Professional Documents
Culture Documents
GBU200 (6F2S1926) 0.10 - Part6 PDF
GBU200 (6F2S1926) 0.10 - Part6 PDF
10)
Eight modules being ordered; eight slots being occupied in IED case
Number of circuits on a module Selection of modules
Binary input circuits (BI) Binary output circuits (BO)
Independent type & variable thresholds
Ordering No.†1
Common circuit type
Hybrid type
- - 160 - 18 36 - 83 5xBI3A+3xBO1A
- 60 - - 6 12 32 87 5xBI2A+1xBO1A+2xBO2A
8 - 128 6 18 38 - 88 4xBI3A+3xBO1A+1xBIO3A
- - 256 - - - - 8C 8xBI3A
7 - 224 - 6 4 - 8G 7xBI3A+1xBIO1A
- - 192 - 12 24 - 8H 6xBI3A+2xBO1A
7 - 192 - 12 16 - 8J 6xBI3A+1xBO1A+1xBIO1A
7 - 96 - 30 52 - 8M 3xBI3A+4xBO1A+1xBIO1A
Note
†1 Ordering No. will be set at A & B positions in ‘Hardware selection’. The Ordering No. herein is only
chosen when the IED is 1/1 case size.
---: Not available
7 8 9 A B C D E F G H J K L
Configurations G I O 2 0 0 - 0 1 - U - 0 0 - 0 0 - 3 0 - 0 00
DC Rating
110-250 Vdc2 1
Outline
1/2 case x 19-inch, flush mounting U
1/2 case x 19-inch, rack mounting V
1/1 case x 19-inch, flush/rack mounting W
Ordering No.‡1
Fast operating type
Selection of modules
Hybrid type
DCAO
DCAI
and
modules implementation order from the left side
- - 32 10 - - - - - 2D 1xBI3A+1xDCAI2A
- - - 30 - - - - - 3R 3xDCAI2A
- - 64 - - 18 36 - - 5J 2xBI3A+3xBO1A
- - - - - 30 60 - - 5L 5xBO1A
- - 64 30 - - - - - 5M 2xBI3A+3xDCAI2A
- - 96 20 - - - - - 5N 3xBI3A+2xDCAI2A
- - 128 30 - - - - - 7K 4xBI3A+3xDCAI2A
Note
†1 Ordering No. will be set at A & B positions in ‘Hardware selection’.
---: Not available
7 S G T E F U 9 V
Configurations G I O 2 0 0 - 0 0 0 0 - 0 0 0 - 0
Outline
Assignment at position “9” (U,V, or W)
[Label sheet]
Accessory names Quantity per order Codes
Pocket sheet label for LEDs(White) 10 EP-211-00
Pocket sheet label for function keys(White) 10 EP-212-00
[Rating jumpers]
Accessory names Quantity per order Codes
Jumpers to change rated current 20 EP-221
[Monitoring plugs]
Accessory names Quantity per order Codes
Plugs for monitoring jacks on the front 4 EP-222
[Engineering tools]
Accessory names Quantity per order Codes
GR-TIEMS 1 license EP-251
PLC-EDITOR 1 license EP-261
[Cable]
Accessory names Quantity per order Codes
GIO200 connection cable (3m) 1 set EP-231-300
GIO200 connection cable (2m) 1 set EP-231-200
GIO200 connection cable (1m) 1 set EP-231-100
GIO200 connection cable (0.5m) 1 set EP-231-050†
†The cable is supplied with a GIO200 as a standard accessory.
