Date: November 2, 2018 NC LIC# P-1403

Charles McGuirt Tower Engineering Professionals


Crown Castle 326 Tryon Road
3530 Toringdon Way, Suite 300 Raleigh, NC 27603
Charlotte, NC 28277 (919) 661-6351

Subject: Structural Analysis Report

Carrier Designation: Verizon Wireless Co-Locate


Carrier Site Number: 101490
Carrier Site Name: DT_Apex_Alltel

Crown Castle Designation: Crown Castle BU Number: 871394


Crown Castle Site Name: Apex
Crown Castle JDE Job Number: 539855
Crown Castle Work Order Number: 1651832
Crown Castle Order Number: 464886 Rev. 0

Engineering Firm Designation: TEP Project Number: 33537.193933

Site Data: 2351 Apex Peakway, Apex, Wake County, NC 27502


Latitude 35° 43' 52.00'', Longitude -78° 50' 16.10''
500 Foot - Guyed Tower

Dear Charles McGuirt,

Tower Engineering Professionals is pleased to submit this “Structural Analysis Report” to determine the
structural integrity of the above-mentioned tower.

The purpose of the analysis is to determine acceptability of the tower stress level. Based on our analysis we have
determined the tower stress level for the structure and foundation, under the following load case, to be:

LC5: Proposed Equipment Configuration Sufficient Capacity

This analysis utilizes an ultimate 3-second gust wind speed of 115 mph as required by the 2018 North Carolina
State Building Code. Applicable Standard references and design criteria are listed in Section 2 - Analysis Criteria.

Structural analysis prepared by: Enrique B. Silva / JWB

Respectfully submitted by:

Adam M. Amortnont, P.E.


November 2, 2018
500-ft Guyed Tower Structural Analysis Report CCI BU No 871394
TEP Project Number 33537.193933, Order 464886, Revision 0 Page 2

TABLE OF CONTENTS

1) INTRODUCTION

2) ANALYSIS CRITERIA
Table 1 - Proposed Equipment Configuration
Table 2 - Other Considered Equipment

3) ANALYSIS PROCEDURE
Table 3 - Documents Provided
3.1) Analysis Method
3.2) Assumptions

4) ANALYSIS RESULTS
Table 4 - Section Capacity (Summary)
Table 5 - Tower Component Stresses vs. Capacity
4.1) Recommendations

5) APPENDIX A
tnxTower Output

6) APPENDIX B
Base Level Drawing

7) APPENDIX C
Additional Calculations

tnxTower Report - version 8.0.4.0


November 2, 2018
500-ft Guyed Tower Structural Analysis Report CCI BU No 871394
TEP Project Number 33537.193933, Order 464886, Revision 0 Page 3

1) INTRODUCTION

This tower is a 500-ft guyed tower designed by Rohn. The tower has been modified multiple times in the past to
accommodate additional loading. The knife plate modifications from 20’ to 100’ designed by GPD Group in March
of 2009 (CCI Doc ID 2530199) were determined to be ineffective and not considered structurally in this analysis.
All information provided to TEP was assumed to be accurate and complete.

2) ANALYSIS CRITERIA

TIA-222 Revision: TIA-222-H


Risk Category: II
Wind Speed: 115 mph
Exposure Category: B
Topographic Factor: 1.0
Ice Thickness: 1.5 in
Wind Speed with Ice: 30 mph
Service Wind Speed: 60 mph

Table 1 - Proposed Equipment Configuration


Center
Number Number Feed
Mounting Line Antenna
of Antenna Model of Feed Line
Level (ft) Elevation Manufacturer
Antennas Lines Size (in)
(ft)
LNX-6515DS-A1M
6 Andrew
w/ Mount Pipe
3 Commscope NHH-65C-R2B w/ Mount Pipe
HBXX-6516DS-A2M
3 Andrew 6 1-5/8
190.0 190.0 w/ Mount Pipe
2 1-3/8
3 Ericsson Radio 4449
3 Ericsson Radio 8843
1 Raycap RRFDC-3315-PF-48
1 Raycap RVZDC-6627-PF-48

Table 2 - Other Considered Equipment


Center
Number Number Feed
Mounting Line Antenna
of Antenna Model of Feed Line
Level (ft) Elevation Manufacturer
Antennas Lines Size (in)
(ft)
500.0 510.0 1 RFS Celwave BCR12-A - -
498.0 1 Kathrein 750 10074
494.0 1 2-1/4
494.0 1 Tower Mounts Side Arm Mount [SO 309-1]
1 Andrew PG1N0F-0090-310
490.0
485.0 1 RFS Celwave 490114 1 1-5/8
485.0 1 Tower Mounts Side Arm Mount [SO 303-1]
481.0 1 Decibel DB420
471.0 1 1-5/8
471.0 1 Tower Mounts Side Arm Mount [SO 303-1]
449.0 1 Comprod 784-70
444.0 1 1-1/4
444.0 1 Tower Mounts Side Arm Mount [SO 303-1]
200.0 1 Lcom HG2409U-PRO
198.0 2 1-5/8
198.0 1 Tower Mounts Side Arm Mount [SO 305-1]

tnxTower Report - version 8.0.4.0


November 2, 2018
500-ft Guyed Tower Structural Analysis Report CCI BU No 871394
TEP Project Number 33537.193933, Order 464886, Revision 0 Page 4

3) ANALYSIS PROCEDURE

Table 3 - Documents Provided


Document Remarks Reference Source

Geotechnical Report GeoTechnologies, Inc. 1449028 CCISites


Foundation Mapping FDH and Vertical Solutions 1450303 CCISites
Tower and Appurtenance Mapping Tower Engineering Professionals 1410292 CCISites
Tower Reinforcement Drawings Pinnacle Towers 2055978 CCISites
Post-Modification Inspection IETS 1956304 CCISites
Tower Reinforcement Drawings GPD Associates 2310911 CCISites
Post-Modification Inspection GPD Associates 2388246 CCISites
Tower Reinforcement Drawings GPD Associates 2530199 CCISites
Post-Modification Inspection Tower Engineering Professionals 2530200 CCISites
Post-Modification Inspection Tower Engineering Professionals 3999681 CCISites
Tower Reinforcement Drawings Tower Engineering Professionals 4136060 CCISites
Post-Modification Inspection Tower Engineering Professionals 5407886 CCISites

3.1) Analysis Method

tnxTower (version 8.0.4.0), a commercially available analysis software package, was used to create a
three-dimensional model of the tower and calculate member stresses for various loading cases.
Selected output from the analysis is included in Appendix A.

tnxTower was used to determine the loads on the modified structure. Additional calculations were
performed to determine the stresses in the reinforced leg sections. These calculations are presented in
Appendix C.

tnxTower Report - version 8.0.4.0


November 2, 2018
500-ft Guyed Tower Structural Analysis Report CCI BU No 871394
TEP Project Number 33537.193933, Order 464886, Revision 0 Page 5

3.2) Assumptions

1) The tower and foundation were built and maintained in accordance with the manufacturer’s
specification.
2) The configuration of antennas, transmission cables, mounts and other appurtenances are as
specified in Tables 1 and 2, and the referenced drawings.
3) All tower components are in sufficient condition to carry their full design capacity.
4) Serviceability with respect to antenna twist, tilt, roll, or lateral translation, is not checked and is
left to the carrier or tower owner to ensure conformance.
5) All antenna mounts and mounting hardware are structurally sufficient to carry the full design
capacity requirements of appurtenance wind area and weight as provided by the original
manufacturer specifications. It is the carrier’s responsibility to ensure compliance to the structural
limitations of the existing and/or proposed antenna mounts. TEP did not perform a site visit to
verify the size, condition or capacity of the antenna mounts and did not analyze antennas
supporting mounts as part of this structural analysis report.
6) The foundation steel reinforcement was assumed to be the minimum required per ACI 318.
7) The existing D to X bracing modifications from 180’ to 240’ designed by TEP in January of 2014
(CCI Doc ID 4136060) were considered as effective in bracing the original diagonal members.
8) The flange jump knife plate modifications from 20’ to 100’ designed by GPD Group in March of
2009 (CCI Doc ID 2530199) were determined to be ineffective and were not considered
structurally in this analysis.
9) The following material grades were assumed:
a) Guy anchor shaft: ASTM A572-50

This analysis may be affected if any assumptions are not valid or have been made in error. Tower
Engineering Professionals should be notified to determine the effect on the structural integrity of the
tower.

