You are on page 1of 43

CEHA SIDE CHANNEL PUMP

Multicellular, self-priming, low NPSH


Shaft sealing by mechanical seal with or without cooling

Fig.0.B.1

Operating instructions

Security Chapter 1
Safety instructions, guarantee
Description and applications Chapter 2
Operating conditions, pump description, performance data
Planning the Installation Chapter 3
Piping system, electric connections, accessories
Unpacking, handling, storage Chapter 4
Checks, storage conditions and safety instructions
Installing the pump Chapter 5
Installation conditions, piping connections, checks
Commissioning and decommissioning Chapter 6
Conditions, safety instructions, checks
Maintenance Chapter 7
Maintenance, disassembly, re-assembly
Help in case of trouble Chapter 8
Analysis and troubleshooting of operating defects
Appendices Chapter 9
Coding, dimensions, cross sectional drawings, data sheet

Caution: This pump or this electric motor / pump assembly may be installed and commissioned by qualified
and authorized personnel only. These personnel have to observe strictly the operating instructions in this
manual and the laws and regulations in force related to the safety.
If you do not pay attention to these operating instructions,
• danger may be caused to the various persons working on the equipment and its users,
• the pump or the electric motor / pump assembly may be damaged,
• the manufacturer is not liable for damage resulting from this non-observance!

Please be aware of your responsibility for neighbouring personnel when working on the pump or the
electric motor / pump assembly!

Document - No. : CEH00BE Sterling Fluid Systems (France)


Revision : 02 1-3 Avenue Georges Politzer-B.P 41-78193 Trappes France
Date : 02/10/2003 Telephone: +33 (0)1 34 82 39 00 Fax: +33 (0)1 34 82 39 61
SAP Doc. : 26594/TD/EN/00 Member of the Sterling Fluid Systems Group
Safety Page 1 of 4 Chapter 1

1.0 Safety Authorized personnel for the use, maintenance,


This operating manual gives basic instructions inspection and assembly must have the
which are to be observed during installation, qualifications needed for this work. Scope of
operation and maintenance of the pump. It is responsibility, skills and monitoring of the
therefore imperative that this manual is read by personnel must be strictly controlled by the
the fitter, personnel/operator in charge of set-up purchaser of the equipment. If the staff do not
and commissioning, as well as by the user. This have the necessary knowledge, they must be
manual is to be kept always available at the trained. The manufacturer or the supplier can
installation site of the pump or electric motor- carry out this training. In addition, the purchaser
pump assembly. is to make sure that the competent personnel
read and fully understood the contents of this
1.1 Meaning of safety symbols used manual.
in this manual
Safety instructions to be observed to avoid any
danger to persons are shown by the symbol: 1.3 Non-compliance with safety
instructions
Non-compliance with safety instructions may
cause danger to personnel, as well as to the
environment and the machine.
Electrical power risks are shown by the symbol: The manufacturer is such cases will not be held
responsible.

Non-observance of these safety instructions may


cause in particular:
Instructions where non-observance could cause x Failure of important functions of the machine
damage to the machine, are shown by the word: or the installation,
Caution x Failure of specified procedures for servicing
and maintenance,
Instructions where non-observance could cause x Exposure of people to electrical, mechanical
supplementary risks when the pump is used in and chemical hazards,
‘’explosible atmosphères’’ are shown by the x Risks of pollution of the environment owing to
symbol: hazardous substances being released.

1.4 Accident prevention


The customer undertakes to respect the safety
instructions shown in this manual, the national
Signs affixed directly on the machine, such as the accident prevention regulations, as well as the
arrow indicating the direction of rotation or the internal regulations relating to the working
arrows indicating fluid suction and discharge conditions, the equipment operation and safety.
connections must be observed and kept legible.

1.2 Qualification and training of


personnel

Doc.Num.: CL01E Information subjected to technical Sterling Fluid Systems (France)


Rev.:01 alterations due to engineering development Member of Group
Date: 01/04/2003 Sterling Fluid Systems
Safety Page 2 of 4 Chapter 1

1.5 Safety instructions for users Pumps and electric motor-pump assemblies,
This pump was designed in compliance with the which convey hazardous fluids must be
standard relating to the safety of the pumps. decontaminated.
Immediately after completion of work all safety
x Parts subject to temperature variations and and protective facilities must be re-installed and
those where contact with them can be made operative again.
dangerous must be protected by suitable After a service or other operation, the instructions
devices. to re-start the machine given in paragraph 6 are to
x Safety devices against accidental contact with be observed.
moving parts (e.g. coupling guards) must not
be removed from the machine while in
operation. 1.7 Use in Explosible Atmospheres
The pump must never be started without these
coupling guards.

The instructions for installation, use and


maintenance given throughout the Owner's
Manual supplied with the pump must be
The coupling guard is a safety component
scrupulously adhered to. This section gives
designed for its function; in no case, it must never
additional information relevant to equipment use
be used as a step or other support point.
in explosible atmospheres.

x In no case, is this pump to operate without


1.7.1 Classification
fluid. The destruction of the shaft outlet
Classification of the Sterling side channel pumps
sealing which could result from such use
as per EC Directive 94/9 "Explosible
would cause fluid leakage endangering the
atmospheres"
safety of persons and the environment.
Group : II
x Ensure that protection is provided against any
Category :2
hazard from electrical power (refer to
Gas :G
regulations in force).
Build safety :c

1.6 Safety instructions for


1.7.2 Marking
maintenance, disassembly and
The nameplate of a Sterling side channel pump
assembly
suitable for operation in explosible atmospheres
It is the customer’s responsibility to ensure that all
carries the following indications:
maintenance, inspection and installation work is
performed by qualified and authorized personnel
- Sterling's name and address,
who have studied this manual.
- the CE approval logo,
Any work on the machine shall only be performed
- the serial number,
when it is at a standstill. It is imperative that the
- the year of manufacture,
procedure for shutting down the machine
- the classification, e.g.: H II 2 G c.
F

described in this manual is to be followed.

Doc.Num.: CL01E Information subjected to technical Sterling Fluid Systems (France)


Rev.:01 alterations due to engineering development Member of Group
Date: 01/04/2003 Sterling Fluid Systems
Safety Page 3 of 4 Chapter 1

1.7.3 Integration 1.7.5 Risks of Spark Production by


The pump may only be integrated into an External Shocks
assembly intended for operation in explosible During use in explosible atmospheres, the
atmospheres, in accordance with EC Directive operator shall see to it that external shocks on the
94/9 "Explosible atmospheres", if its nameplate pump or pump set components, which could
includes the information defined in para. 1.7.2 produce sparks, are not likely to occur, otherwise,
(pump marking). the necessary guards shall be installed.
If the pump is integrated into a complete system,
with other mechanical or electric components, this
complete system may only be validated if all its 1.7.6 Technical Parameter Monitoring
components comply with EC Directive 94/9 The instructions for installation, use and
"Explosible atmospheres". Only if this requirement maintenance given throughout the Owner's
is met will the use of the pump in an explosible Manual supplied with the pump must be
atmosphere (Group II, category 2) be authorized. scrupulously adhered to under all circumstances.
NOTE: However, when the pump has to be used in an
Particular attention shall be paid in checking that explosive atmosphere, the monitoring of the
these requirements are complied with for every following parameters has to be reinforced
component item of the complete system. significantly:
The use of a single component not meeting the
requirements of EC Directive 94/9 "Explosible x presence and correct operation of an
atmospheres" entails that the pump cannot be emergency shutdown system, provided with
used in explosible atmospheres, even though its an interlock preventing non-controlled
nameplate includes the adequate symbols: untimely restarts,
HF II 2 G c. x conformity of the transmission coupling,
x presence and conformity of the coupling
guard,
1.7.4 Conformity of the Pump Set x conformity of the direction of rotation and
Coupling impossibility of inadvertent reversal thereof,
The transmission coupling shall be provided with x sufficient fluid level in the pump at startup and
a system which prevents the two half-couplings to adequate supply during operation,
come into contact in case of abnormal wear of the x use of the pump only within the authorized
flexible transmission components. operating range (flowrate, water head, power,
Coupling guard speed, NPSH, operation at zero flow without
The coupling guard used in explosible bypass is absolutely prohibited),
atmospheres shall meet the following criteria: x compliance with the supplier's service
x it shall be made of a non-sparking material instructions (carried fluid, temperature,
(e.g. bronze, brass, aluminum, etc.), specific gravity, viscosity, startup intervals),
x its mechanical design shall be such that it is x conformity of the bearing operating
strong enough to resist any distortions likely temperature (monitoring and lubrication
to result in a contact with a rotating part, even provided),
in case of illegal use of the guard (e.g. use of x absence of vibrations and/or overheats due to
the coupling guard as a step). poor drive coupling alignment or stresses on
Motor the pump flanges,
The drive motor shall meet the requirements of x adjustment and control of the acceptable
the CE Directive "Explosible atmospheres" it is leaks,
subjected to. x conformity of the shaft seal temperatures,
Doc.Num.: CL01E Information subjected to technical Sterling Fluid Systems (France)
Rev.:01 alterations due to engineering development Member of Group
Date: 01/04/2003 Sterling Fluid Systems
Safety Page 4 of 4 Chapter 1

x check of sealing (shaft seal, body, plug,


piping).

1.8 Alteration of the machine


and of spare parts
No alteration or modification may be undertaken
without prior agreement of the manufacturer.
Genuine spare parts and accessories specified by
the manufacturer contribute to safety. The
manufacturer of the machine cannot be held
responsible in the event of accident related to the
use of parts other than genuine parts.
During the guarantee period, any repairs or
modifications can be made only by our fitters or
with our agreement.

1.9 Non-observance of safety


instructions
Safety related to the correct operation of the
machine can be guaranteed only if the
instructions in this manual are respected, as well
as the conditions and operational limits mentioned
in the data sheet attached.

1.10 Warranty / guarantee


The Sterling SIHI guarantee is satisfied only
under the following conditions:

x The pump is installed and operated in perfect


compliance with the instructions and under
conditions approved by Sterling SIHI.
x All modifications will be submitted for Sterling
SIHI's approval before implementation.

Doc.Num.: CL01E Information subjected to technical Sterling Fluid Systems (France)


Rev.:01 alterations due to engineering development Member of Group
Date: 01/04/2003 Sterling Fluid Systems
Description and applications Page 1 of 3 Chapter 2

2.0 Equipment application required NPSH, so that this pump can be used
The pump is to be used only for the operating under very difficult suction conditions.
conditions stated by the purchaser and confirmed Heating and cooling chambers for the pump hous-
by the supplier. The guarantee conditions are ing can be inserted in place of hydraulic stages.
defined as per our general conditions of sale. It is possible to add a retaining stage at the suc-
The conditions of use are defined in the attached tion end of the pump.
data sheet. The shaft outlet sealing can be adapted to suit the
majority of operating conditions.
The construction specifications are defined in
2.1 Safety instructions chapter 9.

