Professional Documents
Culture Documents
Reference Manual
OMICRON Test Universe
2
XRIO Reference
Table of Contents
1 Introduction............................................................................................................................................. 10
2 Basic Elements of the XRIO Format ..................................................................................................... 11
2.1 XRIO Format Structure ...................................................................................................................... 11
2.2 Value types ........................................................................................................................................ 12
3 DEVICE block.......................................................................................................................................... 13
3.1 NAMEPLATE Block ........................................................................................................................... 13
3.2 LOCATION Block............................................................................................................................... 14
3.3 NOMINALVALUES Block .................................................................................................................. 14
3.3.1 PHASES....................................................................................................................................... 15
3.3.2 FNOM........................................................................................................................................... 15
3.3.3 VNOM .......................................................................................................................................... 15
3.3.4 VPRIM_LL.................................................................................................................................... 15
3.3.5 INOM............................................................................................................................................ 15
3.3.6 IPRIM ........................................................................................................................................... 15
3.4 RESIDUALFACTORS Block .............................................................................................................. 15
3.4.1 VLNVN and ININOM .................................................................................................................... 15
3.5 LIMITS Block...................................................................................................................................... 16
3.5.1 VMAX_LL ..................................................................................................................................... 16
3.5.2 IMAX ............................................................................................................................................ 16
3.6 MISC Block ........................................................................................................................................ 17
3.6.1 DEBOUNCETIME ........................................................................................................................ 17
3.6.2 DEGLITCHTIME .......................................................................................................................... 17
3.6.3 OVERLOADSUPTIME ................................................................................................................. 18
4 DISTANCE Block .................................................................................................................................... 19
4.1 Description ......................................................................................................................................... 19
4.2 Structure of the DISTANCE block...................................................................................................... 24
4.3 PROTECTEDOBJECT Block............................................................................................................. 24
4.3.1 PTCONN ...................................................................................................................................... 25
4.3.2 CTSTARPOINT............................................................................................................................ 25
4.3.3 LINEANGLE ................................................................................................................................. 25
4.3.4 LINELENGTH .............................................................................................................................. 25
4.3.5 GRF_MODE................................................................................................................................. 26
4.3.6 KL_MAG....................................................................................................................................... 26
4.3.7 KL_ANGLE................................................................................................................................... 26
4.3.8 ZN_R............................................................................................................................................ 26
4.3.9 ZN_X ............................................................................................................................................ 26
4.3.10 Z0Z1_MAG ................................................................................................................................ 26
4.3.11 Z0Z1_ANGLE ............................................................................................................................ 26
4.3.12 MCF_MODE .............................................................................................................................. 27
4.3.13 KM_MAG.................................................................................................................................... 27
4.3.14 KM_ANGLE ............................................................................................................................... 27
4.3.15 ZM_R ......................................................................................................................................... 27
4.3.16 ZM_X.......................................................................................................................................... 27
4.3.17 Z0MZ1_MAG ............................................................................................................................. 27
4.3.18 Z0MZ1_ANGLE ......................................................................................................................... 27
3
OMICRON Test Universe
4
XRIO Reference
5
OMICRON Test Universe
6
XRIO Reference
8.15 DIFFBIAS......................................................................................................................................... 52
8.15.1 ACTIVE ...................................................................................................................................... 52
8.15.2 DIFF Block ................................................................................................................................. 52
8.15.2.1 IDIFFGG ............................................................................................................................. 53
8.15.2.2 TDIFFGG ............................................................................................................................ 53
8.15.2.3 IDIFFG ................................................................................................................................ 53
8.15.2.4 TDIFFG............................................................................................................................... 53
8.15.3 BIAS Block ................................................................................................................................. 53
8.15.3.1 DEFBIAS ............................................................................................................................ 53
8.15.3.2 BIASDIVISOR..................................................................................................................... 54
8.15.3.3 TOLHARM_ABS ................................................................................................................. 54
8.15.3.4 TOLHARM_REL ................................................................................................................. 54
8.15.3.5 CHARHARM ....................................................................................................................... 54
8.15.3.5.1 ORDERHARM ............................................................................................................. 54
8.15.3.5.2 DELAYHARM............................................................................................................... 54
8.15.3.5.3 CHARTABLE ............................................................................................................... 54
8.15.4 TRIPCHAR................................................................................................................................. 54
8.15.4.1 POINT................................................................................................................................. 54
9 OVERCURRENT Block ........................................................................................................................... 55
9.1 ITOLREL ............................................................................................................................................ 55
9.2 ITOLABS............................................................................................................................................ 55
9.3 TTOLREL........................................................................................................................................... 55
9.4 TTOLABS........................................................................................................................................... 56
9.5 PTCONN............................................................................................................................................ 56
9.6 CTSTARPOINT.................................................................................................................................. 56
9.7 DIRECTIONAL................................................................................................................................... 56
9.8 AUTORESET ..................................................................................................................................... 56
9.9 Groups ............................................................................................................................................... 57
9.9.1 NAME........................................................................................................................................... 57
9.9.2 RESET_RATIO ............................................................................................................................ 57
9.9.3 UNIT............................................................................................................................................. 58
9.9.3.1 NAME ................................................................................................................................... 58
9.9.3.2 ACTIVE................................................................................................................................. 58
9.9.3.3 IPICKUP ............................................................................................................................... 58
9.9.3.4 TINDEX................................................................................................................................. 58
9.9.3.5 CHARTYPE .......................................................................................................................... 59
9.9.3.6 PREDEFCHAR ..................................................................................................................... 60
9.9.3.7 CHAR block .......................................................................................................................... 61
9.9.3.8 CHARIAC block .................................................................................................................... 62
9.9.3.9 CHARI2T block ..................................................................................................................... 63
9.9.3.10 TABLE block ....................................................................................................................... 63
9.9.3.10.1 POINT .......................................................................................................................... 63
7
OMICRON Test Universe
8
XRIO Reference
Glossary
Abbreviations
Definitions
Test Object : Component of the Test Universe software describing the device under
test
XRIO : Specification for Test Object definitions introduced with Test Universe
2.0
XRIO File : Saved XRIO Test Object as a file
XRIO Converter : Test Object with automatic calculation of parameters from settings
9
OMICRON Test Universe
1 Introduction
The XRIO concept was introduced with the OMICRON Test Universe (OTU) 2.0 as the evolution of the
Relay Interface by OMICRON (RIO). It represents the second generation of Test Object models in the
OTU. A test object can be a protection relay, a meter, or any other device that can be tested with the
OMICRON Test Universe.
The purpose of this manual is to describe the structure of the XRIO file and the parameters contained
in it. For a general complete description of the XRIO functionality and usage please refer to the
XRIO User Manual. Since the Custom section is user-defined, only the RIO section will be described
here.
10
XRIO Reference
11
OMICRON Test Universe
Enumeration values consist of a certain number of Strings, only one of which may be selected at any
given moment.
12
XRIO Reference
3 DEVICE block
The DEVICE block must always be present in an XRIO file – all others are optional. Additionally, there
may be only one DEVICE block in the file. All others can be repeated as many times as necessary.
The DEVICE block describes general data for the relay - the only data stored here are those that are
not specific to any given protection function. Examples of this are the nominal current and voltage, the
relay's serial number, etc.
The structure of the DEVICE block is as follows:
All strings in this block are user-definable and have no influence on the test. They exist for
documentation purposes, and they will appear in the report exactly as entered.
13
OMICRON Test Universe
14
XRIO Reference
3.3.1 PHASES
The number of phases of the system. This number may be 2 or 3. The setting determines the available
fault loops in some of the modules, and the calculation of the LN voltages from the LL voltages:
Phases Calculation
2 VLN = VLL / 2
3 VLN = VLL / √3
3.3.2 FNOM
This parameter represents the nominal frequency of the system in cycles per second (Hz).
3.3.3 VNOM
The nominal or secondary voltage in volts L-L.
3.3.4 VPRIM_LL
The primary voltage in volts L-L.
3.3.5 INOM
The nominal or secondary current in A.
3.3.6 IPRIM
The primary current in A.
15
OMICRON Test Universe
3.5.1 VMAX_LL
The maximum voltage in volts L-L that the device under test can withstand in permanence.
3.5.2 IMAX
The maximum current in A that the device under test can withstand in permanence.
16
XRIO Reference
3.6.1 DEBOUNCETIME
The de-bounce time in seconds. This value is used where signal-smoothing algorithms are
implemented. When the de-bouncing filter is in operation, the system will wait for DEBOUNCETIME
after any change in the binary inputs, before registering another change. A value of zero in
DEBOUNCETIME will disable the feature.
t
Signal before filtering:
t = DEBOUNCETIME
3.6.2 DEGLITCHTIME
The deglitch time in seconds. This value is used where signal-smoothing algorithms are implemented.