Technical data
Analog Inputs
Rated current In 1A or 5A (selectable)
Rated voltage Vn 100V to 120V
Rated Frequency Either 50Hz or 60Hz (specified when the ordering)
Overload Rating
Current inputs 4 times rated current continuous
5 times rated current for 3 minutes
6 times rated current for 2 minutes
30 times rated current for 10 seconds
100 times rated current for 1 second
250 times rated current for one power cycle (20 or 16.6ms)
Voltage inputs 2 times rated voltage continuous
2.5 times rated voltage for 1 second
Burden
Phase current inputs 0.1VA at In = 1A, 0.2VA at In = 5A
Earth current inputs 0.3VA at In = 1A, 0.4VA at In = 5A
Sensitive earth fault inputs 0.3VA at In = 1A, 0.4VA at In = 5A
Voltage inputs 0.1VA at Vn
Power Supply
Rated auxiliary voltage 24/48/60Vdc (Operative range: 19.2~ 72Vdc),
48/110Vdc (Operative range: 38.4 ~ 132Vdc),
110/250Vdc (Operative range: 88 ~ 300Vdc)
Superimposed AC ripple on DC supply 15%
Supply interruption 20ms at 110Vdc
Restart time < 5ms
Power consumption 15W (quiescent)
25W (maximum)
Binary Inputs
Input circuit DC voltage 24/48/60Vdc (Operating range: 19.2 – 72Vdc),
48/110Vdc (Operative range: 38.4 – 132Vdc),
110/125/220/250Vdc (Operating range: 88 – 300Vdc)
Note: Pick-up setting is available in BI2 and BIO4 (Setting
range: 18V to 222V)
Capacitive discharge immunity 10μF charged to maximum supply voltage and discharged
into the input terminals, according to ENA TS 48-4 with an
external resistor
Maximum permitted voltage 72Vdc for 24/48/60Vdc rating,
300Vdc for 110/250Vdc rating
Power consumption 0.5W per input at 220Vdc
Binary Outputs
Fast operating contacts
Make and carry 5A continuously
30A, 290Vdc for 0.2s (L/R=5ms)
Break 0.15A, 290Vdc (L/R=40ms)
Operating time Typically 3 ms
Semi-fast operating contacts
Make and carry 8A continuously
30A, 240Vdc for 1s (L/R=5ms)
Break 0.1A at 250Vdc (L/R=40ms)
0.2A at 125Vdc (L/R=40ms)
Operating time Typically 6 ms
Auxiliary contacts
Make and carry 8A continuously
30A, 240Vdc for 1s (L/R=5ms)
Break 0.1A at 250Vdc (L/R=40ms)
0.2A at 125Vdc (L/R=40ms)
Operating time Typically 8 ms
Hybrid contacts (10 A breaking)
Make and carry 8A continuously
10A, 220Vdc for 0.5s (L/R=5ms)
Break 10A, 220Vdc (L/R=20ms)
10A, 110Vdc (L/R=40ms)
Operating time 1 ms
Durability ≥ 10,000 operations (loaded contact)
≥ 100,000 operations (unloaded contact)
Mechanical Design
Installation Flush mounting
Weight Approx. 10kg (1/3 size), 12kg (1/2 size), 15kg (3/4 size), 25kg
(1/1 size)
Case color 2.5Y7.5/1 (approximation to Munsell value)
LED
Number 26 (Fixed for “In service” and “ERROR”)
Color Red / Yellow / Green (configurable) except In service (green)
and Error (red)
Function keys
Number 7
Local Interface
USB Type B
Maximum cable length 2 meters (less than)
Terminal Block
CT/VT input M3.5 Ring terminal (ring lug type terminal only)
Binary input, Binary output M3.5 Ring terminal with 15mm stripping length (for
compression plug type terminal)
1000BASE-LX
Connector type LC duplex connector
Wave length 1310nm fibre
Environmental performance
Atmospheric Environment
Temperature IEC 60068-2-1/2 Operating range:–25C to +55C.
IEC 60068-2-14 Storage / Transit:–25C to +70C.
Cyclic temperature test as per IEC
60068-2-14
Humidity IEC 60068-2-30 56 days at 40C and 93% relative humidity.
IEC 60068-2-78 Cyclic temperature with humidity test as per
IEC 60068-2-30
Enclosure Protection IEC 60529 IP52 - Dust and Dripping Water Proof
IP20 for rear panel
Mechanical Environment
Vibration IEC 60255-21-1 Response - Class 1
Endurance - Class 1
Shock and Bump IEC 60255-21-2 Shock Response Class 1
Shock Withstand Class 1
Bump Class 1
Seismic IEC 60255-21-3 Class 1
Electrical Environment
Dielectric Withstand IEC 60255-27 2kVrms for 1 minute between all terminals
and earth.
2kVrms for 1 minute between independent
circuits.
1kVrms for 1 minute across normally open
contacts.
High Voltage Impulse IEC 60255-27 Three positive and three negative impulses of
IEEE C37.90 5kV(peak), 1.2/50s, 0.5J between all
terminals and between all terminals and
earth.
