You are on page 1of 27

6.

1 Masonry Retaining Walls

Introduction Selection of Retaining Wall


This section has been prepared to provide Boundary and Site Conditions
designers, local authorities and builders with some
standard design details for reinforced concrete By reference to the particular site conditions the type
masonry retaining walls. It has been updated from of wall to be used can be selected, refer to Figure 1,
the previous version to account for the revision to page 2, Type I or II. Note the minimum level
the Masonry Design Standard NZS 4230:2004, the distance requirement (except where a specified back
introduction of AS/NZS 1170 Design Action slope angle exists behind the wall). If this cannot be
Standards, and revisions to other related standards. met then professional engineering advice must be
The design options now include for earthquake sought in order that an appropriate wall design can
action effects. be provided.

It is emphasized that where loading conditions or Soil Conditions


soil types are likely to be outside the criteria given
then professional engineering advice must be By reference to the soil conditions on the site, a
sought. particular soil type can be selected from Table 1
below. Often the local territorial authority will have
the soil types designated within its area and hence
The principal advantages of reinforced concrete
may require a specific soil type to be used in the
masonry walls over their reinforced concrete
design. The design charts provided have classed
counterparts are the elimination of shuttering and
different soils into three types for design simplicity.
the uniformity of the concrete surface texture. Two
These are shown in Table 1.
types of wall more commonly encountered on the
building site have been considered, as follows (refer
Reference should be made to the local territorial
Figure 1, page 2).
authority as to its requirements for soil types. If soil
types outside the classes listed exist, then
Type I is used when excavation is below the level of professional engineering advice must be sought.
a neighbouring property and is to be built as close
as possible to the boundary. Loading Conditions
Type II is used when filling against a neighbouring Design charts have been produced for:
boundary.
(a) Level ground and no water pressure*.
Type II walls are generally more structurally efficient (b) Level ground, no water pressure*, and a
than Type I walls, but foundation detailing is more domestic driveway (light vehicles, 2.5 kPa
complicated and additional attention is required to surcharge).
waterproofing detailing at the base, when the wall
forms part of a habitable space. (c) Maximum back slope angle of soil retained, no
water pressure* or other surcharge present.
The Type I walls only allow for the optional
additional gravity effects of loading from two storey The appropriate loading conditions (a), (b), or (c)
light timber framing (light roof and wall claddings) or must be selected.
one storey timber framing with 90 mm brick veneer * An allowance for pore water pressure in clay soils only is
finish and heavy roof, in accordance with NZS 3604. included in the design.

Table 1: Soil Types Used in Design

Design Parameters
Soil Type Classes of Soil Included 3
ү (kN/m ) Φ (º) C (kPa)
A Dense gravel 19.6 30 0
B* Loose gravel gravelly sand sandy gravel pumice 16.7 30 0
C Clay 16.7 25 12
* The design parameters for each of the soil classes varies in practice. The most unfavourable conditions for the group have been given.

New Zealand
Concrete Masonry
Association Inc.
Figure 1: Key to Wall Types/Loads Permitted

New Zealand
Concrete Masonry
Association Inc.
Only Type I walls allow for the optional additional and Blocklaying) is required during
gravity effects of loading from two storey light timber construction.
framing or one storey timber framing with 90 mm
brick veneer finish, in accordance with NZS 3604. 2. Construction without overview. Observation
Where greater vertical loads are encountered from a Type C.
structure over the retaining wall (up to100 kN/m run
of wall) alternative designs are available in NZS This category is intended where supervision is
4229 Appendix C. not provided. This grade shall be used for
retaining walls having a maximum retained soil
It is vital to ensure that adequate drainage is height up to 1.5 m.
provided behind the retaining wall. Where loading
conditions are beyond the above limitations then The use of the terms Observation Type B and
professional engineering advice should be sought. Observation Type C arises from New Zealand
Standards NZS 4230:2004 Design of Masonry
Where the retaining wall forms part of a building Structures and NZS 4229:1998 Concrete Buildings
structure the territorial authority may require not Requiring Specific Design.
earthquake action effects to be taken into account.
The Earthquake design actions standard, NZS A Licensed Building Practitioner, Bricklaying
1170.5, specifically excludes action effects on and Blocklaying, is qualified in structural concrete
retaining walls and guidance on appropriate design masonry and is acceptable to most territorial
coefficients is therefore limited. By reference to the authorities as able to provide a producer statement
previous loadings standard, NZS 4203:1992 and for workmanship in accordance with NZS 4210.
updated regional risk factors (isoseismals) given in
NZS 1170.5, seismic coefficients have been derived
that reasonably reflect the risks as follows: Specification of Materials
NZS 3604 Earthquake Zone 1: Cd = 0.14 Concrete for Footings
NZS 3604 Earthquake Zone 3: Cd = 0.27 Concrete shall comply with NZS 3109:1997 for
concrete having a minimum crushing strength of
In order to abbreviate the options in the design 25.0 MPa at 28 days.
charts following projects within Zone 2 have been
grouped with Zone 3, and Zone 4 has been omitted Ready mixed concrete should be ordered having 20
altogether. Specific engineering design will be mm maximum size aggregate, 25 MPa strength and
required for that zone. with a 100 mm slump.