When the deglitching filter is in operation, the system will only register signal changes if they last at
least for DEGLITCHTIME. A value of zero in DEGLITCHTIME will disable the feature.
t t
Signal before filtering:
t = DEGLITCHTIME
17
OMICRON Test Universe
3.6.3 OVERLOADSUPTIME
The Overload Detection Suppression Time, in seconds. After any change in the values of the analog
outputs, overload detection will be disabled during this time. This will prevent false positives while the
system adapts to the new load conditions. A value of zero in OVERLOADSUPTIME will disable the
feature, and will therefore detect the overload condition at all times.
18
XRIO Reference
4 DISTANCE Block
The DISTANCE block holds the settings for Distance units. It is the required block of the Distance and
Advanced Distance test modules, and must therefore be present when one of these modules is
inserted in the OCC file. Quick CMC, Sequencer and Autoreclosure also automatically create a
DISTANCE block. For all the rest of the modules, the DISTANCE block is optional.
The DISTANCE block has a more complex structure than the device block. This is mostly due to the
need to describe arbitrary zone shapes; today's distance protections may have any number of
protection zones, each of then having any shape, and the DISTANCE block is designed to model them.
The following is an overview of the functionality described by the block.
4.1 Description
The DISTANCE block is divided in two sub-blocks: PROTECTEDOBJECT and PROTECTIONDEVICE.
PROTECTEDOBJECT holds the general settings of a Distance protection, while
PROTECTIONDEVICE holds the zone settings. In turn, PROTECTIONDEVICE contains two sub-
blocks: TOLERANCES and ZONES. The TOLERANCES block contains the general tolerances, which
will apply to all the zones by default, unless zone-specific tolerances are defined. The ZONES block,
on the other hand, contains any number of ZONE blocks. A ZONE block describes the shape of a
zone, and the zone-specific tolerances if defined (otherwise, the general tolerances will be used).
Tolerances for trip times are set both relative in percent (TTOLREL) and absolute in Ohms
(ZTOLABS). Tolerances for impedances are also set both relative in percent (ZTOLREL) and absolute
in Ohms (ZTOLABS). The relative impedance tolerance for a zone is converted into an absolute value
on the line angle. Specifically, the reach of the zone on the line angle is multiplied by the percent value.
|Z|
φL
R
The grounding factor can be set either with kL, RE/RL and XE/XL or Z0/Z1. The user must select
which of these methods they desire to use. All parameters are present in the XRIO file, and an
additional parameter (GRF_MODE) determines which one of them is active.
19
OMICRON Test Universe
In addition, the mutual coupling factor can also be described in three different ways. It can be set
either with kM, RM/RL and XM/XL or Z0M/Z1. Again, all parameters are present in the XRIO file, and
an additional parameter (MCF_MODE) determines which one of them is active.
There are three different types of shapes for a zone: a generic shape defined by individual lines and
arcs, the mho shape, and the lens/tomato shape. A given zone may have only one of these shapes.
A generic shape is constructed from multiple individual elements; an individual element may be a line
or an arc.
Lines are defined by a point and an angle. The point in turn may be defined in Cartesian or Polar
coordinates.
It is assumed that a shape is only a "single" shape, which means that there is only one single
connected area where all points are considered "inside" of the shape and only one additional area (the
inversion in relationship to the whole Cartesian space) where all points are considered "outside".
A shape does not necessarily have to be "closed". An "open" shape divides the Cartesian space into
two areas (half-spaces), both of which extend to infinity. A "closed" shape defines a finite area for
"inside" and an infinite area for "outside".
Because each characteristic shape is considered a "single" shape, there are a few constraints for the
elements that constitute a valid characteristic:
• Two adjacent elements in the ordered list of elements must have at least one intersection
point. Thus, two adjacent lines cannot be parallel, and arcs must intersect the adjacent
element if prolonged sufficiently.
• No intersection between two non-adjacent elements in the ordered list of elements is allowed
within the segment that is defined by the two intersection points with the preceding and
succeeding element. Otherwise, the characteristic would fall apart into multiple independent
parts and would no longer be "single".
The software will verify these constraints, and reject as invalid any shape that does not fulfill them.
20
XRIO Reference
With the implementation of the impedance tolerance, an "outer" and an "inner" tolerance figure can be
constructed. The tolerance figures do not necessarily have to be single shapes any more.
There are cases where the figures can fall apart into separate shapes. Additionally, not all border
elements from the nominal shape need to be part of the tolerance figures (such as whenever their
"size" is smaller than the tolerance value).
Figure 3 illustrates a tolerance diagram with some interesting characteristics. It has two separate inner
tolerance shapes, and not all border elements are used as border elements for the tolerance shapes.
21
OMICRON Test Universe
A mho characteristic is a special kind of zone, with a circular shape. The mho characteristic is defined
by an angle, a reach and an offset.
The center of the circle is located on a line going through the origin, and with an angle with the X axis
equal to the mho angle; The radius r is calculated as follows:
r = (REACH + OFFSET) / 2
B = REACH + OFFSET
22
XRIO Reference
WIDTH and AB ratio are mutually exclusive. Only one of these values is taken as a parameter – the
SHAPE_MODE parameter selects which one is used.
If A < B, the shape is a lens. For A > B, the shape is a tomato - the valid part is just the outer arcs of
the two circles in the figure. For A = B, the lens/tomato resolves to a standard mho shape.
23
OMICRON Test Universe
The detailed meaning and usage of these parameters is described in the following sections.
24
XRIO Reference
4.3.1 PTCONN
This parameter controls the connection of the power (voltage) transformer. There are two possible
values: BUS (direction busbar) and LINE (direction line). In the Distance module and in some other
modules, this setting determines whether the voltages are turned off (dir busbar) or go back to nominal
(dir line) in the post-fault stage if a trip has occurred.
Relay
PT
PT
Relay
4.3.2 CTSTARPOINT
This parameter controls the connection of the star point of the current transformer. There are two
possible values: BUS (direction busbar) and LINE (direction line). This setting determines whether the
currents are rotated. If the CT is grounded towards the line, the currents are output as calculated by
the test module; if the CT is grounded towards the busbar (that is, towards the protected object) all
currents are rotated by 180° before being sent to the relay.
Busbar Busbar
4.3.3 LINEANGLE
The line angle in degrees.
4.3.4 LINELENGTH
The length of the line in Ohms.
25
OMICRON Test Universe
4.3.5 GRF_MODE
This parameter selects which of the different versions of the Grounding Factor is used. Possible
values for this setting are KL, ZNR_ZNX and Z0Z1.
Setting Factor selected
KL kL
ZNR_ZNX RE/RL and XE/XL
Z0Z1 Z0 / Z1
4.3.6 KL_MAG
Magnitude of the complex grounding factor.
4.3.7 KL_ANGLE
Angle of the complex grounding factor, in degrees.
4.3.8 ZN_R
This is the real part of the second option for describing the complex grounding factor.
4.3.9 ZN_X
This is the imaginary part of the second option for describing the complex grounding factor. The first
value ZN_R (RE/RL) and the second value ZN_X (XE/XL) are calculated into kL according to the
following equations for each individual ZL:
RE
fR =
RL
XE
fX =
XL
Z E RE + jX E
kL = =
Z L RL + jX L
f R ⋅ RL + jf X ⋅ X L
kL =
RL + jX L
4.3.10 Z0Z1_MAG
This is the magnitude of the third way to express the complex grounding factor.
4.3.11 Z0Z1_ANGLE
This is the angle of the third way to express the complex grounding factor, in degrees. Z0 and Z1 are
converted into kL according to the following equation:
1⎛ Z ⎞
k L = ⎜⎜ 0 − 1⎟⎟
3 ⎝ Z1 ⎠
26
XRIO Reference
4.3.12 MCF_MODE
This parameter selects which of the different versions of the mutual coupling factor is used. Possible
values for this setting are KM, ZMR_ZMX and Z0MZ1.
Setting Factor selected
KM kM
ZMR_ZMX RM/RL and XM/XL
Z0MZ1 Z0 / Z1
4.3.13 KM_MAG
Magnitude of the complex mutual coupling factor.
4.3.14 KM_ANGLE
Angle of the complex mutual coupling factor, in degrees.
4.3.15 ZM_R
This is the real part of the second option for describing the complex mutual coupling factor.
4.3.16 ZM_X
This is the imaginary part of the second option for describing the complex mutual coupling factor. The
first value ZM_R (RM/RL) and the second value ZM_X (XM/XL) are calculated into kM according to the
following equations for each individual ZL:
RM
fR =
RL
XM
fX =
XL
Z M RM + jX M
kM = =
ZL RL + jX L
f R ⋅ RL + jf X ⋅ X L
kM =
RL + jX L
4.3.17 Z0MZ1_MAG
This is the magnitude of the third way to express the mutual coupling factor.
