You are on page 1of 12

Installation Instructions

Model CDC-4
Conventional Detector Card

INTRODUCTION The Model CDC-4 from Siemens Building Technologies, Inc. is


a card that allows conventional detectors to be used on the
FireFinder-XLS system. It provides four Class A or Class B
conventional detection zones. Each zone can support two-wire
photoelectric or ionization compatible smoke detectors and an
unlimited number of normally open circuit closure devices. The
module also supports Siemens Fire Safety flame and beam
detectors. The relay base, remote lamp and audible base may
also be used with the CDC-4. The CDC-4 uses one network
address on the FireFinder-XLS system. It has diagnostic LED
indicators showing module status and the status of each zone.

OPERATION Activation of any device on the circuit initiates a zone alarm and
causes any previously programmed functions to operate. Any
circuit in an alarm or trouble condition is displayed on the PMI.

The CDC-4 is designed to function in a local degrade mode


during failure of the FireFinder-XLS main processor or during
the loss of the system communication network. While in the
degrade mode, the CDC-4 can report both alarm and trouble
conditions and can activate local outputs on other modules
within the same enclosure.

The maximum zone alarm current can be set to either 175mA


or 100mA and is set in pairs for zones 1/2 and 3/4. When a
compatible detector is selected in the Zeus Programming Tool,
the maximum zone alarm current is automatically set by the
CDC-4. Detectors requiring the 100mA zone current limit (see
table on page 11) cannot be used on the same zone pair as
detectors requiring the 175mA zone current limit (see table on
pages 7-11). Figure 1
CDC-4 Conventional
CDC-4 zones may be configured either as alarm-causing or Detector Card
supervisory-causing, if allowed by the local Authority Having
Jurisdiciton.

Do not use shorting devices on circuits with accessories on them. The shorting
devices will lower the zone voltage to a point where the accessories will not operate.

Siemens Building Technologies


P/N 315-034200-5 Fire Safety
Any or all of the CDC-4 circuits may be programmed to operate with Alarm Verifica-
tion. This allows the automatic verification of alarm conditions caused by smoke
detectors in order to prevent nuisance alarms. For further information, refer to the
FireFinder-XLS Manual, P/N 315-033744.

When upgrading the firmware in the CDC-4, be sure to check the PC board version.
Version 2.0 and above firmware are only compatible with PC board P/N 580-034888.
If version 2.0 or above firmware is uploaded into the older version of the CDC-4, the
PMI displays “ROM SW Version Error”. The PC board revision number is printed on
the back of the CDC-4 board.

Controls and Indicators The front panel of the CDC-4 contains one reset switch, sixteen LEDs, and three
HNET address switches as shown in Figure 1

A reset switch is located on the top of the front panel. Pushing the reset switch re-
initializes the CDC-4 operation (similar to a cold boot).

The LEDs follow the reset switch and their functions are defined as follows:

POWER (Green) Normally ON. When illuminated, indi-


cates that power for the CDC-4 is applied
to the card.

CARD FAIL (Yellow) Normally OFF. When illuminated, indi-


cates that the card microprocessor has
failed.

HNET FAIL (Yellow) Normally OFF. When illuminated, indi-


cates that the HNET communication with
the CDC-4 has terminated and the card
goes into degrade mode (applicable only
when card resides in the HNET network).

GND FAULT (Yellow) Normally OFF. When illuminated, indi-


cates that the CDC-4 has detected either
a negative or positive ground fault.

ZONE 1 ALARM (Red) Normally OFF. When illuminated indi-


cates that an alarm condition has been
detected in Zone 1. It will stay on
continuously until the system is reset.

ZONE 1 TROUBLE (Yellow) Normally OFF. When illuminated, indicates


that a trouble condition has been de-
tected in Zone 1. It will stay on continu-
ously until the condition is cleared.

ZONE 1 CLASS A OPEN (Yellow) Normally OFF. When illuminated, indi-


cates that there is a break in the Class A
wiring in Zone 1.

ZONE 2 ALARM (Red) Normally OFF. When illuminated indi-


cates that an alarm condition has been
detected in Zone 2. It will stay on
continuously until the system is reset.