4) ANALYSIS RESULTS

Table 4 - Section Capacity (Summary)


Section Critical % Pass /
Elevation (ft) Component Type Size P (lb) ΦPallow (lb)
No. Element Capacity Fail
T1 500 - 480 Leg ROHN 2 EH 1 -7959.61 46048.38 17.3 Pass
T2 480 - 460 Leg ROHN 2 EH 36 -14010.40 43855.60 31.9 Pass
T3 460 - 440 Leg ROHN 2 EH 67 -16410.60 46048.38 35.6 Pass
T4 440 - 420 Leg ROHN 2 EH 102 -34365.70 62906.76 54.6 Pass
T5 420 - 400 Leg ROHN 2.5 STD 159 -34595.00 61325.88 56.4 Pass
T6 400 - 380 Leg ROHN 2.5 STD 191 -33228.90 58405.60 56.9 Pass
T7 380 - 360 Leg ROHN 2.5 STD 223 -37214.00 61325.88 60.7 Pass
T8 360 - 340 Leg ROHN 2.5 STD 256 -53621.40 75218.43 71.3 Pass
T9 340 - 320 Leg ROHN 2.5 EH 313 -54085.40 79978.18 67.6 Pass
T10 320 - 300 Leg ROHN 2.5 EH 346 -53444.10 76169.70 70.2 Pass
T11 300 - 280 Leg ROHN 2.5 EH 379 -54166.40 76169.70 71.1 Pass
T12 280 - 260 Leg ROHN 2.5 EH 412 -54529.00 76169.70 71.6 Pass
T13 260 - 240 Leg ROHN 2.5 EH 445 -61292.50 76169.70 80.5 Pass
T14 240 - 220 Leg ROHN 2.5 EH 480 -67330.50 99127.24 67.9 Pass
T15 220 - 200 Leg ROHN 2.5 EH 537 -69720.70 99127.24 70.3 Pass
T16 200 - 180 Leg ROHN 2.5 EH 594 -71849.00 94406.90 76.1 Pass

tnxTower Report - version 8.0.4.0


November 2, 2018
500-ft Guyed Tower Structural Analysis Report CCI BU No 871394
TEP Project Number 33537.193933, Order 464886, Revision 0 Page 6

Section Critical % Pass /


Elevation (ft) Component Type Size P (lb) ΦPallow (lb)
No. Element Capacity Fail
2.5 XH w/ 3 STD Half
T17 180 - 160 Leg Note 1 Note 1 Note 1 73.2 Pass
Sleeve
2.5 XH w/ 3 STD Half
T18 160 - 140 Leg Note 1 Note 1 Note 1 69.6 Pass
Sleeve
2.5 XH w/ 3 STD Half
T19 140 - 120 Leg Note 1 Note 1 Note 1 73.2 Pass
Sleeve
2.5 XH w/ 3 STD Half
T20 120 - 100 Leg Note 1 Note 1 Note 1 77.9 Pass
Sleeve
T21 100 - 80 Leg Rohn 2.5 EH w/ L3x3x1/4 Note 1 Note 1 Note 1 78.7 Pass
T22 80 - 60 Leg Rohn 3 STD w/ L3x3x1/4 Note 1 Note 1 Note 1 80.1 Pass
T23 60 - 40 Leg Rohn 3 STD w/ L3x3x1/4 Note 1 Note 1 Note 1 83.2 Pass
T24 40 - 20 Leg Rohn 3 STD w/ L3x3x1/4 Note 1 Note 1 Note 1 84.2 Pass
3 STD w/ 3.5 STD Half
T25 20 - 4.81771 Leg Note 1 Note 1 Note 1 67.4 Pass
Sleeve
T26 4.81771 - 0 Leg ROHN 3 X-STR 942 -96077.30 133855.00 71.8 Pass
T1 500 - 480 Diagonal ROHN 1.5 x 16GA 12 -2255.53 6157.30 36.6 Pass
T2 480 - 460 Diagonal ROHN 1.5 x 16GA 44 -1720.12 6157.30 27.9 Pass
T3 460 - 440 Diagonal ROHN 1.5 x 16GA 77 -2455.42 6157.30 39.9 Pass
33.8
T4 440 - 420 Diagonal ROHN 1.5 x 16GA 109 -2083.60 6157.30 Pass
36.0 (b)
27.1
T5 420 - 400 Diagonal ROHN 1.5 x 16GA 188 -1691.54 6241.33 Pass
27.1 (b)
T6 400 - 380 Diagonal ROHN 1.5 x 16GA 220 -776.82 6241.33 12.4 Pass
T7 380 - 360 Diagonal ROHN 1.5 x 16GA 233 -1625.30 6241.33 26.0 Pass
T8 360 - 340 Diagonal ROHN 1.5 x 16GA 267 -2577.54 6241.33 41.3 Pass
T9 340 - 320 Diagonal ROHN 1.5 x 16GA 344 -3007.65 6241.33 48.2 Pass
T10 320 - 300 Diagonal ROHN 1.5 x 16GA 377 -2062.10 6241.33 33.0 Pass
T11 300 - 280 Diagonal ROHN 1.5 x 16GA 388 -1736.03 6241.33 27.8 Pass
T12 280 - 260 Diagonal ROHN 1.5 x 16GA 421 -2317.72 6241.33 37.1 Pass
59.2
T13 260 - 240 Diagonal ROHN 1.5 x 16GA 476 -3693.79 6241.33 Pass
60.4 (b)
T14 240 - 220 Diagonal ROHN 1.5 x 16GA 532 -2028.06 6241.33 32.5 Pass
T15 220 - 200 Diagonal ROHN 1.5 x 16GA 589 -1198.79 6241.33 19.2 Pass
T16 200 - 180 Diagonal ROHN 1.5 x 16GA 604 -2988.96 6241.33 47.9 Pass
T17 180 - 160 Diagonal ROHN 1.5 x 16GA 659 -1092.74 6241.33 17.5 Pass
T18 160 - 140 Diagonal ROHN 1.5 x 16GA 692 -2619.40 6241.33 42.0 Pass
T19 140 - 120 Diagonal ROHN 1.5 x 16GA 725 -3676.50 6241.33 58.9 Pass
33.5
T20 120 - 100 Diagonal ROHN 1.5 x 16GA 772 -2091.45 6241.33 Pass
35.6 (b)
T21 100 - 80 Diagonal ROHN 1.5 x 16GA 811 -1794.64 6472.44 27.7 Pass
T22 80 - 60 Diagonal ROHN 1.5 x 16GA 824 -3008.01 6472.44 46.5 Pass
46.9
T23 60 - 40 Diagonal ROHN 1.5 x 16GA 874 -3037.35 6472.44 Pass
49.6 (b)
T24 40 - 20 Diagonal ROHN 1.5 x 16GA 910 -2689.29 6472.44 41.5 Pass
T25 20 - 4.81771 Diagonal ROHN 1.5 x 16GA 938 -2362.03 6430.43 36.7 Pass
T26 4.81771 - 0 Horizontal C14x2-3/8x3/16 (BP) 947 -146.04 110250.00 28.5 Pass
2.8
T1 500 - 480 Top Girt ROHN 1.5 x 16GA 6 -202.97 7334.49 Pass
3.4 (b)
5.7
T2 480 - 460 Top Girt ROHN 1.5 x 16GA 38 591.88 10428.56 Pass
9.5 (b)

tnxTower Report - version 8.0.4.0


November 2, 2018
500-ft Guyed Tower Structural Analysis Report CCI BU No 871394
TEP Project Number 33537.193933, Order 464886, Revision 0 Page 7