4.3.18 Z0MZ1_ANGLE
This is the angle of the third way to express the mutual coupling factor, in degrees. Z0 and Z1 are
converted into kM according to the following equation:
Z0
kM =
3⋅ Z1
27
OMICRON Test Universe
4.4.1 ARCRES
If set, the arc resistance is separated from the fault resistance so that the fault resistance is composed
of the part on the line plus the pure resistive arc resistance. In this case, for phase-to-ground faults,
the arc resistance is not compensated with the grounding factor (multiplied by (1 + kL)).
4.4.2 IMPCORR
If set, the fault impedance is multiplied by (1 A / lnom) before the fault quantities are calculated.
4.4.3 IMPPRIM
If set, all impedances are considered as primary impedances and are multiplied by Vnom / Vprim Iprim / Inom
before the fault quantities are calculated.
4.4.4 CALC_RERL_XEXL
If set, the grounding factor is calculated using RE/RL and XE/XL.
4.4.5 TOLERANCES
This block holds the default tolerances for the zones. Each zone may define its own tolerances, which
will then supersede the ones defined in this block.
28
XRIO Reference
4.4.6 TTOLPLUS
Positive time tolerance, in seconds.
4.4.7 TTOLMINUS
Negative time tolerance, in seconds.
4.4.8 TTOLREL
Relative time tolerance, in times percent.
4.4.9 ZTOLREL
Relative Z tolerance, in percent.
4.4.10 ZTOLABS
Absolute Z tolerance, in Ω.
4.4.11 ZONES
This block is a container for all the distance zones defined in the XRIO file. The ZONES block may
contain any number of ZONE sub-blocks. Each ZONE sub-block in turn defines a Distance zone.
29
OMICRON Test Universe
4.4.12 ZONE
The ZONE block is composed of zone settings, the zone tolerance blocks and one zone shape block.
There are three possible types of shape blocks, but they are mutually exclusive: only one of them may
appear in the XRIO file for a given zone. The Classic UI in the Test Object enforces this constraint
(zones cannot be added via the standard UI). Anyone wishing to generate an XRIO file externally must
be aware of this and make sure only one shape block per zone is present in the XRIO file.
4.4.13 ACTIVE
Indicates if the zone is active or not. Inactive zones remain defined, but are not used by the test
modules.
4.4.14 MAN_LABEL
If set, the label displayed for the zone will be the one entered in the LABEL setting; otherwise, the
software will ignore the value of the LABEL setting and will display an automatically generated label.
30
XRIO Reference
4.4.15 LABEL
Descriptive label for the zone. Please see the section 4.4.14 MAN_LABEL for details on when this
label will be used.
4.4.15.1 INDEX
INDEX sets a unique index for all zones with the same TYPE and FAULTLOOP. This is necessary to
reassign relative shots to the different zones of different relays. It is recommended to number the
zones from inside to outside as usual (first zone number 1, second zone number 2...).
4.4.15.2 TYPE
Selects the type of the zone. The following values are possible:
The following different zone types are available:
• TRIPPING
• EXTENDED
• STARTING
• NONTRIPPING
Tripping zone Zone where the relay is supposed to trip in the specified time.
Extended zone It behaves exactly like normal tripping zones. The difference is that it is
possible to activate or deactivate all extended zones from a single setting
in the Distance module.
The software keeps no links between extended zones and tripping zones.
Thus, no automatic activation of an extended zone related to the
corresponding tripping zone or automatic deactivation of the tripping zone
if the corresponding extended zone is active is possible.
Starting zone This kind of zone cuts across all the tripping and extended zones. They
have an associated trip time, and trip is blocked outside of the zone.
Starting zones are always non-directional.
Non-tripping zone Do not have an associated trip time (and therefore no time tolerances).
They cut across all the tripping and extended zones. Non-tripping zones
are always non-directional.
Table 2: Types of Distance zones
4.4.15.3 FAULTLOOP
Selects the fault loop to which the zone applies. The following values are possible (grouped by type):
31
OMICRON Test Universe
4.4.15.4 TRIPTIME
The nominal trip time for the zone, in seconds.
4.4.15.5.1 TTPL_VALID
If True, the TTOLPLUS tolerance is taken from this block; if False, from the
DISTANCE.PROTECTIONDEVICE.TOLERANCES block.
4.4.15.5.2 TTOLPLUS
Positive time tolerance, in seconds.
4.4.15.5.3 TTMI_VALID
If True, the TTOLMINUS tolerance is taken from this block; if False, from the
DISTANCE.PROTECTIONDEVICE.TOLERANCES block.
4.4.15.5.4 TTOLMINUS
Negative time tolerance, in seconds.
4.4.15.5.5 TTRL_VALID
If True, the TTOLREL tolerance is taken from this block; if False, from the
DISTANCE.PROTECTIONDEVICE.TOLERANCES block.
4.4.15.5.6 TTOLREL
Relative time tolerance, in times percent.
32
XRIO Reference
4.4.15.5.7 ZTRL_VALID
If True, the ZTOLREL tolerance is taken from this block; if False, from the
DISTANCE.PROTECTIONDEVICE.TOLERANCES block.
4.4.15.5.8 ZTOLREL
Relative Z tolerance, in percent.
4.4.15.5.9 ZTAB_VALID
If True, the ZTOLABS tolerance is taken from this block; if False, from the
DISTANCE.PROTECTIONDEVICE.TOLERANCES block.
4.4.15.5.10 ZTOLABS
Absolute Z tolerance, in Ω.
4.4.15.6.1 ANGLE
The angle of the mho shape in degrees.
4.4.15.6.2 REACH
The reach of the mho shape in forward direction in Ohms.
4.4.15.6.3 OFFSET
The offset of the mho shape in backward direction in Ohms.
4.4.15.6.4 INVERT
The INVERT flag indicates which part of the Impedance Plane belongs to the zone. Normally (INVERT
= False) the inside of the circle delimited by the mho shape is the zone, and all the rest of the plane is
outside of the zone. If INVERT is True, the entire plane belongs to the zone except for the area inside
the mho shape.
33
OMICRON Test Universe
4.4.15.7.1 ANGLE
The angle of the lens/tomato shape in degrees.
4.4.15.7.2 REACH
The reach of the lens/tomato shape in forward direction in Ohms.
4.4.15.7.3 OFFSET
The offset of the lens/tomato shape in backward direction in Ohms.
4.4.15.7.4 INVERT
The INVERT flag indicates which part of the Impedance Plane belongs to the zone. Normally (INVERT
= False) the inside of the lens/tomato shape is the zone, and all the rest of the plane is outside of the
zone. If INVERT is True, all the plane belongs to the zone except the area inside the lens/tomato
shape.
4.4.15.7.5 SHAPE_MODE
This parameter selects which parameter between WIDTH and RATIO_AB will be used to determine
the shape of the zone. Possible values for this setting are WIDTH and RATIO_AB.
4.4.15.7.6 WIDTH
The width of the lens/tomato shape in Ohms.
4.4.15.7.7 RATIO_AB
The ratio A/B of the lens/tomato shape.
34
XRIO Reference
4.4.15.9 INVERT
The INVERT flag indicates which part of the Impedance Plane belongs to the zone. Normally
(INVERT = False) the inside of a closed shape is the zone, and all the rest of the plane is outside of
the zone. If INVERT is True, the entire plane belongs to the zone except for the area inside the closed
shape.
For open shapes, the flag inverts the effect of the individual INSIDE parameters for each shape
element.
4.4.15.10 AUTOCLOSE
With the AUTOCLOSE flag, a shape can be made to be closed automatically. This is done by implicitly
setting the LEFT/RIGHT flag for the last border element so that the shape is closed. Additionally the
AUTOCLOSE flag sets the "inside" notion of the shape so that the inside of the closed shape is
INSIDE.
35
OMICRON Test Universe
4.4.15.11.1 REFPOINT_TYPE
Selects whether the Cartesian or the Polar coordinates of the Reference Point will be used. Possible
values for this parameter are CARTESIAN and POLAR.
4.4.15.11.2 REFPOINT_R
Real part of the Cartesian coordinates of the reference point.
4.4.15.11.3 REFPOINT_X
Imaginary part of the Cartesian coordinates of the reference point.
4.4.15.11.4 REFPOINT_MAG
Radial coordinate (distance) of the Polar coordinates of the reference point.
4.4.15.11.5 REFPOINT_ANGLE
Angular coordinate (angle) of the Polar coordinates of the reference point in degrees.
4.4.15.11.6 ANGLE
Line angle referred to the X-axis.