Siemens Building Technologies 2 P/N 315-034200-5


Fire Safety
ZONE 2 TROUBLE (Yellow) Normally OFF. When illuminated, indicates
that a trouble condition has been de-
tected in Zone 2. It will stay on continu-
ously until the condition is cleared.

ZONE 2 CLASS A OPEN (Yellow) Normally OFF. When illuminated, indi-


cates that there is a break in the Class A
wiring in Zone 2.

ZONE 3 ALARM (Red) Normally OFF. When illuminated indi-


cates that an alarm condition has been
detected in Zone 3. It will stay on
continuously until the system is reset.

ZONE 3 TROUBLE (Yellow) Normally OFF. When illuminated, indicates


that a trouble condition has been de-
tected in Zone 3. It will stay on continu-
ously until the condition is cleared.

ZONE 3 CLASS A OPEN (Yellow) Normally OFF. When illuminated, indi-


cates that there is a break in the Class A
wiring in Zone 3.

ZONE 4 ALARM (Red) Normally OFF. When illuminated indi-


cates that an alarm condition has been
detected in Zone 4. It will stay on
continuously until the system is reset.

ZONE 4 TROUBLE (Yellow) Normally OFF. When illuminated, indicates


that a trouble condition has been de-
tected in Zone 4. It will stay on continu-
ously until the condition is cleared.

ZONE 4 CLASS A OPEN (Yellow) Normally OFF. When illuminated, indi-


cates that there is a break in the Class A
wiring in Zone 4.

Three rotary dial switches at the bottom of the front panel are used to set the HNET
network address of the CDC-4.

PRE-INSTALLATION The network address switches must be set prior to inserting the card into the CC-5
(refer to Figure 1):

Network Address Switches: Set the three-digit HNET network address for the
CDC-4 using the three rotary dial address switches located near the bottom of the
HUNDREDS
front panel. (Refer to Figure 1 for the location of the switches.) The address for the
TENS
CDC-4 must be the same as the address selected for it in the Zeus Programming
ONES Tool. To set the address, turn the pointers on each of the three dials to the numbers
HNET
for the selected address. For example, if the address is 123, set the pointer for the
HUNDREDS dial to “1”, set the pointer for the TENS dials to “2”, and set the pointer
for the the ONES dial to “3”. The range of allowable addresses is from 001 to 251
(leading zeros must be used).

Siemens Building Technologies 3 P/N 315-034200-5


Fire Safety
WIRING

Remove all system power before installation, first battery, then AC. (To power up,
connect the AC first, then the battery.)

All device field wiring to the CDC-4 is connected to the terminal blocks of the CC-5
card cage slot in which it is installed.

To Connect the External Wiring: ZONE 1 ZONE 2

LINE+ (RETURN)

LINE+ (RETURN)
LINE- (RETURN)

LINE- (RETURN)
1. Loosen the screw of the

LINE+ (OUT)

LINE+ (OUT)
LINE- (OUT)

LINE- (OUT)
terminal by turning it counter-
clockwise.
2. Insert the wire into the side of
the terminal block
3. Tighten the screw of the 1 2 3 4 5 6 7 8

terminal block by turning it


clockwise.
9 10 11 12 13 14 15 16

Connect +24V from PSC-12 to terminal

LINE+ (RETURN)
LINE+ (RETURN)

LINE- (RETURN)
LINE- (RETURN)
17 and -24V from PSC-12 to terminal 18

LINE+ (OUT)
LINE+ (OUT)

LINE- (OUT)
LINE- (OUT)
of the slot in the CC-5 where the CDC
will be installed using 12-18 AWG (Refer
to Fig.2).
ZONE 3 ZONE 4
Refer to Figure 3. All circuits are power ONE SLOT OF CC-5 FOR CDC-4
limited to NFPA 70 per NEC 760. Each
detector or group of detectors must use
a two-wire circuit of at least 18 AWG, 17 18 19 20 21 22 23 24

thermoplastic fixture wire, enclosed in


24V+

24V–
conduit. If permitted by local building
codes, 18 AWG limited energy, shielded
cable without conduit may also be used. TO 24VDC FROM PSC-12

The CDC-4 may be connected to existing Figure 2


device loops that have a 3.9K or 4.7K Wiring 24V Power Lines
end-of-line resistor (1/4W, 5%) or a 50uF,
50V end-of-line capacitor installed. Always use a 50uF, 50V end-of-line capacitor for
new installations and whenever practical in existing detector loops for all detector
models except the Siemens PBA-1191, which requires a 4.7K end-of-line resistor, as
shown in Figure 3.

