Source/Grid Data

Source Voltage 33 kV
Source Fault Current 31.5 kA
Source Fault MVA 1800.46681 MVA
Source X/R 14
Base MVA 100 MVA
Nominal kV (Bus kV) / Base kV
Primary 33 kV
Sec 11 kV
Transformer Data
Number Of Transfo 1 Nos
Transfo MVA 15 MVA
Transfo Z % 10 %
Transfo X/R 18.6
Transformer Volt Ratio
Primary 33 kV
Sec 11 kV
Transformer Primary Tap 100 %
So, if +2.5% tap is applied on primary side, you can enter
0 %
102.5%
Calc

Load Data
Type 80 %Motor 20 % Static
S 8 MVA
Power Factor 0.8
P 6.4 MW (kW = kVA * CosØ)
Q 4.8 MVAR (Q = Sqrt (S2-P2))

New Ratio and Base kV


Primary 33

Sec 11

Zpu for Power Grid / Source


Zbase = 10.89000 Ohm Zpu = 0.0555

Zohms = 0.6048 Ohm Xpu = 0.0554

Rpu = 0.00396

Zpu for Transformer

Zpu = 0.66667 66.67 %

Xpu = 0.66570524788 66.57 %

Rpu = 0.03579060472 3.58 %

Zpu Total at Fault Location


Zpu (Source) + Zpu (Trafo) = Zpu Total = 0.722208
Xpu = 0.7211052526
Rpu = 0.0397477479
X/R = 18.142041

3-Phase Short Circuit Current

Ik" Short Circuit kA 7.27 kA


Vb 33
Sbase 100
33 kV
11 kV

15 MVA
10 %Zo
18.6 X/R

9.985579 %X
0.536859 %R

66.66667 %Zn
66.57052 %X
3.57906 %R

Load Data

Type 100 %Motor 0 % Static


S 12 MVA
pf 0.8
P 9.6 MW (kW = kVA * CosØ)
Q 7.2 MVAR (Q = Sqrt (S2-P2))

Ppu 0.096
Qpu 0.072
Spu 0.12
Vs 1
Delta V
Vr 1