Section Critical % Pass /


Elevation (ft) Component Type Size P (lb) ΦPallow (lb)
No. Element Capacity Fail
9.7
T3 460 - 440 Top Girt ROHN 1.5 x 16GA 71 -709.15 7334.49 Pass
11.0 (b)
2.3
T4 440 - 420 Top Girt ROHN 1.5 x 16GA 105 237.09 10428.56 Pass
3.8 (b)
8.4
T5 420 - 400 Top Girt ROHN 1.5 x 16GA 161 -624.68 7401.19 Pass
14.1 (b)
2.9
T6 400 - 380 Top Girt ROHN 1.5 x 16GA 193 306.44 10428.56 Pass
4.9 (b)
2.9
T7 380 - 360 Top Girt ROHN 1.5 x 16GA 228 305.91 10428.56 Pass
4.9 (b)
3.7
T8 360 - 340 Top Girt ROHN 1.5 x 16GA 260 370.60 9931.96 Pass
6.0 (b)
12.6
T9 340 - 320 Top Girt ROHN 1.5 x 16GA 317 -929.32 7401.19 Pass
20.1 (b)
7.3
T10 320 - 300 Top Girt ROHN 1.5 x 16GA 350 -539.49 7401.19 Pass
11.5 (b)
3.7
T11 300 - 280 Top Girt ROHN 1.5 x 16GA 383 383.55 10428.56 Pass
6.2 (b)
5.9
T12 280 - 260 Top Girt ROHN 1.5 x 16GA 415 -438.01 7401.19 Pass
9.6 (b)
6.0
T13 260 - 240 Top Girt ROHN 1.5 x 16GA 450 622.67 10428.56 Pass
10.0 (b)
5.7
T14 240 - 220 Top Girt ROHN 1.5 x 16GA 483 598.15 10428.56 Pass
9.6 (b)
5.6
T15 220 - 200 Top Girt ROHN 1.5 x 16GA 538 584.65 10428.56 Pass
9.4 (b)
5.8
T16 200 - 180 Top Girt ROHN 1.5 x 16GA 597 604.03 10428.56 Pass
9.7 (b)
5.9
T17 180 - 160 Top Girt ROHN 1.5 x 16GA 652 613.71 10428.56 Pass
9.9 (b)
3.0
T18 160 - 140 Top Girt ROHN 1.5 x 16GA 686 316.56 10428.56 Pass
5.1 (b)
8.2
T19 140 - 120 Top Girt ROHN 1.5 x 16GA 719 -609.16 7401.19 Pass
10.8 (b)
5.8
T20 120 - 100 Top Girt ROHN 1.5 x 16GA 752 600.53 10428.56 Pass
9.7 (b)
4.5
T21 100 - 80 Top Girt ROHN 1.5 x 16GA 784 469.26 10428.56 Pass
7.5 (b)
4.7
T22 80 - 60 Top Girt ROHN 1.5 x 16GA 818 494.15 10428.56 Pass
8.0 (b)
4.2
T23 60 - 40 Top Girt ROHN 1.5 x 16GA 851 437.71 10428.56 Pass
7.0 (b)
5.9
T24 40 - 20 Top Girt ROHN 1.5 x 16GA 883 612.23 10428.56 Pass
9.9 (b)
6.0
T25 20 - 4.81771 Top Girt ROHN 1.5 x 16GA 917 621.83 10428.56 Pass
10.0 (b)
T26 4.81771 - 0 Top Girt C14x2-3/8x3/16 (BP) 944 17918.20 111628.00 16.1 Pass
15.7
T1 500 - 480 Bottom Girt ROHN 1.5 x 16GA 8 -1149.35 7334.49 Pass
19.9 (b)
8.9
T2 480 - 460 Bottom Girt ROHN 1.5 x 16GA 42 -651.39 7334.49 Pass
10.8 (b)
13.0
T3 460 - 440 Bottom Girt ROHN 1.5 x 16GA 74 -955.69 7334.49 Pass
18.0 (b)
10.4
T4 440 - 420 Bottom Girt ROHN 1.5 x 16GA 107 -759.76 7334.49 Pass
12.2 (b)
3.4
T5 420 - 400 Bottom Girt ROHN 1.5 x 16GA 163 -248.16 7401.19 Pass
5.5 (b)
2.5
T6 400 - 380 Bottom Girt ROHN 1.5 x 16GA 198 -183.66 7401.19 Pass
3.9 (b)

tnxTower Report - version 8.0.4.0


November 2, 2018
500-ft Guyed Tower Structural Analysis Report CCI BU No 871394
TEP Project Number 33537.193933, Order 464886, Revision 0 Page 8

Section Critical % Pass /


Elevation (ft) Component Type Size P (lb) ΦPallow (lb)
No. Element Capacity Fail
7.5
T7 380 - 360 Bottom Girt ROHN 1.5 x 16GA 230 -557.40 7401.19 Pass
10.3 (b)
7.1
T8 360 - 340 Bottom Girt ROHN 1.5 x 16GA 264 743.72 10428.56 Pass
12.0 (b)
8.5
T9 340 - 320 Bottom Girt ROHN 1.5 x 16GA 320 -626.98 7401.19 Pass
11.4 (b)
4.1
T10 320 - 300 Bottom Girt ROHN 1.5 x 16GA 353 -306.70 7401.19 Pass
6.2 (b)
6.0
T11 300 - 280 Bottom Girt ROHN 1.5 x 16GA 385 -445.64 7401.19 Pass
8.8 (b)
10.9
T12 280 - 260 Bottom Girt ROHN 1.5 x 16GA 418 -803.64 7401.19 Pass
16.0 (b)
15.4
T13 260 - 240 Bottom Girt ROHN 1.5 x 16GA 452 -1142.36 7401.19 Pass
17.7 (b)
5.7
T14 240 - 220 Bottom Girt ROHN 1.5 x 16GA 486 596.73 10428.56 Pass
9.6 (b)
5.7
T15 220 - 200 Bottom Girt ROHN 1.5 x 16GA 543 568.27 9931.96 Pass
9.1 (b)
7.8
T16 200 - 180 Bottom Girt ROHN 1.5 x 16GA 600 813.88 10428.56 Pass
13.1 (b)
3.1
T17 180 - 160 Bottom Girt ROHN 1.5 x 16GA 656 325.46 10428.56 Pass
5.2 (b)
6.9
T18 160 - 140 Bottom Girt ROHN 1.5 x 16GA 689 720.99 10428.56 Pass
11.6 (b)
14.1
T19 140 - 120 Bottom Girt ROHN 1.5 x 16GA 722 1475.40 10428.56 Pass
23.7 (b)
5.1
T20 120 - 100 Bottom Girt ROHN 1.5 x 16GA 754 530.10 10428.56 Pass
8.5 (b)
4.1
T21 100 - 80 Bottom Girt ROHN 1.5 x 16GA 788 430.39 10428.56 Pass
6.9 (b)
9.2
T22 80 - 60 Bottom Girt ROHN 1.5 x 16GA 821 961.22 10428.56 Pass
15.5 (b)
6.1
T23 60 - 40 Bottom Girt ROHN 1.5 x 16GA 853 638.45 10428.56 Pass
10.3 (b)
5.6
T24 40 - 20 Bottom Girt ROHN 1.5 x 16GA 888 580.11 10428.56 Pass
9.3 (b)
14.4
T25 20 - 4.81771 Bottom Girt ROHN 1.5 x 16GA 920 1429.89 9931.96 Pass
23.0 (b)
T2 480 - 460 Guy A@479.385 5/8 960 12779.10 26711.49 47.8 Pass
T4 440 - 420 Guy A@422.523 9/16 969 11088.40 22049.58 50.3 Pass
T8 360 - 340 Guy A@342.523 9/16 981 9427.86 22049.58 42.8 Pass
T13 260 - 240 Guy A@259.385 9/16 990 10401.10 22049.58 47.2 Pass
T17 180 - 160 Guy A@179.385 9/16 996 14246.80 22049.58 64.6 Pass
T20 120 - 100 Guy A@119.385 1/2 1002 10882.90 16946.68 64.2 Pass
T23 60 - 40 Guy A@59.3854 7/16 1008 6791.60 13103.75 51.8 Pass
T2 480 - 460 Guy B@479.385 5/8 959 13015.40 26711.49 48.7 Pass
T4 440 - 420 Guy B@422.523 9/16 966 11359.20 22049.58 51.5 Pass
T8 360 - 340 Guy B@342.523 9/16 978 9724.05 22049.58 44.1 Pass
T13 260 - 240 Guy B@259.385 9/16 989 10751.20 22049.58 48.8 Pass
T17 180 - 160 Guy B@179.385 9/16 995 13774.40 22049.58 62.5 Pass
T20 120 - 100 Guy B@119.385 1/2 1001 10180.90 16946.68 60.1 Pass
T23 60 - 40 Guy B@59.3854 7/16 1007 6303.27 13103.75 48.1 Pass
T2 480 - 460 Guy C@479.385 5/8 955 12945.50 26711.49 48.5 Pass
T4 440 - 420 Guy C@422.523 9/16 961 11279.20 22049.58 51.2 Pass

tnxTower Report - version 8.0.4.0


November 2, 2018
500-ft Guyed Tower Structural Analysis Report CCI BU No 871394
TEP Project Number 33537.193933, Order 464886, Revision 0 Page 9

