Date: 15/11/2022

Gelan, Kaliti north and Bole lemi 1 Substations Frequency Setting Report
We have gone to those substations for modifying frequency setting as per requested from
operation planning department. As you know frequency is related to the loads. So, we believe
they studied the load and they requested to our department to modify the setting to 49.25 HZ
frequency for the above substations feeder. The feeders are K6 in Kaliti north, L8 in Gelan and
L1 in Bole lemi. We changed the setting to these value but we want to inform the function and its
setting before and after.

Kaliti north substation Frequency Setting for Micom P127 relay

[81] Frequency
Before After
F1? No F1? No
F2? No F2? 81< = 49.25 HZ
tF2? 0 sec
F3? No F3? No
F4? No F4? No
F5? No F5? No
F6? No F6? No

Bole lemi 1 Substation Frequency Setting for Micom P127 relay

[81] Frequency
Before After
F1? No F1? 81< = 49.25HZ
tF1? 0 sec
F2? No F2? No
F3? No F3? No
F4? No F4? No
F5? No F5? No
F6? No F6? No

Note: when we set the frequency value, frequency out of range alarm was coming on the relay.
But we tried to analyze why this alarm is coming. We set the value 49.25HZ, it is in the range.
Why it comes? This alarm dismissed when we changed the Inh.alarm- F out? = Yes in the
configuration, it was set No before. So, it needs see again.
Gelan Substation Frequency Setting for CYG PRS7367

[81] Frequency
Before After
En-UFLS1 Disabled En-UFLS1 Enabled
Fr-UFLS1 49.5HZ Fr-UFLS1 49.25HZ
Fr-tLS1 100 sec Fr-tLS1 0 sec