You are on page 1of 52

ITC LIMITED PAPERBOARDS &

SPECIALITY PAPERS DIVISION


UNIT - KOVAI

Technical Report
Protective Relay Co-ordination

February – 2006

By

Engineering Service Excellence


Elsytec Power Projects Pvt Ltd
Consultancy & Engineering Services
Chennai-600 083
Contents
S.No Description Page No

1. Introduction 1

2. Executive Summary 2

3. Relay Settings and Timings

3.1. Over Current Relay Settings

3.1.1. Fault Calculations 4

3.1.2. Recommended Over Current Settings 7

3.1.3. Existing Relay Settings for Over Current 13

3.1.4. Time-Current Characteristics Curves 19

3.2. Earth Fault Relay Settings

3.2.1. Recommended Earth Fault Relay Settings 22

3.2.2. Existing Relay Settings 30

4 Comparison of Existing and Recommended Settings

4.1. Over Current Settings 36

4.2. Earth Fault Settings 42

5 Proposed additional Relays recommended by Elsytec 48

6. Recommended Settings for Over Current and Earth Fault 49

7. Relay Catalogues

8. Single Line Diagrams

6.1. Single line Diagram Showing Over Current Relay Setting &
Timings. (Drg.No: EPPPL/1188/ITC/001)
6.2. Single line Diagram Showing Earth Fault Relay Setting &
Timings. (Drg.No: EPPPL/1188/ITC/002)
1. INTRODUCTION
1. INTRODUCTION

Elsytec Power Projects Pvt Ltd Chennai was asked to study the protective relaying at ITC
Kovai Unit in the wake of recent disturbances in grid and local faults in the plant which caused
tripping of their in plant turbine as well as Utility supply. Also any addition /alteration required to
protective relaying scheme were asked to be identified in the light of their proposed export of
power from in plant generator to Grid.
A snap study was undertaken by Elsytec Power Projects Pvt Limited by making a visit to
their plant on 16th and 17th of Jan 2006 and Electrical system details along with protection scheme
were studied by holding discussions with their engineers.
Following are the high lights of discussion and study.
• Three major tripping that happened recently were discussed in depth and details analyzed
• The analysis revealed serious shortcomings in the maintenance of system which led to the
faulty tripping of in plant generator and Grid
• Failure to connect/test certain protective relays
• Necessity to tighten the preventive maintenance checks which are vulnerable in nature
• Necessity to check the relay co-ordination as well as test and calibrate the relays
• Necessity check and revamp earthing system
This report details the present settings and analyses the tripping scenarios in the faults that
affected the plants as well as scenarios faults at various levels. The report also details the existing
settings, their tripping times, previous consultant’s settings and their tripping time and under
various scenarios and Elsytec’s suggested modification in settings where necessary.
Report is divided in to following sections:
• Fault level calculations
• Existing settings and tripping times and sequence during 3.0kV fault which crippled the
mill
• Tripping times for faults at various buses
• Elsytec’s suggested settings for proper Co-ordination with various settings in tabular
format and setting marked in SLD for easy reference
2.EXECUTIVE SUMMARY
2. EXECUTIVE SUMMARY

Present scenario Electrical Installation:


The H.T distribution of electrical installation is shown in Dwg No: TCE-4312A-733-
AU-3002 and it primarily consists of the following:
• 110 kV substation with its attendant breakers and CT’s and isolators
10/12.5 MVA 110kV/11kV transformer
• Neutral grounding Resistor to limit the earth fault current to 100 amps
• 11 KV switchgear SB1, SB2, SB3, SB4 comprising of withdrawal type Vacuum circuit
breaker switchgear
• Distribution Transformers ratings 1 MVA11kV/3.0 kV, 2.5MVA 11kV/433 volts,
2.0MVA 11kV/433V, 1.6MVA 11kV/433V and 315kVA, 11kV/433 volts
• All 433 volts secondary side neutral of transformer are solidly earthed
• 3.0 KV side of 11kV/3.0kV transformers neutral is resistor earthed to limit the current to
100 amps.
In plant Generator:
• 8MW 11kV extraction cum condensing set has been recently commissioned
• This is connected to associated vacuum circuit breaker board as shown in single line
diagram and hooked up to switchgear SB1 through tie breakers
• Condensing capacity is understood be 3.5 MW
• In plant generator can meet almost entire load of mill
Operating Scenario:
Normally the in plant generator and Grid are operated in parallel with necessary
protection and synchronizing facilities as shown single diagram. Marginal power to the tune of
500kW is drawn under healthy condition. In case of Grid disturbances Vector surge relay in 11kV
switchgear in SB1 islands the generator.

Protection scenario:
• All 11kV switchgear are provided with IDMTL electromagnetic relays of Type TJM
Easun Reyrolle make for their associated feeder protection with two over current and one
earth fault element
• Sensitive earth fault relays type MIT Easun Reyrolle make are also seen to be
provided in SB1 and appear to have not been connected and they appear to be in
service in Generator panel
• Vector surge relay of type MICOM GE Alstom make is in service at 11kV incomer
breaker of grid at SB1 and appears to be operating effectively
Recommendation and comments:
Elsytec Power projects Pvt Ltd has carried out detailed fault calculation study
and arrived at appropriate settings for the relay coordination consistent with plant
scenarios.
1. Basically the presents settings need adjustments to the new values indicated in the report
as present settings lack co ordination as given in Section-3.
2. It may be noted that incoming fault level and equivalent line impedance is ignored in this
fault calculations, as it is less than 10% of the available impedances of the mill circuits.
Also the cable impedances are not taken into consideration as these values are very small
to have any effect in the calculations.
3. Neutral CT and sensitive earth fault relay in 433 volts transformer neutral is to be
provided.
4. Sensitive earth fault relay in SB1 to be put in service. It should be noted that certain faults
in the system like 3.0 kV bus faults will not operate the O/C element of 11kV switchgear
as the fault current will not be sufficient to operate these relays and residual current in
sensitive earth fault relay can only serve as back up for 3kV system protective relays.
5. Please note Instantaneous settings in present settings are 99.99%, may be this is to be
switched off.
6. Reverse power element in MICOM relay to be disabled as and when the generator is
connected for export of power after discussing with TNEB for any other requirements for
export of power.
7. It is imperative D.C trip supply is maintained in healthy condition to avoid repetition of
failures and prevent fire risks and burn outs in future Possibly Trip supply supervision
relay and alarm at central place like T.G control panel can be installed apart from daily
check of “trip circuit healthy” lamp check manually on daily basis.
8. Earthing system integrity and maintain earth grid resistance with in 1ohm is a basic
requirement.
9. Relay and meter testing shall be carried out at periodic interval not exceeding 2 year is a
must.
3.RELAY SETTINGS & TIMINGS
Project : ITC Ltd PSPD - Kovai Unit ELSYTEC POWER PROJECTS PVT LTD,
CHENNAI.

3. Relay Settings and Timings


3.1. Over Current Relay Settings
3.1.1. Fault Calculations - Phase Fault
Base 10 MVA
SB-1 (11kV)
Transformer (10MVA) = 9.61 %
TG(8MW) = 12 % SOURCE CURRENT
T/F || TG = 5.33641832 % T/F 5.462
%Zeq = 5.33641832 % TG 4.374
Fault MVA = 187.392 MVA 9.836
Short Circuit Current Isc = 9.836 kA

SB-2 (11kV)
Transformer (10MVA) = 9.61 %
TG (8MW) = 12 % SOURCE CURRENT
T/F || TG = 5.33641832 % T/F 5.462
%Zeq = 5.33641832 % TG 4.374
Fault MVA = 187.392 MVA 9.836
Short Circuit Current Isc = 9.836 kA

SB-3 (11kV)
Transformer (10MVA) = 9.61 % SOURCE CURRENT
TG(8MW) = 12 % T/F 5.462
T/F || TG = 5.33641832 % TG 4.374
%Zeq = 5.33641832 % 9.836
Fault MVA = 187.392 MVA
Short Circuit Current Isc = 9.836 kA

SB-4 (11kV)
Transformer (10MVA) = 9.61 % SOURCE CURRENT
TG(8MW) = 12 % T/F 5.462
T/F || TG = 5.33641832 % TG 4.374
%Zeq = 5.33641832 % 9.836
Fault MVA = 187.392 MVA
Short Circuit Current Isc = 9.836 kA

SB-5 (3kV)
a Transformer (10MVA) = 9.61 % SOURCE CURRENT
b TG(8MW) = 12 % T/F 0.5266985
c Tr-2 (1MVA) = 50 % TG 0.422
d a || b = 5.336 % 0.948
e %Zeq = c+d = 55.336 %
Fault MVA = 18.071 MVA
Short Circuit Current Isc = 3.478 kA

TG-PMCC-3 (3.3kV)
a Transformer (10MVA) = 9.61 % SOURCE CURRENT
b TG(8MW) = 12 % T/F 0.9300875
c Aux.Tr-3 (2.5MVA) = 26 % TG 0.745
d a || b = 5.33641832 % 1.675
e %Zeq = c+d = 31.3364183 %
Fault MVA = 31.912 MVA
Short Circuit Current Isc = 5.583 kA

4
Project : ITC Ltd PSPD - Kovai Unit ELSYTEC POWER PROJECTS PVT LTD,
CHENNAI.

TG - PMCC1 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Aux.Tr-1 (2MVA) = 40 % T/F 0.6428741
d a || b = 5.33641832 % TG 0.515
e %Zeq = c+d = 45.3364183 % 1.158
Fault MVA = 22.057 MVA
Short Circuit Current Isc = 29.411 kA

TG-1 Switchgear (11kV)


Transformer (10MVA) = 9.61 % SOURCE CURRENT
TG (8MW) = 12 % T/F 5.4616429
T/F || TG = 5.33641832 % TG 4.374
%Zeq = 5.33641832 % 9.836
Fault MVA = 187.392 MVA
Short Circuit Current Isc = 9.836 kA

PMCC-1 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Tr-1 (2.5MVA) = 28 % T/F 0.8742874
d a || b = 5.33641832 % TG 0.700
e %Zeq = c+d = 33.3364183 % 1.574
Fault MVA = 29.997 MVA
Short Circuit Current Isc = 39.997 kA

PMCC-3 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Tr-3 (2MVA) = 33.00 % T/F 0.7602591
d a || b = 5.33641832 % TG 0.609
e %Zeq = c+d = 38.3364183 % 1.369
Fault MVA = 26.085 MVA
Short Circuit Current Isc = 34.781 kA

PMCC-4 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Tr-4 (2MVA) = 32.8 % T/F 0.7642462
d a || b = 5.33641832 % TG 0.612
e %Zeq = c+d = 38.1364183 % 1.376
Fault MVA = 26.222 MVA
Short Circuit Current Isc = 34.963 kA

PMCC-5 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Tr-5 (2MVA) = 33.15 % T/F 0.757296
d a || b = 5.33641832 % TG 0.606
e %Zeq = c+d = 38.4864183 % 1.364
Fault MVA = 25.983 MVA
Short Circuit Current Isc = 34.645 kA

5
Project : ITC Ltd PSPD - Kovai Unit ELSYTEC POWER PROJECTS PVT LTD,
CHENNAI.

PMCC-6 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Tr-6 (315kVA) = 147.301587 % T/F 0.190946
d a || b = 5.33641832 % TG 0.153
e %Zeq = c+d = 152.638006 % 0.344
Fault MVA = 6.551 MVA
Short Circuit Current Isc = 8.736 kA

PMCC-7 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Tr-7 (1.6MVA) = 41.9375 % T/F 0.6165262
d a || b = 5.33641832 % TG 0.494
e %Zeq = c+d = 47.2739183 % 1.110
Fault MVA = 21.153 MVA
Short Circuit Current Isc = 28.205 kA

PMCC-8 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Tr-8 (1.6MVA) = 40.4375 % T/F 0.6367297
d a || b = 5.33641832 % TG 0.510
e %Zeq = c+d = 45.7739183 % 1.147
Fault MVA = 21.847 MVA
Short Circuit Current Isc = 29.130 kA

PMCC-9 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Tr-9 (1.6MVA) = 41.5625 % T/F 0.6214559
d a || b = 5.33641832 % TG 0.498
e %Zeq = c+d = 46.8989183 % 1.119
Fault MVA = 21.322 MVA
Short Circuit Current Isc = 28.431 kA

DCD-10 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Tr-10 (1.6MVA) = 41.875 % T/F 0.6173424
d a || b = 5.33641832 % TG 0.494
e %Zeq = c+d = 47.2114183 % 1.112
Fault MVA = 21.181 MVA
Short Circuit Current Isc = 28.243 kA

DCD- 11 (433V)
a Transformer (10MVA) = 9.61 %
b TG(8MW) = 12 % SOURCE CURRENT
c Tr-11 (1.6MVA) = 41.625 % T/F 0.6206289
d a || b = 5.33641832 % TG 0.497
e %Zeq = c+d = 46.9614183 % 1.118
Fault MVA = 21.294 MVA
Short Circuit Current Isc = 28.393 kA

6
Primary
Fault Current in Tripping Time
S.No SB No Description Relay Type Current in PS TMS I//Ipu
kA (Sec)
CT(A)
252-3 SB-1 TIE TO TG-1 SG CDD 31 4.374 500 1 0.7 8.75 0.98
252-26 TG-1 TIE TO SB-1 CDD 31 4.374 500 1 0.7 8.75 0.98
252-21 TG-1 I/C FROM TG CDG 31 4.374 600 1 0.85 7.29 1.3

Fault at TG-1 (11kV)


252-25 TG-1 OG TO AUX.TR-3 CDG 31 9.836 200 1 0.3 49.18 0.31
252-21 TG-1 I/C FROM TG CDG 31 4.374 600 1 0.85 9.10 1.15
252-1 SB-1 I/C FOR SB-1 TJM 10 5.462 800 1 0.4 6.83 1.5
152-1 SB-1 I/C FROM 110kV Line ICM 21 0.546 75 1 0.85 7.28 2.4
252-3 SB-1 TIE TO TG-1 SG CDD 31 5.462 500 1 0.7 10.92 0.88
252-26 TG-1 TIE TO SB-1 CDD 31 5.462 500 1 0.7 10.92 0.88

Fault at SB-5 (3kV)


352-1 SB-5 I/C FROM TR-2 TJM 10 3.478 200 1 0.1 17.39 0.26
252-10 SB-3 OG TO TR-2 TJM 10 0.948 100 0.75 0.1 12.65 0.39
252-9 SB-3 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-3 TJM 10 0.948 400 1 0.3 2.37 2.4
252-1 SB-1 I/C FOR SB-1 TJM 10 0.527 800 1 0.4 0.66 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 0.053 75 1 0.85 0.70 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 0.422 500 1 0.7 0.84 Infinity
252-26 TG-1 TIE TO SB-1 CDD 31 0.422 500 1 0.7 0.84 Infinity
252-21 TG-1 I/C FROM TG CDG 31 0.422 600 1 0.85 0.70 Infinity

Fault at TG-PMCC-3 (3.3kV)


352-2 SB-6 I/C FROM AUX.TR-3 CDG 31 5.583 500 1 0.1 11.17 0.13
252-25 TG-1 OG TO AUX.TR-3 CDG 31 1.675 200 1 0.3 8.37 0.42
252-21 TG-1 I/C FROM TG CDG 31 0.930 600 1 0.85 1.55 6
252-1 SB-1 I/C FOR SB-1 TJM 10 0.745 800 1 0.4 0.93 infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 0.074 75 1 0.85 0.99 infinity
252-3 TG-1 TIE TO TG-1 SG CDD 31 0.745 500 1 0.7 1.49 4
252-26 TG-1 TIE TO SB-1 CDD 31 0.745 500 1 0.7 1.49 4

Fault at TG-PMCC-2 (433V)


452-2 SB-4 I/C FROM AUX.TR-2 CDG 31 29.411 3000 1 0.1 9.80 0.13
252-23 SB-3 OG TO AUX.TR-2 CDG 31 1.110 200 1 0.3 5.55 0.48
252-21 SB-1 I/C FROM TG CDG 31 0.493 600 1 0.85 0.82 Infinity