Section Critical % Pass /


Elevation (ft) Component Type Size P (lb) ΦPallow (lb)
No. Element Capacity Fail
T8 360 - 340 Guy C@342.523 9/16 973 9659.23 22049.58 43.8 Pass
T13 260 - 240 Guy C@259.385 9/16 985 10766.50 22049.58 48.8 Pass
T17 180 - 160 Guy C@179.385 9/16 991 13720.40 22049.58 62.2 Pass
T20 120 - 100 Guy C@119.385 1/2 997 10058.30 16946.68 59.4 Pass
T23 60 - 40 Guy C@59.3854 7/16 1003 6217.06 13103.75 47.4 Pass
Top Guy Pull- 6.6
T2 480 - 460 4 1/2x3/8 957 3801.31 57408.75 Pass
Off@479.385 9.1 (b)
Top Guy Pull- 7.0
T13 260 - 240 4 1/2x3/8 988 3999.04 57408.75 Pass
Off@259.385 9.6 (b)
Top Guy Pull- 6.9
T17 180 - 160 4 1/2x3/8 992 3941.50 57408.75 Pass
Off@179.385 9.4 (b)
Top Guy Pull- 6.7
T20 120 - 100 4 1/2x3/8 999 3856.86 57408.75 Pass
Off@119.385 9.2 (b)
Top Guy Pull- 4.9
T23 60 - 40 5x3/8 1005 3123.51 63787.50 Pass
Off@59.3854 7.5 (b)
Torque Arm
T4 440 - 420 C12x20.7 967 3208.69 201375.29 53.2 Pass
Top@422.523
Torque Arm
T8 360 - 340 C12x20.7 979 2545.35 201375.29 46.0 Pass
Top@342.523
Summary
Leg (T24) 84.2 Pass
Diagonal (T13) 60.4 Pass
Horizontal (T26) 28.5 Pass
Top Girt (T9) 20.1 Pass
Bottom Girt (T19) 23.7 Pass
Guy A (T17) 64.6 Pass
Guy B (T17) 62.5 Pass
Guy C (T17) 62.2 Pass
Top Guy Pull-Off
9.6 Pass
(T13)
Torque Arm Top
53.2 Pass
(T4)
Bolt Checks 60.4 Pass
Rating = 84.2 Pass

tnxTower Report - version 8.0.4.0


November 2, 2018
500-ft Guyed Tower Structural Analysis Report CCI BU No 871394
TEP Project Number 33537.193933, Order 464886, Revision 0 Page 10

Table 5 - Tower Component Stresses vs. Capacity - LC5


Notes Component Elevation (ft) % Capacity Pass / Fail

1,2 Mast Foundation Soil Interaction - 79.9 Pass


1,2 Mast Foundation Structural - 38.0 Pass
1,2 Inner Guy Anchor Foundation - 39.3 Pass
1,2 Middle Guy Anchor Foundation - 17.3 Pass
1,2 Outer Guy Anchor Foundation - 21.0 Pass
1,2 Inner Guy Anchor Rod - 42.0 Pass
1,2 Middle Guy Anchor Rod - 38.0 Pass
1,2 Outer Guy Anchor Rod - 41.2 Pass

Structure Rating (max from all components) = 84.2%


Notes:
1) See additional documentation in “Appendix C - Additional Calculations” for calculations supporting the % capacity listed.
2) Rating per TIA-222-H Section 15.5

4.1) Recommendations

1) If the load differs from that described in Tables 1 and 2 of this report, the referenced drawings, or
the provisions of this analysis are found to be invalid, another structural analysis should be
performed.
2) The tower and its foundation have sufficient capacity to carry the proposed load configuration.
No modifications are required at this time.

tnxTower Report - version 8.0.4.0


November 2, 2018
500-ft Guyed Tower Structural Analysis Report CCI BU No 871394
TEP Project Number 33537.193933, Order 464886, Revision 0 Page 11

APPENDIX A

TNXTOWER OUTPUT

tnxTower Report - version 8.0.4.0


500.0 ft R=426' (-11)

3.41667
N.A.

421.9
T1

R=348' (-22.5)
480.0 ft

4 1/2x3/8

5/8
482.6

EH
T2

ROHN 2 EH

S
LC
460.0 ft

=6
22
'3
R=139' (-17)

421.9
T3

-13
/16
440.0 ft

"
IT=
10
970.7
T4

%
420.0 ft

9
9//16
16 EH
R=138'6" (6) R=138' (4)

EHS
469.6
T5

S LC
LC=5
400.0 ft

=579
R=300' (8) R=300' (6)

79'8-
'8-13
R=401' (6) R=400' (1)

13/32
469.6
ROHN 2.5 STD
T6

/32"
PLAN

" IT
380.0 ft

IT=1
=10%
0%
469.6
T7

N.A.

360.0 ft
BCR12-A
5/8"x6-ft
750
PG1N0F-0090-310
490114
DB420
784-70
2.4"
16"
HG2409U-PRO
Side
NHH-65C-R2B
HBXX-6516DS-A2M
(2)
RADIO
(3)
RVZDC-6627-PF-48
RRFDC-3315-PF-48
Sector
3"
Knife
xRADIO
LNX-6515DS-A1M
Dia.
6"
10074
dia.
Arm
Plate
SideLight
Mount
(Abandoned)
4449
(Abandoned)
xLRod
Mount
(Abandoned)
30"
10'
4449
8843
1/2"x4"x33"
(Apex)
[SM
stabilizer
Beacon
w/
[SO
Mount
405-3]
(Abandoned)
309-1]
303-1]
305-1]
w/
(Existing)
w/Mount
Pipe
Mount
(Abandoned)
Pipe
Pipe 510
500
494
485
471
444
372
252
198
190
131
120
100
80
60
40
20
(Existing)
DESIGNED APPURTENANCE LOADING
1018.4
T8

TYPE ELEVATION TYPE ELEVATION


340.0 ft BCR12-A (Abandoned) 510 HBXX-6516DS-A2M w/ Mount Pipe 190
9
9//116

16" Dia. x 30" Beacon 500 (Existing)


6EEH
585.2

(2) RADIO 4449 190


T9

16" Dia. x 30" Beacon 500


HSS

RADIO 4449 190


LC
LC=4

5/8"x6-ft LRod 500


320.0 ft
=449

750 10074 494 (3) RADIO 8843 190


49'5-
'5-3/4

Side Arm Mount [SO 309-1] 494 RVZDC-6627-PF-48 190


585.2

3/4"
T10

PG1N0F-0090-310 (Abandoned) 485 RRFDC-3315-PF-48 (Existing) 190


" IT
IT=10

300.0 ft 490114 (Abandoned) 485 Sector Mount [SM 405-3] 190


=1 %

3" x 6" SideLight 131


0%

Side Arm Mount [SO 303-1] (Abandoned) 485


585.2

3" x 6" SideLight 131


T11

DB420 (Abandoned) 471


Side Arm Mount [SO 303-1] (Abandoned) 471 3" x 6" SideLight 131
280.0 ft
784-70 444 Knife Plate 1/2"x4"x33" 120
Side Arm Mount [SO 303-1] 444 Knife Plate 1/2"x4"x33" 120
585.2
T12

ROHN 2.5 EH

2.4" dia. x 10' stabilizer 444 Knife Plate 1/2"x4"x33" 120


ROHN 1.5 x 16GA

ROHN 1.5 x 16GA

ROHN 1.5 x 16GA

198 @ 2.40885

260.0 ft 3" x 6" SideLight 372 Knife Plate 1/2"x4"x33" 120


A53-B-42

3" x 6" SideLight 372 Knife Plate 1/2"x4"x33" 120


4 1/2x3/8

9/
A572-50

N.A.

16

Knife Plate 1/2"x4"x33" 120


645.8
T13

3" x 6" SideLight 372


EH
S

16" Dia. x 30" Beacon 252 Knife Plate (Apex) 100


LC

240.0 ft Knife Plate (Apex) 100


=

16" Dia. x 30" Beacon 252


39
1'

Knife Plate (Apex) 100


2-

HG2409U-PRO 198
690.7

3/
T14

Knife Plate (Apex) 80


16

Side Arm Mount [SO 305-1] 198


"

Knife Plate (Apex) 80


IT

220.0 ft NHH-65C-R2B w/ Mount Pipe 190


=1

Knife Plate (Apex) 80


0%

NHH-65C-R2B w/ Mount Pipe 190


Knife Plate (Apex) 60
N.A.