4.4.15.11.7 INSIDE
The inside flag for a border element (LINE or ARC) defines which part of the plane split by this border
element is considered inside the shape. By default, the left half-plane defined by the line is considered
inside, since it is supposed that the shape is constructed by the border elements in a counter-
clockwise direction. If the flag is set to RIGHT, it is the opposite. Instead of switching the flag, it would
be possible to change the angle of the line by 180° - this flag is simply a more convenient way of
achieving the same effect.
For auto-closed figures (AUTOCLOSE parameter is True) INSIDE will have no effect, since the rule
that the figure must be closed has precedence over the INSIDE settings of individual elements.
INSIDE is useful when AUTOCLOSE has not been selected.
Please note that GENERICSHAPE.INVERT exchanges inside and outside for the complete figure.
36
XRIO Reference
4.4.15.12.1 REFPOINT_TYPE
Selects whether the Cartesian or the Polar coordinates of the Reference Point will be used. Possible
values for this parameter are CARTESIAN and POLAR.
4.4.15.12.2 REFPOINT_R
Real part of the Cartesian coordinates of the reference point.
4.4.15.12.3 REFPOINT_X
Imaginary part of the Cartesian coordinates of the reference point.
4.4.15.12.4 REFPOINT_MAG
Radial coordinate (distance) of the Polar coordinates of the reference point.
4.4.15.12.5 REFPOINT_ANGLE
Angular coordinate (angle) of the Polar coordinates of the reference point.
4.4.15.12.6 RADIUS
Arc radius.
4.4.15.12.7 STARTANGLE
Starting angle of the arc in degrees.
4.4.15.12.8 ENDANGLE
Ending angle of the arc in degrees.
37
OMICRON Test Universe
4.4.15.12.9 DIR
Rotational sense of the arc. This parameter selects between the two possible ways to go from
STARTANGLE to ENDANGLE. Possible values are CW (clockwise) and CCW (counterclockwise).
4.4.15.12.10 INSIDE
Possible values are LEFT and RIGHT. Please see section 4.4.15.11.7 in page 36.
38
XRIO Reference
5 CBCONFIGURATION Block
The CBCONFIGURATION block contains the settings for the CB Simulation and affects all the
modules that use it. This functionality was previously part of the DISTANCE module, but has been
moved into this independent block.
CB Simulation is now performed in the CMC 256 test set and its function is completely independent of
any test module. It is configured with the Circuit Breaker Configuration module, which can be inserted
in Control Center test plans. The timing parameters of CB Simulation are stored in the XRIO file so
they are part of the data of a specific relay.
5.1 TRIPTIME
The delay time between the start of the relay's Trip command until the breaker opens. This time is in
seconds.
5.2 CLOSETIME
The delay time between the start of the relay's Close command until the breaker closes. This time is in
seconds.
5.3 P52AB
Percentage of the maneuver time at which the 52a and 52b outputs change configuration. If this
setting were 100%, then the outputs would not change until the maneuver is fully completed.
39
OMICRON Test Universe
6 VISTARTING Block
The VISTARTING block contains the settings for the VI-Starting module. This module is designed to
verify the characteristic of a voltage-dependent Overcurrent starting function (VI-Starting function),
6.1 ITOL
Specifies the relative tolerance for the test current threshold, in percent.
6.2 VTOL
Specifies the relative tolerance for the test voltage threshold, in percent.
6.3 CHARVIS
Describes the characteristic. The block is structured as follows:
6.3.1 IG
Defines the first pick-up current threshold (I> stage).
6.3.2 IGG
Defines the second pick-up current threshold (I>> stage).
40
XRIO Reference
6.3.3 VLNIG
Defines the voltage threshold of the I> stage for line-neutral faults.
6.3.4 VLNIGG
Defines the voltage threshold of the I>> stage for line-neutral faults.
6.3.5 VLLIG
Defines the voltage threshold of the I> stage for line- line faults.
6.3.6 VLLIGG
Defines the voltage threshold of the I>> stage for line-line faults.
41
OMICRON Test Universe
7 SYNCHRO Block
The SYNCHRO block contains the parameters for the Synchronizer module.
Synchronizing relays are designed to measure two voltages with respect to phase angle, frequency,
and magnitude to safeguard against the interconnection of two unsynchronized systems.
Synchronizing relays are also used in switching operations to link two parts of a system that are
already synchronously connected via other paths in the system. Autoreclose is a good example of
such a switching operation.
42
XRIO Reference
7.1 TG_PHASE_SHIFT
This value defines the phase shift (if any) coming from an optional block or coupling transformer. This
value is given in degrees.
7.2 STARTING
Defines the type of start signal to be applied to the test object after the pre-synchronization time. The
following table describes the effect of each of the possible values of the setting:
Value Effect
PULSE A 50 ms start pulse is output at the same time that the maximum
synchronization time starts
CONTINUOUS The start signal is active during the maximum synchronization and post
synchronization times.
NONE No signal is applied
This setting also defines the type of release signal to be applied either at the end of the maximum
synchronization time (test failed) or at the end of the post-synchronization time (test passed).
7.3 PHASE_SEQUENCE1
This setting describes the direction of the phase rotation in the System 1. Possible values are L1L2L3
and L1L3L2.
7.4 PHASE_SYSTEM1
The phase or phases from the system to use for synchronization and whether they are Wye or Delta.
Systems 1 and 2 must be configured either both as Wye or both as Delta. When testing Wye, you can
configure any combination of line-to-neutral voltages going from System 1 to System 2. Likewise when
testing Delta, you can configure any combination of line-to-line going from System 1 to System 2.
Possible values for this setting are L1N, L2N, L3N, L1L2, L2L3, L3L1, L1L3, L3L2, L2L1, L1L2L3,
L1L3L2, L12L23L31 and L13L32L21.
7.5 PHASE_SEQUENCE2
This setting describes the direction of the phase rotation in the System 2. Possible values are L1L2L3
and L1L3L2.
43
OMICRON Test Universe
7.6 PHASE_SYSTEM2
The phase or phases from the system to use for synchronization and whether they are Wye or Delta.
Systems 1 and 2 must be configured either both as Wye or both as Delta. When testing Wye, you can
configure any combination of line-to-neutral voltages going from System 1 to System 2. Likewise when
testing Delta, you can configure any combination of line-to-line going from System 1 to System 2.
Possible values for this setting are L1N, L2N, L3N, L1L2, L2L3, L3L1, L1L3, L3L2, L2L1, L1L2L3,
L1L3L2, L12L23L31 and L13L32L21.
7.7 USE_RATIO_SYS1
This setting allows for cases in which the test object is fed with voltages from two voltage transformers
having different ratios. If the setting is False, a value can be set for Vnom (secondary) of system 2 in
the VNOM_SEC_SYS2 setting. When the setting is True, both systems function as if the transformers
feeding the test object would have the same ratio Vprim/Vsec. The VNOM_SEC_SYS2 setting is then
ignored.
7.8 VNOM_SEC_SYS2
If the secondary voltage of System 2 is different from that of System 1, it is possible to enter the
System 2 voltage in this parameter.
Depending on the phase system setting made at "Connected voltage", this voltage is either the phase-
phase or the phase-neutral voltage: for L1-L2, L2-L3 and L3-L1 phase systems the system voltage to
be set is the phase-phase voltage, while for L1-E, L2-E, L3-E and L1-L2-L3 phase systems the system
voltage to be set is the phase-neutral voltage.
If the secondary voltage of system 2 is different from the one of system 1, Synchronizer operates in
relative mode and the output of system 2 is calculated accordingly.
44
XRIO Reference
7.9.1 D_VMAX
System 1 and System 2 are required to have approximately the same voltage at the moment of
synchronism and actual CB closure.
A maximum overvoltage (D_VMAX) and undervoltage (D_VMIN) can be entered for the difference in
System 1 and System 2 voltages. In addition, the over- and undervoltages can have a tolerance. The
tolerances can be entered either as an absolute value (VTOLABS) in volts or as a percentage of the
(DV) value (VTOLREL). For any given voltage, both tolerances are calculated and the larger of the two
is used.
7.9.2 D_VMIN
Maximum undervoltage. See 7.9.1 for details.
7.9.3 VTOLABS
Absolute voltage tolerance. See 7.9.1 for details.
45
OMICRON Test Universe
7.9.4 VTOLREL
Relative voltage tolerance. See 7.9.1 for details.
7.9.5 D_FMAX
System 1 and System 2 are required to have the same frequency at the moment of synchronism and
actual CB closure.
A maximum oversynchronous (D_FMAX) and subsynchronous (D_FMIN) value can be entered for the
difference in System 1 and System 2 frequencies. In addition, these frequencies can have a tolerance.