2.4 Performance data


Q(m3/h) – H(m) – P(kW) - NPSH
(See following pages)

x You may use the pump only for the application


stated in the data sheet as otherwise accidents
to people and the environment may occur.
x Do not exceed the density and viscosity stated The pump must not operate out of the output
in the data sheet. Otherwise there is danger of range defined by the minimum and maximum flow
damage to the pump. for each size.

2.2 Accessories
The accessories delivered with the pump or the
electrical pump unit are indicated in the data
sheet. The corresponding operating and installa-
tion instructions can also be found in the appen-
dix.
The installation of additional accessories may be
carried out only after receiving approval from the
manufacturer of the machine.

2.3 Construction and operation


CEHA pumps are side channel, multicellular, self-
priming pumps designed with up to 8 stages, hav-
ing a horizontal configuration and offering numer-
ous metallurgical variants.
They allow for the simultaneous pumping of gas
and liquid.
The use of a pre-compression turbine at the suc-
tion end makes it possible to obtain a very small

Doc.No.: CEH02ABE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date: 02/04/2003 Sterling Fluid Systems
Description and applications Page 2 of 3 Chapter 2

Performance data
CEH-Pumps
n = 1450 rpm Design tolerances: Output ± 5%
Density = 1kg/l Delivery height ± 5%
Viscosity = 1mm²/s Power +10%
NPSH 1 effective suction of a non gas-free liquid – NPSH 2 pumping under load Measuring tolerances: DIN 1944

Q [m³/h]
Series 0.4 (1) 0.6 1.0 1.5 2.5 (2)
Sizes H P H P H P H P H P
[m] [kW] [m] [kW] [m] [kW] [m] [kW] [m] [kW]
CEH 1201 32 0.42 30 0.4 26 0.35 20 0.29 11.5 0.22
CEH 1202 57 0.76 53 0.72 46 0.64 36 0.53 19.5 0.38
CEH 1203 83 1.1 77 1.04 65 0.92 52 0.77 28 0.53
CEH 1204 108 1.44 100 1.36 85 1.2 68 1.02 36 0.69
CEH 1205 133 1.78 123 1.68 105 1.5 83 1.26 44 0.84
CEH 1206 159 2.1 147 2 125 1.78 99 1.5 52 1
CEH 1207 184 2.45 170 2.3 144 2.05 115 1.74 60 1.14
CEH 1208 209 2.8 193 2.65 164 2.35 130 1.98 68 1.3
NPSH 1[m] 1.3 1.3 1.35 1.4 1.55
NPSH 2[m] 0.11 0.11 0.11 0.11 0.48
NPSH 1 effective suction of a non gas-free liquid – NPSH 2 pumping under load of a high vapor pressure liquid

1.0 (1) 1.5 2.5 3.5 4.5 (2)


CEH 3101 48 1.14 44 1.06 34 0.86 25 0.68 17 0.57
CEH 3102 87 2.1 79 1.94 61 1.56 44 1.22 29 0.99
CEH 3103 126 3.1 114 2.8 88 2.25 63 1.76 41 1.4
CEH 3104 165 4.05 149 3.7 115 2.95 82 2.3 52 1.82
CEH 3105 204 5 184 4.55 142 3.65 101 2.85 64 2.25
CEH 3106 243 6 219 5.5 169 4.35 120 3.4 76 2.65
CEH 3107 282 7 254 6.3 196 5.1 139 3.9 88 3.1
CEH 3108 321 7.9 289 7.2 222 5.8 159 4.45 100 3.5
NPSH 1[m] 1.35 1.25 1.1 0.95 0.95
NPSH 2[m] 0.17 0.17 0.17 0.17 0.18
NPSH 1 effective suction of a non gas-free liquid – NPSH 2 pumping under load of a high vapor pressure liquid

3.5 (1) 4.5 6.0 7.5 (2)


CEH 3601 35 1.2 28 0.99 19 0.78 9.5 0.59
CEH 3602 63 2.2 50 1.82 33 1.4 16 1.02
CEH 3603 91 3.15 72 2.65 46 2 22 1.46
CEH 3604 119 4.15 94 3.45 60 2.6 28 1.9
CEH 3605 147 5.1 117 4.25 74 3.25 34 2.35
CEH 3606 175 6.1 139 5.1 88 3.85 41 2.75
CEH 3607 203 7.1 161 5.9 102 4.45 47 3.2
CEH 3608 231 8.1 184 6.7 115 5.1 53 3.65
NPSH 1[m] 0.95 0.95 1.1 1.4
NPSH 2[m] 0.17 0.18 0.19 0.21
NPSH 1 effective suction of a non gas-free liquid – NPSH 2 pumping under load of a high vapor pressure liquid
(1)
: Minimum operating flow
(2)
: Maximum operating flow

Doc.No.: CEH02ABE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date: 02/04/2003 Sterling Fluid Systems
Description and applications Page 3 of 3 Chapter 2

Performance data
CEH-Pumps
n = 1450 rpm Design tolerances: Output ± 5%
Density = 1kg/l Delivery height ± 5%
Viscosity = 1mm²/s Power +10%
NPSH 1 effective suction of a non gas-free liquid – NPSH 2 pumping under load Measuring tolerances: DIN 1944

Q [m³/h]
Series 6.0 (1) 7.5 9.0 10.5 12.0 (2)
Sizes H P H P H P H P H P
[m] [kW] [m] [kW] [m] [kW] [m] [kW] [m] [kW]
CEH 4101 37 2.05 31 1.82 26 1.58 19.5 1.36 13.5 1.2
CEH 4102 67 3.65 56 3.2 45 2.75 33 2.3 20 1.98
CEH 4103 98 5.3 82 4.6 65 3.95 46 3.3 27 2.75
CEH 4104 128 6.9 107 6.0 84 5.1 60 4.25 33 3.55
CEH 4105 159 8.6 132 7.4 104 6.3 73 5.2 40 4.3
CEH 4106 189 10.2 157 8.8 123 7.5 86 6.2 47 5.1
CEH 4107 220 11.8 182 10.2 143 8.7 99 7.1 54 5.9
CEH 4108 250 13.4 208 11.6 162 9.8 113 8.1 60 6.7
NPSH 1[m] 0.85 0.9 0.95 1.05 1.15
NPSH 2[m] 0.22 0.24 0.28 0.35 0.45
NPSH 1 effective suction of a non gas-free liquid – NPSH 2 pumping under load of a high vapor pressure liquid

10.5 (1) 12.0 14.0 16.0 18.0 20.0 (2)


CEH 5101 45 4.2 42 4.1 37 3.75 32 3.4 26 3.05 19 2.7
CEH 5102 82 7.9 76 7.6 67 6.8 56 6.1 45 5.4 33 4.65
CEH 5103 120 11.6 111 11 96 9.9 81 8.8 64 7.7 47 6.6
CEH 5104 157 15.4 145 14.4 126 13 106 11.6 84 10 60 8.6
CEH 5105 195 19.2 179 17.8 156 16 130 14.2 103 12.4 74 10.6
CEH 5106 232 23 214 21.5 186 19.2 155 17 123 14.8 88 12.6
CEH 5107 270 26.5 248 24.5 216 22 180 19.6 142 17 102 14.6
CEH 5108 307 30.5 283 28 245 25 205 22.5 161 19.4 116 16.4
NPSH 1[m] 0.95 1.0 1.05 1.15 1.25 1.35
NPSH 2[m] 0.35 0.4 0.45 0.5 0.55 0.65
NPSH 1 effective suction of a non gas-free liquid – NPSH 2 pumping under load of a high vapor pressure liquid

16.0 (1) 18.0 20.0 25.0 30.0 35.0 (2)


CEH 6101 53 8 50 7.6 46 7.3 36 6.2 25 4.9 13 4
CEH 6102 96 14.8 90 14.2 83 13.4 64 11.2 43 8.8 23 7.1
CEH 6103 139 21.5 130 20.5 120 19.4 92 16.4 61 12.8 32 10.2
CEH 6104 182 28.5 170 27 157 25.5 120 21.5 79 16.6 41 13.3
CEH 6105 225 35 210 33.5 194 31.5 148 26.5 97 20.5 51 16.4
CEH 6106 268 42 251 40 231 38 176 31.5 115 24.5 60 19.5
CEH 6107 311 49 291 46.5 268 44 204 36.5 133 28.5 69 22.6
CEH 6108 354 56 331 53 305 50 232 41.5 151 32.5 78 25.7
NPSH 1[m] 1.3 1.3 1.3 1.3 1.5 1.65
NPSH 2[m] 0.35 0.4 0.4 0.55 0.65 0.85
NPSH 1 effective suction of a non gas-free liquid – NPSH 2 pumping under load of a high vapor pressure liquid
(1)
: Minimum operating flow
(2)
: Maximum operating flow

Doc.No.: CEH02ABE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date: 02/04/2003 Sterling Fluid Systems
Planning the installation Page 1 of 4 Chapter 3

3.0 Planning of the Installation 3.1.1 Installation diagram

3.1 Piping system

by-pass

Caution

x Respect the direction of flow of the fluid flow


normalizer
(arrows on the pump flanges).
x The diameters of the pipes must not be
smaller than the diameters of the
Fig. 3.1
corresponding pump orifices (see data sheet).
x Check that cleaning of all pipes has been
1 – Gate-valve at the discharge
carried out prior to installation of the pump.
2 – Qmin-diaphragm or relief valve
x Adjust the piping positioning to ensure it does
3 – Qmax-diaphragm
not cause any stress on the pump orifices.
4 – Pressure gauge
x Avoid abrupt changes of piping diameter and
5 - Pressure gauge
short radius pipe elbows.
6 – Gate-valve at the suction end
x In case of change of diameter, use
asymmetrical (eccentric) convergent transition
pieces in order to avoid the formation of air
3.1.2 Suction line
pockets in the pipes.
In case of effective suction lift operation:
x Install a flow stabilising length before the
suction branch of the pump; it should have the
same diameter as the pump and a length 10 to
20 times the diameter of the pump.
x The flow velocity in the suction line must not
exceed 1m/s.
x The pipe holders and anchoring must be
designed in such a way that thermal expansion
in the pipe system does not have any effect on
the pump flanges.
Fig.3.2
x Provide for connections for pressure gauges
x The suction line is to be vertical and then
and for filling of pump with liquid.
must slightly ascend to the pump.
x In critical applications, (liquids with impurities)
x If a foot valve is used, it must be installed at
the system must be protected by a fine-
least 0.50 m below the lowest pumping level.
meshed strainer.