Figure 2 (pages 4-5) provides a map of the seismic Concrete for Infilling
zones given in NZS 3604. While this is the current
seismic zone map from NZS 3604 2011, there have Concrete infill grout shall comply with NZS 4210
been further changes by the Department of Building Masonry Construction: Materials and Workmanship,
and Housing to the Canterbury region which extends having minimum crushing strength of 20 MPa at 28
the Zone 2 status to Waimakariri and Selwyn days and a spread between 450-530 mm when
districts including Banks Peninsular. This require- tested in accordance with the appropriate test
ment is part of their compliance document B1 AS1. requirements of NZS 3112:1986 Specification for
Users of the designs in these areas are advised to Methods of Test for Concrete".
contact the appropriate TA for final confirmation of
the seismic zone for their project. When the minimum dimension of the grout core is
less than 60 mm, then a fine grout consisting of
Construction Methods concreting sand and cement should be used,
otherwise a coarse grout is required with maximum
Two standards of criteria on construction methods aggregate size of 12.5 mm or 19.0 mm.
have been set down in the design tables:
Mortar for Laying Blocks
1. Construction with overview. Observation Type
B Mortar shall comply with NZS 4210 Masonry
Construction: Materials and Workmanship, having a
Inspection by either a suitably qualified minimum compressive strength of 12.5 MPa when
Engineer, Territorial Authority building inspector tested in accordance with Appendix 2.A of NZS
or Licenced Building Practitioner (Bricklaying 4210.

New Zealand
Concrete Masonry
Association Inc.
© Copyright Standards New Zealand.
Content from NZS 3604:2011 has been reproduced by New Zealand Concrete Masonry Association Inc with permission from Standards New Zealand under Copyright Licence 000923.
Please see Standard for full details, available from www.standards.co.nz.

Figure 2: Earthquake Zones

New Zealand
Concrete Masonry
Association Inc.
© Copyright Standards New Zealand.
Content from NZS 3604:2011 has been reproduced by New Zealand Concrete Masonry Association Inc with permission from Standards New Zealand under Copyright Licence 000923.
Please see Standard for full details, available from www.standards.co.nz.

Figure 2: Earthquake Zones (continued)

New Zealand
Concrete Masonry
Association Inc.
Reinforcing Steel from accumulating at the top of the wall and
overloading the drainage system.
Reinforcing steel shall be Grade 500E to AS/NZS
4671:2001, Steel Reinforcing Materials. The assumed weight of materials is:
3
Particular attention should be taken to the cover Concrete and Blockwork 23.5 kN/m
requirements for vertical reinforcing shown on the
construction diagrams as it is critical to the design Soil:
strength of the walls. Reinforcing steel extending
from footing pours that does not meet the Uncompacted gravelly
3
requirements must not be bent to achieve a fit. sands or clay 16.7 kN/m
Seek professional engineering advice for remedial
options should this occur. Dense gravelly sands or
3
gravels 19.6 kN/m
Masonry Construction Pumice 12.7 kN/m
3