8
Primary
Fault Current in Tripping Time
S.No SB No Description Relay Type Current in PS TMS I//Ipu
kA (Sec)
CT(A)
252-1 SB-1 I/C FOR SB-1 TJM 10 0.616 800 1 0.4 0.77 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 0.062 75 1 0.85 0.82 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 0.616 500 1 0.7 1.23 5
252-26 TG-1 TIE TO SB-1 CDD 31 0.616 500 1 0.7 1.23 5

Fault at PMCC-1 (433V)


452-11 PMCC1 I/C FROM SB2 CDG 31 39.997 4000 1 0.15 10.00 0.18
252-8 SB-2 OG TO TR-1 NO RELAY
252-7 SB-2 I/C FROM SB-1 TJM 10 1.574 150 1 0.3 10.50 0.88
252-2 SB-1 OG TO SB-2 TJM 10 1.574 150 1 0.3 10.50 0.88
252-1 SB-1 I/C FOR SB-1 TJM 10 0.874 800 1 0.4 1.09 12
152-1 SB-1 I/C FROM 110kV Line ICM 21 0.087 75 1 0.85 1.17 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 0.700 500 1 0.7 1.40 5
252-26 TG-1 TIE TO SB-1 CDD 31 0.700 500 1 0.7 1.40 5
252-21 TG-1 I/C FROM TG CDG 31 0.700 600 1 0.85 1.17 7
Fault at PMCC-3 (433V)
252-12 PMCC3 I/C FROM SB2 CDG 31 34.781 3000 1 0.15 11.59 0.18
252-11 SB-3 OG TO TR-3 TJM 10 1.369 125 1 0.1 10.95 0.31
252-9 SB-3 I/C FROM SB1 NO RELAY 1.369
252-4 SB-1 OG TO SB-3 TJM 10 1.369 400 1 0.3 3.42 2.6
252-1 SB-1 I/C OF SB-1 TJM 10 0.760 800 1 0.4 0.95 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 0.076 75 1 0.85 1.01 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 0.609 500 1 0.7 1.22 4.5
252-26 TG-1 TIE TO SB-1 CDD 31 0.609 500 1 0.7 1.22 4.5
252-21 TG-1 I/C FROM TG CDG 31 0.609 600 1 0.85 1.01 6

Fault at PMCC-4 (433V)


452-13 PMCC4 I/C FROM TR-4 CDG 31 34.963 3000 1 0.15 11.65 0.18
252-12 SB-3 OG TO TR-4 TJM 10 1.376 125 1 0.1 11.01 0.31
252-9 SB-3 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-3 TJM 10 1.376 400 1 0.3 3.44 2.6
252-1 SB-1 I/C OF SB-1 TJM 10 0.764 800 1 0.4 0.96 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 0.076 75 1 0.85 1.02 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 0.764 500 1 0.7 1.53 4.5
252-26 TG-1 TIE TO SB-1 CDD 31 0.764 500 1 0.7 1.53 4.5
252-21 TG-1 I/C FROM TG CDG 31 0.612 600 1 0.85 1.02 6

9
Primary
Fault Current in Tripping Time
S.No SB No Description Relay Type Current in PS TMS I//Ipu
kA (Sec)
CT(A)
Fault at PMCC-5 (433V)
452-14 PMCC-5 I/C FROM TR-5 CDG 31 34.645 3000 1 0.15 11.55 0.19
252-13 SB-3 OG TO TR-5 TJM 10 1.364 125 1 0.1 10.91 0.31
252-9 SB-3 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-3 TJM 10 1.364 400 1 0.3 3.41 2.6
252-1 SB-1 I/C OF SB-1 TJM 10 0.757 800 1 0.4 0.95 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 0.076 75 1 0.85 1.01 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 0.757 500 1 0.7 1.51 4.5
252-26 TG-1 TIE TO SB-1 CDD 31 0.757 500 1 0.7 1.51 4.5
252-21 TG-1 I/C FROM TG CDG 31 0.606 600 1 0.85 1.01 6

Fault at PMCC-6 (433V)


452-20 PMCC-6 I/C FROM TR-6 CDG 31 8.736 600 1 0.15 14.56 0.15
252-20 SB-4 OG TO TR-6 TJM 10 0.344 25 1 0.1 13.75 0.29
252-9 SB-4 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-4 TJM 10 0.344 500 1 0.3 0.69 Infinity
252-1 SB-1 I/C OF SB-1 TJM 10 0.191 800 1 0.4 0.24 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 0.019 75 1 0.85 0.25 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 0.153 500 1 0.7 0.31 Infinity
252-26 TG-1 TIE TO SB-1 CDD 31 0.153 500 1 0.7 0.31 Infinity
252-21 TG-1 I/C FROM TG CDG 31 0.153 600 1 0.85 0.25 Infinity

Fault at PMCC-7 (433V)


452-19 PMCC-7 I/C FROM TR-7 CDG 31 28.205 2500 1 0.15 11.28 0.18
252-19 SB-4 OG TO TR-7 TJM 10 1.110 100 1 0.1 11.10 0.3
252-9 SB-4 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-4 TJM 10 1.110 500 1 0.3 2.22 2.6
252-1 SB-1 I/C FOR SB-1 TJM 10 0.617 800 1 0.4 0.77 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 0.062 75 1 0.85 0.82
252-3 SB-1 TIE TO TG-1 SG CDD 31 0.494 500 1 0.7 0.99 Infinity
252-26 TG-1 TIE TO SB-1 CDD 31 0.494 500 1 0.7 0.99 Infinity
252-21 TG-1 I/C FROM TG CDG 31 0.494 600 1 0.85 0.82 Infinity

10
Primary
Fault Current in Tripping Time
S.No SB No Description Relay Type Current in PS TMS I//Ipu
kA (Sec)
CT(A)
Fault at PMCC-8 (433V)
452-18 PMCC-8 I/C FROM TR-8 CDG 31 29.130 2500 1 0.15 11.65 0.18
252-18 SB-4 OG TO TR-7 TJM 10 1.147 100 1 0.1 11.47 0.3
252-9 SB-4 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-4 TJM 10 1.147 500 1 0.3 2.29 2.6
252-1 SB-1 I/C FOR SB-1 TJM 10 0.617 800 1 0.4 0.77 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 0.062 75 1 0.85 0.82 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 0.530 500 1 0.7 1.06 Infinity
252-26 TG-1 TIE TO SB-1 CDD 31 0.530 500 1 0.7 1.06 Infinity
252-21 TG-1 I/C FROM TG CDG 31 0.530 600 1 0.85 0.88 Infinity

Fault at PMCC-9 (433V)


452-17 PMCC-9 I/C FROM TR-9 CDG 31 28.431 2500 1 0.15 11.37 0.18
252-17 SB-4 OG TO TR-7 TJM 10 1.119 100 1 0.1 11.19 0.3
252-9 SB-4 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-4 TJM 10 1.119 500 1 0.3 2.24 2.6
252-1 SB-1 I/C FOR SB-1 TJM 10 0.621 800 1 0.4 0.78 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 0.062 75 1 0.85 0.83 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 0.498 500 1 0.7 1.00 Infinity
252-26 TG-1 TIE TO SB-1 CDD 31 0.498 500 1 0.7 1.00 Infinity
252-21 TG-1 I/C FROM TG CDG 31 0.498 600 1 0.85 0.83 Infinity

Fault at DCD 10 (433V)


452-16 DCD-10 I/C FROM TR-10 CDG 31 28.243 2500 1 0.15 11.30 0.18
252-16 SB-4 OG TO TR-10 TJM 10 1.112 100 1 0.1 11.12 0.3
252-9 SB-4 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-4 TJM 10 1.112 500 1 0.3 2.22 2.6
252-1 SB-1 I/C FOR SB-1 TJM 10 0.617 800 1 0.4 0.77 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 0.062 75 1 0.85 0.82 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 0.494 500 1 0.7 0.99 Infinity
252-26 TG-1 TIE TO SB-1 CDD 31 0.494 500 1 0.7 0.99 Infinity
252-21 TG-1 I/C FROM TG CDG 31 0.494 600 1 0.85 0.82 Infinity

11
Primary
Fault Current in Tripping Time
S.No SB No Description Relay Type Current in PS TMS I//Ipu
kA (Sec)
CT(A)
Fault at DCD 11 (433V)
452-15 DCD-11 I/C FROM TR-11 CDG 31 28.393 2500 1 0.15 11.36 0.18
252-15 SB-4 OG TO TR-11 TJM 10 1.118 100 1 0.1 11.18 0.3
252-9 SB-4 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-4 TJM 10 1.118 500 1 0.3 2.24 2.6
252-1 SB-1 I/C FOR SB-1 TJM 10 0.621 800 1 0.4 0.78 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 0.062 75 1 0.85 0.83 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 0.497 500 1 0.7 0.99 Infinity
252-26 TG-1 TIE TO SB-1 CDD 31 0.497 500 1 0.7 0.99 Infinity
252-21 TG-1 I/C FROM TG CDG 31 0.497 600 1 0.85 0.83 Infinity

12
3.1.3. Existing Relay Settings for Over Current
Primary
Fault Current Tripping
S.No SB No Description Relay Type Current in PS TMS I//Ipu
in kA Time (Sec)
CT(A)
Fault at SB-1 (11kV)
1 SB-1 OG TO SB-2 TJM 10 9.836 150 1 0.5 65.57 1.2
2 SB-1 I/C FOR SB-1 TJM 10 5.462 800 0.75 0.7 9.10 2.1
3 SB-1 I/C FROM 110kV Line ICM 21 0.546 75 0.75 0.8 9.71 2.4
4 SB-1 TIE TO TG-1 SG CDD 31 4.374 500 1.25 0.95 7.00 1.3
5 TG-1 TIE TO SB-1 CDD 31 4.374 500 1 0.65 8.75 0.84
6 TG-1 I/C FROM TG CDG 31 4.374 600 1 0.4 7.29 0.58

Fault at SB-2 (11kV)


1 SB-2 OG TO TR-1 NO RELAY
2 SB-2 I/C FROM SB-1 TJM 10 9.836 150 0.5 0.5 131.14 1
3 SB-1 OG TO SB-2 TJM 10 9.836 150 1 0.5 65.57 1.2
4 SB-1 I/C FOR SB-1 TJM 10 5.462 800 0.75 0.7 9.10 2.1
5 SB-1 I/C FROM 110kV Line ICM 21 0.546 75 0.75 0.8 9.71 2.4
6 SB-1 TIE TO TG-1 SG CDD 31 4.374 500 1.25 0.95 7.00 1.3
7 TG-1 TIE TO SB-1 CDD 31 4.374 500 1 0.65 8.75 0.84
8 TG-1 I/C FROM TG CDG 31 4.374 600 1 0.4 7.29 0.58

Fault at SB-3 (11kV)


1 SB-3 OG TO TR-2 TJM 10 9.836 100 0.5 0.4 196.71 0.75
2 SB-3 I/C FROM SB-1 NO RELAY
3 SB-1 OG TO SB-3 TJM 10 9.836 400 1 0.6 24.59 1.25
4 SB-1 I/C FOR SB-1 TJM 10 5.462 800 0.75 0.7 9.10 2.2
5 SB-1 I/C FROM 110kV Line ICM 21 0.546 75 0.75 0.8 9.71 2.4
6 SB-1 TIE TO TG-1 SG CDD 31 4.374 500 1.25 0.95 7.00 1.45
7 TG-1 TIE TO SB-1 CDD 31 4.374 500 1 0.65 8.75 0.82
8 TG-1 I/C FROM TG CDG 31 4.374 600 1 0.4 7.29 0.58

Fault at SB-4 (11kV)


1 SB-4 OG TO TR-11 TJM 10 9.836 100 0.75 0.5 131.14 1
2 SB-3 I/C FROM SB-1 NO RELAY
3 SB-1 OG TO SB-4 TJM 10 9.836 500 1 0.7 19.67 1.7
4 SB-1 I/C FOR SB-1 TJM 10 5.462 800 0.75 0.7 9.10 2.1
Primary
Fault Current Tripping
S.No SB No Description Relay Type Current in PS TMS I//Ipu
in kA Time (Sec)
CT(A)
5 SB-1 I/C FROM 110kV Line ICM 21 0.546 75 0.75 0.8 9.71 2.4
6 SB-1 TIE TO TG-1 SG CDD 31 4.374 500 1.25 0.95 7.00 1.45
7 TG-1 TIE TO SB-1 CDD 31 4.374 500 1 0.65 8.75 0.82
8 TG-1 I/C FROM TG CDG 31 4.374 600 1 0.4 7.29 0.58

Fault at TG-1 (11kV)


1 TG-1 OG TO AUX.TR-3 CDG 31 9.836 200 1 0.55 49.18 0.55
2 TG-1 I/C FROM TG CDG 31 4.374 600 1 0.4 9.10 2.3
3 SB-1 I/C FOR SB-1 TJM 10 5.462 800 0.75 0.7 9.10 2.1
4 SB-1 I/C FROM 110kV Line ICM 21 0.546 75 0.75 0.8 9.71 2.4
5 SB-1 TIE TO TG-1 SG CDD 31 5.462 500 1.25 0.95 8.74 1.3
6 TG-1 TIE TO SB-1 CDD 31 5.462 500 1 0.65 10.92 0.84

Fault at SB-5 (3kV)


1 SB-5 I/C FROM TR-2 TJM 10 3.478 200 1 0.3 17.39 0.75
1 SB-3 OG TO TR-2 TJM 10 0.948 100 0.5 0.4 18.97 0.85
2 SB-3 I/C FROM SB-1 NO RELAY
3 SB-1 OG TO SB-3 TJM 10 0.948 400 1 0.6 2.37 4.5
4 SB-1 I/C FOR SB-1 TJM 10 0.527 800 0.75 0.7 0.88 Infinity
5 SB-1 I/C FROM 110kV Line ICM 21 0.053 75 0.75 0.8 0.94 Infinity
6 SB-1 TIE TO TG-1 SG CDD 31 0.422 500 1.25 0.95 0.67 Infinity
7 TG-1 TIE TO SB-1 CDD 31 0.422 500 1 0.65 0.84 Infinity
8 TG-1 I/C FROM TG CDG 31 0.422 600 1 0.4 0.70 Infinity
Fault at TG-PMCC-2 (415V)
1 SB-4 I/C FROM AUX.TR-2 CDG 31 29.411 3000 1 0.15 9.80 1
2 SB-3 OG TO AUX.TR-2 CDG 31 1.110 200 1 0.5 5.55 0.79
3 SB-1 I/C FROM TG CDG 31 0.493 600 1 0.4 0.82 Infinity
4 SB-1 I/C FOR SB-1 TJM 10 0.616 800 0.75 0.7 1.03 20
5 SB-1 I/C FROM 110kV Line ICM 21 0.062 75 0.75 0.8 1.10 Infinity
6 SB-1 TIE TO TG-1 SG CDD 31 0.616 500 1.25 0.95 0.99 6
7 TG-1 TIE TO SB-1 CDD 31 0.616 500 1 0.65 1.23 4
Primary
Fault Current Tripping
S.No SB No Description Relay Type Current in PS TMS I//Ipu
in kA Time (Sec)
CT(A)
Fault at SB-6 (3.3kV)
1 SB-6 I/C FROM AUX.TR-3 CDG 31 5.583 500 1 0.15 11.17 0.18
2 SB-1 OG TO AUX.TR-3 CDG 31 5.583 200 1 0.55 27.92 1.8
3 SB-1 I/C FROM TG CDG 31 0.745 600 1 0.4 1.24 2.3
4 SB-1 I/C FOR SB-1 TJM 10 0.930 800 0.75 0.7 1.55 13
5 SB-1 I/C FROM 110kV Line ICM 21 0.310 75 0.75 0.8 5.51 3.2
6 SB-1 TIE TO TG-1 SG CDD 31 0.930 500 1.25 0.95 1.49 5
7 TG-1 TIE TO SB-1 CDD 31 0.930 500 1 0.65 1.86 2.5

Fault at PMCC-1 (433V)