Total circuit resistance must not exceed 70 ohms—40 ohms if accessories (relay/
audible bases) are used.

Each detector zone can be wired Class A or Class B individually.

The screw terminals can accommodate one 12 -18 AWG or two 16-18 AWG.

All unused zones must be terminated with a 50uF capacitor (Terminals 1 and 4 for
Zone 1, Terminals 5 and 8 for Zone 2, Terminals 9 and 12 for Zone 3, and Terminals 13
and 16 for Zone 4).

Siemens Building Technologies 4 P/N 315-034200-5


Fire Safety
NOTES:
1. All circuits can be Class A or 9. Only one device accessory
Class B. per circuit is guaranteed to
2. All circuits are power limited activate on the CDC-4.
to NFPA 70 per NEC 760. 10. When mixing different
3. All circuits are supervised. model detectors on a zone,
do not install more detectors
4. Refer to the UL Compatible
than the smallest number
Two-Wire Detector List for
shown in the “Number of
the maximum number of
Detectors Per Zone” column
detectors per zone.
of the compatibility table.
5. Do not mix smoke detectors For example, if installing
with the PBA-1191. Siemens PE-11 and PE-3
6. Do not mix different detectors on the same zone,
manufacturer’s smoke do not install more than
detectors on the same zone. fifteen detectors on that
ZONE 1 ZONE 2 7. Max resistance: 70 ohms/ zone. When configuring the
CLASS A CLASS B * * IN CANADA, circuit, 40 ohms/circuit if zone in Zeus, enter the
+ MOUNT USING
MODEL EL-33
accessories (relay/audible model name of the detector
EOL
bases) are used. with the smallest number
50uF, 50V 8. Do not use shorting devices (PE-3 in this example).
P/N 100-115588
on circuits with accessories 11. Positive and negative ground
on them. fault detected at <20K ohms
for terminals 1-16.

PBA-1191
_ + _ _
+ +
A B C D E F
LINE+ (RETURN)

LINE- (RETURN)

DO NOT
LINE+ (OUT)

LINE- (OUT)

EOL EOLR
50uF, 50V USE
4.7K, 1/4W EOL
P/N 100-115588 P/N 140-820188 50uF, 50V
+
LINE+

P/N 100-115588
LINE-

+
LINE+

LINE-
NC NC
ZONE 3 ZONE 4

1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16

Figure 3
CDC-4 Detector Zones

Siemens Building Technologies 5 P/N 315-034200-5


Fire Safety
INSTALLATION The CDC-4 plugs perpendicularly into one slot in the CC-5 card-cage via two 96-pin
DIN connectors and can occupy any slot in the card cage. (Refer to Figure 4.)

Insert the CDC-4 card into the card guides rightside up


(lettering on the front panel is legible).

Slide the card in until the card edge connectors contact


the receptacles on the motherboard.

Verify that the DIN connectors of the card and the card-
cage aligned properly. The card can only plug in one
direction to the card cage, if it does not align, DO NOT
FORCE the card.

Place thumbs on the front panel adjacent to the captive


screws and gently apply even pressure on the card until
the connectors seat in the receptacles on the
motherboard. Secure with the captive screws.

Power up the system and verify that the CDC-4 power


LED turns ON.
Figure 4
Installing The CDC-4

INITIATING DEVICES Refer to the UL Compatible Two-Wire Detector List for the number of detectors that
may be used on a CDC-4 zone.

Refer to Figure 3 for initiating device wiring. All circuits are power limited to NFPA 70
per NEC 760. Each detector or group of detectors must use a two-wire circuit of at
least 18 AWG, thermoplastic fixture wire, enclosed in conduit. If permitted by local
building codes, 18 AWG limited energy, shielded cable without conduit may also be
used.