Voltage Dips, IEC 60255-11, 1. Voltage dips:
Interruptions, IEC 61000-4-29, 0 % residual voltage for 20 ms
Variations and Ripple IEC 61000-4-17 40 % residual voltage for 200 ms
on DC supply IEC 60255-26 Ed 3 70 % residual voltage for 500 ms
2. Voltage interruptions:
0 % residual voltage for 5 s
3. Ripple:
15 % of rated d.c. value, 100 / 120 Hz
4. Gradual shut-down / start-up:
60 s shut-down ramp, 5 min power off, 60s
start-up ramp
5. Reversal of d.c. power supply polarity:
1 min
Capacitive Discharge ENA TS 48-4 10μF charged to maximum supply voltage
and discharged into the input terminals with
an external resistance
Environmental performance
Electromagnetic Environment
High Frequency IEC 60255-22-1 Class 3, 1 MHz burst in common / differential modes
Disturbance / IEC 61000-4-18 Auxiliary supply and I/O ports: 2.5 kV / 1 kV
Damped Oscillatory IEC 60255-26 Ed 3 Communications ports: 1 kV / 0 kV
Wave
Electrostatic IEC 60255-22-2 Class 4, Contact: 2, 4, 6, 8kV
Discharge IEC 61000-4-2 Air: 2, 4, 8, 15kV
IEEE C37.90.3-2001
IEC 60255-26 Ed 3
Radiated RF IEC 60255-22-3, Sweep test ranges: 80 MHz to 1 GHz and 1.4
Electromagnetic GHz to 2.7 GHz.
Disturbance IEC 61000-4-3 Level 3 Spot tests at 80, 160, 380, 450, 900, 1850 and
IEC 60255-26 Ed 3 2150 MHz.
Field strength: 10 V/m
IEEE C37.90.2-1995 Field strength 35V/m for frequency sweep of
25MHz to 1GHz.
Fast Transient IEC 60255-22-4 5 kHz, 5/50ns disturbance
Disturbance IEC 61000-4-4 Auxiliary supply and input / output ports: 4 kV
IEC 60255-26 Ed 3 Communications ports: 2 kV
Surge Immunity IEC 60255-22-5 1.2/50µms surge in common/differential modes:
IEC 61000-4-5 Auxiliary supply and input / output ports: 4, 2,
IEC 60255-26 Ed 3 1, 0.5 kV / 1, 0.5 kV
Communications ports: up to 1, 0.5 kV / 0 kV
Surge Withstand IEEE C37.90.1-2002 3kV, 1MHZ damped oscillatory wave
4kV, 5/50ns fast transient
Conducted RF IEC 60255-22-6 Sweep test range: 150 kHz to 80MHz
Electromagnetic IEC 61000-4-6 Spot tests at 27 and 68 MHz.
Disturbance IEC 60255-26 Ed 3 Voltage level: 10 V r.m.s
Power Frequency IEC 60255-22-7 50/60 Hz disturbance for 10 s in common /
Disturbance IEC 61000-4-16 differential modes†
IEC 60255-26 Ed 3 Binary input ports: 300 V / 150 V
Power Frequency IEC 61000-4-8 Class 4 Field applied at 50/60Hz with strengths of:
Magnetic Field IEC 60255-26 Ed 3 30A/m continuously,
300A/m for 1 second.
Conducted and IEC 60255-25 Conducted emissions:
Radiated Emissions EN 55022 Class A, 0.15 to 0.50MHz: <79dB (peak) or <66dB
EN 61000-6-4 (mean)
IEC 60255-26 Ed 3 0.50 to 30MHz: <73dB (peak) or <60dB (mean)
Radiated emissions
30 to 230 MHz: < 40 dB(uV/m)
230 to 1000 MHz: < 47 dB(uV/m)
Measured at a distance of 10 m
†For differential mode, ‘CMP_NUM’ setting utilized.
Overvoltage Protection
Overvoltage (OV) thresholds: 1.0 – 220.0V in 0.1V steps
OV delay type: DTL, IDMTL
OV IDMTL Time Multiplier Setting TMS: 0.010 – 100.000 in 0.001 steps
OV DTL delay: 0.00 300.00s in 0.01s steps
DO/PU ratio: 10 100% in 1% steps
1st OV Reset Delay: 0.0 – 300.0s in 0.1s steps
Undervoltage Protection
Undervoltage (UV) thresholds: 5.0 – 130.0V in 0.1V steps
UV delay type: DTL, IDMTL
UV IDMTL Time Multiplier Setting TMS: 0.010 – 100.000 in 0.001 steps
UV DTL delay: 0.00 – 300.00s in 0.01s steps
UV Reset Delay: 0.0 – 300.0s in 0.1s steps
Under/Over Frequency Protection
Under/Over frequency threshold: -10.00 – +10.00Hz in 0.01Hz steps
DTL delay: 0.00 – 300.00s in 0.01s steps
Undervoltage block: 40.0 – 100.0V in 0.1V steps
Voltage Restraint Protection (51V)
Voltage threshold 10.0 to 120.0V in 0.1V steps
Sensitivity range 20 to 100% of voltage threshold
Thermal Overload Protection
I = k.IFLC (Thermal setting): 0.40 – 2.00A in 0.01A steps (1A rating)
2.00 – 10.00A in 0.01A steps (5A rating)
Time constant (): 0.5 - 500.0 mins in 0.1min steps
Thermal alarm: 50 - 100% in 1% steps
Accuracy
IDMTL Overcurrent Pick-up: Setting value 2%
All Other Overcurrent Pick-ups: Setting value 5%
Overcurrent PU/DO ratio: 95%
Undercurrent Pick-up: Setting value 2%
Undercurrent PU/DO ratio: 105%
IDMTL Overvoltage Pick-up: Setting value 2%
All Other Overvoltage Pick-ups: Setting value 5%
Inverse Time Delays: 5% or 30ms (1.5 to 30 times setting)
Definite Time Delays: 1% (for more than 50ms setting) or 10ms
Transient Overreach for instant. elements: 5% for X/R = 100.