The tolerances can be entered either as an absolute value (FTOLABS) in volts or as a percentage of
the (DF) value (FTOLREL). For any given frequency, both tolerances are calculated and the larger of
the two is used.
7.9.6 D_FMIN
Maximum subsynchronous value. See 7.9.5 for details.
7.9.7 FTOLABS
Absolute frequency tolerance. See 7.9.5 for details.
7.9.8 FTOLREL
Relative frequency tolerance. See 7.9.5 for details.
7.9.9 D_PHASEANGLE
System 1 and System 2 are required to be in phase after taking into consideration any CB closure
delays and coupling transformer phase shifts.
The maximum difference in phase angle between System 1 and System 2 at the moment of
synchronism and actual CB closure can be set to +/-360 degrees.
In addition, the phase difference can have a tolerance. The tolerances can be entered as either an
absolute value in degrees (PHASEANGLE_TOLABS) or as a percentage of the value
(PHASEANGLE_TOLREL) . For any given angle, both tolerances are calculated and the larger of the
two is used.
7.9.10 PHASEANGLE_TOLABS
Absolute phase tolerance. See 7.9.9 for details.
7.9.11 PHASEANGLE_TOLREL
Relative phase tolerance. See 7.9.9 for details.
46
XRIO Reference
7.9.12 INNER_LIMIT
Generally, the synchronizing relay controls one of the systems (e.g., a generator) in order to get it to
match the reference system in terms of voltage, phase, and frequency. The control signals are V> and
V< for raising and lowering the output voltage and f> and f< for raising and lowering the output
frequency.
The Dead Zones are areas where the synchronizing relay is not allowed to output any adjustment
control commands.
The Dead Zones are defined by OUTER_LIMIT and INNER_LIMIT. The Synchronizer Test Module
verifies that the entered values are within the upper and lower limits for oversynchronous and
subsynchronous operation.
7.9.13 OUTER_LIMIT
Outer limit of the dead zone. See 7.9.12 for details.
7.9.14 MIN_SYNC_TIME
Some synchronization relays only release the CB close command if the synchronization conditions
(DV, Df, DPhi) are met for a certain time. This minimum synchronization time can be defined here. If
defined, the minimum synchronization time is considered for the calculation of the expected nominal
response of the relay.
The minimum synchronization time is entered in seconds, the tolerance for the synchronization time
(MIN_SYNC_TIME_TOL) is entered as a percentage of the time.
7.9.15 MIN_SYNC_TIME_TOL
Relative tolerance for the minimum synchronization time. See 7.9.14 for details.
47
OMICRON Test Universe
8 DIFFERENTIAL Block
This block contains the settings for Differential protection.
8.1 WINDING_COUNT
The number of windings in the protected object. Possible values for this setting are 2 and 3.
If the OBJECT_TYPE is not TRANSFORMER, this setting may only be 2.
8.2 REF_WINDING
This setting is used to select the reference winding for fault calculations. It must contain a string equal
to the name of one of the existing windings (DIFFERENTIAL.WINDING.NAME).
48
XRIO Reference
8.3 OBJECT_TYPE
The type of the protected object. Possible values for this setting are TRANSFORMER, GENERATOR,
BUSBAR and MOTOR.
8.4 ITOL_REL
Relative current tolerance, in percent.
8.5 ITOL_ABS
Absolute current tolerance, in times the nominal current.
8.6 TTOL_REL
Relative time tolerance, in percent.
8.7 TTOL_ABS
Absolute time tolerance, in seconds.
8.8 TREF
This setting is obsolete and has no effect.
8.9 TRET
Reset or delay time. This time will be kept after every Differential shot to allow the protection device to
reset.
8.10 TMAX
Maximum fault time. If a trip is not detected during this time, the software will consider that the relay
has not tripped.
8.11 IREF
Reference for the normalization of currents. The possible values for this setting are INOM_PRO
(normalize using the protected object nominal current) and INOM_CT (normalize using the nominal
T
49
OMICRON Test Universe
8.12 USECT
True if the protected object uses CT grounding transformers, False otherwise.
8.13 DELTACT
Selects whether the compensation for Delta-connected CTs is activated.
8.14 WINDING
The WINDING block contains the parameters that define an individual winding. The number of
WINDING sub-blocks in the DIFFERENTIAL block must be equal to the number set in the
DIFFERENTIAL.WINDING_COUNT setting.
Please note that the Differential modules use the transformer ratios in this block rather than those in
the DEVICE block for calculation of the currents.
8.14.1 NAME
The name of the winding.
8.14.2 INULL_ELIMINATION
Method for the elimination of I0. The following values are possible:
Value Meaning
NONE No elimination method is used
IL_I0 Line current – Zero sequence current
YD YD interposing transformer
YDY YDY interposing transformer
8.14.3 CONNECTION
The connection of the winding. Possible values are Y (Wye), D (Delta) and Z.
8.14.4 CONNECTIONNUMBER
Connection number of the winding, from 0 to 11. Please note that not all connection numbers are
compatible with all the possible CONNECTION values.
8.14.5 NOM_PD_PH
The nominal current of the protection device current transformer.
8.14.6 NOM_CT_PH
The nominal primary current of the protection device current transformer.
8.14.7 GROUNDING_CT_PH
The star point grounding of the CT. Possible values can be BUS (toward busbar) or TRANSFORMER
(toward protected object).
8.14.8 NOM_PD_N
The nominal current of the ground CT.
8.14.9 NOM_CT_N
The nominal primary current of the ground CT.
8.14.10 GROUNDING_CT_N
The star point grounding of the ground CT. Possible values can be BUS (toward busbar) or
TRANSFORMER (toward protected object).
51
OMICRON Test Universe
8.14.11 VN
The nominal voltage of the winding, in V.
8.14.12 SN
The nominal power of the winding, in VA.
8.14.13 GROUNDING_TRF
Indicates whether the star point of the CT is grounded.
8.14.14 TAP_SETTING
Divisor for the output currents of this winding.
8.14.15 DELTA_CONN_CT
If True, this setting enables compensation of Delta-connected CTs.
8.15 DIFFBIAS
The DIFFBIAS block is structured in the following way:
8.15.1 ACTIVE
This parameter is obsolete and has no effect.
52
XRIO Reference
8.15.2.1 IDIFFGG
The setting for the Idiff>> unit in times the nominal current (DEVICE.NOMINALVALUES.INOM).
8.15.2.2 TDIFFGG
Nominal trip time for the Idiff>> unit, in seconds.
8.15.2.3 IDIFFG
The setting for the Idiff> unit in times the nominal current (DEVICE.NOMINALVALUES.INOM).
8.15.2.4 TDIFFG
Nominal trip time for the Idiff> unit, in seconds.
8.15.3.1 DEFBIAS
This setting selects the formula that will be used for the calculation of Ibias. The following values are
possible:
Value Formula
IPIS_SUM_ABS Ibias = (|Ip|+|Is|)/K1
IPIS_SUM Ibias = (Ip+Is)/K1
IPIS_SUM_ABS_K2 Ibias = (|Ip|+|Is|*K2)/K1
IPIS_MAX Ibias = max(Ip,Is)
IPIS_MIN Ibias = min(Ip,Is)
IPIS_SQRT Ibias = sqrt(Ip*Is*cos(a))
53
OMICRON Test Universe
8.15.3.2 BIASDIVISOR
The K1 divisor for the Ibias calculation formulas.
8.15.3.3 TOLHARM_ABS
Absolute tolerance for the harmonic restraint function.
8.15.3.4 TOLHARM_REL
Relative tolerance for the harmonic restraint function, in percent.
8.15.3.5 CHARHARM
The BIAS block may contain any number of CHARHARM blocks. Each block describes the restraint
characteristic for a single harmonic. It is possible for the number of CHARHARM block in BIAS to be
zero. Each CHARHARM has the following structure:
8.15.3.5.1 ORDERHARM
The order of the harmonic, starting at 2.
8.15.3.5.2 DELAYHARM
This setting is obsolete and has no effect.
8.15.3.5.3 CHARTABLE
The CHARTABLE contains any number of POINT sub-blocks, with a minimum of 2. These points
define the harmonic restraint characteristic. See 8.15.4.1 for the definition of the POINT block.
8.15.4 TRIPCHAR
The TRIPCHAR block contains the operating characteristic of the differential protection. It is composed
of any number of POINT sub-blocks, with a minimum of 2. These points define the harmonic restraint
characteristic.
8.15.4.1 POINT
The POINT block is structured as follows:
ID Type Description
X Real X coordinate of the point
Y Real Y coordinate of the point
54
XRIO Reference
9 OVERCURRENT Block
The OVERCURRENT block holds the settings for the Overcurrent function. It is structured as follows:
9.1 DISPLAY_ABSOLUTE
This parameter is obsolete and has no effect.