690.7

NHH-65C-R2B w/ Mount Pipe 190


T15

(2) LNX-6515DS-A1M w/ Mount Pipe 190 Knife Plate (Apex) 60


200.0 ft (Existing) Knife Plate (Apex) 60
(2) LNX-6515DS-A1M w/ Mount Pipe 190 Knife Plate (Apex) 40
690.7

(Existing)
T16

Knife Plate (Apex) 40


(2) LNX-6515DS-A1M w/ Mount Pipe 190 Knife Plate (Apex) 40
180.0 ft (Existing)
Knife Plate (Apex) 20
4 1/2x3/8

HBXX-6516DS-A2M w/ Mount Pipe 190


9/ 1

Knife Plate (Apex) 20


880.1

(Existing)
6E
T17

Knife Plate (Apex) 20


HS

HBXX-6516DS-A2M w/ Mount Pipe 190


2.5 XH w/ 3 STD Half Sleeve

160.0 ft (Existing)
L
C=
23
819.5

9'5
T18

SYMBOL LIST
-19
/32
N.A.

140.0 ft MARK SIZE MARK SIZE


"

A Rohn 2.5 EH w/ L3x3x1/4 D N.A.


IT=
819.5
T19

10

B 3 STD w/ 3.5 STD Half Sleeve E C14x2-3/8x3/16 (BP)


%

120.0 ft C ROHN 3 X-STR F 4 @ 1.20443


4 1/2x3/8

1/
2

MATERIAL STRENGTH
880.1

EH
T20

S
LC

100.0 ft GRADE Fy Fu GRADE Fy Fu


=1
9

A572-50 50 ksi 65 ksi A53-B-42 42 ksi 63 ksi


3'4
"
890.6
T21

IT
A

=1
0%

TOWER DESIGN NOTES


N.A.

80.0 ft
1. Tower is located in Wake County, North Carolina.
885.4

2. Tower designed for Exposure B to the TIA-222-H Standard.


T22

Rohn 3 STD w/ L3x3x1/4

3. Tower designed for a 115 mph basic wind in accordance with the TIA-222-H Standard.
60.0 ft
7 /1
6E 4. Tower is also designed for a 30 mph basic wind with 1.27 in ice. Ice is considered to increase in thickness
HS with height.
5x3/8

LC
952.7
T23

=1 5. Deflections are based upon a 60 mph wind.


56
'10
40.0 ft -9 /
16 6. Tower Risk Category II.
"
IT= 7. Topographic Category 1 with Crest Height of 0'
10
% 8. TIA-222-H Annex S
885.4
T24

N.A.

20.0 ft
657.8

22244 lb 19531 lb 21855 lb


T25

4.8 ft
17914.9460.7

28
T26

0.0 ft
E

31

30

22
18

55

883 lb 7
lb
0

21850 lb 20380 lb 21349 lb


lb

lb
Top Guy Pull-Offs

270452 lb (Axial) R=400'


Diagonal Grade

# Panels @ (ft)

R=300'
Face Width (ft)

4315 lb-ft (Torque)


Bottom Girts

R=139'
Horizontals

Weight (lb)
Leg Grade

Diagonals

Top Girts
Section

ALL REACTIONS ARE FACTORED


Legs

Tower Engineering Professionals Job: Apex (BU 871394)


Project: TEP No. 33537.193933
326 Tryon Road
Client: Drawn by: App'd:
Raleigh, NC 27603 Crown Castle jbalk
Code: Date: Scale:
Tower Engineering Professionals Phone: (919) 661-6351 TIA-222-H 11/02/18 NTS
Path: Dwg No.
FAX: (919) 661-6350 C:\Users\jbalk\Desktop\Work In Progress\Week of 10-29-2018\33537\P-163302_L-193933_871394_Apex_Structural Analysis\tnxTower\871394_LC5.eri
E-1
Job Page
tnxTower Apex (BU 871394) 1 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Tower Input Data

The main tower is a 3x guyed tower with an overall height of 500' above the ground line.
The base of the tower is set at an elevation of 0' above the ground line.
The face width of the tower is 3'5'' at the top and tapered at the base.
This tower is designed using the TIA-222-H standard.
The following design criteria apply:
Tower is located in Wake County, North Carolina.
Tower base elevation above sea level: 479'.
Basic wind speed of 115 mph.
Risk Category II.
Exposure Category B.
Simplified Topographic Factor Procedure for wind speed-up calculations is used.
Topographic Category: 1.
Crest Height 0'.
Nominal ice thickness of 1.275 in.
Ice thickness is considered to increase with height.
Ice density of 56 pcf.
A wind speed of 30 mph is used in combination with ice.
Temperature drop of 50 °F.
Deflections calculated using a wind speed of 60 mph.
TIA-222-H Annex S.
Pressures are calculated at each section.
Safety factor used in guy design is 0.9524.
Stress ratio used in tower member design is 1.05.
Local bending stresses due to climbing loads, feed line supports, and appurtenance mounts are not considered.

Options
Consider Moments - Legs Distribute Leg Loads As Uniform Use ASCE 10 X-Brace Ly Rules
Consider Moments - Horizontals Assume Legs Pinned √ Calculate Redundant Bracing Forces
Consider Moments - Diagonals √ Assume Rigid Index Plate Ignore Redundant Members in FEA
Use Moment Magnification √ Use Clear Spans For Wind Area SR Leg Bolts Resist Compression
Use Code Stress Ratios √ Use Clear Spans For KL/r All Leg Panels Have Same Allowable
Use Code Safety Factors - Guys √ Retension Guys To Initial Tension Offset Girt At Foundation
Escalate Ice √ Bypass Mast Stability Checks √ Consider Feed Line Torque
Always Use Max Kz √ Use Azimuth Dish Coefficients √ Include Angle Block Shear Check
Use Special Wind Profile √ Project Wind Area of Appurt. Use TIA-222-H Bracing Resist. Exemption
√ Include Bolts In Member Capacity √ Autocalc Torque Arm Areas Use TIA-222-H Tension Splice Exemption
Leg Bolts Are At Top Of Section Add IBC .6D+W Combination Poles
Secondary Horizontal Braces Leg √ Sort Capacity Reports By Component Include Shear-Torsion Interaction
Use Diamond Inner Bracing (4 Sided) Triangulate Diamond Inner Bracing Always Use Sub-Critical Flow
SR Members Have Cut Ends Treat Feed Line Bundles As Cylinder Use Top Mounted Sockets
SR Members Are Concentric Ignore KL/ry For 60 Deg. Angle Legs Pole Without Linear Attachments
Pole With Shroud Or No Appurtenances
Outside and Inside Corner Radii Are
Known
Job Page
tnxTower Apex (BU 871394) 2 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Wind 180

Guy A
Leg A

Wind 90

Fa
A

ce
ce
Fa

B
X
Leg C Z Leg B
Gu
yC Face C yB
Gu

Wind 0

Corner & Starmount Guyed Tower


Job Page
tnxTower Apex (BU 871394) 3 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Wind 180
yA
Gu

Gu
yB
Leg A

Wind 90

Fa
A

ce
ce
Fa

B
X
Leg C Z Leg B

Face C

Wind 0

Guy C

Face Guyed

Tower Section Geometry


Tower Tower Assembly Description Section Number Section
Section Elevation Database Width of Length
Sections
ft ft ft
T1 500'-480' 3'5'' 1 20'
T2 480'-460' 3'5'' 1 20'
T3 460'-440' 3'5'' 1 20'
T4 440'-420' 3'5'' 1 20'
T5 420'-400' 3'5'' 1 20'
T6 400'-380' 3'5'' 1 20'
T7 380'-360' 3'5'' 1 20'
T8 360'-340' 3'5'' 1 20'
T9 340'-320' 3'5'' 1 20'
T10 320'-300' 3'5'' 1 20'
T11 300'-280' 3'5'' 1 20'
T12 280'-260' 3'5'' 1 20'
T13 260'-240' 3'5'' 1 20'
T14 240'-220' 3'5'' 1 20'
T15 220'-200' 3'5'' 1 20'
T16 200'-180' 3'5'' 1 20'
Job Page
tnxTower Apex (BU 871394) 4 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Tower Tower Assembly Description Section Number Section