1 PMCC1 I/C FROM SB2 CDG 31 39.997 4000 0.5 0.3 20.00 0.31
2 SB-2 I/C FROM SB-1 TJM 10 1.574 150 0.5 0.5 20.99 1
3 SB-1 OG TO SB-2 TJM 10 1.574 150 1 0.5 10.50 1.2
4 SB-1 I/C FOR SB-1 TJM 10 0.874 800 0.75 0.7 1.46 2.1
5 SB-1 I/C FROM 110kV Line ICM 21 0.087 75 0.75 0.8 1.55 2.4
6 SB-1 TIE TO TG-1 SG CDD 31 0.700 500 1.25 0.95 1.12 1.3
7 TG-1 TIE TO SB-1 CDD 31 0.700 500 1 0.65 1.40 0.84
8 TG-1 I/C FROM TG CDG 31 0.700 600 1 0.4 1.17 0.58

Fault at PMCC-3 (433V)


1 PMCC3 I/C FROM SB2 CDG 31 34.781 3000 1 0.4 11.59 0.48
2 SB-3 OG TO TR-3 TJM 10 1.369 125 1 0.5 10.95 1.5
3 SB-3 I/C FROM SB1 NO RELAY 1.369
4 SB-1 OG TO SB-3 TJM 10 1.369 400 1 0.5 3.42 2.7
5 SB-1 I/C OF SB-1 TJM 10 0.760 800 0.75 0.7 1.27 17
6 SB-1 I/C FROM 110kV Line ICM 21 0.076 75 0.75 0.8 1.35 12
7 SB-1 TIE TO TG-1 SG CDD 31 0.609 500 1.25 0.95 0.97 18
8 TG-1 TIE TO SB-1 CDD 31 0.609 500 1 0.65 1.22 8
9 TG-1 I/C FROM TG CDG 31 0.609 600 1 0.4 1.01 2.5

Fault at PMCC-4 (433V)


1 PMCC4 I/C FROM TR-4 CDG 31 34.963 3000 1 0.4 11.65 0.5
2 SB-3 OG TO TR-4 TJM 10 1.376 125 1 0.5 11.01 1.5
3 SB-3 I/C FROM SB-1 NO RELAY
Primary
Fault Current Tripping
S.No SB No Description Relay Type Current in PS TMS I//Ipu
in kA Time (Sec)
CT(A)
4 SB-1 OG TO SB-3 TJM 10 1.376 400 1 0.5 3.44 2.7
5 SB-1 I/C OF SB-1 TJM 10 0.764 800 0.75 0.7 1.27 17
6 SB-1 I/C FROM 110kV Line ICM 21 0.076 75 0.75 0.8 1.36 12
7 SB-1 TIE TO TG-1 SG CDD 31 0.764 500 1.25 0.95 1.22 18
8 TG-1 TIE TO SB-1 CDD 31 0.764 500 1 0.65 1.53 8
9 TG-1 I/C FROM TG CDG 31 0.612 600 1 0.4 1.02 2.5

Fault at PMCC-5 (433V)


1 PMCC-5 I/C FROM TR-5 CDG 31 34.645 3000 1 0.4 11.55 0.5
2 SB-3 OG TO TR-5 TJM 10 1.364 125 1 0.5 10.91 1.5
3 SB-3 I/C FROM SB-1 NO RELAY
4 SB-1 OG TO SB-3 TJM 10 1.364 400 1 0.5 3.41 2.7
5 SB-1 I/C OF SB-1 TJM 10 0.757 800 0.75 0.7 1.26 17
6 SB-1 I/C FROM 110kV Line ICM 21 0.076 75 0.75 0.8 1.35 12
7 SB-1 TIE TO TG-1 SG CDD 31 0.757 500 1.25 0.95 1.21 18
8 TG-1 TIE TO SB-1 CDD 31 0.757 500 1 0.65 1.51 8
9 TG-1 I/C FROM TG CDG 31 0.606 600 1 0.4 1.01 2.5

Fault at PMCC-6 (433V)


1 PMCC-6 I/C FROM TR-6 CDG 31 8.736 600 1 0.3 14.56 0.35
2 SB-4 OG TO TR-6 TJM 10 0.344 25 0.5 0.5 27.51 1.1
3 SB-4 I/C FROM SB-1 NO RELAY
4 SB-1 OG TO SB-4 TJM 10 0.344 500 1 0.7 0.69 Infinity
5 SB-1 I/C OF SB-1 TJM 10 0.191 800 0.75 0.7 0.32 Infinity
6 SB-1 I/C FROM 110kV Line ICM 21 0.019 75 0.75 0.8 0.34 Infinity
7 SB-1 TIE TO TG-1 SG CDD 31 0.153 500 1.25 0.95 0.24 Infinity
8 TG-1 TIE TO SB-1 CDD 31 0.153 500 1 0.65 0.31 Infinity
9 TG-1 I/C FROM TG CDG 31 0.153 600 1 0.4 0.25 Infinity

Fault at PMCC-7 (433V)


1 PMCC-7 I/C FROM TR-7 CDG 31 28.205 2500 1 0.4 11.28 0.51
2 SB-4 OG TO TR-7 TJM 10 1.110 100 1 0.5 11.10 1.5
3 SB-4 I/C FROM SB-1 NO RELAY
4 SB-1 OG TO SB-4 TJM 10 1.110 500 1 0.7 2.22 17
Primary
Fault Current Tripping
S.No SB No Description Relay Type Current in PS TMS I//Ipu
in kA Time (Sec)
CT(A)
5 SB-1 I/C FOR SB-1 TJM 10 0.617 800 0.75 0.7 1.03 Infinity
6 SB-1 I/C FROM 110kV Line ICM 21 0.062 75 0.75 0.8 1.10 Infinity
7 SB-1 TIE TO TG-1 SG CDD 31 0.494 500 1.25 0.95 0.79 12
8 TG-1 TIE TO SB-1 CDD 31 0.494 500 1 0.65 0.99 8
9 TG-1 I/C FROM TG CDG 31 0.494 600 1 0.4 0.82 3

Fault at PMCC-8 (433V)


1 PMCC-8 I/C FROM TR-8 CDG 31 29.130 2500 1 0.3 11.65 0.38
2 SB-4 OG TO TR-7 TJM 10 1.147 100 1 0.5 11.47 1.5
3 SB-4 I/C FROM SB-1 NO RELAY
4 SB-1 OG TO SB-4 TJM 10 1.147 500 1 0.7 2.29 17
5 SB-1 I/C FOR SB-1 TJM 10 0.637 800 0.75 0.7 1.06 Infinity
6 SB-1 I/C FROM 110kV Line ICM 21 0.064 75 0.75 0.8 1.13 Infinity
7 SB-1 TIE TO TG-1 SG CDD 31 0.510 500 1.25 0.95 0.82 1
8 TG-1 TIE TO SB-1 CDD 31 0.510 500 1 0.65 1.02 8
9 TG-1 I/C FROM TG CDG 31 0.510 600 1 0.4 0.85 3

Fault at PMCC-9 (433V)


1 PMCC-9 I/C FROM TR-9 CDG 31 28.431 2500 0.5 0.75 22.74 0.75
2 SB-4 OG TO TR-7 TJM 10 1.119 100 0.75 0.6 14.92 1.7
3 SB-4 I/C FROM SB-1 NO RELAY
4 SB-1 OG TO SB-4 TJM 10 1.119 500 1 0.7 2.24 17
5 SB-1 I/C FOR SB-1 TJM 10 0.621 800 0.75 0.7 1.04 Infinity
6 SB-1 I/C FROM 110kV Line ICM 21 0.062 75 0.75 0.8 1.10 Infinity
7 SB-1 TIE TO TG-1 SG CDD 31 0.498 500 1.25 0.95 0.80 Infinity
8 TG-1 TIE TO SB-1 CDD 31 0.498 500 1 0.65 1.00 8
9 TG-1 I/C FROM TG CDG 31 0.498 600 1 0.4 0.83 3

Fault at DCD 10 (433V)


1 DCD-10 I/C FROM TR-10 CDG 31 28.243 2500 0.75 0.3 15.06 0.35
2 SB-4 OG TO TR-10 TJM 10 1.112 100 0.75 0.5 14.82 1.4
3 SB-4 I/C FROM SB-1 NO RELAY
4 SB-1 OG TO SB-4 TJM 10 1.112 500 1 0.7 2.22 17
5 SB-1 I/C FOR SB-1 TJM 10 0.617 800 0.75 0.7 1.03 Infinity
Primary
Fault Current Tripping
S.No SB No Description Relay Type Current in PS TMS I//Ipu
in kA Time (Sec)
CT(A)
6 SB-1 I/C FROM 110kV Line ICM 21 0.062 75 0.75 0.8 1.10 Infinity
7 SB-1 TIE TO TG-1 SG CDD 31 0.494 500 1.25 0.95 0.79 Infinity
8 TG-1 TIE TO SB-1 CDD 31 0.494 500 1 0.65 0.99 8
9 TG-1 I/C FROM TG CDG 31 0.494 600 1 0.4 0.82 3

Fault at DCD 11 (433V)


1 DCD-11 I/C FROM TR-11 CDG 31 28.393 2500 0.75 0.2 15.14 0.23
2 SB-4 OG TO TR-11 TJM 10 1.118 100 0.75 0.5 14.90 1.4
3 SB-4 I/C FROM SB-1 NO RELAY
4 SB-1 OG TO SB-4 TJM 10 1.118 500 1 0.7 2.24 17
5 SB-1 I/C FOR SB-1 TJM 10 0.621 800 0.75 0.7 1.03 Infinity
6 SB-1 I/C FROM 110kV Line ICM 21 0.062 75 0.75 0.8 1.10 Infinity
7 SB-1 TIE TO TG-1 SG CDD 31 0.497 500 1.25 0.95 0.80 Infinity
8 TG-1 TIE TO SB-1 CDD 31 0.497 500 1 0.65 0.99 8
9 TG-1 I/C FROM TG CDG 31 0.497 600 1 0.4 0.83 3
3.2. Earth Fault Relay Settings
3.2.1 Recommended Earth Fault Relay Settings
Primary
Fault Current Tripping
S.No SB No Description Relay Type Current in PS TMS I//Ipu
in A Time (Sec)
CT(A)
Fault at SB-1 (11kV)
252-2 SB-1 OG TO SB-2 TJM 10 100 150 0.3 0.1 2.22 0.75
252-1 SB-1 I/C FOR SB-1 MIT 161 100 800 0.075 0.15 1.67 2.05
SB-1 GT T/F NUTRAL MIT 161 100 100 0.6 0.15 1.67 2.05
152-1 SB-1 I/C FROM 110kV Line ICM 21 100 75 0.75 0.2 1.78 2.30
252-3 SB-1 TIE TO TG-1 SG MIT 161 100 500 0.1 0.15 2.00 1.51
252-26 TG-1 TIE TO SB-1 MIT 161 100 500 0.1 0.15 2.00 1.51
252-21 TG-1 I/C FROM TG CDG 31 100 600 0.1 0.4 1.67 1.80

Fault at SB-2 (11kV)


252-8 SB-2 OG TO TR-1 NO RELAY
252-7 SB-2 I/C FROM SB-1 TJM 10 100 150 0.3 0.1 2.22 0.75
252-2 SB-1 OG TO SB-2 TJM 10 100 150 0.3 0.1 2.22 0.75
252-1 SB-1 I/C FOR SB-1 MIT 161 100 800 0.075 0.15 1.67 2.05
152-1 SB-1 I/C FROM 110kV Line ICM 21 100 75 0.75 0.2 1.78 2.30
252-3 SB-1 TIE TO TG-1 SG MIT 161 100 500 0.1 0.15 2.00 1.51
252-26 TG-1 TIE TO SB-1 MIT 161 100 500 0.1 0.15 2.00 1.51
252-21 TG-1 I/C FROM TG CDG 31 100 600 0.1 0.45 1.67 1.80

Fault at SB-3 (11kV)


252-10 SB-3 OG TO TR-2 TJM 10 100 100 0.5 0.1 2.00 0.90
252-9 SB-3 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-3 MIT 161 100 400 0.125 0.125 2.00 1.25
252-1 SB-1 I/C FOR SB-1 MIT 161 100 800 0.075 0.15 1.67 2.05
152-1 SB-1 I/C FROM 110kV Line ICM 21 100 75 0.75 0.2 1.78 2.30
252-3 SB-1 TIE TO TG-1 SG MIT 161 100 500 0.1 0.15 2.00 1.51
252-26 TG-1 TIE TO SB-1 MIT 161 100 500 0.1 0.15 2.00 1.51
Primary
Fault Current Tripping
S.No SB No Description Relay Type Current in PS TMS I//Ipu
in A Time (Sec)
CT(A)
252-21 TG-1 I/C FROM TG CDG 31 100 600 0.1 0.45 1.67 1.80
Fault at SB-4 (11kV)
252-15 SB-4 OG TO TR-11 TJM 10 100 200 0.25 0.1 2.00 0.90
252-14 SB-3 I/C FROM SB-1 NO RELAY
252-5 SB-1 OG TO SB-4 MIT 161 100 500 0.1 0.125 2.00 1.25
252-1 SB-1 I/C FOR SB-1 MIT 161 100 800 0.075 0.15 1.67 2.05
152-1 SB-1 I/C FROM 110kV Line ICM 21 100 75 0.75 0.2 1.78 2.30
252-3 SB-1 TIE TO TG-1 SG MIT 161 100 500 0.1 0.15 2.00 1.51
252-26 TG-1 TIE TO SB-1 MIT 161 100 500 0.1 0.15 2.00 1.51
252-21 TG-1 I/C FROM TG CDG 31 100 600 0.1 0.45 1.67 1.80

Fault at TG-1 (11kV)


252-25 TG-1 OG TO AUX.TR-3 CDG 31 100 200 0.25 0.3 2.00 0.92
252-21 TG-1 I/C FROM TG CDG 31 100 600 0.1 0.45 1.67 1.80
252-1 SB-1 I/C FOR SB-1 MIT 161 100 800 0.075 0.15 1.67 2.05
152-1 SB-1 I/C FROM 110kV Line ICM 21 100 75 0.75 0.2 1.78 2.30
252-3 SB-1 TIE TO TG-1 SG MIT 161 100 500 0.1 0.15 2.00 1.51
252-26 TG-1 TIE TO SB-1 MIT 161 100 500 0.1 0.15 2.00 1.51

Fault at SB-5 (3kV)


352-1 SB-5 I/C FROM TR-2 TJM 10 100 200 0.25 0.1 2.00 0.90
SB-5 TR-2 NUTRAL MIT 161 100 200 0.25 0.1 2.00 1.00
252-10 SB-3 OG TO TR-2 TJM 10 100 100 0.5 0.1 2.00 0.90
252-9 SB-3 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-3 MIT 161 100 400 0.125 0.125 2.00 1.25
252-1 SB-1 I/C FOR SB-1 MIT 161 100 800 0.075 0.15 1.67 2.05
152-1 SB-1 I/C FROM 110kV Line ICM 21 100 75 0.75 0.2 1.78 2.30
252-3 SB-1 TIE TO TG-1 SG MIT 161 100 500 0.1 0.15 2.00 1.51
252-26 TG-1 TIE TO SB-1 MIT 161 100 500 0.1 0.15 2.00 1.51
252-21 TG-1 I/C FROM TG CDG 31 100 600 0.1 0.45 1.67 1.80
Primary
Fault Current Tripping
S.No SB No Description Relay Type Current in PS TMS I//Ipu
in A Time (Sec)
CT(A)

Fault at TG PMCC-3(3.3kV)
352-2 SB-6 I/C FROM AUX.TR-3 CDG 31 100 500 0.1 0.1 2.00 0.26
SB-6 AUX.TR NUTRAL MIT 161 100 500 0.1 0.075 2.00 0.75
252-25 SB-1 OG TO AUX.TR-3 CDG 31 100 200 0.25 0.3 2.00 0.92
252-21 SB-1 I/C FROM TG CDG 31 100 600 0.1 0.45 1.67 1.80
252-1 SB-1 I/C FOR SB-1 MIT 161 100 800 0.075 0.15 1.67 2.05
152-1 SB-1 I/C FROM 110kV Line ICM 21 100 75 0.75 0.2 1.78 2.30
252-3 SB-1 TIE TO TG-1 SG MIT 161 100 500 0.1 0.15 2.00 1.51
252-26 TG-1 TIE TO SB-1 MIT 161 100 500 0.1 0.15 2.00 1.51