9.2 ITOLREL
Relative current tolerance, in percent.
9.3 ITOLABS
Absolute current tolerance, in times the nominal current.
9.4 TTOLREL
Relative time tolerance, in percent.
55
OMICRON Test Universe
9.5 TTOLABS
Absolute time tolerance, in seconds.
9.6 PTCONN
This parameter controls the connection of the power (voltage) transformer. There are two possible
values: BUS (direction busbar) and LINE (direction line).
9.7 CTSTARPOINT
This parameter controls the connection of the star point of the current transformer. There are two
possible values: BUS (direction busbar) and LINE (direction line). This setting determines whether the
currents are rotated. If the CT is grounded towards the line, the currents are output as calculated by
the test module; if the CT is grounded towards the busbar (that is, towards the protected object) all
currents are rotated by 180° before being sent to the relay
9.8 DIRECTIONAL
Defines whether the Overcurrent unit under test is directional. In the case of the Overcurrent unit,
voltages will be turned on to test directional units, but no test of the directional behavior itself will be
performed.
9.9 AUTORESET
W hen True, the reset time for each shot is calculated automatically from the characteristic's
parameters. W hen False, the times set in the test module are used.
56
XRIO Reference
9.10 Groups
An Overcurrent group describes the behavior of the Overcurrent functions for one or more fault loops.
The appropriate group is selected automatically according to the fault loop set in the Overcurrent test
module. Each group is defined independently, and will be stored in the XRIO file even if it is not used
for the test.
All groups must be present in the XRIO file, whether or not they are used for the test. There are four
Overcurrent groups, as follows:
9.10.1 NAME
The NAME string identifies the group. It must be one of the following strings: LN, LL, I2 or I0. Each
group must have a specific Name depending on the XRIO ID, as seen in the table in section 9.10 .
9.10.2 RESET_RATIO
The ratio is defined as the Reset value divided by the Pickup value.
The Reset or Dropout value is the value of the current for which a unit that has tripped goes back to
the non-tripped state.
The Pickup value is the value of the current for which an inactive protection unit becomes active or
started.
57
OMICRON Test Universe
9.10.3 UNIT
The UNIT block contains the settings for an individual Overcurrent unit. The number of UNIT sub-
blocks in the GROUP block must be equal to the number of possible units, whether they are actually
used in the test or not. Currently, the number of units in a group is three (I>, I>> and I>>>). Therefore,
there will be three and only three UNIT blocks in each GROUP.
The I> unit may have any operating characteristic, the I>> and I>> may only have Definite Time
characteristics. All the data in the Group that has to do with the characteristic refers only to the I> unit.
9.10.3.1 NAME
The name of the unit. It must be one of the following: IG, IGG or IGGG.
9.10.3.2 ACTIVE
If the unit is not active, it will not be considered when the module calculates the expected behavior of
the relay.
9.10.3.3 IPICKUP
Pickup value of the unit, in times the nominal current.
9.10.3.4 TINDEX
Time index. For Definite Time characteristics, this will be the nominal operating time of the unit. For
curve characteristics, this value is a factor that, when multiplied by the trip time obtained from the
characteristic for a given operating current, will give us the nominal operating time.
For example, let's suppose that the characteristic is set to IEC Normal Inverse, TINDEX is 0.5 and the
operating current is 3 times the Ipickup of the I> unit. The IEC Normal Inverse equation will return an
operating time of 6.3019 s for that current. Therefore, the nominal trip time for the test will be
6.3019 x 0.5 = 3.1510 s.
58
XRIO Reference
9.10.3.5 CHARTYPE
This Enumeration setting defines the type of the characteristic. Different types of characteristics have
different equations. The types supported by the software are:
Type Description
PREDEFINED One of the characteristics that are predefined in the Overcurrent Test Object.
When the type is PREDEFINED, the PREDEFCHAR setting is used to specify
the exact characteristic used.
2
I2T The I t characteristic is defined by the following equation:
MP
t = A ⋅ D ⋅ ln P
M −Q
⎛ I ⎞
where M = ⎜⎜ T ⎟⎟
⎝ IS ⋅ In ⎠
t is the nominal operating time in seconds, D is the time dial (TINDEX) and A, P
and Q are user-defined parameters.
IAC This is the characteristic of the GE IAC – type relays. Its equation is:
⎡ B D E ⎤
t = Td ⋅ ⎢ A + + + 3⎥
⎣ M − C (M − C ) (M − C ) ⎦
2
⎛ I ⎞
where M = ⎜⎜ T ⎟⎟
⎝ IS ⋅ In ⎠
INVERSE Generic inverse characteristic. Its equation is based on the IEEE Standard
Equation, with two additional coefficients (K1 and K2) that offer extra flexibility:
A ⋅ D + K1
t= P
+ B⋅ D + K2
⎛ IT ⎞
⎜⎜ ⎟⎟ − Q
⎝ IS ⋅ In ⎠
where t is the nominal operating time in seconds, D is the time dial (TINDEX)
and A, B, P, Q, K1 and K2 are user-defined parameters.
59
OMICRON Test Universe
It is important to note that the value of this setting determines which type of characteristic block will be
included in the UNIT block, if any. Of the possible CHAR, CHARI2T, CHARIAC and TABLE blocks,
only one of them may be present; which one it will be is determined by the value of CHARTYPE, with
the following correspondence:
9.10.3.6 PREDEFCHAR
This setting is effective only when CHARTYPE is set to PREDEFINED. The possible values of the
setting are:
Type Description
DEFTIME Definite time characteristic.
INVERSE IEC Normal Inverse. It uses the INVERSE equation (9.10.3.5 ) with the
following values for the coefficients:
A = 0.14
P = 0.02
Q=1
B, K1 and K2 are zero
VERY_INVERSE IEC Very Inverse. It uses the INVERSE equation (9.10.3.5 ) with the
following values for the coefficients:
A = 13.5
P=1
Q=1
B, K1 and K2 are zero
EXTR_INVERSE IEC Extremely Inverse. It uses the INVERSE equation (9.10.3.5 ) with the
following values for the coefficients:
A = 80
P=2
Q=1
B, K1 and K2 are zero
60
XRIO Reference
ID Type Description
NAME String Name of the characteristic. It can be any string.
A Real Parameter A of the INVERSE equation (see Table 6)
B Real Parameter B of the INVERSE equation (see Table 6)
P Real Parameter P of the INVERSE equation (see Table 6)
Q Real Parameter Q of the INVERSE equation (see Table 6)
K1 Real Parameter K1 of the INVERSE equation (see Table 6)
K2 Real Parameter K2 of the INVERSE equation (see Table 6)
AUTORESR Real R parameter of the INVERSE auto-reset equation
AUTOREST Real T parameter of the INVERSE auto-reset equation
The A, B, P, Q, K1 and K2 parameters are fed directly into the INVERSE equation.
R ⋅ Td
tr =
1− M T
where:
61
OMICRON Test Universe
ID Type Description
NAME String Name of the characteristic. It can be any string.
A Real Parameter A of the IAC equation (see Table 6)
B Real Parameter B of the IAC equation (see Table 6)
C Real Parameter C of the IAC equation (see Table 6)
D Real Parameter D of the IAC equation (see Table 6)
E Real Parameter E of the IAC equation (see Table 6)
AUTORESR Real R parameter of the IAC auto-reset equation
AUTOREST Real T parameter of the IAC auto-reset equation
The A, B, C, D and E parameters are fed directly into the IAC equation.
R ⋅ Td
tr =
1− M T
where:
62
XRIO Reference
ID Type Description
NAME String Name of the characteristic. It can be any string.
A Real Parameter A of the I2T equation (see Table 6)
P Real Parameter P of the I2T equation (see Table 6)
Q Real Parameter Q of the I2T equation (see Table 6)
The A, P and Q parameters are fed directly into the I2T equation.
The TABLE block has a NAME parameter, which can be any string, and any number of POINT sub-
blocks. The POINT blocks define the shape of the characteristic in the current / time plane.
The POINT blocks must be in sorted by growing currents and decreasing times. This means, that each
point must have equal or greater current and equal or smaller time than the preceding POINT. The first
POINT may be anywhere in the plane. The program will perform linear interpolation between points,
so it is up to the user to provide a sufficient number of points to obtain a smooth characteristic. The
first and last segments will be prolonged to infinity.
