DIGITAL MULTIMETER

EPM-04 / EPM-05 / EPM-06


GENERAL: Current Transformer Ratio Setup:
EPM-0X Series Multimeters are designed for measuring electrical parameters ( for EPM-04 / EPM-05 / EPM-06)
in 3-phase networks : Set Press the Set key for 3 sec.to select CT ratios.

3-phase A V Hz Max.Demand Max/Min cosj


Voltages
EPM-04 • • Set Press Set again and enter the CT Ratio setup 500
EPM-05 • • • • menu
EPM-06 • • • • • •
Press UP / DOWN keys to select required CT 300
ratio.
EPM-04 Digital Multimeter; Maximum Demand, Maximum and Minimum
Voltages Set
EPM-04 is a multimeter which measures : Press the Set key to save the required CT ratio. 300
- 3 phase currents (IL1, IL2, IL3) ,
- AC RMS values of 6 different line voltages If you don’t touch any key for about 3 sec.
(VL1-N, VL2-N, VL3-N, VL1-L2, VL2-L3, VL3-L1), Measurement 12.3
Mode the device returns automatically to the
- Maximum demand values in adjustable periods, measurement mode.
- Maximum and minimum voltages Voltage Transformer (Utr) Ratio Setup:
EPM-05 Digital Multimeter with Frequency; Maximum Demand, ( for EPM-04 / EPM-05 / EPM-06)
Maximum and Minimum Voltages
EPM-05 is a multimeter which measures : Set Press the Set key for 3 sec.to select Utr ratios.
- 3 phase currents (IL1, IL2, IL3) ,
- AC RMS values of 6 different line voltages
(VL1-N, VL2-N, VL3-N, VL1-L2, VL2-L3, VL3-L1), Fint VT by UP/DOWN keys. Press Set again and 001
Set enter the Utr Ratio setup menu
- Frequency
- Maximum demand values in adjustable periods,
- Maximum and minimum voltages
Press UP/DOWN keys to select required Utr 010
EPM-06 Digital Multimeter with Frequency, Cosj, Maximum Demand, ratios.
Maximum and Minimum Voltages :
EPM-06 is a multimeter that measures : Set
- 3 phase currents (IL1, IL2, IL3), Press the Set key to save the required Utr ratios. 010
- AC RMS voltage values
- (VL1-N, VL2-N, VL3-N, VL1-L2, VL2-L3, VL3-L1),
- Frequency, Measurement If you don’t touch any key for about 3 sec. the device
Mode returns automatically to the measurement mode.
- Cosj of each phase and the average of 3 phases, 12.3
- Maximum demand values in adjustable periods,
- Maximum and minimum voltages Displaying the Phase-Neutral and Phase-Phase voltages:
EPM -06 has 5 displays 3 displays for currents, 1display for voltages, for (for EPM-04 / EPM-05 / EPM-06) L1
cosj and frequency. This screen displays as default, the measured value ~V 220 L2
L3
of VL1-N LED L1 lights
FUNCTIONS: You may scroll through the phase and phase to neutral L1

voltage values by pressing this key ~V 382 L2


L3

1- Frequency-meter function
(for EPM-05 / EPM-06) Demand Time Setup:
Frequency value is measured in case L1 phase voltage value is higher (for EPM-04 / EPM-05 / EPM-06)
than 50 V. Set Press Set key for 3 sec to start demand time setup.
2- Maximum Demand Function
EPM-04, EPM-05 and EPM-06 monitor demand and maximum demand Press DOWN key multiple times until arriving to the
values. Demand value is defined as the moving average RMS value demand time (dt)
measured in demand time. Set
Maximum Demand value is the maximum value of the average RMS values Press Set key to enter demand time Setup.Preset
recorded during demand time. EPM-04, EPM-05 and EPM-06 record this
maximum value in memory and keep continuously measuring maximum
value will be displayed. 25
demand as defined, comparing it with the last recorded value. If it is bigger Set the required demand time by UP/DOWN keys.
than the last recorded value, it replaces last one in memory. Demand value Set 30
stored is in each 2 minutes. Press Set key to save the required demand time.
Measurement If you don’t touch any key for about 3 sec. the
3- Cosj function Mode device returns automatically to the measurement
As a cosj meter, the EPM-06 measures seperately the cosj value of the mode.
each phase and the average cosj value. Displaying the Maximum and Minimum Voltages:
These values are displayed by scrolling UP and DOWN keys. However to (for EPM-04 / EPM-05 / EPM-06)
display the related average cosj value, VL1-L2 or VL2-L3 must be selected. Press phase select key until you see the phase which L1
you want to know the maximum and minimum. ~V 380 L2
L3