Fault at TG-PMCC-2 (433V)


452-2 PMCC-2 I/C FROM AUX.TR-2 CDG 31 551 3000 0.1 0.1 1.84 0.29
PMCC-2 AUX.TR NUTRAL MIT 161 551 3000 0.1 0.075 1.84 0.86
252-23 TG-1 OG TO AUX.TR-2 CDG 31 21.69 200 0.25 0.3 0.43 INFINITY
252-21 TG-1 I/C FROM TG CDG 31 21.69 600 0.1 0.45 0.36 INFINITY
252-1 SB-1 I/C FOR SB-1 MIT 161 21.69 800 0.075 0.15 0.36 INFINITY
152-1 SB-1 I/C FROM 110kV Line ICM 21 21.69 75 0.75 0.2 0.39 INFINITY
252-3 SB-1 TIE TO TG-1 SG MIT 161 21.69 500 0.1 0.15 0.43 INFINITY
252-26 TG-1 TIE TO SB-1 MIT 161 21.69 500 0.1 0.15 0.43 INFINITY
Fault at PMCC-1 (433V)
452-11 PMCC1 I/C FROM SB2 CDG 31 750 4000 0.1 0.1 1.88 0.29
PMCC1 TR-1 NUTRAL MIT 161 750 4000 0.1 0.075 1.88 0.83
252-8 SB-2 OG TO SB-2 NO RELAY
252-7 SB-2 I/C FROM SB-1 TJM 10 29.52 150 0.3 0.1 0.66 INFINITY
252-2 SB-1 OG TO SB-2 TJM 10 29.52 150 0.3 0.1 0.66 INFINITY
252-1 SB-1 I/C FOR SB-1 MIT 161 29.52 800 0.075 0.15 0.49 INFINITY
152-1 SB-1 I/C FROM 110kV Line ICM 21 29.52 75 0.75 0.2 0.52 INFINITY
252-3 SB-1 TIE TO TG-1 SG MIT 161 29.52 500 0.1 0.15 0.59 INFINITY
252-26 TG-1 TIE TO SB-1 MIT 161 29.52 500 0.1 0.15 0.59 INFINITY
Primary
Fault Current Tripping
S.No SB No Description Relay Type Current in PS TMS I//Ipu
in A Time (Sec)
CT(A)
252-21 TG-1 I/C FROM TG CDG 31 29.52 600 0.1 0.45 0.49 INFINITY
Fault at PMCC-3 (433V)
252-12 PMCC3 I/C FROM SB-3 CDG 31 652 3000 0.1 0.1 2.17 0.25
PMCC3 TR-3 NUTRAL MIT 161 652 3000 0.1 0.075 2.17 0.67
252-11 SB-3 OG TO TR-3 TJM 10 25.67 125 0.4 0.1 0.51 INFINITY
252-9 SB-3 I/C FROM SB1 NO RELAY 25.67
252-4 SB-1 OG TO SB-3 MIT 161 25.67 400 0.125 0.125 0.51 INFINITY
252-1 SB-1 I/C OF SB-1 MIT 161 25.67 800 0.075 0.15 0.43 INFINITY
152-1 SB-1 I/C FROM 110kV Line ICM 21 25.67 75 0.75 0.2 0.46 INFINITY
252-3 SB-1 TIE TO TG-1 SG MIT 161 25.67 500 0.1 0.15 0.51 INFINITY
252-26 TG-1 TIE TO SB-1 MIT 161 25.67 500 0.1 0.15 0.51 INFINITY
252-21 TG-1 I/C FROM TG CDG 31 25.67 600 0.1 0.45 0.43 INFINITY

Fault at PMCC-4 (433V)


452-13 PMCC4 I/C FROM TR-4 CDG 31 656 3000 0.1 0.1 2.19 0.24
PMCC4 TR-4 NUTRAL MIT 161 656 3000 0.1 0.075 2.19 0.67
252-12 SB-3 OG TO TR-4 TJM 10 25.80 125 0.4 0.1 0.52 INFINITY
252-9 SB-3 I/C FROM SB-1 NO RELAY 25.80
252-4 SB-1 OG TO SB-3 MIT 161 25.80 400 0.125 0.125 0.52 INFINITY
252-1 SB-1 I/C OF SB-1 MIT 161 25.80 800 0.075 0.15 0.43 INFINITY
152-1 SB-1 I/C FROM 110kV Line ICM 21 25.80 75 0.75 0.2 0.46 INFINITY
252-3 SB-1 TIE TO TG-1 SG MIT 161 25.80 500 0.1 0.15 0.52 INFINITY
252-26 TG-1 TIE TO SB-1 MIT 161 25.80 500 0.1 0.15 0.52 INFINITY
252-21 TG-1 I/C FROM TG CDG 31 25.80 600 0.1 0.45 0.43 INFINITY

Fault at PMCC-5 (433V)


452-14 PMCC-5 I/C FROM TR-5 CDG 31 650 3000 0.1 0.1 2.17 0.25
PMCC-5 TR-5 NUTRAL MIT 161 649.56 3000 0.1 0.075 2.17 0.68
252-13 SB-3 OG TO TR-5 TJM 10 25.57 125 0.4 0.1 0.51 INFINITY
252-9 SB-3 I/C FROM SB-1 NO RELAY 25.57
Primary
Fault Current Tripping
S.No SB No Description Relay Type Current in PS TMS I//Ipu
in A Time (Sec)
CT(A)
252-4 SB-1 OG TO SB-3 MIT 161 25.57 400 0.125 0.125 0.51 INFINITY
252-1 SB-1 I/C OF SB-1 MIT 161 25.57 800 0.075 0.15 0.43 INFINITY
152-1 SB-1 I/C FROM 110kV Line ICM 21 25.57 75 0.75 0.2 0.45 INFINITY
252-3 SB-1 TIE TO TG-1 SG MIT 161 25.57 500 0.1 0.15 0.51 INFINITY
252-26 TG-1 TIE TO SB-1 MIT 161 25.57 500 0.1 0.15 0.51 INFINITY
252-21 TG-1 I/C FROM TG CDG 31 25.57 600 0.1 0.45 0.43 INFINITY

Fault at PMCC-6 (433V)


452-20 PMCC-6 I/C FROM TR-6 CDG 31 164 600 0.1 0.1 2.73 0.20
PMCC-6 TR-6 NUTRAL MIT 161 164 600 0.1 0.075 2.73 0.52
252-20 SB-4 OG TO TR-6 TJM 10 6.45 25 2 0.1 0.13 INFINITY
252-9 SB-4 I/C FROM SB-1 NO RELAY 6.45
252-4 SB-1 OG TO SB-4 MIT 161 6.45 500 0.1 0.125 0.13 INFINITY
252-1 SB-1 I/C OF SB-1 MIT 161 6.45 800 0.075 0.15 0.11 INFINITY
152-1 SB-1 I/C FROM 110kV Line ICM 21 6.45 75 0.75 0.2 0.11 INFINITY
252-3 SB-1 TIE TO TG-1 SG MIT 161 6.45 500 0.1 0.15 0.13 INFINITY
252-26 TG-1 TIE TO SB-1 MIT 161 6.45 500 0.1 0.15 0.13 INFINITY
252-21 TG-1 I/C FROM TG CDG 31 6.45 600 0.1 0.45 0.11 INFINITY

Fault at PMCC-7 (433V)


452-19 PMCC-7 I/C FROM TR-7 CDG 31 529 2500 0.1 0.1 2.12 0.26
PMCC-7 TR-7 NUTRAL MIT 161 529 2500 0.1 0.075 2.12 0.70
252-19 SB-4 OG TO TR-7 TJM 10 20.82 100 0.5 0.1 0.42 INFINITY
252-9 SB-4 I/C FROM SB-1 NO RELAY 20.82
252-4 SB-1 OG TO SB-4 MIT 161 20.82 500 0.1 0.125 0.42 INFINITY
252-1 SB-1 I/C FOR SB-1 MIT 161 20.82 800 0.075 0.15 0.35 INFINITY
152-1 SB-1 I/C FROM 110kV Line ICM 21 20.82 75 0.75 0.2 0.37 INFINITY
252-3 SB-1 TIE TO TG-1 SG MIT 161 20.82 500 0.1 0.15 0.42 INFINITY
252-26 TG-1 TIE TO SB-1 MIT 161 20.82 500 0.1 0.15 0.42 INFINITY
252-21 TG-1 I/C FROM TG CDG 31 20.82 600 0.1 0.45 0.35 INFINITY
Primary
Fault Current Tripping
S.No SB No Description Relay Type Current in PS TMS I//Ipu
in A Time (Sec)
CT(A)

Fault at PMCC-8 (433V)


452-18 PMCC-8 I/C FROM TR-8 CDG 31 546 2500 0.1 0.1 2.18 0.25
PMCC-8 TR-8 NUTRAL MIT 161 546 2500 0.1 0.075 2.18 0.67
252-18 SB-4 OG TO TR-8 TJM 10 21.50 100 0.5 0.1 0.43 INFINITY
252-9 SB-4 I/C FROM SB-1 NO RELAY 21.50
252-4 SB-1 OG TO SB-4 MIT 161 21.50 500 0.1 0.125 0.43 INFINITY
252-1 SB-1 I/C FOR SB-1 MIT 161 21.50 800 0.075 0.15 0.36 INFINITY
152-1 SB-1 I/C FROM 110kV Line ICM 21 21.50 75 0.75 0.2 0.38 INFINITY
252-3 SB-1 TIE TO TG-1 SG MIT 161 21.50 500 0.1 0.15 0.43 INFINITY
252-26 TG-1 TIE TO SB-1 MIT 161 21.50 500 0.1 0.15 0.43 INFINITY
252-21 TG-1 I/C FROM TG CDG 31 21.50 600 0.1 0.45 0.36 INFINITY

Fault at PMCC-9 (433V)


452-17 PMCC-9 I/C FROM TR-9 CDG 31 533 2500 0.1 0.1 2.13 0.26
PMCC-9 TR-9 NUTRAL MIT 161 533 2500 0.1 0.075 2.13 0.69
252-17 SB-4 OG TO TR-9 TJM 10 20.98 100 0.5 0.1 0.42 INFINITY
252-9 SB-4 I/C FROM SB-1 NO RELAY 20.98
252-4 SB-1 OG TO SB-4 MIT 161 20.98 500 0.1 0.125 0.42 INFINITY
252-1 SB-1 I/C FOR SB-1 MIT 161 20.98 800 0.075 0.15 0.35 INFINITY
152-1 SB-1 I/C FROM 110kV Line ICM 21 20.98 75 0.75 0.2 0.37 INFINITY
252-3 SB-1 TIE TO TG-1 SG MIT 161 20.98 500 0.1 0.15 0.42 INFINITY
252-26 TG-1 TIE TO SB-1 MIT 161 20.98 500 0.1 0.15 0.42 INFINITY
252-21 TG-1 I/C FROM TG CDG 31 20.98 600 0.1 0.45 0.35 INFINITY

Fault at DCD 10 (433V)


452-16 DCD-10 I/C FROM TR-10 CDG 31 530 2500 0.1 0.1 2.12 0.26
DCD-10 TR-10 NUTRAL MIT 161 530 2500 0.1 0.075 2.12 0.70
252-16 SB-4 OG TO TR-10 TJM 10 20.84 100 0.5 0.1 0.42 INFINITY
252-9 SB-4 I/C FROM SB-1 NO RELAY 20.84
Primary
Fault Current Tripping
S.No SB No Description Relay Type Current in PS TMS I//Ipu
in A Time (Sec)
CT(A)
252-4 SB-1 OG TO SB-4 MIT 161 20.84 500 0.1 0.125 0.42 INFINITY
252-1 SB-1 I/C FOR SB-1 MIT 161 20.84 800 0.075 0.15 0.35 INFINITY
152-1 SB-1 I/C FROM 110kV Line ICM 21 20.84 75 0.75 0.2 0.37 INFINITY
252-3 SB-1 TIE TO TG-1 SG MIT 161 20.84 500 0.1 0.15 0.42 INFINITY
252-26 TG-1 TIE TO SB-1 MIT 161 20.84 500 0.1 0.15 0.42 INFINITY
252-21 TG-1 I/C FROM TG CDG 31 20.84 600 0.1 0.45 0.35 INFINITY

Fault at DCD 11 (433V)


452-15 DCD-11 I/C FROM TR-11 CDG 31 532 2500 0.1 0.1 2.13 0.26
DCD-11 TR-11 NUTRAL MIT 161 532 2500 0.1 0.075 2.13 0.69
252-15 SB-4 OG TO TR-11 TJM 10 20.94 100 0.5 0.1 0.42 INFINITY
252-9 SB-4 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-4 MIT 161 20.94 500 0.1 0.125 0.42 INFINITY
252-1 SB-1 I/C FOR SB-1 MIT 161 20.94 800 0.075 0.15 0.35 INFINITY
152-1 SB-1 I/C FROM 110kV Line ICM 21 20.94 75 0.75 0.2 0.37 INFINITY
252-3 SB-1 TIE TO TG-1 SG MIT 161 20.94 500 0.1 0.15 0.42 INFINITY
252-26 TG-1 TIE TO SB-1 MIT 161 20.94 500 0.1 0.15 0.42 INFINITY
252-21 TG-1 I/C FROM TG CDG 31 20.94 600 0.1 0.45 0.35 INFINITY

Recommended relays and settings


3.2.2. Existing Earth Fault Relay Settings
Primary
Fault Current Tripping
S.No SB No Description Relay Type Current in PS TMS I//Ipu
in A Time (Sec)
CT(A)
Fault at SB-1 (11kV)
252-2 SB-1 OG TO SB-2 TJM 10 100 150 0.1 0.2 6.67 0.75
252-1 SB-1 I/C FOR SB-1 TJM 10 100 800 0.2 0.2 0.63 7
152-1 SB-1 I/C FROM 110kV Line ICM 21 100 75 0.1 0.1 13.33 0.23
252-3 SB-1 TIE TO TG-1 SG MIT 161 100 500 0.005 0.7 40.00 1.28
252-26 TG-1 TIE TO SB-1 MIT 161 100 500 0.005 0.25 40.00 0.458
252-21 TG-1 I/C FROM TG CDG 31 100 600 0.1 0.3 1.67 1.1

Fault at SB-2 (11kV)


252-8 SB-2 OG TO TR-1 NO RELAY 100
252-7 SB-2 I/C FROM SB-1 TJM 10 100 150 0.1 0.5 6.67 1.7
252-2 SB-1 OG TO SB-2 TJM 10 100 150 0.1 0.2 6.67 0.75
252-1 SB-1 I/C FOR SB-1 TJM 10 100 800 0.2 0.2 0.63 7
152-1 SB-1 I/C FROM 110kV Line ICM 21 100 75 0.1 0.1 13.33 0.23
252-3 SB-1 TIE TO TG-1 SG MIT 161 100 500 0.005 0.7 40.00 1.28
252-26 TG-1 TIE TO SB-1 MIT 161 100 500 0.005 0.25 40.00 0.458
252-21 TG-1 I/C FROM TG CDG 31 100 600 0.1 0.3 1.67 1.1

Fault at SB-3 (11kV)


252-10 SB-3 OG TO TR-2 TJM 10 100 100 0.1 0.1 10.00 0.31
252-9 SB-3 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-3 TJM 10 100 400 0.1 0.15 2.50 1
252-1 SB-1 I/C FOR SB-1 TJM 10 100 800 0.2 0.2 0.63 7
152-1 SB-1 I/C FROM 110kV Line ICM 21 100 75 0.1 0.1 13.33 0.27
252-3 SB-1 TIE TO TG-1 SG MIT 161 100 500 0.005 0.7 40.00 1.28
252-26 TG-1 TIE TO SB-1 MIT 161 100 500 0.005 0.25 40.00 0.458
252-21 TG-1 I/C FROM TG CDG 31 100 200 0.1 0.3 5.00 0.5

Fault at SB-4 (11kV)