Doc.No.: CEH03ABE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date: 02/04/2003 Sterling Fluid Systems
Planning the installation Page 2 of 4 Chapter 3

In case of pumping under load: flow


normalizer

Fig.3.4

3.1.3 Discharge line


Fig.3.3
x The piping must slightly descend to the
pump.
Caution
x The liquid level must be kept at least 0.50 m
above the axis of the suction line.
Adjustment to the operating point of the pump is
x In case of pumping in a vacuum tank, we
to be carried out by the means of a gate valve
recommend the installation of balance piping
installed at the pump discharge line.
of Ø 25 to 50 mm (1" to 2") returning to the
If there is a risk of exceeding the working
tank.
pressure, a protective device must be installed,
such as a bypass line with diaphragm or a
In both cases of pumping:
pressure relief valve.
working pressure = pressure at pump discharge
with zero flow + suction pressure
Caution Installing a slow-closing non-return check valve
will prevent hammering in high pressure
x The gate valve in the suction line must be installations with long piping.
kept completely open when starting, as well Use constant diameter piping.
as during the operation of the pump.
x The suction line must be protected and
insulated against heat. 3.1.4 Installing a diaphragm
x A filter must be installed in the piping in case
of pumping of contaminated liquids. Its
section must have at least three times the
Caution
diameter of the pipe section with a mesh size
equal to 0.1 mm.
- Q-max-diaphragm
x Arrange a length of flow stabilising line just
In order to avoid exceeding the permitted flow, a
before the pump. In case of changes in
diaphragm should be fitted into the pump
diameter, use an asymmetrical convergent
discharge line (see installation diagram).
transition piece to avoid the formation of gas
This will prevent any danger of operating with
pockets.
cavitation.

- Q-min-diaphragm, relief valve

Doc.No.: CEH03ABE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date: 02/04/2003 Sterling Fluid Systems
Planning the installation Page 3 of 4 Chapter 3

- The installation of a relief valve or a These accessories make it possible to check, for
diaphragm in the by-pass piping will ensure example:
that the required minimum flow for the pump x The power absorbed by the motor.
is present (see installation diagram). This will A load detector measures the power
provide for sufficient cooling of the pump and absorbed by the motor. If this power is too
avoid mechanical overloads. high, the motor is switched-off.
x The fluid temperature (PT100).
3.1.5 Pressure checking The PT100 probe is a resistance thermometer
Pressure checks will be carried out by means of intended for checking the temperature of
pressure gauges installed on the suction line and bearings or pumped liquid. A threaded pipe
on the discharge line of the pump (see installation connection is essential for it to be installed.
diagram). The switch-off temperature has to be adjusted
10 C higher than the operating temperature.
3.1.6 Double envelope of cooling x The level of the pumped liquid.
or reheating casings To protect the pump from a possible lack of
liquid in the course of operation, it is possible
to use a level detector.
x The gradual starting of the motor.
Caution
3.4 Pumping of liquefied gases and
The cooling or heating piping for the shaft sealing
condensates
system will be connected to the ports provided for
For the pump to handle liquefied gases and
that purpose.
condensates it is especially important that the
design and installation is carried out by

* specialists. Incorrect operations during starting –


causing “dry” operation - lead to damage to pump
15° 15°
parts.
Please follow the instructions below:
Fig.3.5 x The loss of pressure must be reduced to a
minimum in the suction line.
x The suction must not be disturbed by
*: Port in the double envelope of the case for
bends, filter, gate-valve or changes in diameter
cooling or heating fluid.
x A length of stabilizer pipe must be installed
Shut-off valves are to be installed in the inlet and
with a length 10-20 times the diameter of the
outlet pipes.
suction flange (see installation diagram).
x The available NPSH (net positive load at the
suction flange) scheduled for the project must
3.2 Electrical connections
allow for a safety factor compared to the
The connections and the protection system for the
required NPSH.
electric motor will be made in accordance with the
x The by-pass piping is to return to the tank
requirements and regulations currently in force.
and not to the pump inlet.
x The supply line must be as short as possible.
3.3 Accessories
With longer lines, which may be exposed to
Various accessories can be installed to contribute
strong sunlight, correct insulation must be
to the safety of the equipment.
provided.

Doc.No.: CEH03ABE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date: 02/04/2003 Sterling Fluid Systems
Planning the installation Page 4 of 4 Chapter 3

x As liquefied gases may give off oxides,


suitable filters must be provided to prevent
oxides from entering the pump. These must be
cleaned at regular intervals.
x Degassing piping must be installed between
the flow stabilizer piping and the gas phase of
the tank at the suction end (see installation
diagram). This piping must be 25 to 50 mm (1’’
to 2’’) in diameter
x If the pump is to be used for several tanks
with various mixtures of liquefied gases and
different vapour pressures, high performance
non-return valves must be mounted on the
pump discharge end. This is to prevent the
liquid which is being pumped from returning to
the suction end when gate-valves are
actuated.
x When draining several tanks with only one
pump, a device allowing for isolation of the
empty tank must be installed, to prevent any
gas from entering the other tanks.
x Before each start-up, make sure that the pump
is filled with liquid. It is recommended to fit a
degassing lever valve below the outlet valve.
When filling the pump this valve is kept open
continuously, until the liquid comes out.
x In order to check the liquid level, a level detec-
tor must be installed to prevent the pump from
dry operation. A special design exists which
makes it possible to add a retention stage di-
rectly on the pump (CEH..../7).
x Keep the pressure balance line open at the
end which supplies to the tank.
x When using the pump in explosion hazard
areas, make sure that the various ancillaries
are in conformity with the current safety
standard.
x At pump start-up, the outlet gate-valve is to
remain half open. If this valve is fully opened,
there is the danger that the pump will operate
beyond its specification range and this leads to
the formation of vapour in the pump.

Doc.No.: CEH03ABE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date: 02/04/2003 Sterling Fluid Systems
Unpacking, handling, storage Page 1 of 2 Chapter 4

4.0 Unpacking, handling, storage specific conditions). This protection is designed


for storage duration of 3 months.

4.1 Safety measures


4.3.1 Short-term storage, less than
three months
If the pump or the electric pump unit is not to be
installed immediately after delivery, the equipment
will have to be stored in a dry location and free
x Never stay below the suspended load. from vibrations, for a duration not exceeding three
x Keep a sufficient safety distance during trans- months. Moreover, it is advised to turn the pump
port of the load. shaft over manually and periodically to avoid any
x Use only appropriate hoisting slings which are risks of seizing of mobile parts.
in perfect condition.
x Adjust the length of the hoisting slings in such
a way that the pump or the electrical pump 4.3.2 Long-term storage
unit is suspended horizontally and stable. If the storage duration exceeds three months, in
x Do not use the eyebolts on the pump compo- addition to the precautionary measures specified
nents or on the motor for lifting the assembled in 4.3.1, it is necessary to wash the pump with
pump or the complete unit. They are intended fresh water and to re-apply the preserving fluid
only for handling spare parts during assem- every three months. Make sure that the product
bling or dismantling. used is compatible with the pump materials and
x Do not separate the documents attached to complies with the environmental protection and
the pump. personnel safety regulations currently in force.
x Do not remove the protection caps from the
pump flanges.
x Handle the pump or the pump-motor-base 4.3.3 Lengthy installation stoppage
plate assembly with care and avoid impacts. In the event of installation stopping for more than
3 weeks (this period could be much more shorter
in unfavorable climatic conditions), drain the
pump, wash it with fresh water and spray the cor-
4.2 Unpacking rosion-resistant agent inside. Make sure that the
Just after taking delivery of the equipment and product used is compatible with the pump materi-
before unpacking, a visual control of the packing als and complies with the environmental protec-
is recommended. If transport damage is visible, tion and personnel safety regulations currently in
its extent is to be noted on the receipt or on the force
delivery note. Possible claims are to be lodged
immediately with the carrier.
4.4 Handling
The electric motor-pump assembly weights, as
4.3 Preservation and storage well as those of the various components, are
After platform testing, every pump is drained and specified on the drawings in the appendix at-
an internal corrosion-resistant protection is ap- tached.
plied (except for pumps in stainless material or

Doc.No.: CEH04ABE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 00 alterations due to engineering development Member of Group
Date: 03/10/2000 Sterling Fluid Systems
Unpacking, handling, storage Page 2 of 2 Chapter 4

x During slinging and handling of the pump or


the unit, make sure that the hoisting ropes or
slings cannot escape from the hook. x When using a single hoisting rope or sling,
it is necessary to cross them in the hook to
prevent them slipping and the load tipping
during handling.

Fig.4.1
Handling the pump Fig.4.3

Fig.4.2
Handling the pump unit

Doc.No.: CEH04ABE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 00 alterations due to engineering development Member of Group
Date: 03/10/2000 Sterling Fluid Systems
Installing the pump Page 1 of 6 Chapter 5

5.0 Installing the pump


5.4 Tools
The assembly and installation of the pump or of the
5.1 Preconditions electrical pump unit does not require any special
The pump or the electric motor-pump assembly tools, only regular tools of a mechanical and
must have been unpacked and transported in electrical workshop are needed.
conformity with the recommendations shown in
chapter 4.
5.4.1 Environmental conditions
The permissible ambient temperature is between –
5.2 Personnel qualifications 20°C and + 60 °C. The humidity of the air should
The work described in this chapter must be carried be as low as possible in order to avoid corrosion.
out by qualified and authorized personnel only.