Total circuit resistance must not exceed 70 ohms—40 ohms if accessories (relay/
audible bases) are used.

If the smoke detector has an alarm verification function, the circuit must not be
programmed for alarm verification.

See NFPA 72 Standard for the number of normally open contact devices allowed.

See UL Compatible Two-Wire Detectors for the list of compatible devices.

For specific wiring and installation information, read the instructions provided with
each device.

Siemens Building Technologies 6 P/N 315-034200-5


Fire Safety
ELECTRICAL RATINGS

Initiating Circuits

Voltage range (standby) 21.7 - 22.8 VDC

Supervisory Current 4mA per zone max

Alarm Current 175mA per zone max 100mA per zone max

Power Supply

24V Back Plane Current 0

Supervisory Supervisory
110mA + 8mA per zone max 110mA + 8mA per zone max
Screw Terminal 24V Current
Alarm Alarm
110mA + 320mA per zone max 110mA + 280mA per zone max

6.2V Back Plane Current 150mA max

Supervisory Supervisory
150mA + 8mA per zone max 150mA + 8mA per zone max
24V Standby Current
Alarm Alarm
150mA + 320mA per zone max 150mA + 280mA per zone max

UL COMPATIBLE TWO-WIRE DETECTORS

The detectors listed in the following tables are compatible with the CDC-4 (UL
identifier CDC). The CDC-4 and all Siemens detectors shown below are ULC listed.
Contact the manufacturer for listing information on models other than Siemens.

Manufacturer Detector UL Detector B ase U L B ase Number of ULC Listed


Model Identifier Model Identifier Detectors
Per Zone

Siemens DF-1192 DF-1192 DFB-1190 DFB-1190 4 Y

Siemens DI-3 DI-3 DB-3S DB-3S 30 Y


DI-3H DI-3H 30 Y
DI-A3 DI-A3 30 Y
DI-A3H DI-A3H 30 Y

Siemens DI-B3 DI-B3 AD-3I AD-3I 30 Y


DI-B3H DI-B3H 30 Y

Siemens DI-4A DI-4A DB-4TS DB-4TS 30 Y


DB-4TF DB-4TF 30

Siemens DI-6 DI-6 DB-4TS DB-4TS 30 Y


DB-4TF DB-4TF 30

Siemens DT-3P-135 DT-3P-135 DB-3S DB-3S Unli mi ted Y

Siemens DT-11 DT-11 DB-11 DB-11 30 Y


DB-3S w/ADPT DB-3S 30

Siemens PBA-1191 PBA-1191 PBB-1191 PBB-1191 1 Y

Siemens PE-3 PE-3 DB-3S DB-3S 15 Y


PE-3T PE-3T 15 Y

Siemens PE-3 PE-3 AD-3ILP AD-3ILP 15 Y


PE-3T PE-3T 15 Y

Siemens PE-11 PE-11 DB-11 DB-11 30 Y


AD-11P AD-11P 30
AD-11PR AD-11PR 30

Siemens PE-11T PE-11T DB-11 DB-11 30 Y


DB-3S w/ADPT DB-3S 30

Siemens Building Technologies 7 P/N 315-034200-5


Fire Safety
Manufacturer Detector UL Detector B ase U L B ase Number of ULC Listed
Model Identifier Model Identifier Detectors
Per Zone

Air Products RW-2W-N RW-2W-N 45681-200 45681-200 60 N


and Controls

Air Products RW-2W-P RW-2W-P 45681-200 45681-200 30 N


and Controls

Manufacturer Detector UL Detector B ase U L B ase Number of ULC Listed


Model Identifier Model Identifier Detectors
Per Zone

Apollo 55000-150 55000-150 45681-200 45681-200 60 N


to to 45681-220 45681-220 60
55000-153 55000-153 45681-227 45681-227 40
45681-230 45681-230 40
45681-231 45681-231 40
45681-232 45681-232 60

Apollo 55000-250 55000-250 45681-200 45681-200 60 N


45681-220 45681-220 60
45681-227 45681-227 40
45681-230 45681-230 40
45681-231 45681-231 40
45681-232 45681-232 60