9.10.3.10.1 POINT
The POINT block is structured as follows:
ID Type Description
X Real X coordinate of the point (current in times the pickup
value of the I> unit)
Y Real Y coordinate of the point (operating time)
63
OMICRON Test Universe
10 METER Block
The METER block describes a metering function. The device under test (meter) may be single-
function or multifunctional, may measure energy or other quantities. The structure of the METER block
is as follows:
10.1 TYPE
Defines the type of the meter. In case of single-functional meters, the metering function is predefined
and cannot be changed. Multifunctional meters may test any number of functions, to be selected in the
Test Module. The possible values for this setting are:
64
XRIO Reference
10.2 SINGLEPHASE
When True, testing of single-phase meters and single-phase testing of three-phase meters will be
enabled.
10.3 GATED_MECHANISM
When True, the Mechanism test in the Meter module will use a binary input to signal different test
stages.
10.4 THREEWIRE
Allows choosing between 3-phase 4-wire meters (False) and 3-phase 3-wire meters (True).
10.5 DIRECTION
Specifies the energy direction that the meter will measure. This setting applies only if the meter type
(TYPE) was either W_H or VAR_H. The possible values for this setting are:
Value Meter behavior
EXPORTING The meter will measure energy in the Exporting direction only
IMPORTING The meter will measure energy in the Importing direction only
BIDIRECTIONAL The meter will measure energy in either direction
Table 9: Energy directions
10.6 EXPORTDIR
Selects which direction is considered Exporting and which is Importing. The possible values for this
setting are:
Value Definition
POSITIVE Power flowing from generator to consumer is "Exporting"
NEGATIVE Power flowing from consumer to generator is "Exporting"
Table 10: Definitions of Exporting
10.7 QUADRANT
Specifies the quadrant in which the meter will measure. This setting applies only if an apparent power
meter (VA_H) was selected in TYPE. The possible values for this setting are:
Value Meter behavior
Q1 The meter will measure energy in the first quadrant only
Q2 The meter will measure energy in the second quadrant only
Q3 The meter will measure energy in the third quadrant only
Q4 The meter will measure energy in the fourth quadrant only
Q_ALL The meter will measure energy in all quadrants
65
OMICRON Test Universe
10.8 PULSE_TYPE
This setting selects which of the edges of the meter pulse will be considered the "Pulse" that the meter
module will use. If the value of the setting is RISING, the leading edge of the pulse is used; if the value
is FALLING, the trailing edge of the pulse will be used.
10.9 CERTIFIED
This string has no influence in the test, but it will appear in the report. It is possible to assign any value
to the string.
10.10 CLASS
The class of the meter. This value will be used by the module to provide a default value for the test
tolerances.
10.11 PULSES_PER_REV
Number of pulses the meter will emit during a complete revolution of the meter disk.
10.12 SETTLING
Settling time of the meter in seconds. This time should be sufficient for the meter to stabilize and
measure correctly after a change in the input magnitudes.
10.13 CONSTANT
The meter constant, in Pulses per Quantity. The meaning of Quantity depends on the metering
function; for example, for a Watt hour meter, the value of CONSTANT is in Pulses per kWh.
66
XRIO Reference
11 TRANSDUCER Block
The TRANSDUCER block holds the settings for testing Measurement Transducers. The structure of
the block is the following:
11.1 TRDCR_OUT
This setting selects the type of transducer output. Its possible values are the following:
11.2 ANGLE_REF
This setting reflects the method used to calculate the phase angle of the power system:
67
OMICRON Test Universe
11.3 ERROR_REF
Selects the reference for the full-scale error calculation. This reference may be the range from 0 to the
maximum characteristic value or the range from –max to +max; the latter is only possible if a
symmetrical characteristic was defined; else "0...+max." is set by default and cannot be changed.
Possible values for this setting are ZERO_MAX (0...+max.) and MAX_MAX (–max… +max).
11.4 SETTLING
The stabilization time of the transducer. This time must be sufficient so the transducer provides a
correct measurement after a change in the input values.
11.5 CTSTARPOINT
This parameter controls the connection of the star point of the current transformer. There are two
possible values: BUS (direction busbar) and LINE (direction line). This setting determines whether the
currents are rotated. If the CT is grounded towards the line, the currents are output as calculated by
the test module; if the CT is grounded towards the busbar (that is, towards the protected object) all
currents are rotated by 180° before being sent to the transducer.
68
XRIO Reference
11.6.1 TYPE
This setting defines the type of the transducer function. It must be one of the following:
Value Description
ACT_PWR Active Power
REACT_PWR Reactive Power
APP_PWR Apparent Power
FREQUENCY Frequency
AC_CURRENT Current
AC_VOLTAGE Voltage
PWR_FACTOR Power Factor
LF_TRDCR LF [(1-P/S)*sign Q]
VV_PHASE Phase [V-V]
VI_PHASE Phase [V-I]
II_PHASE Phase [I-I]
I_AVG_SIGNED Signed Average Current
DC_CURRENT DC Current
DC_VOLTAGE DC Voltage
DC_PWR DC Power
LL_VOLTAGE L-L Voltage
Table 14: Transducer functions
11.6.2 TOLERANCE
The relative tolerance for the test, in percent.
11.6.3 PHASES
Number of phases of the transducer. The possible values are P1 (single phase) and P3 (three phase).
69
OMICRON Test Universe
Each characteristic is defined by means of a minimum and a maximum point, plus a knee point in the
case of Compound characteristics. All these points, and in general the operating characteristic, are
defined in the first quadrant. If the SYMMETRICAL setting is True, the characteristic is mirrored into
the third quadrant.
70
XRIO Reference
11.6.4.1 TYPE
The following types of operating characteristics are possible:
71
OMICRON Test Universe
11.6.4.2 SYMMETRICAL
Check here whether your transducer's operating characteristic is symmetrical. Whether or not a
characteristic is symmetrical depends on the transducer's output range. If you are in doubt, please
refer to the transducer's operating instructions.
11.6.4.3 MIN_INP
The transducer's minimum input value. Together with MIN_OUT, this setting defines the initial point of
the characteristic.
11.6.4.4 MIN_OUT
The transducer's minimum output value. Together with MIN_INP, this setting defines the initial point of
the characteristic.
11.6.4.5 KNEE_INP
Input of the knee point of the compound characteristic.
11.6.4.6 KNEE_OUT
Output of the knee point of the compound characteristic.
11.6.4.7 MAX_INP
The transducer's maximum input value. Together with MAX_OUT, this setting defines the final point of
the characteristic.
11.6.4.8 MAX_OUT
The transducer's maximum output value. Together with MIN_OUT, this setting defines the final point of
the characteristic.
72
XRIO Reference
11.6.4.9 SAT_OUT
Value of the output after which the response of the transducer becomes flat. It must be equal or
greater than MAX_OUT.
The following example shows how these values define the characteristic:
SAT_OUT
MAX_OUT
KNEE_OUT
MIN_OUT
KNEE_INP
MIN_INP MAX_INP
73
OMICRON Test Universe
1 About XML
The XRIO format is now defined with an XML schema. However, the principle of a block, row and
value structure was kept in the transition. For an overview of the different schema definitions, please
have a look in the OMICRON\Test Universe\Apps\XRIO folder, where the schema definitions are
available as XML schema files (*.xsd).
ATTENTION: It is strongly recommended not to change any of these files in any way.
One basic change for the new format is the usage of “single value“ parameters only. The old format
allowed defining parameters (rows) with multiple values (ARCP in Distance for example). Those
parameters are all shown in extra lines and are marked with an index like for example ARCP [1] for the
first value of the parameter ARCP in the old RIO format. The second value is written in a new line and
shown as ARCP [2], and so on. The new parameters in XRIO are always in the same row. In the
previous example, ARCP [1] in RIO was replaced by REFPOINT_MAG in XRIO, ARCP [2] by
REFPOINT_ANGLE, etc.
The block structure of RIO was also changed on some places. Blocks in XRIO and in RIO are marked
in dark gray. If the RIO format does not have a corresponding sub block of the structure in XRIO, the
row is left empty.
Multipliers in XRIO are used in a much simpler way than in the old RIO format. Instead of having XOR
relations or an extensive use of optional parameters, described with a cardinality of 0..1 or 0..n, as was
the case in RIO, most of the blocks and parameters in XRIO are defined with a constant multiplier of 1.
In some cases, some rows of the RIO format are shown using the same multiplier (again, ARCP is an
example). This is used for multi-value parameters of the old RIO format. Although in XRIO any of
those parameter / value pairs are shown in an extra row, it was formerly used in one row with a unique
cardinality but with many values. This also has the advantage to mark the beginning and the end of a
previous multi-value parameter more clearly.
74
XRIO Reference
2.1 DEVICE
The DEVICE Block in XRIO has no longer a flat structure. The list of parameters is now grouped in the
sub blocks: NAMEPLATE, LOCATION, NOMINALVALUES, RESIDUALFACTORS, LIMITS, and MISC.