5.4.2 Base and foundation


5.3 Safety measures The pump or the electrical pump unit must be
installed always on a horizontal floor or foundation
not subject to external vibration. In case of doubt
use vibration dampening feet.
For the pumps equipped with shaft sealing by
stuffing box, provide a seepage recovery pipe.
x Remove the caps from the pump flanges only
when connecting the pipes.
x Connect the pipes carefully as to avoid any 5.4.3 Space required
leakage when subjected to pressure. The space required for installing the pump unit is
x Make sure that the gate-valves at the suction end shown in the overall dimensions drawing attached.
and at the discharge end are closed.
Make sure there is easy access to the shut-off gates
x Observe internal regulations concerning
and valves as well as to the measuring instruments.
conditions of operation.
x Wash off the corrosion-resistant substance as
shown in chapter 4 to prevent any contamination
of the plant. 5.5 Checks before installation
x Provide an electric motor control switch and
protection system.
Caution

The following points must be checked before


installing the pump or the electric motor-pump
x Check that all electrical connections are free from assembly:
voltage and ensure that the installation cannot be 1. Absence of voltage on the electrical connection
switched on inadvertently. and ensure that the installation cannot be
switched on inadvertently.
2. Compatibility of the electric power cable with the
power of the motor concerned.
3. Cleanliness and insulation of the suction line and
discharge line and of the other related pipes.
4. It should be possible to rotate the pump easily by
hand.
Doc.No.: CEH05ABE Information subjected to technical Sterling Fluid Systems (France)
Rev.: 02 alterations due to engineering development Member of Group
Date: 02/10/2003 Sterling Fluid Systems
Installing the pump Page 2 of 6 Chapter 5

5. Observance of instructions, regulations and


internal precautions to be observed when
carrying out the installation.
Caution

5.6 Mounting the electric motor-pump The couplings are to be assembled on the shafts
assembly in the installation taking care to avoid any impact. They can be
heated to facilitate assembly. The shaft ends must
be perfectly aligned, and the distance between the
two Sterling SIHI half-couplings must be 2 to 3 mm.
Caution
straight edge

1. Check that the general instructions given in 3.1


concerning piping are respected.
2. Make the unit perfectly level on its foundation
a b
block by using metal shims; take care that
these shims are as close as possible to the
anchoring points.
3. Carry out an even diagonal tightening of the b1
a1
unit retaining bolts on its foundation block,
taking care not to cause deformation of the
base. 2 to 3 mm
4. Check and adjust if necessary, the pump/motor a = a1 b = b1
alignment (see 5.7). Fig.5.1
5. Remove the protective caps from the pump
flanges, taking care that no foreign body enters If couplings other than Sterling SIHI couplings are
the pump. used, refer to the manufacturer's instructions.
6. Check and adjust if necessary, the positioning
of the pipe flanges on the pump flanges; no
stress must be applied to the pump flanges
during positioning and tightening. When using
in conditions of varying temperature, take care
particularly to avoid the transfer of stresses to
the pump flanges due to piping expansion. x It is essential that the coupling is equipped with a
7. Check the presence and the correct positioning guard in accordance with current regulations on
of the seals between the flanges. the prevention of accidents and the protection of
8. Tighten the piping flanges evenly and persons.
diagonally on the pump.
9. Check the pump/motor alignment (see 5.7)
and readjust it, if necessary, by loosening the
flanges and starting again at point 4.

5.8 Coupling in ATEX conform


5.7 Coupling pumpsets
Doc.No.: CEH05ABE Information subjected to technical Sterling Fluid Systems (France)
Rev.: 02 alterations due to engineering development Member of Group
Date: 02/10/2003 Sterling Fluid Systems
Installing the pump Page 3 of 6 Chapter 5

The following instructions for couplings need


especially to be followed for pumpsets which are
manufactured in conformity with Directive 94/9/EC Failure to observe these instructions
for operations as category II equipment in may result in breakage of the coupling. Danger from
hazardous areas. flying fragments! The coupling then becomes an
exlosion hazard.
Limitations
Only the coupling type BDS and HDS is released for Mounting the coupling parts
pumpsets in conformity with 94/9/EC. Before beginning installation, the shaft ends and the
coupling parts must be carefully cleaned. Before
These couplings are designed to be operated cleaning the coupling parts with solvent the flexible
according the following parameters: elements must be removed.
o Max 25 starts per hour If necessary, heating the coupling parts (to max
o Daily operating cycle up to 24 h 150°C) will facilitate fitting. With temperatures over
o Operation within the specified alignment 80°C the flexible elements must be removed from
o Temperature range -30°C to +80°C in the the coupling part s before heating.
immediate vicinity of the coupling

Storage
If coupling parts are stored as spare parts, the Coupling parts must be fitted with
storage area must be dry and free from dust. The the aid of suitable equipment to avoid damaging the
flexible elements must not be stored with chemicals, shaft bearings through axial joining forces. Always
solvents, motor fuels, acids, etc.. Furthermore they use a suitable lifting equipment.
should be protected against light, in particular direct
sunlight and bright artificial light with high ultraviolet The shaft ends must not project from the inner sides
content. of the hub. Axial securing is effected by means of
the set screw.

The storage area must not contain


any ozone-generating equipment, e.g. fluorescent Tightening the set screws to a
light sources, mercury vapour lamps, high voltage tightening torque in accordance with the table 5.C.3.
electrical equipment. Damp storage areas are
unsuitable. Ensure that no condensation occurs.
The most favourable atmospheric humidity is below
65%. Failure to observe these instructions
may result in breakage of the coupling. Danger from
Installation flying fragments! The coupling then becomes an
Type B and H couplings shall never be operated explosion hazard.
in pumpsets category II.
After fitting the coupling parts onto the shafts the
The flexible elements are delivered in different flexible elements, if previously removed must be
materials and are then differently couloured or fitted. Previously heated coupling parts must have
marked with stripes in different colours. Only cooled down again to a temperature below +80°C. It
elements of one type must be used in one must be ensured that the flexible elements are of
coupling. identical size and colour or have identical marking.

When assembling a pumpset with a coupling, Move together the components to be coupled.
the fits of the bores and shafts must be checked,
see table 5.c1

Table 5.C.1 Tolerances for coupling fit Danger of squeezing!


Fit Nominal Shaft Coupling
diameter tolerance bore Alignment
tolerance The couplings connect the 2 shaft ends of the driver
Shaft ” 50 mm k6 H7 and the pump. The alignment of the shaft ends
tolerance > 50 mm m6 needs to be adjusted within the following tolerances.

The errors of alignment are differentiated into:

Doc.No.: CEH05ABE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 02 alterations due to engineering development Member of Group
Date: 02/10/2003 Sterling Fluid Systems
Installing the pump Page 4 of 6 Chapter 5

o Axial misalignment: the allowable


difference between maximum and minimum
axial gap S between the two coupling halfes is Operation:
given Table 5.C.2.
o Angular misalignment: this can
If any irregularities are registered
usefully be measured as the difference in the
during operation (vibrations or noise) the pumpset is
gap dimension ǻS = Smax – Smin. The allowable
to be switched off immediately. Determine the cause
values are given in Table 5.C.2 depending on
of the fault using the fault list in Chapter 8. This list
coupling size and speed
contains possible faults, their reasons and
o Radial misalignment is the radial
succested actions.
offset between the shaft centers.
If the analysis is not possible then contact the
The allowable values are the same ǻs values
Sterling Service.
like for the angular misalignment given in Table
5.C.2..
Maintenance:
The method to adjust the alignment is:
first correct the angular misalignment regular control of the torsional
then correct the axial gap backlash is necessary to prevent breakdown.
then correct the radial misalignment.
The useful tool are a feeler gauge and a ruler as The torsional backlash is to be measured in the
shown in figure 5.C.2. following way: One coupling part is rotated against
the other with no torque to a stop. Then this position
Table 5.C.2 Alignment dimensions of the two coupling halfes is marked as shown in the
left had picture of figure 5.C.3. Then the coupling
Coupling Axial Angular and radial alignment
type gaps ǻS max in mm parts are rotated into the other direction as far as
BDS at speed possible without torque. The distance between the
mm 750 1000 1500 2000 3000 two marks is the backlash measure delta sb. The
1/min 1/min 1/min 1/min 1/min maximum values for this measure are given in table
76 2–4 0,25 0,2 0,2 0,15 0,15 5.C.4 by coupling size. If this measure is exceeded,
88 2–4 0,25 0,2 0,2 0,15 0,15 then the flexible elements need to be exchanged.
103 2–4 0,25 0,25 0,2 0,2 0,15
118 2–4 0,3 0,25 0,2 0,2 0,15
135 2–4 0,3 0,25 0,25 0,2 0,15
152 2–4 0,35 0,3 0,25 0,2 0,2 the flexible elements must be
172 2–6 0,4 0,35 0,3 0,25 0,2 replaced in sets (all elements of one coupling at
194 2–6 0,4 0,35 0,3 0,25 0,2 once, independent of the individual wear) Only
218 2–6 0,45 0,4 0,3 0,3 0,2 identically marked flexible elements must be used.
245 2–6 0,5 0,4 0,35 0,3 0,25 Only spareparts from the original equipment
manufacturer is allowed for replacement.
Fixing the coupling on the shaft.
Table 5.C.4 Torsional Backlash measure
For fixing the coupling parts on the shaft there are
set screws, which need to be locked with the Size 76 88 103 118 135 152 172
following torque depending on coupling size: Delta 7,0 5,0 7,0 9,0 10,5 11,5 9,0
mm
Size 194 218 245
Table 5.C.3 Torque for Set Screws delts 8,0 7,0 6,5

Size 76 88 103 118 135 152


Torque Nm 4 4 4 4 8 8
Size 172 194 218 245
Torque Nm 15 25 25 25

Doc.No.: CEH05ABE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 02 alterations due to engineering development Member of Group
Date: 02/10/2003 Sterling Fluid Systems
Installing the pump Page 5 of 6 Chapter 5

Figures:

Figure 5.C.1 Measures for checking alignment

Smax Smax

•S

Smin Smin
•S = Smax - Smin

Figure 5.C.2 Checking of alignment

Ruler

Figure 5.C.3 Measurement of Torsional Backlash

•Sb

Doc.No.: CEH05ABE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 02 alterations due to engineering development Member of Group
Date: 02/10/2003 Sterling Fluid Systems
Installing the pump Page 6 of 6 Chapter 5

5.9 Pump mounting for operation at


high temperature 5.12 Hydrostatic pressure test
When subjecting the piping system to a
hydrostatic pressure test, exclude the pump from
this test. Otherwise make that no foreign bodies
can enter the pump.
Caution

x If this pump is intended to convey a hot fluid,


(with cooled shaft sealing), the retaining
screws at the pump drive end are to be locked.
x The nuts and spring washers at the opposite
The hydrostatic test pressure for the pump must
end must allow for pump dilation in the
not exceed 1.3 times the nominal pump
longitudinal direction.
pressure. (See the data sheet in the appendix).

After mounting the two spring washers in the


opposing position shown, position the flat washer
and screw the self-locking nut into contact (the
washers must be able to be moved by hand).
Then tighten the two self-locking nuts half a turn.

retaining
stud self-locking nut
pump foot
flat washer

spring
base washers

Fig.5.2

5.10 Monitoring and regulation


The monitoring / regulation accessories and
instruments must be set up in accordance with
their individual instructions (see appendix).

5.11 Final checks


The following final checks must be carried out:
x Check all tightening that has been carried out
during the mounting of the pump in the
installation, particularly the tightening of the
connecting flanges.
x Check that the pump can be rotated easily by
hand (turn the motor fan for this).
x Check the alignment.
x Verify the presence and check the fastening of
the coupling guard.