Apollo 55000-350 55000-350 45681-200 45681-200 30 N


45681-220 45681-220 30
45681-227 45681-227 25
45681-230 45681-230 25
45681-231 45681-231 25
45681-232 45681-232 30

Apollo 55000-380 55000-380 45681-200 45681-200 20 N


45681-220 45681-220 20
45681-227 45681-227 15
45681-230 45681-230 15
45681-231 45681-231 15
45681-232 45681-232 20

Manufacturer Detector UL Detector B ase U L B ase Number of ULC Listed


Model Identifier Model Identifier Detectors
Per Zone

Edwards 6250B 001 6249B-001 001 55 Y


6250B 001 6251B-001 001 55 Y
6250B 001 6251B-001A 001 55 Y

Edwards 6269B 001 6249B-001 001 5 Y


6269B 001 6251B-001 001 5 Y
6269B 001 6251B-001A 001 5 Y
6269B 001 6251B-003 001 5 Y

Edwards 6270B 001 6249B-001 001 5 Y


6270B 001 6251B-001 001 5 Y
6270B 001 6251B-001A 001 5 Y
6270B 001 6251B-003 001 5 Y

Siemens Building Technologies 8 P/N 315-034200-5


Fire Safety
Manufacturer Detector UL Detector B ase U L B ase Number of ULC Listed
Model Identifier Model Identifier Detectors
Per Zone
Electro Signal 420C S 10 N/A N/A 70 N
(ESL)
Electro Signal 420C R S11 N/A N/A 70 N
(ESL)
Electro Signal 420CRT S11 N/A N/A 70 N
(ESL)
Electro Signal 420C T S 10 N/A N/A 70 N
(ESL)
Electro Signal 425C S 10 N/A N/A 70 N
(ESL)
Electro Signal 425C R S11 N/A N/A 70 N
(ESL)
Electro Signal 425CRT S11 N/A N/A 70 N
(ESL)
Electro Signal 425C T S 10 N/A N/A 70 N
(ESL)
Electro Signal 429C S 10A N/A N/A 35 N
(ESL)
Electro Signal 429C T S 10A N/A N/A 35 N
(ESL)
Electro Signal 511C/AFT S 10A N/A N/A 35 N
(ESL)
Electro Signal 518C/AFT S 10A N/A N/A 35 N
(ESL)
Electro Signal 521B/BXT S 10A N/A N/A 35 N
(ESL) (w/Sw1 OFF)
Electro Signal 521CRXT S11A N/A N/A 35 N
(ESL) (w/Sw1 OFF)
Electro Signal 528B/BXT S 10A N/A N/A 35 N
(ESL) (w/Sw1 OFF)
Electro Signal 528CRXT S11A N/A N/A 35 N
(ESL) (w/Sw1 OFF)
Electro Signal 611U S 10 601U S 00 70 N
(ESL)
Electro Signal 611UD S 10 601U S 00 70 N
(ESL)
Electro Signal 611UD S 10 609U10 S 00 70 N
(ESL)
Electro Signal 611UT S 10 601U S 00 70 N
(ESL)
Electro Signal 612 S 10 601U S 00 70 N
(ESL)
Electro Signal 612UD S 10 601U S 00 70 N
(ESL)

Electro Signal 612UD S 10 609U10 S 00 70 N


(ESL)
Electro Signal 613U5 S 10 601U S 00 70 N
(ESL)

Siemens Building Technologies 9 P/N 315-034200-5


Fire Safety
Manufacturer Detector UL Detector B ase U L B ase Number of ULC Listed
Model Identifier Model Identifier Detectors
Per Zone