4- Maximum & Minimum Voltages Function


For Maximum and Minimum Voltages Function; EPM-04, EPM-05 and EPM- Press UP key continuously to display the maximum L1

06 stores, the maximum and minimum phase-neutral and phase-phase value of this voltage ~V 414 L2
L3

voltages except 0V , in memory.


When you release the UP key, the screen returns to L1

In all the serie devices: the real time voltage of the selected lines. ~V 380 L2
L3

• Flush mounting form suitable for panel installations.


• Connections are made through terminals. Press DOWN key continuously to display the L1
• Power supply is provided by auxiliary wiring, with a phase-neutral minimum value of this voltage. ~V 352 L2
L3

connection with fuse protection.


When you release the DOWN key, the screen returns
automatically to the measurement mode, to display L1

the real time voltage of the selected lines. ~V 380 L2


L3
DIGITAL MULTIMETER
EPM-04 / EPM-05 / EPM-06
To Reset the Maximum and Minimum Voltage and Maximum Demand Connecting Diagram
Values of the Measured Voltages:
K L
L1
k l K L
L2

(for EPM-04 / EPM-05 / EPM-06)


k l K L
L3
k l
N

Press UP and DOWN keys simultaneously.


EPM-05 and EPM-06 resets the maximum -minimum ~A 000 ok 1 2 3 4 5 6

voltages and maximum demand values. Then device IL1 IL2 IL3

returns to the measurement mode within 3 seconds ~A 000


ok Current Measurement

EPM-04/05/06 TYPE PR 19
automatically. Digital Multimeter
Voltage Measurement Auxiliary Supply

To Display the Frequency: (for EPM-05 / EPM-06) L1 L2 L3 N

7 8 9 10 11 12

Press the Phase Select key multiple times until arriving ~V 379 L1
L2
L3
to the voltage, e.g. VL3-L1 -0.98 Cosj
1A
L
Hz
N
L1

At the voltage VL3-L1, the lowest display reverts to ~V 382 L1


L2
L2

show the frequency of L3-L1 phase-phase voltage and L3 L3

50.0 Cosj N

Hz indicator lights.
Hz

To Display Demands: EPM-04/05/06


Digital Multimeter
TYPE PK 26
(for EPM-04 / EPM-05 / EPM-06) Auxiliary
Supply Voltage Measuring Input
Un
Current Measuring Input
IL1 IL2 IL3
~
Press UP key to display maximum demands of each
L1 L2 L3 N

phase on the top 3 displays titled ~A. Press DOWN ~A 14.1 ok L1


1A
k
K
l
L

key to display demand values.


k l
L2

~A 21.4
K L
ok L3 k l

Note: When the key is released, the current displays


K L
N

23.5
revert to display the actual currents of the lines. ~A
ok 3 Phase neutral

To Display the Cosj:


EPM-04/05/06
L1 Using the phase select key, when voltage is at L1, the Digital Multimeter
~V 220 L2
L3 cosj LED lights and the cosj of VL1-N is displayed -0.98
Cosj
Hz

TYPE PR 16

L1 Using the phase select key, when voltage is at L2, the


~V 221 L2
L3 cosj LED lights and the cosj of VL2-N is displayed -0.98
Cosj
Hz Voltage Current Auxiliary
Measuring Input Measuring Input Supply
L1 L2 L3 N IL1 IL2 IL3 Un