Doc.No.: CEH05ABE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 02 alterations due to engineering development Member of Group
Date: 02/10/2003 Sterling Fluid Systems
Commissioning and Page 1 of 3 Chapter 6
decommissioning

6.0 Commissioning and


decommissioning

6.1 Preconditions x As soon as the rated speed is attained, the


The pump or the electrical pump unit must have flow adjustment will be done by means of the
been installed according to the directions and gate-valve placed at the discharge end of the
instructions in chapter 5. pump. The gate-valve at the suction end must
always be open during operation to prevent
cavitation, both during effective suction and
6.2 Personnel qualification under load.
The work described in this chapter must be
carried out by qualified and authorized personnel
only.
6.4 Filling the pump

6.3 Safety measures


Caution
To preserve the installation from pollution by the
anti-corrosion product and to avoid any
compatibility problem with the pumped substance,
the pump must be rinsed out. The anti-corrosion
x All electrical connections are to be carried out
product is water-soluble.
according to the rules of the trade, in
accordance with current relevant
requirements, laws and regulations.
x Only authorized and qualified personnel may Before the first start, the pump and the suction
carry out this work. line, must be completely filled with the pumping
liquid to prevent the pump running dry and to
avoid the formation of air pockets and thermal
shock.

x Fill the pump correctly in order to avoid any


damage due to dry operation (the shaft sealing 6.5 Electrical connection
or sleeve bearings could be destroyed and The motor has to be connected according to the
moving parts could seize). circuit diagram in the terminal box. (See safety
x Check the direction of rotation only after filling measures in 6.3).
the pump and at the precise moment
described in 6.7.
x Fill the pump very slowly if hot pumping liquid 6.6 Accessories
is used in order to avoid distortions or thermal The installation and connections of the
shock. accessories must be carried out in accordance
x When pumping explosive, harmful, hot, with their attached commissioning instruction
crystalline or corrosive products, ensure that manuals. (See appendix).
persons and the environment are not
endangered.

Doc.No.: CEH06ABE Information subject to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date: 02/04/2003 Sterling Fluid Systems
Commissioning and Page 2 of 3 Chapter 6
decommissioning

6.7 Checking before switching-on If the pumping pressure does not constantly
rise with increasing speed, stop the motor
again and bleed the pump carefully again.
5. After reaching operating speed, adjust the
Caution
operating point of the pump by means of the
regulating gate-valve in the discharge line.
Before switching-on the pump unit, ensure that
nobody can be endangered by starting the pump
unit.
It is mandatory to check the following points:
Caution
1. The pipelines are all connected and the unions
are leak proof. Operating with the gate-valve closed at the
2. The pump and pipes are correctly filled and air discharge end, even for short durations, is
has been bled. possible only if the installation is equipped with a
3. The cooling system supply (if applicable) is by-pass providing for circulation of the minimum
open and its system has been bled. flow necessary for the correct operation of the
4. If the installation is protected by a relief valve pump. If not, operating with the gate-valve closed
make sure that its adjustment is correct, at the discharge end quickly causes destruction of
particularly in accordance with the pressure the sealing and seizing of the moving parts.
rating of the pump housing.
5. The regulating gate-valve at the discharge
end is fully opened. 6.9 Frequency of switching on/off
6. The gate-valve at the suction end is completely The CEHA pump may be switched on up to 15
open. times per hour.
7. The coupling alignment has been checked and
is correct (see chapter 5).
8. The coupling guard is in place. 6.10 Checks during operation
9. The motor is ready for operation.
10.At this point check the direction of rotation
of the motor (short pressure on the switch), the
rotation of the CEHA pump is anti-clockwise
Caution
when facing at the end of the pump drive shaft.
During operation, the following points must be
checked:
6.8 Commissioning x Constant rotation speed and pressure at the
discharge end.
For commissioning proceed as follows:
x The pump runs regularly, smoothly, and
1. Open the gate-valve at the suction end fully.
without vibration.
2. Open the regulating gate-valve at the
x Check the liquid level in the tank at the suction
discharge end fully. When pumping
end.
condensates, only half-open this valve (see
x Check the temperature of the pump bearing
3.4).
(maximum temperature 80 °C or 50 °C above
3. Switch on the motor.
the ambient temperature).
4. Check the pressure on the pressure gauge at
x Check the temperature of the shaft sealing
the discharge end.
coolant.
Doc.No.: CEH06ABE Information subject to technical Sterling Fluid Systems (France)
Rev.: 01 alterations due to engineering development Member of Group
Date: 02/04/2003 Sterling Fluid Systems
Commissioning and Page 3 of 3 Chapter 6
decommissioning

x If shaft sealing is provided by a stuffing box, 10 6.11 Decommissioning


to 20 drops per minute leakage is necessary When decommissioning the unit, proceed as
and normal to avoid overheating of the sealing follows:
system. 1. Shut-off the motor power supply.
x If shaft sealing is provided by a rotating 2. Close the regulating gate-valve at the
mechanical seal, a slight leak is possible at the discharge end.
first startup; if the conditions allow it, let it run 3. Close the gate-valve at the suction end.
for 30 minutes so that the components take up 4. Close the shaft sealing coolant inlet.
their positions. If the leak persists, dismantle. Drain the pump if there is a risk of freezing.

Caution
If draining the pump produces explosive, harmful,
In the event of significant leakage, stop the pump
or crystalline products, take the necessary
as soon as possible, and check the shaft sealing.
measures to protect persons and the
environment.
If the pump has to be dispatched elsewhere, it
must be free of any dangerous product.
In the event of prolonged stoppage of the pump, it
must be rinsed and then protected internally with
a suitable anti-corrosion product.

Doc.No.: CEH06ABE Information subject to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date: 02/04/2003 Sterling Fluid Systems
Maintenance, disassembly, Page 1 of 6 Chapter 7
assembly

7.0 Maintenance, disassembly, After 8 000 service hours, or at the latest 2 years
assembly after commissioning, check the inner sleeve bear-
ing for wear. Change it if necessary.
7.1 Preconditions
The pump or the electrical pump unit must be put Shaft sealing
out of operation in accordance with the instruc- During operation, the mechanical seal does not
tions in chapter 6. require any maintenance. As a general rule, it
can be considered that the mechanical seal has
7.2 Personnel qualification the same life time as the plain bearings of the
The work described in this chapter must be car- pump.
ried out by qualified and authorized personnel A shaft eccentric deviation of 0.08 mm and the
only. vibrations generated by cavitation can cause rup-
Any work on electrical connections must be car- ture of the film that lubricates the friction surfaces
ried out by authorized skilled staff only. of the mechanical seal and cause intermittent dry
operation. Under these operating conditions, the
7.3 Safety measures lifespan of the mechanical seal can be signifi-
cantly reduced.
A slight leak can appear during the first operating
hours. If this persists, disassemble and clean the
friction surfaces.
Replacement of the mechanical seal: see 7.7.4
x If the pump has conveyed an explosive, hot,
toxic, crystalline, etc. product, the necessary 7.5 Disassembly
measures must be taken to ensure that per-
sons and the environment are not endangered. 7.5.1 Preparation for disassembly
x If the pump is to be despatched elsewhere, it Proceed as follows:
must be free from any trace of pumped prod- 1. Ensure that the power supply is switched-off
uct. and cannot be switched-on inadvertently
x Since the pump might still contain pumped during the operation.
product, it must be carefully rinsed prior to dis- 2. Disconnect the motor in the terminal box.
assembly. 3. Shut-off the isolation gate-valves at the suction
and discharge ends, and carefully drain this
part of the installation.
7.4 Maintenance and inspection 4. If necessary, disconnect and dismantle the
measuring and checking instruments.
5. Disassemble the pump flanges and disassem-
ble the pump from the base plate.
Caution 6. Drain, and then rinse the pump, if necessary.

After commissioning this kind of pump requires


only little maintenance.
For checks during operation refer to 6.10.
Bearings
The ball bearing is lifetime lubricated and does
not require any maintenance.

Doc.No.: CEH07BE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date: 02/04/2003 Sterling Fluid Systems
Maintenance, disassembly, Page 2 of 6 Chapter 7
assembly

7.5.2 Spare parts CAUTION


When ordering spare parts, note the information
shown on the pump identification plate, that is to The hexagonal nut 9220 has a left-hand thread
say:
1. The exact type of pump.
2. The complete pump identification number. 5. Disassemble successively the impellor 2310,
Use the cross-sectional drawing attached to note the key 9402, the centrifugal body 1080 and
the Part Numbers of the items required. the shaft sleeve 5240 (only sizes 4100 –
The spare parts must meet the manufacturer 6100), then the retaining stage 1081 (for
technical requirements, and the guarantee is only pumps with this feature).
valid when genuine original parts are used. 6. Then disassemble the inlet body 1090, the
Sterling SIHI will not held liable in the event of vane impeller 2350, the key 9411 (9401) and
failure or accident related to the use of parts other the discharge body 1140. Repeat this proce-
than genuine parts. dure as many times as there are stages, (the
last discharge body bears the number 1141).
7. Remove the screws 9011 and the bearing cap
7.5.3 Disassembly of the pump 3600, then remove the circlip 9320, and the
See the sectional drawing attached. spacer 5051.
The working surface must be clean, free from dirt, 8. Separate the bearing casing 3500 from the
filings etc. and be perfectly clear. discharge flange 1070 and from the stuffing
1. To facilitate later assembly make a mark over box casing 4510 by removing the screws
the entire length of the pump body and num- 9012.
ber the parts. 9. Use a hub puller to extract the bearing casing
2. Disassembly starts at the suction end. 3500 with the ball bearing 3210 and the spacer
3. Remove the nuts 9201, the flat washers 5500, 5050.
the spring washers 9512 (only for model with 10.Remove the complete cover 4710, after having
cooling casing), the tie bolts 9050 and take off removed the screws 9010. Extract the me-
the suction flange 1060. chanical seal casing 4410.
11.Measure and note the position of the mechani-
cal seal on the shaft (for use during re-
assembly), then disassemble it.

The pump can still contain a residue of pumped


fluid or rinsing product. Take precautions to con-
tain any leakage.

4. Release the lock washer 9310 and loosen the


hexagonal nut 9220 while holding the shaft
with a strap wrench or gripping it in a soft jaw
vice.

Doc.No.: CEH07BE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date: 02/04/2003 Sterling Fluid Systems
Maintenance, disassembly, Page 3 of 6 Chapter 7
assembly

with unsuitable equipment can cause an acci-


7.6 Work after disassembly dent following on a leak.
Sterling SIHI reserves the exclusive right to carry
out service operations on these components.
7.6.1 Cleaning instructions 4. Shaft 2100
Any strong marking on the shaft, at the mechani-
cal seal, at the lip sealing ring or at the shell
bearing positions requires the shaft to be
changed.
5. Shall bearing 0241and 5452
The use of some solvents requires special pre- In the event of severe wear of the shell bearing
cautions. Refer to the supplier's recommendations 0241 (play >0.2mm) and 5452 (stainless steel
and to current regulations. pumps), change it as follows:
x Extract the worn shell bearing.
x Degrease the bore using a solvent. Coat the
Clean all parts using an appropriate solvent. A parts with adhesive in accordance with the in-
scraper can be used to remove the adhesive resi- structions of the adhesive manufacturer (Loc-
due from the mating faces of the bodies; when tite 640 or equivalent).
carrying out this operation, take care not to dam- x Cold-press the shell bearing.
age the surface finishes. For the shell bearing 241, pay attention to the
angular orientation of the lubrication groove (Fig
7.6.2 Repair instructions 7.1) in the body 1080.