Hochiki DCD-135 HD-3 NS4-220 HB-3 20 N


NS6-220 20

Hochiki DCD-135 HD-3 NS4-224 HB-5 20 N


NS6-224 20

Hochiki DCD-190 HD-3 NS4-220 HB-3 20 N


NS6-220 20

Hochiki DCD-190 HD-3 NS4-224 HB-5 20 N


NS6-224 20

Hochiki SIH-24F HD-3 HS-22D HB-3 20 Y


YBA-M22 HB-3 20 Y

Hochiki SIH-24F HD-3 HSB-224 HB-53 20 Y

Hochiki SIH-24F HD-3 HSC-224R HB-73 20 Y

Hochiki SIH-24F HD-3 HS-224D HB-5 20 Y


YBA-M224 HB-5 20 Y

Hochiki SIJ-24 HD-3 NS4-220 HB-3 15 Y


NS6-220 15 Y

Hochiki SIJ-24 HD-3 NS4-224 HB-5 15 Y


NS6-224 15 Y

Hochiki SLK-24F HD-3 HS-22D HB-3 20 Y


SLK-24FH YBA-M22 HB-3 20 Y

Hochiki SLK-24F HD-3 HS-224D HB-5 20 Y


SLK-24FH YBA-M224 HB-5 20 Y

Hochiki SLK-24F HD-3 HSB-224 HB-53 20 Y


SLK-24FH 20 N

Hochiki SLK-24F HD-3 HSC-224R HB-73 20 N


SLK-24FL 20 N

Hochiki SLK-24FL HD-3 HSB-2 HB-50 20 N


HSB-2N 20 N

Hochiki SLR-24H HD-3 NS4-220 HB-3 20 N


SLR-24V NS6-220 20 N

Hochiki SLR-24H HD-3 NS4-224 HB-5 20 N


SLR-24V NS6-224 20 N

Hochiki SLR-835 HD-3 NS4-220 HB-3 15 N


SLR-835W NS6-220 15 N

Hochiki SLR-835 HD-3 NS4-224 HB-5 15 N


SLR-835W NS6-224 15 N

Hochiki SLR-835H HD-5 NS4-224 HB-5 15 N


SLR-835HW NS6-224 15 N

Hochiki SLR-835H HD-5 NS4-220 HB-3 15 N


SLR-835HW NS6-220 15 N
NS6-220W 15 N

Siemens Building Technologies 10 P/N 315-034200-5


Fire Safety
Manufacturer Detector UL Detector B ase U L B ase Number of ULC Listed
Model Identifier Model Identifier Detectors
Per Zone

System Sensor 2400AT A N/A N/A 1 N


(BRK)

System Sensor 2400AIT A N/A N/A 1 N


(BRK)

Zone current limit is adjusted to 100mA for the following models. Do not mix these detectors with those
listed above on the same z one pair (Zones 1 and 2 or Zones 3 and 4). These detectors are compatible with
firmware revision 2.0 and higher with PC board P/N 580-034888. The line resistance between the wiring
terminals near the CDC-4 and any shorting devices must not exceed 30 ohms.

Manufacturer Detector UL Detector B ase U L B ase Number of ULC Listed


Model Identifier Model Identifier Detectors
Per Zone

System Sensor 1151 A B110LP and A 25 Y


(BRK) B116LP

System Sensor 1400 A N/A N/A 30 Y


(BRK)

System Sensor 1451 A B 401, B 401B A 25 Y


(BRK) and B406B

System Sensor 1451DH* A DH400 A 25 N


(BRK)

System Sensor 2151 A B110LP and A 25 Y


(BRK) B116LP

System Sensor 2300T A N/A N/A 25 N


(BRK)

System Sensor 2400 A N/A N/A 25 Y


(BRK)

System Sensor 2400TH A N/A N/A 25 Y


(BRK)

System Sensor 2451 A B 401, B 401B A 25 Y


(BRK) and B406B

System Sensor 2451* A DH400 A 25 Y


(BRK)

System Sensor 2451TH A B 401, B 401B A 25 N


(BRK) and B406B

System Sensor 5451 A B401 and A 25 N


(BRK) B 401B

System Sensor DH400I* A N/A N/A 25 N


(BRK) (1451DH
w/DH400)

System Sensor DH400P* A N/A N/A 25 N


(BRK) (2451DH
w/DH400)

*Model DH400I i s the 1451DH wi th DH400 housi ng. Model DH400P i s the 2451 wi th DH400 housi ng.

Siemens Building Technologies 11 P/N 315-034200-5


Fire Safety
Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd.
8 Fernwood Road 2185 Derry Road West
Florham Park, New Jersey 07932 Mississauga, Ontario L5N 7A6 Canada P/N 315-034200-5

You might also like