252-15 SB-4 OG TO TR-11 TJM 10 100 100 0.2 0.5 5.00 0.43
252-14 SB-3 I/C FROM SB-1 NO RELAY
252-5 SB-1 OG TO SB-4 TJM 10 100 500 0.2 0.8 1.00 20
252-1 SB-1 I/C FOR SB-1 TJM 10 100 800 0.2 0.2 0.63 7
Primary
Fault Current Tripping
S.No SB No Description Relay Type Current in PS TMS I//Ipu
in A Time (Sec)
CT(A)
152-1 SB-1 I/C FROM 110kV Line ICM 21 100 75 0.1 0.1 13.33 0.27
252-3 SB-1 TIE TO TG-1 SG MIT 161 100 500 0.005 0.7 40.00 1.28
252-26 TG-1 TIE TO SB-1 MIT 161 100 500 0.005 0.25 40.00 0.458
252-21 TG-1 I/C FROM TG CDG 31 100 200 0.1 0.3 5.00 0.5

Fault at TG-1 (11kV)


252-25 TG-1 OG TO AUX.TR-3 CDG 31 100 200 0.1 0.1 5.00 0.43
252-21 TG-1 I/C FROM TG CDG 31 100 600 0.1 0.3 1.67 1.1
252-1 SB-1 I/C FOR SB-1 TJM 10 100 800 0.2 0.2 0.63 7
152-1 SB-1 I/C FROM 110kV Line ICM 21 100 75 0.1 0.1 13.33 0.27
252-3 SB-1 TIE TO TG-1 SG MIT 161 100 500 0.005 0.7 40.00 1.28
252-26 TG-1 TIE TO SB-1 MIT 161 100 500 0.005 0.25 40.00 0.458

Fault at SB-5 (3kV)


352-1 SB-5 I/C FROM TR-2 TJM 10 100 200 0.1 0.1 5.00 0.43
252-10 SB-3 OG TO TR-2 TJM 10 100 100 0.1 0.1 10.00 0.31
252-9 SB-3 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-3 TJM 10 100 400 0.1 0.15 2.50 1
252-1 SB-1 I/C FOR SB-1 TJM 10 100 800 0.2 0.2 0.63 7
152-1 SB-1 I/C FROM 110kV Line ICM 21 100 75 0.1 0.1 13.33 0.27
252-3 SB-1 TIE TO TG-1 SG MIT 161 100 500 0.005 0.7 40.00 1.28
252-26 TG-1 TIE TO SB-1 MIT 161 100 500 0.005 0.25 40.00 0.458
252-21 TG-1 I/C FROM TG CDG 31 100 600 0.1 0.3 1.67 1.1

Fault at TG -PMCC-3 (3.3kV)


352-2 SB-6 I/C FROM AUX.TR-3 CDG 31 100 500 0.1 0.1 2.00 0.26
252-25 SB-1 OG TO AUX.TR-3 CDG 31 100 200 0.1 0.1 5.00 0.16
252-21 SB-1 I/C FROM TG CDG 31 100 600 0.1 0.3 1.67 1.1
252-1 SB-1 I/C FOR SB-1 TJM 10 100 800 0.2 0.2 0.63 7
152-1 SB-1 I/C FROM 110kV Line ICM 21 100 75 0.1 0.1 13.33 0.27
252-3 SB-1 TIE TO TG-1 SG MIT 161 100 500 0.005 0.7 40.00 1.28
252-26 TG-1 TIE TO SB-1 MIT 161 100 500 0.005 0.25 40.00 0.458
Primary
Fault Current Tripping
S.No SB No Description Relay Type Current in PS TMS I//Ipu
in A Time (Sec)
CT(A)

Fault at TG-PMCC-2 (433V)


452-1 SB-4 I/C FROM AUX.TR-2 CDG 31 551 3000 0.1 0.1 1.84 0.28
252-23 SB-3 OG TO AUX.TR-2 CDG 31 21.69 200 0.1 0.1 1.08 Infinity
252-21 SB-1 I/C FROM TG CDG 31 21.69 600 0.1 0.3 0.36 Infinity
252-1 SB-1 I/C FOR SB-1 TJM 10 21.69 800 0.2 0.2 0.14 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 21.69 75 0.1 0.1 2.89 0.55
252-3 SB-1 TIE TO TG-1 SG MIT 161 21.69 500 0.005 0.7 8.68 2.22
252-26 TG-1 TIE TO SB-1 MIT 161 21.69 500 0.005 0.25 8.68 0.793

Fault at PMCC-1 (433V)


452-11 PMCC1 I/C FROM SB2 CDG 31 750 4000 0.1 0.1 1.88 0.3
252-7 SB-2 I/C FROM SB-1 TJM 10 29.52 150 0.1 0.5 1.97 1.7
252-2 SB-1 OG TO SB-2 TJM 10 29.52 150 0.1 0.2 1.97 1.7
252-1 SB-1 I/C FOR SB-1 TJM 10 29.52 800 0.2 0.2 0.18 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 29.52 75 0.1 0.1 3.94 0.45
252-3 SB-1 TIE TO TG-1 SG MIT 161 29.52 500 0.005 0.7 11.81 1.937
252-26 TG-1 TIE TO SB-1 MIT 161 29.52 500 0.005 0.25 11.81 0.692
252-21 TG-1 I/C FROM TG CDG 31 29.52 600 0.1 0.3 0.49 Infinity

Fault at PMCC-3 (433V)


452-12 PMCC3 I/C FROM SB-3 CDG 31 652 3000 0.1 0.2 2.17 0.55
252-11 SB-3 OG TO TR-3 TJM 10 25.67 125 0.1 0.2 2.05 1.7
252-9 SB-3 I/C FROM SB1 NO RELAY
252-4 SB-1 OG TO SB-3 TJM 10 25.67 400 0.1 0.15 0.64 Infinity
252-1 SB-1 I/C OF SB-1 TJM 10 25.67 800 0.2 0.2 0.16 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 25.67 75 0.1 0.1 3.42 0.5
252-3 SB-1 TIE TO TG-1 SG MIT 161 25.67 500 0.005 0.7 10.27 2.056
252-26 TG-1 TIE TO SB-1 MIT 161 25.67 500 0.005 0.25 10.27 0.735
252-21 TG-1 I/C FROM TG CDG 31 25.67 600 0.1 0.3 0.43 Infinity

Fault at PMCC-4 (433V)


452-13 PMCC4 I/C FROM TR-4 CDG 31 656 3000 0.1 0.1 2.19 0.27
252-12 SB-3 OG TO TR-4 TJM 10 25.80 125 0.1 0.2 2.06 1.7
Primary
Fault Current Tripping
S.No SB No Description Relay Type Current in PS TMS I//Ipu
in A Time (Sec)
CT(A)
252-9 SB-3 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-3 TJM 10 25.80 400 0.1 0.15 0.65 Infinity
252-1 SB-1 I/C OF SB-1 TJM 10 25.80 800 0.2 0.2 0.16 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 25.80 75 0.1 0.1 3.44 0.5
252-3 SB-1 TIE TO TG-1 SG MIT 161 25.80 500 0.005 0.7 10.32 2.051
252-26 TG-1 TIE TO SB-1 MIT 161 25.80 500 0.005 0.25 10.32 0.733
252-21 TG-1 I/C FROM TG CDG 31 25.80 600 0.1 0.3 0.43 Infinity

Fault at PMCC-5 (433V)


452-14 PMCC-5 I/C FROM TR-5 CDG 31 650 3000 0.1 0.15 2.17 0.4
252-13 SB-3 OG TO TR-5 TJM 10 25.57 125 0.1 0.2 2.05 1.7
252-9 SB-3 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-3 TJM 10 25.57 400 0.1 0.15 0.64 Infinity
252-1 SB-1 I/C OF SB-1 TJM 10 25.57 800 0.2 0.2 0.16 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 25.57 75 0.1 0.1 3.41 0.5
252-3 SB-1 TIE TO TG-1 SG MIT 161 25.57 500 0.005 0.7 10.23 2.059
252-26 TG-1 TIE TO SB-1 MIT 161 25.57 500 0.005 0.25 10.23 0.736
252-21 TG-1 I/C FROM TG CDG 31 25.57 600 0.1 0.3 0.43 Infinity

Fault at PMCC-6 (433V)


452-20 PMCC-6 I/C FROM TR-6 NO RELAY 164 - - -
252-20 SB-4 OG TO TR-6 TJM 10 6.45 25 0.1 0.1 2.58 0.7
252-9 SB-4 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-4 TJM 10 6.45 500 0.2 0.8 0.06 Infinity
252-1 SB-1 I/C OF SB-1 TJM 10 6.45 800 0.2 0.2 0.04 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 6.45 75 0.1 0.1 0.86 Infinity
252-3 SB-1 TIE TO TG-1 SG MIT 161 6.45 500 0.005 0.7 2.58 5.124
252-26 TG-1 TIE TO SB-1 MIT 161 6.45 500 0.005 0.25 2.58 1.83
252-21 TG-1 I/C FROM TG CDG 31 6.45 600 0.1 0.3 0.11 Infinity

Fault at PMCC-7 (433V)


452-19 PMCC-7 I/C FROM TR-7 CDG 31 529 2500 0.1 0.1 2.12 0.26
252-19 SB-4 OG TO TR-7 TJM 10 20.82 100 0.1 0.2 2.08 1.7
252-9 SB-4 I/C FROM SB-1 NO RELAY
Primary
Fault Current Tripping
S.No SB No Description Relay Type Current in PS TMS I//Ipu
in A Time (Sec)
CT(A)
252-4 SB-1 OG TO SB-4 TJM 10 20.82 500 0.2 0.8 0.21 Infinity
252-1 SB-1 I/C FOR SB-1 TJM 10 20.82 800 0.2 0.2 0.13 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 20.82 75 0.1 0.1 2.78 0.52
252-3 SB-1 TIE TO TG-1 SG MIT 161 20.82 500 0.005 0.7 8.33 2.264
252-26 TG-1 TIE TO SB-1 MIT 161 20.82 500 0.005 0.25 8.33 0.809
252-21 TG-1 I/C FROM TG CDG 31 20.82 600 0.1 0.3 0.35 Infinity

Fault at PMCC-8 (433V)


452-18 PMCC-8 I/C FROM TR-8 CDG 31 546 2500 0.1 0.1 2.18 0.26
252-18 SB-4 OG TO TR-7 TJM 10 21.50 100 0.1 0.2 2.15 1.68
252-9 SB-4 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-4 TJM 10 21.50 500 0.2 0.8 0.21 Infinity
252-1 SB-1 I/C FOR SB-1 TJM 10 21.50 800 0.2 0.2 0.13 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 21.50 75 0.1 0.1 2.87 0.45
252-3 SB-1 TIE TO TG-1 SG MIT 161 21.50 500 0.005 0.7 8.60 2.229
252-26 TG-1 TIE TO SB-1 MIT 161 21.50 500 0.005 0.25 8.60 0.796
252-21 TG-1 I/C FROM TG CDG 31 21.50 600 0.1 0.3 0.36 Infinity

Fault at PMCC-9 (433V)


452-17 PMCC-9 I/C FROM TR-9 CDG 31 533 2500 0.1 0.1 2.13 0.26
252-17 SB-4 OG TO TR-7 TJM 10 20.98 100 0.1 0.2 2.10 1.7
252-9 SB-4 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-4 TJM 10 20.98 500 0.2 0.8 0.21 Infinity
252-1 SB-1 I/C FOR SB-1 TJM 10 20.98 800 0.2 0.2 0.13 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 20.98 75 0.1 0.1 2.80 0.45
252-3 SB-1 TIE TO TG-1 SG MIT 161 20.98 500 0.005 0.7 8.39 2.255
252-26 TG-1 TIE TO SB-1 MIT 161 20.98 500 0.005 0.25 8.39 0.806
252-21 TG-1 I/C FROM TG CDG 31 20.98 600 0.1 0.3 0.35 Infinity
Fault at DCD 10 (433V)
452-16 DCD-10 I/C FROM TR-10 CDG 31 530 2500 0.4 0.5 0.53 Infinity
252-16 SB-4 OG TO TR-10 TJM 10 20.84 100 0.2 0.2 1.04 Infinity
252-9 SB-4 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-4 TJM 10 20.84 500 0.2 0.8 0.21 Infinity
252-1 SB-1 I/C FOR SB-1 TJM 10 20.84 800 0.2 0.2 0.13 Infinity
Primary
Fault Current Tripping
S.No SB No Description Relay Type Current in PS TMS I//Ipu
in A Time (Sec)
CT(A)
152-1 SB-1 I/C FROM 110kV Line ICM 21 20.84 75 0.1 0.1 2.78 0.45
252-3 SB-1 TIE TO TG-1 SG MIT 161 20.84 500 0.005 0.7 8.34 2.262
252-26 TG-1 TIE TO SB-1 MIT 161 20.84 500 0.005 0.25 8.34 0.808
252-21 TG-1 I/C FROM TG CDG 31 20.84 600 0.1 0.3 0.35 Infinity
Fault at DCD 11 (433V)
452-15 DCD-11 I/C FROM TR-11 CDG 31 532 2500 0.4 0.5 0.53 Infinity
252-15 SB-4 OG TO TR-11 TJM 10 20.95 100 0.2 0.5 1.05 Infinity
252-9 SB-4 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-4 TJM 10 20.95 500 0.2 0.8 0.21 Infinity
252-1 SB-1 I/C FOR SB-1 TJM 10 20.94 800 0.2 0.2 0.13 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 20.94 75 0.1 0.1 2.79 0.45
252-3 SB-1 TIE TO TG-1 SG MIT 161 20.94 500 0.005 0.7 8.38 2.257
252-26 TG-1 TIE TO SB-1 MIT 161 20.94 500 0.005 0.25 8.38 0.806
252-21 TG-1 I/C FROM TG CDG 31 20.94 600 0.1 0.3 0.35 Infinity
4. COMPARISON OF EXISTING
&RECOMMENDED SETTINGS
4.1. Comparison of Existing & Recommended Settings - Over Current
Primary
Tripping Tripping Time
S.No SB No Description Relay Type Current in PS TMS PS TMS
Time (Sec) (Sec)
CT(A)
Existing Service Settings ELSYTEC's Recommended Settings
Fault at SB-1 (11kV)
252-2 SB-1 OG TO SB-2 TJM 10 150 1 0.5 1.2 1 0.3 0.67
252-1 SB-1 I/C FOR SB-1 TJM 10 800 0.75 0.7 2.1 1 0.4 1.5
152-1 SB-1 I/C FROM 110kV Line ICM 21 75 0.75 0.8 2.4 1 0.85 2.4
252-3 SB-1 TIE TO TG-1 SG CDD 31 500 1.25 0.95 1.3 1 0.7 0.96
252-26 TG-1 TIE TO SB-1 CDD 31 500 1 0.65 0.84 1 0.7 0.96
252-21 TG-1 I/C FROM TG CDG 31 600 1 0.4 0.58 1 0.85 1.25

Fault at SB-2 (11kV)


252-8 SB-2 OG TO TR-1 NO RELAY
252-7 SB-2 I/C FROM SB-1 TJM 10 150 0.5 0.5 1 1 0.3 0.67
252-2 SB-1 OG TO SB-2 TJM 10 150 1 0.5 1.2 1 0.3 0.67
252-1 SB-1 I/C FOR SB-1 TJM 10 800 0.75 0.7 2.1 1 0.4 1.5
152-1 SB-1 I/C FROM 110kV Line ICM 21 75 0.75 0.8 2.4 1 0.85 2.4
252-3 SB-1 TIE TO TG-1 SG CDD 31 500 1.25 0.95 1.3 1 0.7 0.96
252-26 TG-1 TIE TO SB-1 CDD 31 500 1 0.65 0.84 1 0.7 0.96
252-21 TG-1 I/C FROM TG CDG 31 600 1 0.4 0.58 1 0.85 1.2

Fault at SB-3 (11kV)