Wall construction shall follow the provisions of NZS Blockwork and concrete are designed to the
4210. Construction will predominantly use open requirements of the New Zealand Building Code,
ended, depressed web units; i.e. 1516, 2016, 2516; Clause B1, Structure.
or where available H block configuration, e.g.
H2016. All cells are to be filled with grout. Seismic action effect options have now been
included in the design tables. They should be
Design Notes applied where the retaining wall forms part of a
building structure, or otherwise as required by
The design charts were produced by consultants the territorial authority. The tables cover three
CHP Wellington Limited in response to a of the four seismic zones defined by the Timber
commission by the New Zealand Concrete Masonry Framed Buildings Standard, NZS 3604:2011,
Association to update the previous section covering with Zones 2 and 3 having been grouped using
masonry retaining walls for domestic construction. the more onerous factors for Zone 3. Users
should seek professional engineering advice
The criteria used by the consultants were as follows: should they wish to achieve a slightly more
economic design for Zone 2, or where requiring
The retained soil at the top of the wall from the a solution for Zone 4.
back of the footing heel is level for a distance
equal to the height of wall (except for tables Calculations assume a minimum 100 mm cover
where a specified back slope angle exists). All of earth or paving materials on top of projecting
soil contained from the back of the wall to a 45° footings. Where footings are constructed
line from the base of the footing must be of the integrally with a floor slab and there is no such
type assumed in the design from Table 1, or cover it is assumed that the slab will provide
where backfilling has taken place, must be the additional resistance to overturning
granular with a minimum Φ = 35° and required.
3
maximum γd = 19.6 kN/m .
Assumed soil parameters
The walls are not designed for the forces due
to compacting machinery working on the The following soil types have been grouped
retained soil. Adequate precautions, e.g. together to provide three soil types for ease of
shoring, strutting, etc. must be taken to ensure use.
no damage occurs to the wall during this
operation. Soil forces are calculated using the Coulomb
active earth pressure theory assuming wall
The design considers stability of the wall for movements, lateral and rotational, are sufficient
sliding, overturning and bearing on the soil to allow active pressure to develop and that
immediately adjacent to the wall. Overall wall/soil friction can develop.
stability of the soil mass has not been
considered. For both cohesive and granular soil types, the
soil and surcharge are assumed to act at an
A drainage layer of suitable granular material is angle of either two thirds Φ or Φ. The first
provided at the back of the wall, with a value applies to Wall Type I and approximates
perforated pipe at the base discharging to the the effect of wall friction. The second value
open. Surface water must also be prevented applies to Type II Walls where the "virtual back"

New Zealand
Concrete Masonry
Association Inc.
of the wall is a plane through the soil itself, and Determine whether it is appropriate to include
wall friction is replaced by internal friction of the earthquake effects and if so what Earthquake
soil. Zone is appropriate (see Figure 2).

When calculating the passive soil pressure at Reinforcement tables indicating the maximum
the toe of the footing, cohesive soils are height to be retained for the appropriate wall,
assumed to be fully drained (i.e. no pore water soil types, and loading conditions, will
pressures are present). The passive pressure determine whether a 140 mm, 190 mm, or a
on the toe is taken as acting over the entire 240 mm wall should be used.
depth from the soil level to the base of the key;
the full value is used. The top row for the 190 mm series walls has
been provided to give minimised footing
For cohesive type soils the effects of pore dimensions for lower height wall options.
water pressure are included to allow for slow
drainage within the retained soil. Enter selected chart, using maximum height of
soil retained, to read off reinforcing and
The soil stress at the toe of the footing is minimum footing dimensions required.
assumed to be a uniform rectangular stress
block over a portion of the footing. The Where the footing is part of a substantial
minimum ultimate bearing rupture capacity of concrete slab (e.g. house or garage floor slab
the soil is assumed to be 300 kPa, the in good ground) any key required can be
equivalent of ‘Good Ground” as defined in the omitted.
Timber Framed Buildings standard, NZS
3604:2011. Only Type I walls allow for the optional
additional gravity effects of loading from two
In cohesive soils, base adhesion contributes to storey light timber framing or one storey timber
the sliding resistance. The value of base framing with 90 mm brick veneer finish, in
adhesion used is multiplied by the width of the accordance with NZS 3604.
footing over which ultimate soil bearing
pressure develops (i.e. the rectangular stress Where greater vertical loads are encountered
block). from a structure over the retaining wall (up
to100 kN/m run of wall) alternative designs are
The base friction coefficient is taken as tan in available in NZS 4229 Appendix C.
granular soils, and two thirds tan Ф in cohesive
soils where a key exists.
Examples
Buoyancy effects have not been considered.
The following examples intend to illustrate the use of
Masonry Design the design charts:
The design has been based upon NZS
Example 1
4230:1990 Code of Practice for the Design of
Masonry Structures. 60 mm cover to reinforcing A wall within a basement garage of a single storey
steel from soil side of the wall has been used light timber framed residence has a substantial area
for 140mm and 190 mm walls, and 70 mm of concrete slab and footings constructed on good
cover for 240 mm walls. Refer to Figure 3 ground. It is to retain sandy soil from the neigh-
(page 8) for construction details showing block bouring property and is directly adjacent to the site
layout, reinforcing location, bar bend radii, etc. boundary. The ground to be retained is flat for a
distance of 3 m from the wall face, is used as a
Use of Design Charts domestic driveway, and is determined to be 2,250
mm above the top of the footing. The site is in
By reference to boundary and site conditions, Earthquake Zone 1.
the appropriate wall type can be selected, Type
I or II (see Figure 1). As excavation cannot be under the neighbour’s
property and the wall is required to support the
Select the appropriate soil type (see Table 1). light timber framed building above use a Type I
wall.
Determine if a surcharge for light private
vehicle parking is required, or if the retained As the wall supports a domestic driveway use
soil will have a back slope angle. surcharge based charts.