All new blocks have a fixed cardinality of one.
The list of parameters is extended by the new parameter OVERLOADSUPTIME. This parameter
describes the time of the overload suppression. The overload indication is suppressed by 50ms per
default.
75
OMICRON Test Universe
2.2 DISTANCE
DISTANCE required many structural changes. Most of the general DISTANCE settings of RIO were
put in a new sub block called “PROTECTEDOBJECT”. The old “DEFAULT” settings block was
completely removed, together with some of the general settings. All multi-value rows are now replaced
by additional parameter rows. Those lines are marked with yellow. For example the multi-value KL-line
of the old RIO, where the first value described the magnitude and the second described the angle, is
now replaced by the two parameters KL_MAG, and KL_ANGLE.
The new PROTECTIONDEVICE block is organized in the sub blocks TOLERANCES and ZONES.
The formally known sub block ZONE of the old RIO format is now a sub block of ZONES. Furthermore,
the ZONE sub-block structure is more detailed in XRIO. Instead of having a single SHAPE sub-block,
it is now divided in sub-blocks for TOLERANCES, GENERICSHAPES, MOSHAPE, and
LENSTOMATOSHAPE, where the last two ones were formally part of the SHAPE block of the old RIO.
The LINE and ARC parameters are no longer multi-value. They are described now with extra
parameter lines in the corresponding sub-blocks of the GENERICSHAPE block, accordingly called
LINE and ARC.
Circuit breaker time could now be set in the new CB Simulation module and the corresponding XRIO
definition, so the corresponding parameters were removed.
76
XRIO Reference
77
OMICRON Test Universe
LINE 0..n
REFPOINT_TYPE 1 POLAR
REFPOINT_R 1 0.0 Ω LINE[1] 0..1
REFPOINT_X 1 0.0 Ω LINE[2] 0..1
REFPOINT_MAG 1 0.0 Ω 0 LINEP[1]
REFPOINT_ANGLE 1 0.0 ° -360.0 360.0 LINEP[2]
0..1
ANGLE 1 0.0 ° -360.0 360.0 LINE(P)[3]
INSIDE 1 LEFT LINE(P)[4]
ARC 0..n
REFPOINT_TYPE 1 POLAR
REFPOINT_R 1 0Ω ARC[1]
0..1
REFPOINT_X 1 0Ω ARC[2]
REFPOINT_MAG 1 0Ω 0 ARCP[1]
REFPOINT_ANGLE 1 75.0 ° -360.0 360.0 ARCP[2]
RADIUS 1 0.0 Ω 0 ARC(P)[3]
STARTANGLE 1 260.0 ° -360.0 360.0 ARC(P)[4] 0..1
ENDANGLE 1 300.0 ° -360.0 360.0 ARC(P)[5]
DIR 1 CCW ARC(P)[6]
INSIDE 1 LEFT ARC(P)[7]
MHOSHAPE 0..1 MHOSHAPE 0..1
ANGLE 1 75.0 ° -360.0 360.0 ANGLE 1
REACH 1 1.0 Ω REACH 1
OFFSET 1 0.0 Ω OFFSET 1
INVERT 1 false INVERT 0..1
LENSTOMATOSHAPE 0..1 LENSTOMATOSHAPE 0..1
ANGLE 1 75.0 ° -360.0 360.0 ANGLE 1
REACH 1 1.0 Ω REACH 1
OFFSET 1 0.0 Ω OFFSET 1
INVERT 1 false INVERT 0..1
SHAPE_MODE 1 WIDTH
WIDTH 0..1 0.8 Ω WIDTH 0..1
RATIO_AB 0..1 0.8 AB 0..1
78
XRIO Reference
DEFAULTS 0..1
TESTMODE 0..1
ITEST 0..1
VTEST 0..1
TPREFAULT 0..1
TMAXFAULT 0..1
TPOSTFAULT 0..1
FAULTINCMODE 0..1
FAULTINCANGLE 0..1
DCOFFSET 0..1
TREF 0..1
ALLOWRED 0..1
KS[1]
0..1
KS[2]
KSISKL 0..1
ZS[1]
0..1
ZS[2]
79
OMICRON Test Universe
2.3 CBCONFIGURATION
This completely new XRIO definition describes test object settings for the new CB Configuration
module that was introduced in TU 2.0. Therefore, there is no existing RIO definition to change.
XRIO 2.0
Mult. Default Min Max
CBCONFIGURATION 0..n
TRIPTIME 1 50 ms 20 ms 500 ms
CLOSETIME 1 100 ms 20 ms 1000 ms
P52AB 1 20.0 % 0.0 % 45.0 %
80
XRIO Reference
2.4 VISTARTING
As in the other RIO test object definitions, the ACTIVE parameter was removed. Furthermore, some
syntactical changes were done to avoid XML language character conflicts. So, any ‘ > ‘ character was
replaced by a ‘ G ‘.
81
OMICRON Test Universe
2.5 SYNCHRONIZER
Only a few changes were done in SYNCHRONIZER. The ACTIVE parameter and the TCBCLOSE
parameter were removed.
82
XRIO Reference
2.6 DIFFERENTIAL
In DIFFERENTIAL, the ACTIVE parameter was removed (as in all other object types). Furthermore,
the LINEDIFF sub block was completely removed. This block was introduced in the past as a possible
extension of the differential functionality. However, this functionality was never implemented and
therefore this block was never needed. The tolerance settings (ITOL, TTOL, and TOLHARM) moved
from multi- to single-value parameters.
Significant changes were done for the definitions of the characteristics CHARHARM and TRIPCHAR.
They are not described any more with multi value lines START, LINE, and STOP, where START and
STOP has to be defined once. Instead, these characteristics are defined in extra sub blocks called
POINT, which consist of the two coordinate parameters X and Y. Every sub block of the “POINT” type
that describes the characteristic coordinates has to be included twice as a minimum. This reflects the
necessity of the START and STOP parameters in the old RIO format.
One small syntactical change was done for the DIFF parameter group (IDFF>, etc.). Due to the fact
that the ‘ > ‘ and ‘ < ‘ characters form part of the XML language definition, those characters were
replaced by G and GG respectively.
TAP_SETTING and DELTA_CN_CT are completely new parameters for new features in TU 2.0, which
supports delta connected CTs.
The CONVREALY setting was removed; its functionality is now invoked automatically, depending on
the type of the protected object.
83
OMICRON Test Universe
84
XRIO Reference
CHARTABLE 1
POINT 2..n
START [1]
1
START [2]
X 1 0.0 Ixf/Idiff[%] 0.0 LINE [1]
0..n
Y 1 0.0 Idiff/Inom 0.0 LINE [2]
STOP [1]
1
STOP [2]
TRIPCHAR 0..1 TRIPCHAR 0..1
POINT 2..n
START [1]
1
START [2]
X 1 0.0 IBias/In 0.0 LINE [1]
0..n
Y 1 0.0 Idiff/In 0.0 LINE [2]
STOP [1]
1
STOP [2]
LINEDIFF 0..1
ACTIVE 0..1
METHOD 0..1
I-PICKUP 0..1
D-PHI 0..1
TRIP> 0..1
85
OMICRON Test Universe
2.7 OVERCURRENT
Significant changes in OVERCURRENT were done in the characteristic description. All multi-value
parameters (CHAR and CHARI2T, POINT) were replaced by sub blocks where all parameter values
are listed explicitly in single value parameters. The tolerance settings in the upper level were replaced
by single value parameters too, but without an extra sub block. As usual, the ACTIVE line was
completely removed.
86
XRIO Reference
CHARIAC 0..1
NAME 1 "Name"
A 1 0.20780 s
B 1 0.86300 s
C 1 0.80000
D 1 -0.41800 s
E 1 0.19470 s
AUTORESR 1 1.0
AUTOREST 1 2.0
CHARI2T 0..1
NAME 1 "Name" CHARI2T [1]
A 1 100.0 CHARI2T [2]
0..1
P 1 2.0 CHARI2T [3]
Q 1 1.0 CHARI2T [4]
TABLE 0..1 TABLE 0..1
NAME 1 "Name" NAME 1
POINT 1..n
X 1 2.0 IPickup 0 POINT [1]
0..1
Y 1 20.0 s 0 POINT [2]
87
OMICRON Test Universe
2.8 METER
The ACTIVE parameter of RIO was removed. V_PRIM, V_SEC, I_PRIM, I_SEC were removed too.
They are handled now in the DEVICE block.
Some parameters for the METER block were added in XRIO. They came along with new features
available in TU 2.0. The first three parameters are Boolean and the forth parameter called
EXPORTDIR is an enumeration with the possible settings POSITIVE or NEGATIVE.
88
XRIO Reference
2.9 TRANSDUCER
89