252-10 SB-3 OG TO TR-2 TJM 10 100 0.5 0.4 0.75 0.75 0.1 0.23
252-9 SB-3 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-3 TJM 10 400 1 0.6 1.25 1 0.3 0.67
252-1 SB-1 I/C FOR SB-1 TJM 10 800 0.75 0.7 2.2 1 0.4 1.5
152-1 SB-1 I/C FROM 110kV Line ICM 21 75 0.75 0.8 2.4 1 0.85 2.4
252-3 SB-1 TIE TO TG-1 SG CDD 31 500 1.25 0.95 1.45 1 0.7 0.96
252-26 TG-1 TIE TO SB-1 CDD 31 500 1 0.65 0.82 1 0.7 0.96
252-21 TG-1 I/C FROM TG CDG 31 600 1 0.4 0.58 1 0.85 1.2

Fault at SB-4 (11kV)


252-15 SB-4 OG TO TR-11 TJM 10 100 0.75 0.5 1 1 0.1 0.23
252-14 SB-3 I/C FROM SB-1 NO RELAY
252-5 SB-1 OG TO SB-4 TJM 10 500 1 0.7 1.7 1 0.3 0.7
252-1 SB-1 I/C FOR SB-1 TJM 10 800 0.75 0.7 2.1 1 0.4 1.5
152-1 SB-1 I/C FROM 110kV Line ICM 21 75 0.75 0.8 2.4 1 0.85 2.4
252-3 SB-1 TIE TO TG-1 SG CDD 31 500 1.25 0.95 1.45 1 0.7 0.98
Primary
Tripping Tripping Time
S.No SB No Description Relay Type Current in PS TMS PS TMS
Time (Sec) (Sec)
CT(A)
Existing Service Settings ELSYTEC's Recommended Settings
252-26 TG-1 TIE TO SB-1 CDD 31 500 1 0.65 0.82 1 0.7 0.98
252-21 TG-1 I/C FROM TG CDG 31 600 1 0.4 0.58 1 0.85 1.3

Fault at TG-1 (11kV)


252-25 TG-1 OG TO AUX.TR-3 CDG 31 200 1 0.55 0.55 1 0.3 0.31
252-21 TG-1 I/C FROM TG CDG 31 600 1 0.4 2.3 1 0.85 1.15
252-1 SB-1 I/C FOR SB-1 TJM 10 800 0.75 0.7 2.1 1 0.4 1.5
152-1 SB-1 I/C FROM 110kV Line ICM 21 75 0.75 0.8 2.4 1 0.85 2.4
252-3 SB-1 TIE TO TG-1 SG CDD 31 500 1.25 0.95 1.3 1 0.7 0.88
252-26 TG-1 TIE TO SB-1 CDD 31 500 1 0.65 0.84 1 0.7 0.88

Fault at SB-5 (3kV)


352-1 SB-5 I/C FROM TR-2 TJM 10 200 1 0.3 0.75 1 0.1 0.26
252-10 SB-3 OG TO TR-2 TJM 10 100 0.5 0.4 0.85 0.75 0.1 0.39
252-9 SB-3 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-3 TJM 10 400 1 0.6 4.5 1 0.3 2.4
252-1 SB-1 I/C FOR SB-1 TJM 10 800 0.75 0.7 Infinity 1 0.4 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 75 0.75 0.8 Infinity 1 0.85 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 500 1.25 0.95 Infinity 1 0.7 Infinity
252-26 TG-1 TIE TO SB-1 CDD 31 500 1 0.65 Infinity 1 0.7 Infinity
252-21 TG-1 I/C FROM TG CDG 31 600 1 0.4 Infinity 1 0.85 Infinity

Fault at SB-6 (3.3kV)


352-2 SB-6 I/C FROM AUX.TR-3 CDG 31 500 1 0.15 1 1 0.1 0.13
252-25 TG-1 OG TO AUX.TR-3 CDG 31 200 1 0.5 0.79 1 0.3 0.42
252-21 TG-1 I/C FROM TG CDG 31 600 1 0.4 Infinity 1 0.85 6
252-1 SB-1 I/C FOR SB-1 TJM 10 800 0.75 0.7 20 1 0.4 infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 75 0.75 0.8 Infinity 1 0.85 infinity
252-3 TG-1 TIE TO TG-1 SG CDD 31 500 1.25 0.95 6 1 0.7 4
252-26 TG-1 TIE TO SB-1 CDD 31 500 1 0.65 4 1 0.7 4

Fault at TG-PMCC-2 (4+A114V)


452-2 SB-4 I/C FROM AUX.TR-2 CDG 31 3000 1 0.15 0.18 1 0.1 0.13
252-23 SB-3 OG TO AUX.TR-2 CDG 31 200 1 0.55 1.8 1 0.3 0.48
252-21 SB-1 I/C FROM TG CDG 31 600 1 0.4 2.3 1 0.85 Infinity
252-1 SB-1 I/C FOR SB-1 TJM 10 800 0.75 0.7 13 1 0.4 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 75 0.75 0.8 3.2 1 0.85 Infinity
Primary
Tripping Tripping Time
S.No SB No Description Relay Type Current in PS TMS PS TMS
Time (Sec) (Sec)
CT(A)
Existing Service Settings ELSYTEC's Recommended Settings
252-3 SB-1 TIE TO TG-1 SG CDD 31 500 1.25 0.95 5 1 0.7 5
252-26 TG-1 TIE TO SB-1 CDD 31 500 1 0.65 2.5 1 0.7 5

Fault at PMCC-1 (433V)


452-11 PMCC1 I/C FROM SB2 CDG 31 4000 0.5 0.3 0.31 1 0.15 0.18
252-8 SB-2 I/C FROM SB-1 TJM 10 150 0.5 0.5 1 1 0.3 0.88
252-7 SB-1 OG TO SB-2 TJM 10 150 1 0.5 1.2 1 0.3 0.88
252-1 SB-1 I/C FOR SB-1 TJM 10 800 0.75 0.7 2.1 1 0.4 12
152-1 SB-1 I/C FROM 110kV Line ICM 21 75 0.75 0.8 2.4 1 0.85 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 500 1.25 0.95 1.3 1 0.7 5
252-26 TG-1 TIE TO SB-1 CDD 31 500 1 0.65 0.84 1 0.7 5
252-21 TG-1 I/C FROM TG CDG 31 600 1 0.4 0.58 1 0.85 7

Fault at PMCC-3 (433V)


252-12 PMCC3 I/C FROM SB2 CDG 31 3000 1 0.4 0.48 1 0.15 0.18
252-11 SB-3 OG TO TR-3 TJM 10 125 1 0.5 1.5 1 0.1 0.31
252-9 SB-3 I/C FROM SB1 NO RELAY
252-4 SB-1 OG TO SB-3 TJM 10 400 1 0.5 2.7 1 0.3 2.6
252-1 SB-1 I/C OF SB-1 TJM 10 800 0.75 0.7 17 1 0.4 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 75 0.75 0.8 12 1 0.85 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 500 1.25 0.95 18 1 0.7 4.5
252-26 TG-1 TIE TO SB-1 CDD 31 500 1 0.65 8 1 0.7 4.5
252-21 TG-1 I/C FROM TG CDG 31 600 1 0.4 2.5 1 0.85 6

Fault at PMCC-4 (433V)


452-13 PMCC4 I/C FROM TR-4 CDG 31 3000 1 0.4 0.5 1 0.15 0.18
252-12 SB-3 OG TO TR-4 TJM 10 125 1 0.5 1.5 1 0.1 0.31
252-9 SB-3 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-3 TJM 10 400 1 0.5 2.7 1 0.3 2.6
252-1 SB-1 I/C OF SB-1 TJM 10 800 0.75 0.7 17 1 0.4 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 75 0.75 0.8 12 1 0.85 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 500 1.25 0.95 18 1 0.7 4.5
252-26 TG-1 TIE TO SB-1 CDD 31 500 1 0.65 8 1 0.7 4.5
252-21 TG-1 I/C FROM TG CDG 31 600 1 0.4 2.5 1 0.85 6
Primary
Tripping Tripping Time
S.No SB No Description Relay Type Current in PS TMS PS TMS
Time (Sec) (Sec)
CT(A)
Existing Service Settings ELSYTEC's Recommended Settings
Fault at PMCC-5 (433V)
452-14 PMCC-5 I/C FROM TR-5 CDG 31 3000 1 0.4 0.5 1 0.15 0.19
252-13 SB-3 OG TO TR-5 TJM 10 125 1 0.5 1.5 1 0.1 0.31
252-9 SB-3 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-3 TJM 10 400 1 0.5 2.7 1 0.3 2.6
252-1 SB-1 I/C OF SB-1 TJM 10 800 0.75 0.7 17 1 0.4 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 75 0.75 0.8 12 1 0.85 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 500 1.25 0.95 18 1 0.7 4.5
252-26 TG-1 TIE TO SB-1 CDD 31 500 1 0.65 8 1 0.7 4.5
252-21 TG-1 I/C FROM TG CDG 31 600 1 0.4 2.5 1 0.85 6

Fault at PMCC-6 (433V)


452-20 PMCC-6 I/C FROM TR-6 CDG 31 600 1 0.3 0.35 1 0.15 0.15
252-20 SB-4 OG TO TR-6 TJM 10 25 0.5 0.5 1.1 1 0.1 0.29
252-9 SB-4 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-4 TJM 10 500 1 0.7 Infinity 1 0.3 Infinity
252-1 SB-1 I/C OF SB-1 TJM 10 800 0.75 0.7 Infinity 1 0.4 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 75 0.75 0.8 Infinity 1 0.85 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 500 1.25 0.95 Infinity 1 0.7 Infinity
252-26 TG-1 TIE TO SB-1 CDD 31 500 1 0.65 Infinity 1 0.7 Infinity
252-21 TG-1 I/C FROM TG CDG 31 600 1 0.4 Infinity 1 0.85 Infinity

Fault at PMCC-7 (433V)


452-19 PMCC-7 I/C FROM TR-7 CDG 31 2500 1 0.4 0.51 1 0.15 0.18
252-19 SB-4 OG TO TR-7 TJM 10 100 1 0.5 1.5 1 0.1 0.3
252-9 SB-4 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-4 TJM 10 500 1 0.7 17 1 0.3 2.6
252-1 SB-1 I/C FOR SB-1 TJM 10 800 0.75 0.7 Infinity 1 0.4 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 75 0.75 0.8 Infinity 1 0.85 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 500 1.25 0.95 12 1 0.7 Infinity
252-26 TG-1 TIE TO SB-1 CDD 31 500 1 0.65 8 1 0.7 Infinity
252-21 TG-1 I/C FROM TG CDG 31 600 1 0.4 3 1 0.85 Infinity

Fault at PMCC-8 (433V)


452-18 PMCC-8 I/C FROM TR-8 CDG 31 2500 1 0.3 0.38 1 0.15 0.18
252-18 SB-4 OG TO TR-7 TJM 10 100 1 0.5 1.5 1 0.1 0.3
252-9 SB-4 I/C FROM SB-1 NO RELAY
Primary
Tripping Tripping Time
S.No SB No Description Relay Type Current in PS TMS PS TMS
Time (Sec) (Sec)
CT(A)
Existing Service Settings ELSYTEC's Recommended Settings
252-4 SB-1 OG TO SB-4 TJM 10 500 1 0.7 17 1 0.3 2.6
252-1 SB-1 I/C FOR SB-1 TJM 10 800 0.75 0.7 Infinity 1 0.4 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 75 0.75 0.8 Infinity 1 0.85 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 500 1.25 0.95 1 1 0.7 Infinity
252-26 TG-1 TIE TO SB-1 CDD 31 500 1 0.65 8 1 0.7 Infinity
252-21 TG-1 I/C FROM TG CDG 31 600 1 0.4 3 1 0.85 Infinity
Fault at PMCC-9 (433V)
452-17 PMCC-9 I/C FROM TR-9 CDG 31 2500 0.5 0.75 0.75 1 0.15 0.18
252-17 SB-4 OG TO TR-7 TJM 10 100 0.75 0.6 1.7 1 0.1 0.3
252-9 SB-4 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-4 TJM 10 500 1 0.7 17 1 0.3 2.6
252-1 SB-1 I/C FOR SB-1 TJM 10 800 0.75 0.7 Infinity 1 0.4 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 75 0.75 0.8 Infinity 1 0.85 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 500 1.25 0.95 Infinity 1 0.7 Infinity
252-26 TG-1 TIE TO SB-1 CDD 31 500 1 0.65 8 1 0.7 Infinity
252-21 TG-1 I/C FROM TG CDG 31 600 1 0.4 3 1 0.85 Infinity

Fault at DCD 10 (433V)


452-16 DCD-10 I/C FROM TR-10 CDG 31 2500 0.75 0.3 0.35 1 0.15 0.18
252-16 SB-4 OG TO TR-10 TJM 10 100 0.75 0.5 1.4 1 0.1 0.3
252-9 SB-4 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-4 TJM 10 500 1 0.7 17 1 0.3 2.6
252-1 SB-1 I/C FOR SB-1 TJM 10 800 0.75 0.7 Infinity 1 0.4 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 75 0.75 0.8 Infinity 1 0.85 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 500 1.25 0.95 Infinity 1 0.7 Infinity
252-26 TG-1 TIE TO SB-1 CDD 31 500 1 0.65 8 1 0.7 Infinity
252-21 TG-1 I/C FROM TG CDG 31 600 1 0.4 3 1 0.85 Infinity

Fault at DCD 11 (433V)


452-15 DCD-11 I/C FROM TR-11 CDG 31 2500 0.75 0.2 0.23 1 0.15 0.18
252-15 SB-4 OG TO TR-11 TJM 10 100 0.75 0.5 1.4 1 0.1 0.3
252-9 SB-4 I/C FROM SB-1 NO RELAY
252-4 SB-1 OG TO SB-4 TJM 10 500 1 0.7 17 1 0.3 2.6
252-1 SB-1 I/C FOR SB-1 TJM 10 800 0.75 0.7 Infinity 1 0.4 Infinity
152-1 SB-1 I/C FROM 110kV Line ICM 21 75 0.75 0.8 Infinity 1 0.85 Infinity
252-3 SB-1 TIE TO TG-1 SG CDD 31 500 1.25 0.95 Infinity 1 0.7 Infinity
252-26 TG-1 TIE TO SB-1 CDD 31 500 1 0.65 8 1 0.7 Infinity
252-21 TG-1 I/C FROM TG CDG 31 600 1 0.4 3 1 0.85 Infinity
4.2.Comparison of Existing and Recommended Settings - Earth Fault
Primary
Tripping Time Tripping Time
S.No SB No Description Current in Relay Type PS TMS Relay Type PS TMS
(Sec) (Sec)
CT(A)
Existing Service Settings ELSYTEC Recommended Settings
Fault at SB-1 (11kV)
252-2 SB-1 OG TO SB-2 150 TJM 10 0.1 0.2 0.75 TJM 10 0.3 0.1 0.75
252-1 SB-1 I/C FOR SB-1 800 TJM 10 0.2 0.2 7 MIT 161 0.075 0.15 2.05
SB-1 GT T/F NUTRAL 100 - - - - MIT 161 0.6 0.15 2.05
152-1 SB-1 I/C FROM 110kV Line 75 ICM 21 0.1 0.1 0.23 ICM 21 0.75 0.2 2.30
252-3 SB-1 TIE TO TG-1 SG 500 MIT 161 0.005 0.7 1.28 MIT 161 0.1 0.15 1.51
252-26 TG-1 TIE TO SB-1 500 MIT 161 0.005 0.25 0.458 MIT 161 0.1 0.15 1.51
252-21 TG-1 I/C FROM TG 600 CDG 31 0.1 0.3 1.1 CDG 31 0.1 0.45 1.80

Fault at SB-2 (11kV)


252-8 SB-2 OG TO TR-1 NO RELAY
252-7 SB-2 I/C FROM SB-1 150 TJM 10 0.1 0.5 1.7 TJM 10 0.3 0.1 0.75
252-2 SB-1 OG TO SB-2 150 TJM 10 0.1 0.2 0.75 TJM 10 0.3 0.1 0.75
252-1 SB-1 I/C FOR SB-1 800 TJM 10 0.2 0.2 1.053 MIT 161 0.075 0.15 2.05
152-1 SB-1 I/C FROM 110kV Line 75 ICM 21 0.1 0.1 0.28 ICM 21 0.75 0.2 2.30
252-3 SB-1 TIE TO TG-1 SG 500 MIT 161 0.005 0.7 1.28 MIT 161 0.1 0.15 1.51
252-26 TG-1 TIE TO SB-1 500 MIT 161 0.005 0.25 0.458 MIT 161 0.1 0.15 1.51
252-21 TG-1 I/C FROM TG 600 CDG 31 0.1 0.3 1.3 CDG 31 0.1 0.45 1.80