Caution

The following parts must be checked carefully:


1. Ball bearing 3210
Since bearing is lubricated for life, it does not
require any maintenance. Check it for wear
and change it if necessary. 35°
2. Lip sealing ring 4210
If the shaft is marked at the corresponding loca- Fig 7.1: drive end view
tion, change the lip sealing ring; pay attention
to the correct mounting position to prevent the 6. Body 1090, 1140, 1141
grease from escaping and to prevent dirt en- The body surfaces in contact with the wheel may
tering. be re-machined to max. 0.5 mm with a devia-
3. Mechanical seal 4330 tion of plane parallelism of 10 µm in relation to
Change defective O-rings, check the friction sur- the mating surfaces. The max. admissible
faces. If necessary, change the complete me- roughness height of the re-machined surface
chanical seal and observe the dimension will be Rt = 6 µm. The mating surface of the
noted during disassembly (see 7.7.4). body 1090 has to be re-machined also, in such
Some components are machined within a toler- a way that the depth of the body is greater by
ance as low as 0.2 micron. Any re-machining min. 0.10 mm to max. 0.13 mm (sizes
Doc.No.: CEH07BE Information subjected to technical Sterling Fluid Systems (France)
Rev.: 01 alterations due to engineering development Member of Group
Date: 02/04/2003 Sterling Fluid Systems
Maintenance, disassembly, Page 4 of 6 Chapter 7
assembly

1200/3100/3600) and by min. 0.15 mm to max. x It is mandatory to make sure that bodies are
0.20 mm (sizes 4100/5100/6100) in relation to correctly orientated to ensure correct operation
the thickness of the vane impeller. of the pump (use the body assembly diagram
Since hydraulic performance is linked to the depth attached). The reference marks traced before
of the bodies, do not re-machine more than disassembly simplify this work.
necessary. x For pumps which require adhesive, immedi-
N.B.: For multi-stage pumps and for a complete ately coat the mating faces of the bodies 1140,
overhaul, it is preferable to mix new stages 1141, 1080, and 1090 so as to allow the adhe-
and old re-machined stages to avoid out-of- sive to cure slightly before assembly.
line keying, losses of efficiency or pump
mounting brackets out-of-line with base plate 7.7.2 Tightening torque
mounting holes. Nuts and bolts will be tightened using a torque
7. Vane impeller 2350 wrench. The following tightening torques must be
Re-machining of the wheel involves uncontrolled applied:
changes in specifications and interchangeabil-
ity is no longer guaranteed. Rated Ø M5 M6 M8 M10 M12 M16 M20
8. Body shell bearing 0242 Torque Nm 4.5 8.5 12 25 40 90 175
(Sizes 4100 to 5100 as from 5 stage models,
for cast iron pumps and all stainless steel
pumps). In the event of severe wear, change 7.7.3 Assembling the pump
the bearing. They have to be cold-pressed and 1. Insert the lip sealing ring 4210 into the bearing
coated with a product like Loctite 640 or casing 3500, place into position the spacer
equivalent. 5050 and the ball bearing 3210. Position the
9. Shaft sleeve 5240 bearing cap 3600.
(Sizes 4100 to 6100 only) 2. Press the stationary sealing ring with its O-ring
10.In the event of severe wear, change it. into the cover 4710.
3. Take care not to damage the mechanical seal;
position and secure the mechanical seal on
7.7 Assembly the shaft 2100 in accordance with the dimen-
sion noted during the disassembly.
4. Position the shaft equipped with its mechanical
7.7.1 Instructions before assembly seal, the cover 4710, then pass this assembly
x Make sure that all the parts have been into the bearing casing 3500, the spacer 5050
checked and are perfectly clean (mating and the ball bearing 3210.
faces, body faces). 5. Remove the bearing cover 3600, position the
x Coat all sliding surfaces with molybdenum spacer 5051 and the circlip 9320.
disulfide paste, except carbon surfaces. 6. Secure the bearing cap 3600 using the screws
x Sealing of hydraulic part body mating sur- 9011.
faces is by: 7. Assemble the mechanical seal casing 4410
- EPPLE 33 adhesive or equivalent for cast and the discharge flange 1070 on the shaft
iron pumps. and bearing casing assembly previously as-
- Soft Teflon cord for stainless steel pumps (Ø sembled, then secure with the screws 9012.
0.75 mm for sizes 1200, 3100, 3600 / Ø 1 mm 8. Position the assembly vertically on the bench
for sizes 4100, 5100, 6100). (drive shaft end downwards), wedge it or

Doc.No.: CEH07BE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date: 02/04/2003 Sterling Fluid Systems
Maintenance, disassembly, Page 5 of 6 Chapter 7
assembly

clamp the shaft end in an opening in the 9201 9512


bench.
9. Mount the discharge body 1141 (1140 for the
following stages), the key 9411 (9401), the
vane impeller 2350 and the suction body 1090.
(for pumps with sealing by soft Teflon cord, in-
stall the cord as assembly progresses, coating
it lightly on the mating surface with grease be-
fore positioning it, cross the two ends of the
cord over a distance of 10 mm length and flat- 5500 9050
ten the junction delicately, using the flat of a Fig.7.2
hammer. Complete compression will come Location of spring washers at the suction end
with the final tightening of the pump. Repeat
this procedure, as many times as there are 12. Place the pump on a surface plate,
stages, until all stages are installed. Make sure straighten the retaining lugs and gradually tighten
that bodies are correctly orientated in accor- the tie bolt nuts 9210 two by two diagonally, ob-
dance with the locating drawing attached. Re- serving the tightening torques specified in 7.7.2.
assemble the retaining stage 1081 (for the 13. Insert the key 9400 and the coupling half-
pumps with this feature). Then reassemble sleeve, without hitting it; heat it if necessary.
the sleeve 5240 (only sizes 4100 to 6100), the
centrifugal body 1080 (do not forget the posi-
tioning of the soft Teflon cord sealing for 7.7.4 Changing the mechanical
pumps which require it), the key 9402 and the seal
vane impeller 2310. Changing the mechanical seal can be done with-
10.Position the lock washer 9310. Tighten the out disassembling the pump entirely.
wheel nut 9220 and secure it by bending the
lock washer . 1. Remove the screws 9011, remove the bearing
cap 3600, the circlip 9320, the spacer 5051
and the screws 9012.
2. Extract the bearing casing 3500 with its ball
CAUTION
bearing 3210 and the spacer 5050, then re-
move the screws 9010 and the cover 4710.
The hexagonal nut 9220 has a left-hand thread
3. Measure and note the position of the mechani-
cal seal, then disassemble it.
4. Mount the stationary sealing ring with its O-ring
11. Mount the suction flange 1060, the tie bolts
in the cover 4710.
9050 with the spring washers 9512 (models
5. Take care not to damage the mechanical seal
with cooling casing) and the flat washers 5500.
when passing over the shaft shoulders. Posi-
Tighten the nuts 9201 slightly. Grease the tie
tion and secure the mechanical seal and ob-
bolt ends, the washers and nuts for better
serve the dimension noted during disassem-
tightening torque distribution.
bly.

Doc.No.: CEH07BE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date: 02/04/2003 Sterling Fluid Systems
Maintenance, disassembly, Page 6 of 6 Chapter 7
assembly

6. Position the mechanical seal casing 4410 and


secure with the screws 9010; do not lock the
cover 4710.
7. Mount the bearing casing 3500 with the spacer
5050 and the ball bearing 3210; pay attention
to the position of the guide pin 5610, then se-
cure with the screws 9012.
8. Position the spacer 5051, the circlip 9320, the
bearing cap 3600 and the screws 9011.
9. Place the pump on a surface plate and align it
if necessary, then check the tightening of the
nuts and bolts and complete the tightening of
the screws 9010.

7.8 Checking after assembly

Caution

1. Check that the pump rotates freely by hand.


2. Check and if required, correct the tightening
torque of the tie bolt nuts. Leave the pump
several hours before operating it (to allow the
sealing compound to dry).
3. Perform a hydrostatic test under maximum
pressure equal to 1.3 times the rated pressure
(see the data sheet for the definition of the
rated pressure). Choose a test liquid compati-
ble with the pumped product.
4. After the test, check the tightening torque of
the tie-bolts, correct if necessary.

7.9 Installing in the plant


When installing in the plant, observe the notes
shown in chapter 5.

Doc.No.: CEH07BE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date: 02/04/2003 Sterling Fluid Systems
Help in case of trouble Page 1 of 1 Chapter 8

8.0 Troubleshooting

8.1 Personnel qualifications

Troubleshooting must be carried out by qualified, authorized personnel only.

Problem Cause Solution


Poor performance - Counter pressure too high. Check and readjust the operating point.
Clean the pipes.
- Pump or pipe not full or not completely Bleed and fill the pump and the suction
free of gas. line.
- Suction lift too high or positive suction Check the level of liquid in the tank; open
head too low. the gate-valve at the suction end.
Clean the filter at the suction end.
- Clearances too large due to wear. Replace worn pump parts.
- Wrong direction of rotation. Reverse two phase wires on the motor.
- Foreign body in pump. Open and clean pump.
- Stuffing box too loose. Re-tighten the gland.
- Air leakage between bodies or at flanges Re-machine the bodies sealings.
on the suction line. Replace the flange seals.
Pump runs irregular or noisy - Bodies, shaft sealing, foot valve or Check the body seals.
suction line leaking. Check the shaft sealing.
Check the flange mating.
- Suction lift too high or positive suction Check the liquid level in the tank; open the
head too low. gate at the suction end.
Clean the filter at the suction end.
- Stresses on the pump or on the electric Check the mounting of the pump, the
motor /-pump assembly. coupling alignment and the pipe coupling.
- Foreign body in the pump. Open and clean the pump.
Pump leaking - Leak between the bodies due to loose tie- Check the tightening torque of the tie bolts
bolts. nuts, if the leakage remains re-work the
intermediate pieces sealing.
- Leak at mechanical seal. Check the friction surfaces, replace the
sealings if necessary.
- Leak at stuffing box too large. Adjust the stuffing box.
Change the stuffing box packing rings.
High pump temperature - Pump or pipe not completely filled. Bleed and fill the pump and the suction
line.
- Suction lift too high or positive suction Check the liquid level in the tank; open the
head too low. gate-valve at the suction end.
Clean the filter at the suction end.
- The pump operates with the discharge Open the discharge gate-valve or install a
gate closed without by-pass or the by-pass, check the minimum output.
minimum rated output is not respected.
Motor protective circuit breaker - Stresses on the pump or on the electric Check the mounting of the pump, the
motor / pump assembly. coupling alignment and the pipe coupling.
opens
- The specified operating point is not Check and adjust the operating point (see
correct. data sheet).
- Absorbed current higher than the Check the motor protective circuit breaker
specified max. limit value of the thermal and the electrical connections.
relay.
- Stuffing box too tight. Adjust the stuffing box.
- Foreign body in the pump. Check the pump for free rotation, dismantle
and clean the pump.