Section Elevation Database Width of Length
Sections
ft ft ft
T17 180'-160' 3'5'' 1 20'
T18 160'-140' 3'5'' 1 20'
T19 140'-120' 3'5'' 1 20'
T20 120'-100' 3'5'' 1 20'
T21 100'-80' 3'5'' 1 20'
T22 80'-60' 3'5'' 1 20'
T23 60'-40' 3'5'' 1 20'
T24 40'-20' 3'5'' 1 20'
T25 20'-4'9-27/32'' 3'5'' 1 15'2-5/32''
T26 4'9-27/32''-0' 3'5'' 1 4'9-27/32''

Tower Section Geometry (cont’d)


Tower Tower Diagonal Bracing Has Has Top Girt Bottom Girt
Section Elevation Spacing Type K Brace Horizontals Offset Offset
End
ft ft Panels in in
T1 500'-480' 2'4-29/32'' K Brace Left No No 7.375 1.375
T2 480'-460' 2'4-29/32'' K Brace Left No No 7.375 1.375
T3 460'-440' 2'4-29/32'' K Brace Left No No 7.375 1.375
T4 440'-420' 2'4-29/32'' CX Brace No No 7.375 1.375
T5 420'-400' 2'4-29/32'' K Brace Left No No 7.375 1.375
T6 400'-380' 2'4-29/32'' K Brace Left No No 7.375 1.375
T7 380'-360' 2'4-29/32'' K Brace Left No No 7.375 1.375
T8 360'-340' 2'4-29/32'' CX Brace No No 7.375 1.375
T9 340'-320' 2'4-29/32'' K Brace Left No No 7.375 1.375
T10 320'-300' 2'4-29/32'' K Brace Left No No 7.375 1.375
T11 300'-280' 2'4-29/32'' K Brace Left No No 7.375 1.375
T12 280'-260' 2'4-29/32'' K Brace Left No No 7.375 1.375
T13 260'-240' 2'4-29/32'' K Brace Left No No 7.375 1.375
T14 240'-220' 2'4-29/32'' CX Brace No No 7.375 1.375
T15 220'-200' 2'4-29/32'' CX Brace No No 7.375 1.375
T16 200'-180' 2'4-29/32'' CX Brace No No 7.375 1.375
T17 180'-160' 2'4-29/32'' K Brace Left No No 7.375 1.375
T18 160'-140' 2'4-29/32'' K Brace Left No No 7.375 1.375
T19 140'-120' 2'4-29/32'' K Brace Left No No 7.375 1.375
T20 120'-100' 2'4-29/32'' K Brace Left No No 7.375 1.375
T21 100'-80' 2'4-29/32'' K Brace Left No No 7.375 1.375
T22 80'-60' 2'4-29/32'' K Brace Left No No 7.375 1.375
T23 60'-40' 2'4-29/32'' K Brace Left No No 7.375 1.375
T24 40'-20' 2'4-29/32'' K Brace Left No No 7.375 1.375
T25 20'-4'9-27/32'' 2'4-29/32'' K Brace Left No No 7.375 1.375
T26 4'9-27/32''-0' 1'2-7/16'' X Brace No Yes 0.000 0.000

Tower Section Geometry (cont’d)


Tower Leg Leg Leg Diagonal Diagonal Diagonal
Elevation Type Size Grade Type Size Grade
ft
T1 500'-480' Pipe ROHN 2 EH A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T2 480'-460' Pipe ROHN 2 EH A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
Job Page
tnxTower Apex (BU 871394) 5 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Tower Leg Leg Leg Diagonal Diagonal Diagonal


Elevation Type Size Grade Type Size Grade
ft
(50 ksi) (42 ksi)
T3 460'-440' Pipe ROHN 2 EH A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T4 440'-420' Pipe ROHN 2 EH A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T5 420'-400' Pipe ROHN 2.5 STD A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T6 400'-380' Pipe ROHN 2.5 STD A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T7 380'-360' Pipe ROHN 2.5 STD A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T8 360'-340' Pipe ROHN 2.5 STD A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T9 340'-320' Pipe ROHN 2.5 EH A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T10 320'-300' Pipe ROHN 2.5 EH A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T11 300'-280' Pipe ROHN 2.5 EH A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T12 280'-260' Pipe ROHN 2.5 EH A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T13 260'-240' Pipe ROHN 2.5 EH A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T14 240'-220' Pipe ROHN 2.5 EH A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T15 220'-200' Pipe ROHN 2.5 EH A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T16 200'-180' Pipe ROHN 2.5 EH A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T17 180'-160' Arbitrary Shape 2.5 XH w/ 3 STD Half Sleeve A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T18 160'-140' Arbitrary Shape 2.5 XH w/ 3 STD Half Sleeve A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T19 140'-120' Arbitrary Shape 2.5 XH w/ 3 STD Half Sleeve A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T20 120'-100' Arbitrary Shape 2.5 XH w/ 3 STD Half Sleeve A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T21 100'-80' Arbitrary Shape Rohn 2.5 EH w/ L3x3x1/4 A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T22 80'-60' Arbitrary Shape Rohn 3 STD w/ L3x3x1/4 A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T23 60'-40' Arbitrary Shape Rohn 3 STD w/ L3x3x1/4 A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T24 40'-20' Arbitrary Shape Rohn 3 STD w/ L3x3x1/4 A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
(50 ksi) (42 ksi)
T25 Arbitrary Shape 3 STD w/ 3.5 STD Half Sleeve A572-50 Pipe ROHN 1.5 x 16GA A53-B-42
20'-4'9-27/32'' (50 ksi) (42 ksi)
T26 4'9-27/32''-0' Pipe ROHN 3 X-STR A572-50 Pipe A36
(50 ksi) (36 ksi)

Tower Section Geometry (cont’d)


Tower Top Girt Top Girt Top Girt Bottom Girt Bottom Girt Bottom Girt
Elevation Type Size Grade Type Size Grade
ft
T1 500'-480' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
Job Page
tnxTower Apex (BU 871394) 6 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Tower Top Girt Top Girt Top Girt Bottom Girt Bottom Girt Bottom Girt
Elevation Type Size Grade Type Size Grade
ft
(42 ksi) (42 ksi)
T2 480'-460' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T3 460'-440' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T4 440'-420' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T5 420'-400' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T6 400'-380' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T7 380'-360' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T8 360'-340' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T9 340'-320' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T10 320'-300' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T11 300'-280' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T12 280'-260' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T13 260'-240' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T14 240'-220' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T15 220'-200' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T16 200'-180' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T17 180'-160' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T18 160'-140' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T19 140'-120' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T20 120'-100' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T21 100'-80' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T22 80'-60' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T23 60'-40' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T24 40'-20' Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
(42 ksi) (42 ksi)
T25 Pipe ROHN 1.5 x 16GA A53-B-42 Pipe ROHN 1.5 x 16GA A53-B-42
20'-4'9-27/32'' (42 ksi) (42 ksi)
T26 4'9-27/32''-0' Channel C14x2-3/8x3/16 (BP) A36 Single Angle L14x2-3/8x3/16 (BP) A36
(36 ksi) (36 ksi)

Tower Section Geometry (cont’d)


Job Page
tnxTower Apex (BU 871394) 7 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Tower No. Mid Girt Mid Girt Mid Girt Horizontal Horizontal Horizontal
Elevation of Type Size Grade Type Size Grade
Mid
ft Girts
T26 4'9-27/32''-0' None Channel A36 Channel C14x2-3/8x3/16 (BP) A36
(36 ksi) (36 ksi)

Tower Section Geometry (cont’d)