New Zealand
Concrete Masonry
Association Inc.
The wall is part of a building structure and where it is not part of, or near, any building structure
seismic actions will need to be considered. and the territorial authority does not require seismic
actions to be considered.
The soil is identified as being sandy therefore
use soil B column. By entering the Soil B column in Table 1 the
following design requirements are found:
With 140 mm Type I wall with surcharge and
soil type B, Earthquake Zone 1, the maximum Vertical Reinforcing (60mm rear cover) HD12-
permitted height is 1,700 mm. Therefore use 600
Type I 190 mm Retaining Wall - With
Surcharge. Horizontal Reinforcing HD12-600

The design dimension table is then referenced Footing Length "L" 950 mm
and by referring to the Soil B column of Table 2
it is found that the closest greater "Maximum Key Depth "K" 100 mm
Height" retained is 2,400 mm, giving:
If, for this example, the back slope required was
Vertical Reinforcing (60 mm determined to be 20°, i.e. exceeds the 10° maximum
Rear cover) HD16-400 slope provided on the design chart for this wall,
specific design would be required by a Chartered
Horizontal Reinforcing HD12-600 Professional Engineer.

Footing Length "L" 1,800 mm


Copyright and Disclaimer
The 500 mm deep key may be omitted from the
© 2010 New Zealand Concrete Masonry Association Inc.
footing because of the presence of substantial
area of attached slab and foundations. Except where the Copyright Act and the Limited-License
Agreement allows otherwise, no part of this publication may be
reproduced, stored in a retrieval system in any form or
Example 2 transmitted by any means without prior permission in writing of
the New Zealand Concrete Masonry Association. The
information provided in this publication is intended for general
A Type II wall, 1,750 mm high, is to be constructed guidance only and in no way replaces the services of
in Soil B materials with a back slope of 10°. A 190 professional consultants on particular projects. No liability can
mm wall is chosen and the "Type II 190 mm therefore be accepted, by the New Zealand Concrete Masonry
Retaining Wall – With Backslope" chart is Association, for its use. For full terms and conditions see
http://www.nzcma.org.nz/manual.html.
referenced. The wall is positioned within a site

New Zealand
Concrete Masonry
Association Inc.
Figure 3: Retaining Wall Details

New Zealand
Concrete Masonry
Association Inc.
New Zealand
Concrete Masonry
Association Inc.
New Zealand
Concrete Masonry
Association Inc.
New Zealand
Concrete Masonry
Association Inc.
New Zealand
Concrete Masonry
Association Inc.
New Zealand
Concrete Masonry
Association Inc.
New Zealand
Concrete Masonry
Association Inc.
New Zealand
Concrete Masonry
Association Inc.
New Zealand
Concrete Masonry
Association Inc.
New Zealand
Concrete Masonry
Association Inc.
New Zealand
Concrete Masonry
Association Inc.
New Zealand
Concrete Masonry
Association Inc.
New Zealand
Concrete Masonry
Association Inc.
New Zealand
Concrete Masonry
Association Inc.
New Zealand
Concrete Masonry
Association Inc.
New Zealand
Concrete Masonry
Association Inc.
New Zealand
Concrete Masonry
Association Inc.
New Zealand
Concrete Masonry
Association Inc.
New Zealand
Concrete Masonry
Association Inc.

You might also like