Metering Function
AC current Accuracy 0.5% (at rating)
DC current Accuracy 0.5% (within the range)
AC voltage Accuracy 0.5% (at rating)
Power (P, Q) Accuracy 1.0% (at rating when power quantities being fed)
Energy (Wh, varh) Accuracy 1.0% (at rating)
Frequency Accuracy 0.03%
GPS Time Synchronisation
Protocol SNTP
Cabling
The table below shows the recommended cables in the cross-section and rated-voltage for the
connection with the transformer module (VCT), the binary IO module (BI, BO, and BIO), and
the power supply module (PWS). Rated-voltage required for the cable is 600Vac.
Table Cables for the connection with module
Origin of Required cable-cross-section
Required end-terminal
connection (AWG)
For Ring-lug type:
M3.5 ring-tongue terminal with insulation
BI, BO, BIO 1.5 mm squired or larger
and PWS (Either AWG14 or 15)
For Compression-plug type:
Not applicable
2.5 mm squired or larger
VCT M3.5 ring tongue terminal with insulation
(AWG13)
Protective 5.5 mm squired or larger
M5 ring tongue terminal with insulation
earth (AWG9)
Fuses
The table below shows the required fuse in the PWS. DO NOT change the fuse by the user.
The fuse is complies with IEC60127-2 Sheet 5.
Table Fuse specification in PWS
Specification Description
Rated current 3.15A
Rated voltage 500Vac & 400Vdc
Cutoff velocity Type “T”
Manufacture Littelfuse, Inc.
Type 04773.15XP
An interface unit (IFU†) is designed to convert the information of binary input and output
signals to the information in the IEC 61850 transmission. The IFU consists of binary IO
modules, communication modules and power supplies in a 1/3 case in 19 inch with control and
monitoring applications.
† For ordering, “GBU200-01-122-00-46-30-000; GBU200-0039-462-1E” is defined.
1. Hardware
The code “GBU200-01-122-00-46-30-000” defines the IFU hardware. The code also decides
the components: a 1/3 case in 19 inch case, a BI3A module, a BIO1A module, two
100Base-FX modules, and a power supply module. Respective specifications are shown in
chapter Technical description. The IFU layout is shown in Appendix: Typical External
connection.
3. Communication software
The communication software for LAN and the IEC 61850 (Hot-standby) is identified in
the code “2” of the “GBU200-0039-462-1E”. See the chapter Communication protocol.
Applications Abbreviations Function IDs
IEC 61850 communication 61850 301001
LAN communication REDLAN 340001, 341001
Relay applications IN
Abbreviations V1a V1b V1c V0 V3 V4 I1a I1b I1c IN
SEF
(Function ID)
Overcurrent OC X X X
(440001) Directional OC X X X X X X
Earth fault EF X
(441001) Directional EF X X X X1 X
Sensitive EF SEF X
Voltage-dependent OC
OCV X X X X X X
(444001)
Undercurrent
UC X X X
(450001)
Thermal overload
THM X X X
(451001)
Broken conductor
BCD X X X
(452001)
(453001) EF X
Switch on to fault
SOTF-OC X X X
(454001)
Overvoltage
OV X X X
(460101)
EF overvoltage
OVG X X X X1
(462101)
Negative sequence OV
OVN X X X
(464101)
Under-voltage
UV X X X
(470101)
Relay applications IN
Abbreviations V1a V1b V1c V0 V3 V4 I1a I1b I1c IN
SEF
(Function ID)
Undervoltage for
UVS X X X
phases(471101)
Frequency FRQ X X X
(475001) DFRQ X X X
Protection common UV X X X
(48a001) UVS X X X
OCD X X X
VT failure detection UV X X X
(490001) OVG X X X
EF X
(491001) EF X X X
Fault locator
FL-A X X X X X X
(495001)
Autoreclose
ARC
(4a7001)
Voltage-check
VCHK X X X X X
(4a8001)
DRT_LP OC X X X
(4b0001) EF X
UV X X X
UVS X X X
SIGMA_IY
OC X X X
(713001)
Note: X: Applicable
X1: Deriving zero-sequence voltage from the three-phase voltages is applicable.
