7 I/C FROM SB-1 IN SB-2 TJM 10 150/1A 0.3 0.1
252-8 OG TO TR-1 FROM SB-2 - - - -
252-9 I/C FROM SB-1 IN SB-3 - - - -
252-10 OG TO TR-2 FROM SB-3 TJM 10 100/1A 0.5 0.1
252-11 OG TO TR-3 FROM SB-3 TJM 10 125/1A 0.4 0.1
252-12 OG TO TR-4 FROM SB-3 TJM 10 125/1A 0.4 0.1
252-13 OG TO TR-5 FROM SB-3 TJM 10 125/1A 0.4 0.1
252-14 I/C FROM SB-1 IN SB-4 - - - -
252-15 OG TO TR-11 FROM SB-4 TJM 10 100/1A 0.5 0.1
252-16 OG TO TR-10 FROM SB-4 TJM 10 100/1A 0.5 0.1
252-17 OG TO TR-9 FROM SB-4 TJM 10 100/1A 0.5 0.1
252-18 OG TO TR-8 FROM SB-4 TJM 10 100/1A 0.5 0.1
252-19 OG TO TR-7 FROM SB-4 TJM 10 100/1A 0.5 0.1
252-20 OG TO TR-6 FROM SB-4 TJM 10 100/1A 2 0.1
252-21 I/C FROM TG IN TG SG CDG 31 600/1A 0.1 0.45
252-22 OG TO Aux.TR-1 FROM TG1 CDG 31 200/1A 0.25 0.3
252-23 OG TO Aux.TR-2 FROM TG1 CDG 31 200/1A 0.25 0.3
252-25 OG TO Aux.TR-3 FROM TG1 CDG 31 200/1A 0.25 0.3
252-26 TIE TO TG1 TO SB-1 MIT 161 500/1A 0.1 0.15
352-1 I/C FROM TR-2 IN SB-5 TJM 10 200/1A 0.5 0.1
352-2 I/C FROM Aux.TR-3 IN TG PMCC-3 CDG 31 500/1A 0.1 0.1
452-1 I/C FROM Aux.TR-1 IN TG PMCC-1 CDG 31 3000/1A 0.1 0.1
452-2 I/C FROM Aux.TR-2 IN TG PMCC-2 CDG 31 3000/1A 0.1 0.1
452-11 I/C FROM TR-1 IN PMCC-1 CDG 31 4000/1A 0.1 0.1
452-12 I/C FROM TR-3 IN PMCC-3 CDG 31 3000/1A 0.1 0.1
452-13 I/C FROM TR-4 IN PMCC-4 CDG 31 3000/1A 0.1 0.1
452-14 I/C FROM TR-5 IN PMCC-5 CDG 31 3000/1A 0.1 0.1
452-15 I/C FROM TR-11 IN DCD-11 CDG 31 2500/1A 0.1 0.1
452-16 I/C FROM TR-10 IN DCD-10 CDG 31 2500/1A 0.1 0.1
452-17 I/C FROM TR-9 IN PMCC-9 CDG 31 2500/1A 0.1 0.1
452-18 I/C FROM TR-8 IN PMCC-8 CDG 31 2500/1A 0.1 0.1
452-19 I/C FROM TR-7 IN PMCC-7 CDG 31 2500/1A 0.1 0.1
452-20 I/C FROM TR-6 IN PMCC-6 CDG 31 600/1A 0.1 0.1
GT NEUTRAL MIT 161 100/1A 0.6 0.15
TR-1 NEUTRAL MIT 161 4000/1A 0.1 0.075
TR-2 NEUTRAL MIT 161 200/1A 0.25 0.1
TR-3 NEUTRAL MIT 161 3000/1A 0.1 0.075
TR-4 NEUTRAL MIT 161 3000/1A 0.1 0.075
TR-5 NEUTRAL MIT 161 3000/1A 0.1 0.075
TR-6 NEUTRAL MIT 161 600/1A 0.1 0.075
TR-7 NEUTRAL MIT 161 2500/1A 0.1 0.075
TR-8 NEUTRAL MIT 161 2500/1A 0.1 0.075
TR-9 NEUTRAL MIT 161 2500/1A 0.1 0.075
TR-10 NEUTRAL MIT 161 2500/1A 0.1 0.075
TR-11 NEUTRAL MIT 161 2500/1A 0.1 0.075
Aux.TR-1 NEUTRAL MIT 161 3000/1A 0.1 0.075
Aux.TR-2 NEUTRAL MIT 161 3000/1A 0.1 0.075
50
Aux.TR-3 NEUTRAL MIT 161 500/1A 0.1 0.075
51