Doc.No.: CL08E Information subject to technical Sterling Fluid Systems (France)


Rev.: 00 alterations due to engineering development Member of Group
Date: 03/10/2000 Sterling Fluid Systems
Appendices Page 1 of 12 Chapter 9

9.0 Appendices
9.1 Cross sectional drawing - CEHA pump – shaft sealing by single mechanical seal
*only for sizes 4100 to 6100 as from 5-stage models (cast iron pumps), on any size for stainless steel
pumps. **only for sizes 4100 to 6100.
***flat key (9401) for sizes 5100 and 6100. ****only stainless steel pumps.
Fig.9.1b

2100
9400

9320
9011

3210
3600
5051

5050
4710
5605

3500
4330

4210
9012

9010
4410

5610
9030
4110
5452****
1141
1070

9401***
9411

2350
1140

1090
0242*

0241
5240**

1080
9402

2310
9050
5500

9310
9201

9220
1060

Doc.No.: CEH09BE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date : 02/04/2003 Sterling Fluid Systems
Appendices Page 2 of 12 Chapter 9

9.1.1 Cross sectional drawing - CEHA pump – shaft sealing by single cooled mechanical seal
*only for sizes 4100 to 6100 as from 5-stage models (cast iron pumps), on any size for stainless steel
pumps. **only for sizes 4100 to 6100.
***flat key (9401) for sizes 5100 and 6100. ****only stainless steel pumps.
Fig.9.2.b

5051

9400

2100
9011

9320
3600

3210
4710
5605

5050
4330

3500
9030
4110

9012

4210
9040

9010
4410

5610
9030
4110
1141

5452****
1070

9401***
9411

2350
1140

1090
0242*

0241
5240**

1080
9402

9050

2310
9512

9310
5500

9220
9201

1060

Doc.No.: CEH09BE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date : 02/04/2003 Sterling Fluid Systems
Appendices Page 3 of 12 Chapter 9

9.1.2 Cross sectional drawing - CEHA pump – with retaining stage, shaft sealing by single
mechanical seal
*only for sizes 4100 to 6100 as from 5-stage models (cast iron pumps), on any size for stainless steel
pumps. **only for sizes 4100 to 6100.
fig.9.3.b ***flat key (9401) for sizes 5100 and 6100. ****only stainless steel pumps.

2100
9400

9320
9011

3210
3600
5051

5050
4710
5605

3500
4330

4210
9012

9010
4410

5610
9030
4110
5452****
1141
1070

9401***
9411

2350
0242* 1140

1090

4212
1081

0241
5240**

1080
9402

2310
9050
5500

9310
9201

9220
1060

Doc.No.: CEH09BE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date : 02/04/2003 Sterling Fluid Systems
Appendices Page 4 of 12 Chapter 9

9.2 Appendix – Parts list


CEHA pump – shaft sealing by mechanical seal and cooled mechanical seal
0241 Bearing bush for intermediate 1080
0242* Bearing bush for intermediate 1140 (sizes 4100 to 6100 as from 5 stages)
1060 Suction casing
1070 Discharge casing
1080 Intermediate piece
1081 Retaining stage
1090 Intermediate piece
1140 Intermediate piece
1141 Intermediate piece
2100 Shaft
2310 Impeller
2350 Vane wheel impeller
3210 Grooved ball bearing
3500 Bearing housing
3600 Bearing cover
4210 Sealing ring for ball bearing 3210
4212 Sealing ring
4330 Mechanical seal
4410 Mechanical seal housing
4710 Cover
5050 Spacer
5051 Spacer
5240** Shaft sleeve (intermediate 1080), for sizes 4100 to 6100
5452**** Shell bearing (discharge casing), only for stainless steel pumps
5500 Flat washer (tie bolt)
5605 Stop pin
5610 Splined guide pin (discharge casing/stuffing box housing/bearing housing)
9010 Hexagonal screw (cover fixing)
9011 Hexagonal screw (bearing cover fixing)
9012 Hexagonal screw (discharge casing/stuffing box housing/bearing housing)
9030 Plug (discharge flange drain hole)
9040 Plugging screw (discharge flange for cooled mechanical seal version)
9050 Tie bolt
9201 Hexagonal nut (tie bolt)
9220 Hexagonal nut (shaft, left-handed thread)
9310 Lock washer for shaft nut
9320 Circlip (bearing)
9400 Flat key (motor drive)
9401*** Flat key (vane wheel impeller drive, sizes 5100 and 6100)
9402 Flat key (impeller 2310 drive)
9411 Disc key (vane impellor drive, sizes 1200 to 4100)
9512 Spring washer (pump equipped with cooling casing)

Doc.No.: CEH09BE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date : 02/04/2003 Sterling Fluid Systems
Appendices Page 5 of 12 Chapter 9

9.3 Appendix – Dimension drawing – CEHA pump


a f Ød2

uk ØD Øk
l DNA
dk6 w h2
u
uk
ØkE 15°
t c h1
DNE
Ød2 ue
e1 e2 s b
m2 q1 n2

m1 n1
ue: draining hole - uk: Connection to the sealing cooled casing
Dimensions: G1/4” for sizes 1200 à 5100 - G3/8” for size 6100
Fig.9.3
Sizes DNA DN b C e1 e2 f h1 h2 n1 n2 Q1 s d l t u w
E
1200 20 40 35 10 44 41 171 100 100 100 105 113 13 14 25 16.1 5 176
31/3600 32 65 35 12 50 42 201 112 132 112 135 134 13 19 40 21.5 6 214
4100 40 80 40 15 52 43 195 132 140 132 155 140 13 24 45 26.9 8 238
5100 50 100 45 18 60 66 237 160 165 160 170 159 15 28 50 30.9 8 276
6100 65 100 50 20 64 63 262 180 180 180 195 172 15 32 65 35.3 10 300
(In models with a stage cooling chamber or a retaining stage, the latter take the place of a hydraulic stage)
1 stage 2 stages 3 stages 4 stages
Sizes a m1 m2 a m1 m2 a m1 m2 a m1 m2
12.. 195 238 204 229 272 238 263 306 272 297 340 306
31/36.. 213 261 227 253 301 267 293 341 307 333 381 347
41.. 268 294 260 323 349 315 378 404 370 433 459 425
51.. 305 353 315 380 428 390 455 503 465 530 578 540
61.. 338 391 353 428 481 443 518 571 533 608 661 623

5 stages 6 stages 7 stages 8 stages


Sizes a m1 m2 a m1 m2 a m1 m2 a m1 m2
12.. 331 374 340 365 408 374 399 442 408 433 476 442
31/36.. 373 421 387 413 461 427 453 501 467 493 541 507
41.. 488 514 480 543 569 535 598 624 590 653 679 645
51.. 605 653 615 680 728 690 755 803 765 830 878 840
61.. 698 751 713 788 841 803 878 931 893 968 1021 983
Flanges connection as per DIN 2501 PN40
DNA/E 20 32 40 50 65 80 100
Øk 75 100 110 125 145 160 190
ØD 115 140 150 165 185 200 235
Ød2 x n 14 x4 18 x4 18 x 4 18 x 4 18 x 8 18 x 8 22 x 8

Doc.No.: CEH09BE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date : 02/04/2003 Sterling Fluid Systems
Appendices Page 6 of 12 Chapter 9

9.4 Appendix – CEHA pump - Forces and permissible moments on the flanges

MxA

FyA
FxA FzA

FxE FzE
MxE
FyE

Fig.9.4

If several individual forces are developed, the components of the resultants of these forces should
not exceed the acceptable values in each direction.
The pump brackets must be fixed on a plane base plate with uniform tightening.
If these conditions are not met, it is no longer possible to guarantee either the sealing or the general
mechanical behaviour of the pump.

Suction flange 1060 Discharge flange 1070


N N Nm
Sizes FxE FyE FzE FxA FyA FzA MxE MxA

1200 2500 4000 3000 2000 4000 2000 220 75

3100 3000 4500 3500 2500 4500 2200 320 120

3600 3000 4500 3500 2500 4500 2200 320 120

4100 3500 5000 4000 3000 5000 2400 400 160

5100 4000 6000 4500 3500 6000 2600 570 210

6100 4500 7000 4500 4000 7000 3000 660 290

Doc.No.: CEH09BE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date : 02/04/2003 Sterling Fluid Systems
Appendices Page 7 of 12 Chapter 9

9.5 Appendix – CEHA pump – Identification coding


Position Characteristic Code Definition
1-3 Type CEH Self-priming, multi-cellular, side channel pump, with low NPSH.

4 Construction A Early production stage.


5-8 Sizes 1201-6108 Size and number of stages.
9-10 …/5 Pump for LPG.
…/7 Pump for LPG with retaining stage.
11 Hydraulic A First hydraulic stage.
12 Bearing A One grooved ball bearing to DIN 625 and one liquid surrounded
sleeve bearing
13-15 Shaft sealing 001 Stuffing box flushed from internal source
501 Stuffing box with intensive cooling.
AAE Unbalanced standard mechanical seal, flushed from internal source
Brand: SFS – Type: FN - Mat.: EBPGG.
AA1 Unbalanced standard mechanical seal, flushed from internal source
Brand: SFS – Type: FN – Mat.: GBVGG.
AF3 Balanced standard mechanical seal, flushed from internal source
Brand: SFS – Type: Sterling GNZ – Mat.:Q1AEGG.
AF8 Balanced standard mechanical seal, flushed from internal source
Brand: SFS – Type: Sterling GNZ – Mat.:Q1BEGG.
AF4 Balanced standard mechanical seal, flushed from internal source
Brand: SFS – Type: Sterling GNZ – Mat.:Q1Q1EGG.
AFU Balanced standard mechanical seal, flushed from internal source
Brand: SFS – Type: Sterling GNZ – Mat.:Q1AVGG.
AFJ Balanced standard mechanical seal, flushed from internal source
Brand: SFS – Type: Sterling GNZ – Mat.:Q1BVGG.
AFS Balanced standard mechanical seal, flushed from internal source
Brand: SFS – Type: Sterling GNZ – Mat.:Q1Q1VGG.
AFV Balanced standard mechanical seal, flushed from internal source
Brand: SFS – Type: Sterling GNZ – Mat.:Q1AM1GG.
AFK Balanced standard mechanical seal, flushed from internal source
Brand: SFS – Type: Sterling GNZ – Mat.:Q1BM1GG.
AFT Balanced standard mechanical seal, flushed from internal source
Brand: SFS – Type: Sterling GNZ – Mat.:Q1Q1M1GG.
AS3 Cooled, balanced standard mechanical seal, flushed from internal
source. Brand: SFS – Type: Sterling GNZ – Mat.:Q1AEGG.
ASJ Cooled, balanced standard mechanical seal, flushed from internal
source. Brand: SFS – Type: Sterling GNZ – Mat.:Q1BV1GG
AST Cooled, balanced standard mechanical seal, flushed from internal
source. Brand: SFS – Type: Sterling GNZ – Mat.:Q1Q1M1GG
BF3 Unbalanced standard mechanical seal, flushed from internal source.
Brand: Burgmann – Type: M7N – Mat.:Q1AEGG
BFJ Unbalanced standard mechanical seal, flushed from internal source.
Brand: Burgmann – Type: M7N – Mat.:Q1BVGG