Tower Gusset Gusset Gusset Grade Adjust. Factor Adjust. Weight Mult. Double Angle Double Angle Double Angle
Elevation Area Thickness Af Factor Stitch Bolt Stitch Bolt Stitch Bolt
(per face) Ar Spacing Spacing Spacing
Diagonals Horizontals Redundants
ft ft2 in in in in
T1 500'-480' 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T2 480'-460' 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T3 460'-440' 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T4 440'-420' 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T5 420'-400' 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T6 400'-380' 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T7 380'-360' 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T8 360'-340' 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T9 340'-320' 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T10 320'-300' 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T11 300'-280' 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T12 280'-260' 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T13 260'-240' 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T14 240'-220' 0.00 0.375 A36 1.03 1 1.05 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T15 220'-200' 0.00 0.375 A36 1.03 1 1.05 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T16 200'-180' 0.00 0.375 A36 1.03 1 1.05 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T17 180'-160' 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T18 160'-140' 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T19 140'-120' 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T20 120'-100' 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T21 100'-80' 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T22 80'-60' 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T23 60'-40' 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
Job Page
tnxTower Apex (BU 871394) 8 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Tower Gusset Gusset Gusset Grade Adjust. Factor Adjust. Weight Mult. Double Angle Double Angle Double Angle
Elevation Area Thickness Af Factor Stitch Bolt Stitch Bolt Stitch Bolt
(per face) Ar Spacing Spacing Spacing
Diagonals Horizontals Redundants
ft ft2 in in in in
(36 ksi)
T24 40'-20' 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
(36 ksi)
T25 0.00 0.375 A36 1 1 1.03 Mid-Pt Mid-Pt Mid-Pt
20'-4'9-27/32'' (36 ksi)
T26 0.00 0.000 A36 1 1 1 Mid-Pt Mid-Pt Mid-Pt
4'9-27/32''-0' (36 ksi)

Tower Section Geometry (cont’d)


K Factors1
Tower Calc Calc Legs X K Single Girts Horiz. Sec. Inner
Elevation K K Brace Brace Diags Horiz. Brace
Single Solid Diags Diags
Angles Rounds X X X X X X X
ft Y Y Y Y Y Y Y
T1 500'-480' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T2 480'-460' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T3 460'-440' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T4 440'-420' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T5 420'-400' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T6 400'-380' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T7 380'-360' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T8 360'-340' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T9 340'-320' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T10 320'-300' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T11 300'-280' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T12 280'-260' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T13 260'-240' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T14 240'-220' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T15 220'-200' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T16 200'-180' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T17 180'-160' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T18 160'-140' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T19 140'-120' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T20 120'-100' No No 1 1 1 1 1 1 1 1
Job Page
tnxTower Apex (BU 871394) 9 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

K Factors1
Tower Calc Calc Legs X K Single Girts Horiz. Sec. Inner
Elevation K K Brace Brace Diags Horiz. Brace
Single Solid Diags Diags
Angles Rounds X X X X X X X
ft Y Y Y Y Y Y Y
1 1 1 1 1 1 1
T21 100'-80' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T22 80'-60' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T23 60'-40' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T24 40'-20' No No 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
T25 No No 1 1 1 1 1 1 1 1
20'-4'9-27/32'' 1 1 1 1 1 1 1
T26 No No 1 1 1 1 1 1 1 1
4'9-27/32''-0' 1 1 1 1 1 1 1
1
Note: K factors are applied to member segment lengths. K-braces without inner supporting members will have the K factor in the out-of-plane direction applied to
the overall length.

Tower Section Geometry (cont’d)


Tower Leg Diagonal Top Girt Bottom Girt Mid Girt Long Horizontal Short Horizontal
Elevation
ft
Net Width U Net Width U Net Width U Net U Net U Net U Net U
Deduct Deduct Deduct Width Width Width Width
in in in Deduct Deduct Deduct Deduct
in in in in
T1 500'-480' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T2 480'-460' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T3 460'-440' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T4 440'-420' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T5 420'-400' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T6 400'-380' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T7 380'-360' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T8 360'-340' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T9 340'-320' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T10 320'-300' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T11 300'-280' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T12 280'-260' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T13 260'-240' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T14 240'-220' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T15 220'-200' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T16 200'-180' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T17 180'-160' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T18 160'-140' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T19 140'-120' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T20 120'-100' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T21 100'-80' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T22 80'-60' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T23 60'-40' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T24 40'-20' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
T25 0.000 1 0.000 1 0.000 1 0.000 1 0.000 0.75 0.000 1 0.000 0.75
20'-4'9-27/32''
T26 0.000 1 0.000 0.75 0.000 1 0.000 0.75 0.000 0.75 0.000 1 0.000 0.75
4'9-27/32''-0'
Job Page
tnxTower Apex (BU 871394) 10 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Tower Section Geometry (cont’d)


Tower Leg Leg Diagonal Top Girt Bottom Girt Mid Girt Long Horizontal Short Horizontal
Elevation Connection
ft Type
Bolt Size No. Bolt Size No. Bolt Size No. Bolt Size No. Bolt Size No. Bolt Size No. Bolt Size No.
in in in in in in in
T1 500'-480' Flange 0.750 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T2 480'-460' Flange 0.750 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T3 460'-440' Flange 0.750 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T4 440'-420' Flange 0.750 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T5 420'-400' Flange 0.750 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T6 400'-380' Flange 0.750 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T7 380'-360' Flange 0.750 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T8 360'-340' Flange 0.750 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T9 340'-320' Flange 0.750 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T10 320'-300' Flange 0.750 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T11 300'-280' Flange 0.750 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T12 280'-260' Flange 0.750 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T13 260'-240' Flange 0.750 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T14 240'-220' Flange 0.750 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T15 220'-200' Flange 0.750 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T16 200'-180' Flange 0.750 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T17 180'-160' Flange 0.750 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T18 160'-140' Flange 0.750 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T19 140'-120' Flange 0.750 0 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T20 120'-100' Flange 0.750 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T21 100'-80' Flange 0.875 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T22 80'-60' Flange 0.875 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T23 60'-40' Flange 0.875 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T24 40'-20' Flange 0.875 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
A325X A325X A325X A325X A325N A325X A325N
T25 Flange 0.875 4 0.500 1 0.500 1 0.500 1 0.625 0 0.500 0 0.625 0
20'-4'9-27/32'' A325X A325X A325X A325X A325N A325X A325N
T26 Flange 0.875 0 0.000 0 0.000 0 0.000 0 0.000 0 0.000 0 0.625 0
4'9-27/32''-0' A325X A325N A325N A325N A325N A325X A325N
Job Page
tnxTower Apex (BU 871394) 11 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Guy Data
Guy Guy Guy Initial % Guy Guy Lu Anchor Anchor Anchor End
Elevation Grade Size Tension Modulus Weight Radius Azimuth Elevation Fitting
Adj. Efficiency
ft lb ksi plf ft ft ° ft %
479.385 EHS A 5/8 4240.00 10% 23000.000 0.813 647'11-1/32'' 426' 0.000 -11' 100%
B 5/8 4240.00 10% 23000.000 0.813 621'11-13/32 400' 0.000 1' 100%
C 5/8 4240.00 10% 23000.000 0.813 '' 401' 0.000 6' 100%
618'9-1/8''
422.523 EHS A 9/16 3500.00 10% 23000.000 0.671 606'3/8'' 426' 0.000 -11' 100%
B 9/16 3500.00 10% 23000.000 0.671 579'4-5/16'' 400' 0.000 1' 100%
C 9/16 3500.00 10% 23000.000 0.671 576'5-5/32'' 401' 0.000 6' 100%
342.523 EHS A 9/16 3500.00 10% 23000.000 0.671 502'7-3/16'' 348' 0.000 -22'6'' 100%
B 9/16 3500.00 10% 23000.000 0.671 449'2-1/32'' 300' 0.000 6' 100%
C 9/16 3500.00 10% 23000.000 0.671 447'8-5/32'' 300' 0.000 8' 100%
259.385 EHS A 9/16 3500.00 10% 23000.000 0.671 446'3/8'' 348' 0.000 -22'6'' 100%
B 9/16 3500.00 10% 23000.000 0.671 390'11-1/32'' 300' 0.000 6' 100%
C 9/16 3500.00 10% 23000.000 0.671 389'7-9/16'' 300' 0.000 8' 100%
179.385 EHS A 9/16 3500.00 10% 23000.000 0.671 239'3-3/8'' 139' 0.000 -17' 100%
B 9/16 3500.00 10% 23000.000 0.671 221'9-3/8'' 138' 0.000 4' 100%
C 9/16 3500.00 10% 23000.000 0.671 220'6-1/4'' 138'6'' 0.000 6' 100%
119.385 EHS A 1/2 2690.00 10% 23000.000 0.517 193'2-9/32'' 139' 0.000 -17' 100%
B 1/2 2690.00 10% 23000.000 0.517 178'2-7/8'' 138' 0.000 4' 100%
C 1/2 2690.00 10% 23000.000 0.517 177'4-3/32'' 138'6'' 0.000 6' 100%
59.3854 EHS A 7/16 2080.00 10% 23000.000 0.399 156'9-1/8'' 139' 0.000 -17' 100%
B 7/16 2080.00 10% 23000.000 0.399 146'9-1/8'' 138' 0.000 4' 100%
C 7/16 2080.00 10% 23000.000 0.399 146'5-3/4'' 138'6'' 0.000 6' 100%