Fault at SB-3 (11kV)


252-10 SB-3 OG TO TR-2 100 TJM 10 0.1 0.1 0.31 TJM 10 0.5 0.1 0.90
252-9 SB-3 I/C FROM SB-1 NO RELAY NO RELAY
252-4 SB-1 OG TO SB-3 400 TJM 10 0.1 0.15 1 MIT 161 0.125 0.125 1.25
252-1 SB-1 I/C FOR SB-1 800 TJM 10 0.2 0.2 7 MIT 161 0.075 0.15 2.05
152-1 SB-1 I/C FROM 110kV Line 75 ICM 21 0.1 0.1 0.27 ICM 21 0.75 0.2 2.30
252-3 SB-1 TIE TO TG-1 SG 500 MIT 161 0.005 0.7 1.28 MIT 161 0.1 0.15 1.51
252-26 TG-1 TIE TO SB-1 500 MIT 161 0.005 0.25 0.458 MIT 161 0.1 0.15 1.51
252-21 TG-1 I/C FROM TG 600 CDG 31 0.1 0.3 0.5 CDG 31 0.1 0.45 1.80

Fault at SB-4 (11kV)


252-15 SB-4 OG TO TR-11 200 TJM 10 0.2 0.5 0.43 TJM 10 0.25 0.1 0.90
252-14 SB-3 I/C FROM SB-1 NO RELAY NO RELAY
252-5 SB-1 OG TO SB-4 500 TJM 10 0.2 0.8 20 MIT 161 0.1 0.125 1.25
252-1 SB-1 I/C FOR SB-1 800 TJM 10 0.2 0.2 7 MIT 161 0.075 0.15 2.05
152-1 SB-1 I/C FROM 110kV Line 75 ICM 21 0.1 0.1 0.27 ICM 21 0.75 0.2 2.30
252-3 SB-1 TIE TO TG-1 SG 500 MIT 161 0.005 0.7 1.28 MIT 161 0.1 0.15 1.51
252-26 TG-1 TIE TO SB-1 500 MIT 161 0.005 0.25 0.458 MIT 161 0.1 0.15 1.51
Primary
Tripping Time Tripping Time
S.No SB No Description Current in Relay Type PS TMS Relay Type PS TMS
(Sec) (Sec)
CT(A)
Existing Service Settings ELSYTEC Recommended Settings
252-21 TG-1 I/C FROM TG 600 CDG 31 0.1 0.3 0.5 CDG 31 0.1 0.45 1.80

Fault at TG-1 (11kV)


252-25 TG-1 OG TO AUX.TR-3 200 CDG 31 0.1 0.1 0.16 CDG 31 0.25 0.3 0.92
252-21 TG-1 I/C FROM TG 600 CDG 31 0.1 0.3 1.3 CDG 31 0.1 0.45 1.80
252-1 SB-1 I/C FOR SB-1 800 TJM 10 0.2 0.2 1.053 MIT 161 0.075 0.15 2.05
152-1 SB-1 I/C FROM 110kV Line 75 ICM 21 0.1 0.1 0.28 ICM 21 0.75 0.2 2.30
252-3 SB-1 TIE TO TG-1 SG 500 MIT 161 0.005 0.7 1.28 MIT 161 0.1 0.15 1.51
252-26 TG-1 TIE TO SB-1 500 MIT 161 0.005 0.25 0.458 MIT 161 0.1 0.15 1.51

Fault at SB-5 (3kV)


352-1 SB-5 I/C FROM TR-2 200 TJM 10 0.1 0.1 0.43 TJM 10 0.25 0.1 0.90
SB-5 TR-2 NUTRAL 200 MIT 161 - - - MIT 161 0.25 0.1 1.00
252-10 SB-3 OG TO TR-2 100 TJM 10 0.1 0.1 0.31 TJM 10 0.5 0.1 0.90
252-9 SB-3 I/C FROM SB-1 NO RELAY NO RELAY
252-4 SB-1 OG TO SB-3 400 MIT 161 0.1 0.15 1 MIT 161 0.125 0.125 1.25
252-1 SB-1 I/C FOR SB-1 800 MIT 161 0.2 0.2 7 MIT 161 0.075 0.15 2.05
152-1 SB-1 I/C FROM 110kV Line 75 ICM 21 0.1 0.1 0.27 ICM 21 0.75 0.2 2.30
252-3 SB-1 TIE TO TG-1 SG 500 MIT 161 0.005 0.7 1.28 MIT 161 0.1 0.15 1.51
252-26 TG-1 TIE TO SB-1 500 MIT 161 0.005 0.25 0.458 MIT 161 0.1 0.15 1.51
252-21 TG-1 I/C FROM TG 600 CDG 31 0.1 0.3 1.1 CDG 31 0.1 0.45 1.80

Fault at TG PMCC-3(3.3kV)
352-2 SB-6 I/C FROM AUX.TR-3 500 CDG 31 0.1 0.1 0.26 CDG 31 0.1 0.1 0.26
SB-6 AUX.TR NUTRAL 500 - - - MIT 161 0.1 0.075 0.75
252-25 SB-1 OG TO AUX.TR-3 200 CDG 31 0.1 0.1 0.16 CDG 31 0.25 0.3 0.92
252-21 SB-1 I/C FROM TG 600 CDG 31 0.1 0.3 1.1 CDG 31 0.1 0.45 1.80
252-1 SB-1 I/C FOR SB-1 800 TJM 10 0.2 0.2 7 MIT 161 0.075 0.15 2.05
152-1 SB-1 I/C FROM 110kV Line 75 ICM 21 0.1 0.1 0.27 ICM 21 0.75 0.2 2.30
252-3 SB-1 TIE TO TG-1 SG 500 MIT 161 0.005 0.7 1.28 MIT 161 0.1 0.15 1.51
252-26 TG-1 TIE TO SB-1 500 MIT 161 0.005 0.25 0.458 MIT 161 0.1 0.15 1.51

Fault at TG-PMCC-2 (433V)


452-2 PMCC-2 I/C FROM AUX.TR-2 3000 CDG 31 0.1 0.1 0.28 CDG 31 0.1 0.1 0.29
PMCC-2 AUX.TR NUTRAL 3000 - - - - MIT 161 0.1 0.075 0.86
252-23 TG-1 OG TO AUX.TR-2 200 CDG 31 0.1 0.1 Infinity CDG 31 0.25 0.3 INFINITY
252-21 TG-1 I/C FROM TG 600 CDG 31 0.1 0.3 Infinity CDG 31 0.1 0.45 INFINITY
252-1 SB-1 I/C FOR SB-1 800 TJM 10 0.2 0.2 Infinity MIT 161 0.075 0.15 INFINITY
Primary
Tripping Time Tripping Time
S.No SB No Description Current in Relay Type PS TMS Relay Type PS TMS
(Sec) (Sec)
CT(A)
Existing Service Settings ELSYTEC Recommended Settings
152-1 SB-1 I/C FROM 110kV Line 75 ICM 21 0.1 0.1 0.55 ICM 21 0.75 0.2 INFINITY
252-3 SB-1 TIE TO TG-1 SG 500 MIT 161 0.005 0.7 2.22 MIT 161 0.1 0.15 INFINITY
252-26 TG-1 TIE TO SB-1 500 MIT 161 0.005 0.25 0.793 MIT 161 0.1 0.15 INFINITY

Fault at PMCC-1 (433V)


452-11 PMCC1 I/C FROM SB2 4000 CDG 31 0.1 0.1 0.3 CDG 31 0.1 0.1 0.29
PMCC1 TR-1 NUTRAL 4000 - - MIT 161 0.1 0.075 0.83
252-8 SB-2 OG TO SB-2 NO RELAY NO RELAY
252-7 SB-2 I/C FROM SB-1 150 TJM 10 0.1 0.5 1.7 TJM 10 0.3 0.1 INFINITY
252-2 SB-1 OG TO SB-2 150 TJM 10 0.1 0.2 1.7 TJM 10 0.3 0.1 INFINITY
252-1 SB-1 I/C FOR SB-1 800 TJM 10 0.2 0.2 Infinity MIT 161 0.075 0.15 INFINITY
152-1 SB-1 I/C FROM 110kV Line 75 ICM 21 0.1 0.1 0.45 ICM 21 0.75 0.2 INFINITY
252-3 SB-1 TIE TO TG-1 SG 500 MIT 161 0.005 0.7 1.937 MIT 161 0.1 0.15 INFINITY
252-26 TG-1 TIE TO SB-1 500 MIT 161 0.005 0.25 0.692 MIT 161 0.1 0.15 INFINITY
252-21 TG-1 I/C FROM TG 600 CDG 31 0.1 0.3 Infinity CDG 31 0.1 0.45 INFINITY

Fault at PMCC-3 (433V)


252-12 PMCC3 I/C FROM SB-3 3000 CDG 31 0.1 0.2 0.55 CDG 31 0.1 0.1 0.25
PMCC3 TR-3 NUTRAL 3000 - - MIT 161 0.1 0.075 0.67
252-11 SB-3 OG TO TR-3 125 TJM 10 0.1 0.2 1.7 TJM 10 0.4 0.1 INFINITY
252-9 SB-3 I/C FROM SB1 NO RELAY NO RELAY
252-4 SB-1 OG TO SB-3 400 TJM 10 0.1 0.15 Infinity MIT 161 0.125 0.125 INFINITY
252-1 SB-1 I/C OF SB-1 800 TJM 10 0.2 0.2 Infinity MIT 161 0.075 0.15 INFINITY
152-1 SB-1 I/C FROM 110kV Line 75 ICM 21 0.1 0.1 0.5 ICM 21 0.75 0.2 INFINITY
252-3 SB-1 TIE TO TG-1 SG 500 MIT 161 0.005 0.7 2.056 MIT 161 0.1 0.15 INFINITY
252-26 TG-1 TIE TO SB-1 500 MIT 161 0.005 0.25 0.735 MIT 161 0.1 0.15 INFINITY
252-21 TG-1 I/C FROM TG 600 CDG 31 0.1 0.3 Infinity CDG 31 0.1 0.45 INFINITY

Fault at PMCC-4 (433V)


452-13 PMCC4 I/C FROM TR-4 3000 CDG 31 0.1 0.1 0.27 CDG 31 0.1 0.1 0.24
PMCC4 TR-4 NUTRAL 3000 - - - MIT 161 0.1 0.075 0.67
252-12 SB-3 OG TO TR-4 125 TJM 10 0.1 0.2 1.7 TJM 10 0.4 0.1 INFINITY
252-9 SB-3 I/C FROM SB-1 NO RELAY NO RELAY
252-4 SB-1 OG TO SB-3 400 TJM 10 0.1 0.15 Infinity MIT 161 0.125 0.125 INFINITY
252-1 SB-1 I/C OF SB-1 800 TJM 10 0.2 0.2 Infinity MIT 161 0.075 0.15 INFINITY
152-1 SB-1 I/C FROM 110kV Line 75 ICM 21 0.1 0.1 0.5 ICM 21 0.75 0.2 INFINITY
252-3 SB-1 TIE TO TG-1 SG 500 MIT 161 0.005 0.7 2.051 MIT 161 0.1 0.15 INFINITY
Primary
Tripping Time Tripping Time
S.No SB No Description Current in Relay Type PS TMS Relay Type PS TMS
(Sec) (Sec)
CT(A)
Existing Service Settings ELSYTEC Recommended Settings
252-26 TG-1 TIE TO SB-1 500 MIT 161 0.005 0.25 0.733 MIT 161 0.1 0.15 INFINITY
252-21 TG-1 I/C FROM TG 600 CDG 31 0.1 0.3 Infinity CDG 31 0.1 0.45 INFINITY

Fault at PMCC-5 (433V)


452-14 PMCC-5 I/C FROM TR-5 3000 CDG 31 0.1 0.15 0.4 CDG 31 0.1 0.1 0.25
PMCC-5 TR-5 NUTRAL 3000 - - - - MIT 161 0.1 0.075 0.68
252-13 SB-3 OG TO TR-5 125 TJM 10 0.1 0.2 1.7 TJM 10 0.4 0.1 INFINITY
252-9 SB-3 I/C FROM SB-1 NO RELAY NO RELAY
252-4 SB-1 OG TO SB-3 400 TJM 10 0.1 0.15 Infinity MIT 161 0.125 0.125 INFINITY
252-1 SB-1 I/C OF SB-1 800 TJM 10 0.2 0.2 Infinity MIT 161 0.075 0.15 INFINITY
152-1 SB-1 I/C FROM 110kV Line 75 ICM 21 0.1 0.1 0.5 ICM 21 0.75 0.2 INFINITY
252-3 SB-1 TIE TO TG-1 SG 500 MIT 161 0.005 0.7 2.059 MIT 161 0.1 0.15 INFINITY
252-26 TG-1 TIE TO SB-1 500 MIT 161 0.005 0.25 0.736 MIT 161 0.1 0.15 INFINITY
252-21 TG-1 I/C FROM TG 600 CDG 31 0.1 0.3 Infinity CDG 31 0.1 0.45 INFINITY

Fault at PMCC-6 (433V)


452-20 PMCC-6 I/C FROM TR-6 600 CDG 31 0.1 0.35 CDG 31 0.1 0.1 0.20
PMCC-6 TR-6 NUTRAL 600 - - - MIT 161 0.1 0.075 0.52
252-20 SB-4 OG TO TR-6 25 TJM 10 0.1 0.1 0.7 TJM 10 2 0.1 INFINITY
252-9 SB-4 I/C FROM SB-1 NO RELAY NO RELAY
252-4 SB-1 OG TO SB-4 500 TJM 10 0.2 0.8 Infinity MIT 161 0.1 0.125 INFINITY
252-1 SB-1 I/C OF SB-1 800 TJM 10 0.2 0.2 Infinity MIT 161 0.075 0.15 INFINITY
152-1 SB-1 I/C FROM 110kV Line 75 ICM 21 0.1 0.1 Infinity ICM 21 0.75 0.2 INFINITY
252-3 SB-1 TIE TO TG-1 SG 500 MIT 161 0.005 0.7 5.124 MIT 161 0.1 0.15 INFINITY
252-26 TG-1 TIE TO SB-1 500 MIT 161 0.005 0.25 1.83 MIT 161 0.1 0.15 INFINITY
252-21 TG-1 I/C FROM TG 600 CDG 31 0.1 0.3 Infinity CDG 31 0.1 0.45 INFINITY

Fault at PMCC-7 (433V)


452-19 PMCC-7 I/C FROM TR-7 2500 CDG 31 0.1 0.1 0.26 CDG 31 0.1 0.1 0.26
PMCC-7 TR-7 NUTRAL 2500 - - - MIT 161 0.1 0.075 0.70
252-19 SB-4 OG TO TR-7 100 TJM 10 0.1 0.2 1.7 TJM 10 0.5 0.1 INFINITY
252-9 SB-4 I/C FROM SB-1 NO RELAY NO RELAY
252-4 SB-1 OG TO SB-4 500 TJM 10 0.2 0.8 Infinity MIT 161 0.1 0.125 INFINITY
252-1 SB-1 I/C FOR SB-1 800 TJM 10 0.2 0.2 Infinity MIT 161 0.075 0.15 INFINITY
152-1 SB-1 I/C FROM 110kV Line 75 ICM 21 0.1 0.1 0.52 ICM 21 0.75 0.2 INFINITY
252-3 SB-1 TIE TO TG-1 SG 500 MIT 161 0.005 0.7 2.264 MIT 161 0.1 0.15 INFINITY
252-26 TG-1 TIE TO SB-1 500 MIT 161 0.005 0.25 0.809 MIT 161 0.1 0.15 INFINITY
252-21 TG-1 I/C FROM TG 600 CDG 31 0.1 0.3 Infinity CDG 31 0.1 0.45 INFINITY
Primary
Tripping Time Tripping Time
S.No SB No Description Current in Relay Type PS TMS Relay Type PS TMS
(Sec) (Sec)
CT(A)
Existing Service Settings ELSYTEC Recommended Settings