Doc.No.: CEH09BE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date : 02/04/2003 Sterling Fluid Systems
Appendices Page 8 of 12 Chapter 9

13 - 15 Shaft sealing BFT Unbalanced standard mechanical seal, flushed from internal source.
Brand: Burgmann – Type: M7N – Mat.:Q1Q1TGG
BG3 Balanced standard mechanical seal, flushed from internal source.
Brand: Burgmann – Type: H7N – Mat.:Q1AEGG
BGJ Balanced standard mechanical seal, flushed from internal source.
Brand: Burgmann – Type: H7N – Mat.:Q1BVGG
BGT Balanced standard mechanical seal, flushed from internal source.
Brand: Burgmann – Type: H7N – Mat.:Q1Q1M1GG
CAK Unbalanced standard mechanical seal, flushed from internal source.
Brand: Crane – Type: CR59B – Mat.:BQ1TGG
CBK Balanced standard mechanical seal, flushed from internal source.
Brand: Crane – Type: CR59B – Mat.:BQ1TGG
DAJ Unbalanced standard mechanical seal, flushed from internal source.
Brand: Pacific – Type: PA600 – Mat.:Q1BVGG
DBJ Balanced standard mechanical seal, flushed from internal source.
Brand: Pacific – Type: PA610 – Mat.:Q1BVGG
DAK Unbalanced standard mechanical seal, flushed from internal source.
Brand: Pacific – Type: PA600 – Mat.:Q1BTGG
DBK Balanced standard mechanical seal, flushed from internal source.
Brand: Pacific – Type: PA610 – Mat.:Q1BTGG
DBG Balanced standard mechanical seal, flushed from internal source.
Brand: Pacific – Type: PA610 – Mat.:SAVGG
16-17 Material 0A Main parts in GG, impeller in brass
0B Main parts in GG, impeller in stainless steel
0F Main parts in GG, impeller in PAEK
1A Main parts in GGG, impeller in brass
1B Main parts in GGG, impeller in stainless steel
1F Main parts in GGG, impeller in PAEK
4B Main parts in CrNiMo-steel or cast
4F Main parts in CrNiMo-steel or cast, impeller in PAEK
18 Casing seal 0 Liquid sealing compound
4 Soft Teflon cord.
19
20

Doc.No.: CEH09BE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date : 02/04/2003 Sterling Fluid Systems
Appendices Page 9 of 12 Chapter 9

9.6 Appendix – CEHA pump – Assembling bodies

Groove Mark (external side)

Suction body 1090 Discharge body 1140 / 1141


Fig.9.5

The suction bodies 1090, and discharge bodies 1140 and 1141 together with a vane impellor form a stage.
The foundry marks I, II, III, IV, are visible on the external sides of the bodies. Assembly is carried out by
juxtaposing the marks with the upper generating line as indicated on the assembly drawing; for this, use the
foundry groove visible outside the bodies. The foundry groove in the body 1080 is always located opposite
the foundry groove in body 1090 which precedes it.

CAUTION
If the specified angular position of the stages, as defined, is not respected, pump performance will be
adversely affected.

CEHA pumps can comprise up to 8 stages in regular models.


In models with a stage cooling chamber or a retaining stage, the latter take the place of a hydraulic stage, so
the pump will be able to take only 6 or 7 hydraulic stages (depending on the case); this fact must be taken
into account when evaluating the desired characteristics.

Discharge Discharge Discharge


flange flange flange
1141 1141 1141
1090 1090 1090
1080 1140 1140
1090 1090
1080 1140
1090
Suction 1080
flange Suction
flange
Suction
flange

1-stage pump 2-stage pump 3-stage pump


Fig.9.6

Doc.No.: CEH09BE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date : 02/04/2003 Sterling Fluid Systems
Appendices Page 10 of 12 Chapter 9

9.6.1 Appendix – CEHA pump – Assembling bodies

Discharge Discharge
flange flange
1141 1141
1090 1090
1140 1140
1090 1090
1140 1140
1090 1090
1140 1140
1090 1090
1080 1140
1090
1080
Suction
flange
Suction
4-stage pump 5-stage pump flange

Fig.9.7

Discharge Discharge
flange flange
1141 1141
1090 1090
1140 1140
1090 1090
1140 1140
1090 1090
1140 1140
1090 1090
1140 1140
1090 1090
1140 1140
1090 1090
1080 1140
1090
1080
Suction
flange
Suction
6-stage pump 7-stage pump flange
Fig.9.8

Discharge
flange 1141
1090
1140
1090
1140
1090
1140
1090
1140
1090
1140
1090
1140
1090
1140
1090
1080

Suction
flange
8-stage pump
Fig.9.9

Doc.No.: CEH09BE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date : 02/04/2003 Sterling Fluid Systems
Appendices Page 11 of 12 Chapter 9

9.7 Appendices - Technical data summary


When using CEHA pumps, the following technical data must be taken into account.

Self-priming pump
Direction of rotation: anti-clockwise facing the end of the pump drive shaft
RP: 40 bars
Max. admissible P*: 40 bars at 120°C / 32 bars at 180°C
Test Pressure: 52 bars (1.3 times the rated pressure)
Max. admissible viscosity*: 300 mm²/s
Max. n*: 1800 rpm
*These limits are not valid for all products or all types of construction. For use in conformity and in complete
safety, take into account the existing requirements (standards) concerning the type of sealing and cooling.
Number of stages: 1 to 8 stages maximum (in case of the use of a retaining stage, it takes the place of a
hydraulic stage).
Connecting flanges: as per DIN 2501, PN 40, (positions and dimensions: see dimension drawing).
Bearings: sleeve bearing at the pump end, ball bearing at the drive end

Bearing
Sizes according to
DIN 625
1200 6302
3100 6304
3600 6304
4100 6305
5100 6306
6100 6307

Lubrication: 1 plain bearing at the pump end lubricated by the pumped product, 1 ball bearing at the drive
end lubricated for life.
Mass of the pump:

Approximate weight in kg
1-stage pump weight Add per additional stage
Sizes Cast iron Stainless steel Cast iron Stainless steel
1200 18 19 2.0 2.2
3100 31 33 3.5 4.0
3600 31 33 3.5 4.0
4100 41 43 6.0 6.5
5100 60 63 10.0 11.0
6100 79 83 12.5 13.5

Minimum / maximum output:


Refer to Chapter 2

Doc.No.: CEH09BE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date : 02/04/2003 Sterling Fluid Systems
Appendices Page 12 of 12 Chapter 9

Temperature limits
Minimum temperature of pumped liquid = - 40 °C *
Maximum temperature of pumped liquid = 120 °C *
180°C for high temperature execution *

*These limits are not valid for all products or all types of construction. For use in conformity and in complete
safety, take into account the existing requirements (standards) concerning the type of sealing and cooling.

Maximum permissible temperature of pumping liquid


The highest temperatures usually occur on the pump casing surface, on the bearing housing in the area of
the anti-friction bearings and on the casing cover near the mechanical seal. A dry running must be prevent.

The temperature occurring on the pump casing is almost the same as that of the liquid handled

A maximum temperature of 80°C, if grease lubricated, can be expected in the area of the anti-friction
bearings, provided the requirements for appropriate pump operation are met and regular
maintenance on the bearings is provided. Insulation of the bearing housing is not permissible.

If the pump is adequately filled with liquid, the temperature of the liquid handled in the shaft seal area
should not increase by more than 15°C for dead end operation with a single acting mechanical seal.
With double-acting mechanical seals the temperature rise depends largely on the flushing or sealing
ring (if there is any doubt, please contact Sterling SIHI).

Thus, the following theoretical maximum temperature of the liquid handled as a function of the temperature
class according to EN 13463-1 is obtained. The maximum operating temperature of the pump as well as the
operating limits of the mechanical seal must be observed (if there is any doubt, please contact Sterling SIHI
or the mechanical seal manufacturer).

Temperature class Max. temperature of


acc. EN 13463-1 pumping liquid
T5 85 °C
T4 120 °C
T3 185 °C
T2 285 °C
T1 350 °C

Doc.No.: CEH09BE Information subjected to technical Sterling Fluid Systems (France)


Rev.: 01 alterations due to engineering development Member of Group
Date : 02/04/2003 Sterling Fluid Systems
S.A. Sterling Fluid Systems (France)
Zone Industrielle de Trappes-Elancourt
1-3, Avenue Georges Politzer B.P.41 - 78193 Trappes Cedex, France
Téléphone: +33 (0)1 34 82 39 00 Télécopie: +33 (0)1 34 82 39 61

Declaration of Conformity
for bare shaft pump
In the sense of the EU Directive 98/37/EC, Appendix II B

Herewith we declare that the pump type:

CEH

In the version supplied by us complies with the following relevant regulations:

EU Machine Directive 98/37/EC, Appendix I No. 1


EU Directive 94/9/EC, Group II, category 2

And that is destined for installation in a machine / assembly with other machines to form
a single machine and that it may not be commissioned until it has been determined that
the machine in which this pump is to be installed or with which this pump is to be
assembled complies with the clauses of the EU Machine Directive in the version of
98/37/EC and 94/9/EC.

Harmonised standards used, in particular:

EN 809 EN 13463 - 1
EN 292 part 1 prEN 13463 - 5
EN 292 part 2
In the actual version.

National technical standards and specifications used, in particular:

Unauthorised alterations of the pump unit and any use not in accordance with valid
regulations and / or intended use result in a loss of validity of this declaration.

Notification of Pump: II 2 G c T1-T5


Operation Manager Business Unit Manager

Dr R. EHL O. LOESER

Membres du groupe Sterling Fluid Systems

S.A. Capital 460.000 Euros R.C. Versailles B 775 708 142 00010 Code APE 291C

You might also like