1)Please fill the figure in the yellow column Point /10

CT1
2,600L/min
Hint: Q(L/min) = kw x 860 / ⊿T x 60
37/32℃
CT1
4m

AHU3
AHU3 573 L/min
200kw
CWP1
1,300L/mi 573L/m 1147L/m

AHU2
AHU2 1147 L/min
400kw
1720L/m 287L/m
1300L/m
AHU1 AHU1
287 L/min
100kw

EXT
Close
2007L/m 0

R
CH1

Pipe Q'ty for condenser water system Pipe Q'ty for chilled water system red line is the farthest line
CH1 CP1
Straight pipe 200RT 2,000L/mi Straight pipe
150A 40m 7/12℃ n 150A 80m
Fitting 125A 80m
Elbow 150A 20 nos 80A 80m
Valves Fitting
BTV 150A 6 nos Elbow 150A 20 nos
CV 150A 1 no 125A 10 nos
Y st 150A 1 no 80A 10 nos
Flex 150A 6 nos Tee(Straight side)
150 ⇒125 2 nos 150 ⇒150 2 nos
125 ⇒80 2 nos
Valves
BTV 150A 4 nos
80A 2 nos
CV 150A 1 no
Y st 150A 1 no
80A 1 no
Flex 150A 4 nos