Fault at PMCC-8 (433V)


452-18 PMCC-8 I/C FROM TR-8 2500 CDG 31 0.1 0.1 0.26 CDG 31 0.1 0.1 0.25
PMCC-8 TR-8 NUTRAL 2500 - - - - MIT 161 0.1 0.075 0.67
252-18 SB-4 OG TO TR-8 100 TJM 10 0.1 0.2 1.68 TJM 10 0.5 0.1 INFINITY
252-9 SB-4 I/C FROM SB-1 NO RELAY NO RELAY
252-4 SB-1 OG TO SB-4 500 TJM 10 0.2 0.8 Infinity MIT 161 0.1 0.125 INFINITY
252-1 SB-1 I/C FOR SB-1 800 TJM 10 0.2 0.2 Infinity MIT 161 0.075 0.15 INFINITY
152-1 SB-1 I/C FROM 110kV Line 75 ICM 21 0.1 0.1 0.45 ICM 21 0.75 0.2 INFINITY
252-3 SB-1 TIE TO TG-1 SG 500 MIT 161 0.005 0.7 2.229 MIT 161 0.1 0.15 INFINITY
252-26 TG-1 TIE TO SB-1 500 MIT 161 0.005 0.25 0.796 MIT 161 0.1 0.15 INFINITY
252-21 TG-1 I/C FROM TG 600 CDG 31 0.1 0.3 Infinity CDG 31 0.1 0.45 INFINITY

Fault at PMCC-9 (433V)


452-17 PMCC-9 I/C FROM TR-9 2500 CDG 31 0.1 0.1 0.26 CDG 31 0.1 0.1 0.26
PMCC-9 TR-9 NUTRAL 2500 - - - MIT 161 0.1 0.075 0.69
252-17 SB-4 OG TO TR-9 100 TJM 10 0.1 0.2 1.7 TJM 10 0.5 0.1 INFINITY
252-9 SB-4 I/C FROM SB-1 NO RELAY NO RELAY
252-4 SB-1 OG TO SB-4 500 TJM 10 0.2 0.8 Infinity MIT 161 0.1 0.125 INFINITY
252-1 SB-1 I/C FOR SB-1 800 TJM 10 0.2 0.2 Infinity MIT 161 0.075 0.15 INFINITY
152-1 SB-1 I/C FROM 110kV Line 75 ICM 21 0.1 0.1 0.45 ICM 21 0.75 0.2 INFINITY
252-3 SB-1 TIE TO TG-1 SG 500 MIT 161 0.005 0.7 2.255 MIT 161 0.1 0.15 INFINITY
252-26 TG-1 TIE TO SB-1 500 MIT 161 0.005 0.25 0.806 MIT 161 0.1 0.15 INFINITY
252-21 TG-1 I/C FROM TG 600 CDG 31 0.1 0.3 Infinity CDG 31 0.1 0.45 INFINITY
Fault at DCD 10 (433V)
452-16 DCD-10 I/C FROM TR-10 2500 CDG 31 0.4 0.5 Infinity CDG 31 0.1 0.1 0.26
DCD-10 TR-10 NUTRAL 2500 - - - MIT 161 0.1 0.075 0.70
252-16 SB-4 OG TO TR-10 100 TJM 10 0.2 0.2 Infinity TJM 10 0.5 0.1 INFINITY
252-9 SB-4 I/C FROM SB-1 NO RELAY NO RELAY
252-4 SB-1 OG TO SB-4 500 TJM 10 0.2 0.8 Infinity MIT 161 0.1 0.125 INFINITY
252-1 SB-1 I/C FOR SB-1 800 TJM 10 0.2 0.2 Infinity MIT 161 0.075 0.15 INFINITY
152-1 SB-1 I/C FROM 110kV Line 75 ICM 21 0.1 0.1 0.45 ICM 21 0.75 0.2 INFINITY
252-3 SB-1 TIE TO TG-1 SG 500 MIT 161 0.005 0.7 2.262 MIT 161 0.1 0.15 INFINITY
252-26 TG-1 TIE TO SB-1 500 MIT 161 0.005 0.25 0.808 MIT 161 0.1 0.15 INFINITY
252-21 TG-1 I/C FROM TG 600 CDG 31 0.1 0.3 Infinity CDG 31 0.1 0.45 INFINITY

Fault at DCD 11 (433V)


452-15 DCD-11 I/C FROM TR-11 2500 CDG 31 0.4 0.5 Infinity CDG 31 0.1 0.1 0.26
Primary
Tripping Time Tripping Time
S.No SB No Description Current in Relay Type PS TMS Relay Type PS TMS
(Sec) (Sec)
CT(A)
Existing Service Settings ELSYTEC Recommended Settings
DCD-11 TR-11 NUTRAL 2500 - - - MIT 161 0.1 0.075 0.69
252-15 SB-4 OG TO TR-11 100 TJM 10 0.2 0.5 Infinity TJM 10 0.5 0.1 INFINITY
252-9 SB-4 I/C FROM SB-1 NO RELAY NO RELAY
252-4 SB-1 OG TO SB-4 500 TJM 10 0.2 0.8 Infinity MIT 161 0.1 0.125 INFINITY
252-1 SB-1 I/C FOR SB-1 800 TJM 10 0.2 0.2 Infinity MIT 161 0.075 0.15 INFINITY
152-1 SB-1 I/C FROM 110kV Line 75 ICM 21 0.1 0.1 0.45 ICM 21 0.75 0.2 INFINITY
252-3 SB-1 TIE TO TG-1 SG 500 MIT 161 0.005 0.7 2.257 MIT 161 0.1 0.15 INFINITY
252-26 TG-1 TIE TO SB-1 500 MIT 161 0.005 0.25 0.806 MIT 161 0.1 0.15 INFINITY
252-21 TG-1 I/C FROM TG 600 CDG 31 0.1 0.3 Infinity CDG 31 0.1 0.45 INFINITY
5. Proposed additional Relays recommended
Relays to be procured & installed in all Transformer secondary neutral side at
following places

1. GT
2. Tr-1
3. Tr-2
4. Tr-3
5. Tr-4
6. Tr-5
7. Tr-6
8. Tr-7
9. Tr-8
10. Tr-9
11. Tr-10
12. Tr-11
13. Aux.Tr-1
14. Aux.Tr-2
15. Aux.Tr-3 and also
252-1 Incoming from 10/12.5MVA Transformer
252-4 Outgoing to SB-3 from SB-1.
252-5 Outgoing to SB-4 from SB-1
252-3 Tie feeder from SB-1 to TG
252-26 Tie feeder from TG to SB-1

In the above places MIT 161 type of relays is recommended to installed and CT
ratios to match with LT side CT’s respective Breakers. (Refer 3.2.1.)
5. RECOMMENDED SETTINGS
FOR OVER CURRENT &
EARTH FAULT
RECOMMENDED SETTINGS FOR OVER CURRENT AND EARTH FAULT BY ELSYTEC
RECOMMENDED SETTINGS FOR OVER CURRENT
Plug
Device No Device Location Relay Type CT Ratio TMS
Settings
152-1 I/C FROM 110kV LINE ICM 21 75/1A 1 0.85
252-1 I/C FOR SB-1 TJM 10 800/1A 1 0.4
252-2 OG TO SB-2 FROM SB-1 TJM 10 150/1A 1 0.3
252-3 TIE TO SB-1 TO TG1 CDD 31 500/1A 1 0.7
252-4 OG TO SB-3 FROM SB-1 TJM 10 400/1A 1 0.3
252-5 OG TO SB-4 FROM SB-1 TJM 10 500/1A 1 0.3
252-7 I/C FROM SB-1 IN SB-2 TJM 10 150/1A 1 0.3
252-8 OG TO TR-1 FROM SB-2 - - - -
252-9 I/C FROM SB-1 IN SB-3 - - - -
252-10 OG TO TR-2 FROM SB-3 TJM 10 100/1A 0.75 0.1
252-11 OG TO TR-3 FROM SB-3 TJM 10 125/1A 1 0.1
252-12 OG TO TR-4 FROM SB-3 TJM 10 125/1A 1 0.1
252-13 OG TO TR-5 FROM SB-3 TJM 10 125/1A 1 0.1
252-14 I/C FROM SB-1 IN SB-4 - - - -
252-15 OG TO TR-11 FROM SB-4 TJM 10 100/1A 1 0.1
252-16 OG TO TR-10 FROM SB-4 TJM 10 100/1A 1 0.1
252-17 OG TO TR-9 FROM SB-4 TJM 10 100/1A 1 0.1
252-18 OG TO TR-8 FROM SB-4 TJM 10 100/1A 1 0.1
252-19 OG TO TR-7 FROM SB-4 TJM 10 100/1A 1 0.1
252-20 OG TO TR-6 FROM SB-4 TJM 10 100/1A 1 0.1
252-21 I/C FROM TG IN TG SG CDG 31 600/1A 1 0.85
252-22 OG TO Aux.TR-1 FROM TG1 CDG 31 200/1A 1 0.3
252-23 OG TO Aux.TR-2 FROM TG1 CDG 31 200/1A 1 0.3
252-25 OG TO Aux.TR-3 FROM TG1 CDG 31 200/1A 1 0.3
252-26 TIE TO TG1 TO SB-1 CDD 31 500/1A 1 0.7
352-1 I/C FROM TR-2 IN SB-5 TJM 10 200/1A 1 0.1
352-2 I/C FROM Aux.TR-3 IN TG PMCC-3 CDG 31 500/1A 1 0.1
452-1 I/C FROM Aux.TR-1 IN TG PMCC-1 CDG 31 3000/1A 1 0.1
452-2 I/C FROM Aux.TR-2 IN TG PMCC-2 CDG 31 3000/1A 1 0.1
452-11 I/C FROM TR-1 IN PMCC-1 CDG 31 4000/1A 1 0.15
452-12 I/C FROM TR-3 IN PMCC-3 CDG 31 3000/1A 1 0.15
452-13 I/C FROM TR-4 IN PMCC-4 CDG 31 3000/1A 1 0.15
452-14 I/C FROM TR-5 IN PMCC-5 CDG 31 3000/1A 1 0.15
452-15 I/C FROM TR-11 IN DCD-11 CDG 31 2500/1A 1 0.15
452-16 I/C FROM TR-10 IN DCD-10 CDG 31 2500/1A 1 0.15
452-17 I/C FROM TR-9 IN PMCC-9 CDG 31 2500/1A 1 0.15
452-18 I/C FROM TR-8 IN PMCC-8 CDG 31 2500/1A 1 0.15
452-19 I/C FROM TR-7 IN PMCC-7 CDG 31 2500/1A 1 0.15
452-20 I/C FROM TR-6 IN PMCC-6 CDG 31 600/1A 1 0.15

49
RECOMMENDED SETTINGS FOR EARTH FAULT
Plug
Device No Device Location Relay Type CT Ratio Settings TMS
152-1 I/C FROM 110kV LINE ICM 21 75/1A 0.75 0.2
252-1 I/C FOR SB-1 MIT 161 800/1A 0.075 0.15
252-2 OG TO SB-2 FROM SB-1 TJM 10 150/1A 0.3 0.1
252-3 TIE TO SB-1 TO TG1 MIT 161 500/1A 0.1 0.15
252-4 OG TO SB-3 FROM SB-1 MIT 161 400/1A 0.125 0.125
252-5 OG TO SB-4 FROM SB-1 MIT 161 500/1A 0.1 0.125
252-7 I/C FROM SB-1 IN SB-2 TJM 10 150/1A 0.3 0.1
252-8 OG TO TR-1 FROM SB-2 - - - -
252-9 I/C FROM SB-1 IN SB-3 - - - -
252-10 OG TO TR-2 FROM SB-3 TJM 10 100/1A 0.5 0.1
252-11 OG TO TR-3 FROM SB-3 TJM 10 125/1A 0.4 0.1
252-12 OG TO TR-4 FROM SB-3 TJM 10 125/1A 0.4 0.1
252-13 OG TO TR-5 FROM SB-3 TJM 10 125/1A 0.4 0.1
252-14 I/C FROM SB-1 IN SB-4 - - - -
252-15 OG TO TR-11 FROM SB-4 TJM 10 100/1A 0.5 0.1
252-16 OG TO TR-10 FROM SB-4 TJM 10 100/1A 0.5 0.1
252-17 OG TO TR-9 FROM SB-4 TJM 10 100/1A 0.5 0.1
252-18 OG TO TR-8 FROM SB-4 TJM 10 100/1A 0.5 0.1
252-19 OG TO TR-7 FROM SB-4 TJM 10 100/1A 0.5 0.1
252-20 OG TO TR-6 FROM SB-4 TJM 10 100/1A 2 0.1
252-21 I/C FROM TG IN TG SG CDG 31 600/1A 0.1 0.45
252-22 OG TO Aux.TR-1 FROM TG1 CDG 31 200/1A 0.25 0.3
252-23 OG TO Aux.TR-2 FROM TG1 CDG 31 200/1A 0.25 0.3
252-25 OG TO Aux.TR-3 FROM TG1 CDG 31 200/1A 0.25 0.3
252-26 TIE TO TG1 TO SB-1 MIT 161 500/1A 0.1 0.15
352-1 I/C FROM TR-2 IN SB-5 TJM 10 200/1A 0.5 0.1
352-2 I/C FROM Aux.TR-3 IN TG PMCC-3 CDG 31 500/1A 0.1 0.1
452-1 I/C FROM Aux.TR-1 IN TG PMCC-1 CDG 31 3000/1A 0.1 0.1
452-2 I/C FROM Aux.TR-2 IN TG PMCC-2 CDG 31 3000/1A 0.1 0.1
452-11 I/C FROM TR-1 IN PMCC-1 CDG 31 4000/1A 0.1 0.1
452-12 I/C FROM TR-3 IN PMCC-3 CDG 31 3000/1A 0.1 0.1
452-13 I/C FROM TR-4 IN PMCC-4 CDG 31 3000/1A 0.1 0.1
452-14 I/C FROM TR-5 IN PMCC-5 CDG 31 3000/1A 0.1 0.1
452-15 I/C FROM TR-11 IN DCD-11 CDG 31 2500/1A 0.1 0.1
452-16 I/C FROM TR-10 IN DCD-10 CDG 31 2500/1A 0.1 0.1
452-17 I/C FROM TR-9 IN PMCC-9 CDG 31 2500/1A 0.1 0.1
452-18 I/C FROM TR-8 IN PMCC-8 CDG 31 2500/1A 0.1 0.1
452-19 I/C FROM TR-7 IN PMCC-7 CDG 31 2500/1A 0.1 0.1
452-20 I/C FROM TR-6 IN PMCC-6 CDG 31 600/1A 0.1 0.1
GT NEUTRAL MIT 161 100/1A 0.6 0.15
TR-1 NEUTRAL MIT 161 4000/1A 0.1 0.075
TR-2 NEUTRAL MIT 161 200/1A 0.25 0.1
TR-3 NEUTRAL MIT 161 3000/1A 0.1 0.075
TR-4 NEUTRAL MIT 161 3000/1A 0.1 0.075
TR-5 NEUTRAL MIT 161 3000/1A 0.1 0.075
TR-6 NEUTRAL MIT 161 600/1A 0.1 0.075
TR-7 NEUTRAL MIT 161 2500/1A 0.1 0.075
TR-8 NEUTRAL MIT 161 2500/1A 0.1 0.075
TR-9 NEUTRAL MIT 161 2500/1A 0.1 0.075
TR-10 NEUTRAL MIT 161 2500/1A 0.1 0.075
TR-11 NEUTRAL MIT 161 2500/1A 0.1 0.075
Aux.TR-1 NEUTRAL MIT 161 3000/1A 0.1 0.075
Aux.TR-2 NEUTRAL MIT 161 3000/1A 0.1 0.075

50
Aux.TR-3 NEUTRAL MIT 161 500/1A 0.1 0.075

51