~V 219
L1 -0.98 Cosj 1 2 3 4 5 6 7 8 9 10 13 14
L2
L3 Using the phase select key, when voltage is at L3, the Hz
k l
1A

cosj LED lights and the cosj of VL3-N is displayed -0.86


L1
L1 K L
Cosj
~V 380
k l
L2
L2 Hz K L
L3 k l
L3
K L
N
L1 Using the phase select key, when voltage is at L1-L2, -0.85 3 Phase neutral
~V 379 L2 Cosj
L3 cosj LED lights and the average cosj is displayed Hz Phase
Indicator Led
Display

~V 382
L1
L2 Using the phase select key, when voltage is at L2-L3, 50.0 Cosj
L1 L2 L3 Kilo Leds L1 L2 L3

L3
cosj LED lights and the average cosj is displayed Hz
K ~A kA kA kA

Display Clear

PRECAUTIONS FOR INSTALLATION AND SAFE USE ~A Down


K
Up Button Voltage Back
Kilo Leds
Display
Failure to follow those instructions will result in death or serious injury.
kV
EPM-06
K ~A Clear
Down Button DIGITAL MULTIMETRE
True RMS
Set
Cosj Hz

* Disconnect all power before working on equipment.


L1 L2 L3

L1
Voltage L2
Display Phase Sellect & Phase Frequency& Cosj & Up Phase Sellect &
* When the device is connected to the network, do not remove the front
K
L3
Set Button Indicator Led Cosj Display Hz Led Set Button
Frequency&
panel.
Cos
Cosj Display Hz

* Do not try to clean the device with solvent or the like. Only clean the
device with a dry cloth. Cosj &
Hz Led

* Verify correct terminal connections when wiring. Note: Phase leds light in case, voltage value is higher than 30 V.
* Electrical equipment should be serviced only by your competent seller. Technical data
No responsibility is assured by the manufacturer or any of its subsidiaries Operating Voltage (Un),*
for any consequences arising out of the use of this material. Operating Range (DU) : Please look at labels on the device.
* Only for rack panel mounting. Operating Frequency (f) : 50/60 Hz
* Warning: Accuracy :1%±1digit
a) A switch or circuit breaker must be connected between the network Measuring ranges
and the auxiliary supply input of device. Ammeter : 0,05-5,5A ~
b) Connected switch or circuit breaker must be in close proximity to the Voltmeter :10-300VAC (Phase-Neutral)
device. 10 - 5 0 0 V A C (Phase-Phase)
c) Connected switch or circuit breaker must be marked as the disconnecting For 115VAC :10-170VAC (Phase-Neutral)
device for the equipment. :10-300VAC (Phase-Phase)
d) The type of the used fuse must be FF type and the current of the used Frequencymeter : 45-65Hz
fuse must be 1A. Current Transformer Ratio : 5 ... 10000/5A
e) No need of a vantilator in the installation area Voltage Transformer Ratio : 1 ... 2000
f) Phase leds light at minimum 30V. Measuring Category : CAT III
g) Do not use with generator
Installation / Overvotage Category : II
Wall 18 Pollution Degree :2
The area Measurements Wall
on The Control Panel
79.3mm Power Consumption (Pcons) : <4 VA
70mm Burden (Each Circuit) : <1 VA
Demand Time (Average) : 15 min
140mm

Equipment Protection : Double Insulation ( )


90mm
92mm

Box Protection Class : IP 40


34.5 Terminal Block Protection Class : IP 00
92mm 140mm 58mm Enclosure : Non-flammable
Type PR 19 (96x96)
50mm
50mm
Type PR 16
Operating Temperature Range : - 5°C ; +50°C
10.8 30.1 7.6 9.5
Storage Temperature Range : - 25°C ; +70°C
Dimensions
18
Wire Thickness : 2.5mm2
79.3mm
70mm
60.6
Dimensions : PR19, PR16, PK-26
Installation : Panel Mounted (PR-19, PR-16)
Rail Mounted (PK-26)
143

45.0
99
96mm

90.0

Weight : 0,3kg (PR-19)


90mm

0.45 kg (PK-26)
14.0

8.5

121
34.5 106.0

0.8 kg (PR-16)
138.4
96mm 143 58mm 10.0
Type PK 26
Type PR 19 (96x96) 26.5 21.5
Type PR 16 53.0
58.0
* Please check the device label for proper value.
*Different supply voltages are adjustable upon request.
A2859-Rev.4