You are on page 1of 1

Sepic tank Calculations

Project Akashdeep
Date Dec 16,2003

Eq Fix Flat Flat Flat Flat


Units Type A Type B Type C Type D
Flats per type 168 0 0 0 Water Supply per person 135
Persons per flat 5 0 0 0 Frequency of cleaning 180
Water Closet 1.0 1 0 0 0 168 Length to Breadth Ratio 2
Bath w bucket 0.5 0 0 0 0 0 Soil & sullage separate y
Bath Tub 2.0 0 0 0 0 0
Bath Shower 1.0 0 0 0 0 0
Wash Basin/ Kitchen 0.5 0 0 0 0 0
Urinal w auto Flush 1.0 0 0 0 0 0
Urinal w/o auto Flush 0.5 0 0 0 0 0
Slope Sink 1.0 0 0 0 0 0 Sedimentation depth m 0.3
Laboratory Sink 2.0 0 0 0 0 0 Sludge Digestion m3/person 0.032
Combination fixture 1.0 0 0 0 0 0 Sludge Storage m3/person/day 0.0002
Drinking Fountain 0.5 0 0 0 0 0 m2 / 10 lpm of peak flow 0.92
Ablution Tap 0.5 0 0 0 0 0 waste water coeff w.r.t. water 0.8
Dish Washer 0.5 0 0 0 0 0 Free Board m 0.3

Population 840
Eq fixture units 168
Peak discharge Flow 316 Lpm

Length Width Depth HRT


Septic Tank m 7.65 3.80 2.55 OK
Upflow Filter m 3.80 3.80 2.55