Blank: Not applicable.
Table-1 shows mounting kits for 19” inch rack. Cases (i.e., 3/4 case, 1/2, and 1/3 cases) are
accommodated for the rack by the use of optional mounting kits (see Table-2). Combined
mounting is also available when three-1/3 cases or two-1/2 cases are purchased along with the
kits. Step1 to step3 illustrate how to place the case in the 19” inch rack:
Step1: Remove the flange(s) on the sides of the case.
Step2: Attach the optional kit parts; e.g. joint plates, lock bracket, and screws.
Step3: Place the case in the rack with rack-mounting-screws‡
‡Rack-mounting-screws are not included in the kits below. Prepare the screws by yourself.
Combined mounting in double 1/3 cases Joint kits for two 1/3-size cases EP−202 Figure-2
Combined mounting in triple 1/3 cases Joint kits for three 1/3-size cases EP−203 Figure-3
Simple mounting in a 1/2 case Joint kits for single 1/2-size case EP−204 Figure-4
Combined mounting in double 1/2 cases Joint kits for two 1/2-size case EP−205 Figure-5
Simple mounting for a 3/4 case Joint kits for single 3/4-size case EP−206 Figure-6
Bundled screw
with spring and
flat washer
Bundled
countersunk
screw
Remove gray-stickers on
screw holes.
Paste white-plastic-sheets
on the joint portions.
Remove gray-stickers on
screw holes.
Paste white-plastic-sheets on
the joint portions.
Screw with
spring and flat
washer
Countersunk
screw
Remove gray-stickers on
screw holes.
Screw with
spring and flat
washer
Paste white-plastic-sheets on
the joint portions.
Countersunk
screw
Remove gray-stickers on
screw holes.
Bundled screw
with spring and
flat washer
Bundled
countersunk
screw
Paste white-screw-stickers on
the joint portions.
Appendix 10 CT requirement
5 P 20 : 10VA
The CT transforms primary current within the specified accuracy limit, for primary
current up to the overcurrent factor, when connected to a secondary circuit of the given
burden.
Overcurrent factor: The multiple of the CT rating up to which the accuracy limit is
claimed, typically 10 or 20 times. A value of 20 should be specified where maximum fault
current is high and accurate inverse time grading is required. In applications where fault
current is relatively low, or where inverse time grading is not used, then an overcurrent factor
of 10 may be adequate.
Maximum burden: The total burden calculated at rated secondary current of all
equipment connected to the CT secondary, including relay input burden, lead burden, and
taking the CT’s own secondary resistance into account. It is applied that an extremely low AC
current burden (typically less than 0.1VA for a 1A phase input) allowing relatively low burden
CTs. Relay burden does not vary with settings.
If a burden lower than the maximum specified is connected, the practical overcurrent
factor may be scaled accordingly. For the example given above, at a 1A rated current, the
maximum value of CT secondary resistance plus secondary circuit resistance (RCT + R2)
should be 10 ohms. If a lower value of, say, (RCT + R2) = 5 ohm is applied, then the practical
overcurrent factor may be increased by a factor of two, that is, to 40 amperes.
In summary, the example given of a 5P20 CT of suitable rated burden will meet most
applications of high fault current and tight grading margins. Many less severe applications
may be served by 5P10 or 10P10 transformers.
where,
Vk: Knee point voltage
If: Maximum secondary fault current
RCT: Resistance of CT secondary winding
R2 Secondary circuit resistance, including lead resistance
When using this method, it should be noted that it is often not necessary to transform
the maximum fault current accurately. The knee point should be chosen with consideration of
the settings to be applied and the likely effect of any saturation on protection performance.
Further, care should be taken when determining R2, as this is dependent on the method used
to connect the CTs (e.g. residual connection, core balanced CT connection, etc.).
Vk ≥2×Vs (1–2)
where,
V s: The differential stability voltage setting for the scheme
Dielectric voltage testing shall be carried out after reading the below notices carefully.
Cable connections
Figure-11.A illustrates external connection around the power supply module (PWS). During
dielectric voltage testing, two short-wires attached on PSW shall be carefully handled; follow the
below instructions (1) and (2).
2
4
3
FAIL1
1
8
10
9
FAIL2
7
(1)
(+) 29
30
DC/DC
(-) 31
32
35
36
37
y
38
(2)
FG