Guy Data(cont’d)
Guy Mount Torque-Arm Torque-Arm Torque-Arm Torque-Arm Torque-Arm Torque-Arm Size
Elevation Type Spread Leg Angle Style Grade Type
ft
ft °
479.385 Corner
422.523 Torque Arm 7'1-9/16'' 0.000 Channel A36 Channel C12x20.7
(36 ksi)
342.523 Torque Arm 7'1-9/16'' 0.000 Channel A36 Channel C12x20.7
(36 ksi)
259.385 Corner
179.385 Corner
119.385 Corner
59.3854 Corner

Guy Data (cont’d)


Guy Diagonal Diagonal Upper Diagonal Lower Diagonal Is Pull-Off Pull-Off Type Pull-Off Size
Elevation Grade Type Size Size Strap. Grade
ft
Job Page
tnxTower Apex (BU 871394) 12 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Guy Diagonal Diagonal Upper Diagonal Lower Diagonal Is Pull-Off Pull-Off Type Pull-Off Size
Elevation Grade Type Size Size Strap. Grade
ft
479'4-11/1 A572-50 Solid Round Yes A36 Flat Bar 4 1/2x3/8
6'' (50 ksi) (36 ksi)
422'6-1/4'' A572-50 Solid Round A36 Flat Bar
(50 ksi) (36 ksi)
342'6-1/4'' A572-50 Solid Round A36 Flat Bar
(50 ksi) (36 ksi)
259'4-11/1 A572-50 Solid Round Yes A36 Flat Bar 4 1/2x3/8
6'' (50 ksi) (36 ksi)
179'4-11/1 A572-50 Solid Round Yes A36 Flat Bar 4 1/2x3/8
6'' (50 ksi) (36 ksi)
119'4-11/1 A572-50 Solid Round Yes A36 Flat Bar 4 1/2x3/8
6'' (50 ksi) (36 ksi)
59'4-11/16' A572-50 Solid Round Yes A36 Flat Bar 5x3/8
' (50 ksi) (36 ksi)

Guy Data (cont’d)


Guy Cable Cable Cable Cable Tower Tower Tower Tower
Elevation Weight Weight Weight Weight Intercept Intercept Intercept Intercept
A B C D A B C D
ft lb lb lb lb ft ft ft ft
479.385 526.76 505.64 503.05 38'5-7/8'' 35'6-1/8'' 35'1-29/32''
10.7 sec/pulse 10.3 sec/pulse 10.2 sec/pulse
422.523 406.65 388.75 386.78 33'10-3/16'' 30'11-5/8'' 30'8-1/32''
10.0 sec/pulse 9.6 sec/pulse 9.6 sec/pulse
342.523 337.25 301.39 300.39 23'5-1/32'' 18'9-1/8'' 18'7-9/16''
8.4 sec/pulse 7.5 sec/pulse 7.5 sec/pulse
259.385 299.29 262.31 261.44 18'7-3/32'' 14'3-27/32'' 14'2-3/4''
7.4 sec/pulse 6.5 sec/pulse 6.5 sec/pulse
179.385 160.56 148.82 147.97 5'4-11/16'' 4'7-11/16'' 4'7-3/32''
4.0 sec/pulse 3.7 sec/pulse 3.7 sec/pulse
119.385 99.88 92.15 91.68 3'6-15/32'' 3'1/4'' 2'11-7/8''
3.3 sec/pulse 3.0 sec/pulse 3.0 sec/pulse
59.3854 62.55 58.56 58.45 2'4-3/32'' 2'23/32'' 2'19/32''
2.6 sec/pulse 2.5 sec/pulse 2.5 sec/pulse

Guy Data (cont’d)


Torque Arm Pull Off Diagonal
Guy Calc Calc Kx Ky Kx Ky Kx Ky
Elevation K K
ft Single Solid
Angles Rounds
479.385 No No 1 1 1 1
422.523 No No 1 1 1 1 1 1
342.523 No No 1 1 1 1 1 1
259.385 No No 1 1 1 1
179.385 No No 1 1 1 1
119.385 No No 1 1 1 1
59.3854 No No 1 1 1 1
Job Page
tnxTower Apex (BU 871394) 13 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Guy Data (cont’d)


Torque-Arm Pull Off Diagonal
Guy Bolt Size Number Net Width U Bolt Size Number Net Width U Bolt Size Number Net Width U
Elevation in Deduct in Deduct in Deduct
ft in in in
479.385 0.625 0 0.000 0.75 0.750 2 0.000 1 0.625 0 0.000 0.75
A325N A325N A325N
422.523 0.625 2 0.000 0.75 0.750 0 0.000 1 0.625 0 0.000 0.75
A325X A325N A325N
342.523 0.625 2 0.000 0.75 0.750 0 0.000 1 0.625 0 0.000 0.75
A325X A325N A325N
259.385 0.625 0 0.000 0.75 0.750 2 0.000 1 0.625 0 0.000 0.75
A325N A325N A325N
179.385 0.625 0 0.000 0.75 0.750 2 0.000 1 0.625 0 0.000 0.75
A325N A325N A325N
119.385 0.625 0 0.000 0.75 0.750 2 0.000 1 0.625 0 0.000 0.75
A325N A325N A325N
59.3854 0.625 0 0.000 0.75 0.750 2 0.000 1 0.625 0 0.000 0.75
A325N A325N A325N

Guy Pressures
Guy Guy z qz qz Ice
Elevation Location Ice Thickness
ft ft psf psf in
479.385 A 234'2-5/16'' 33.861 2.304 1.551
B 240'2-5/16'' 34.107 2.321 1.555
C 242'8-5/16'' 34.208 2.328 1.557
422.523 A 205'9-5/32'' 32.632 2.221 1.531
B 211'9-5/32'' 32.901 2.239 1.535
C 214'3-5/32'' 33.011 2.247 1.537
342.523 A 160'5/32'' 30.369 2.067 1.493
B 174'3-5/32'' 31.119 2.118 1.506
C 175'3-5/32'' 31.170 2.121 1.507
259.385 A 118'5-5/16'' 27.868 1.897 1.449
B 132'8-5/16'' 28.788 1.959 1.465
C 133'8-5/16'' 28.849 1.963 1.466
179.385 A 81'2-5/16'' 25.018 1.703 1.395
B 91'8-5/16'' 25.903 1.763 1.412
C 92'8-5/16'' 25.983 1.768 1.414
119.385 A 51'2-5/16'' 21.929 1.492 1.332
B 61'8-5/16'' 23.130 1.574 1.357
C 62'8-5/16'' 23.236 1.581 1.360
59.3854 A 21'2-5/16'' 18.808 1.280 1.220
B 31'8-5/16'' 19.122 1.301 1.270
C 32'8-5/16'' 19.292 1.313 1.274

Guy-Mast Forces (Excluding Wind) - No Ice


Guy Guy Chord Guy Tension Fx Fy Fz Mx My Mz
Elevation Location Angle Top
Bottom
lb
ft ° lb lb lb lb-ft lb-ft lb-ft
Job Page
tnxTower Apex (BU 871394) 14 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Guy Guy Chord Guy Tension Fx Fy Fz Mx My Mz


Elevation Location Angle Top
Bottom
lb
ft ° lb lb lb lb-ft lb-ft lb-ft
479.385 A 49.151 4638.36 0.00 3620.47 -2899.41 -7141.79 0.00 0.00
4240.00
B 50.239 4628.61 2452.96 3660.79 1416.22 3610.66 0.00 -6253.85
4240.00
C 49.872 4624.55 -2470.69 3639.70 1426.45 3589.86 -0.00 6217.82
4240.00
Sum: -17.73 10920.95 -56.74 58.73 -0.00 -36.03
422.523 A 45.639 3790.66 -21.39 2808.89 -2545.35 -5777.35 9111.79 -10006.66
3500.00
A 45.639 3790.66 21.39 2808.89 -2545.35 -5777.35 -9111.79 10006.66
3500.00
B 46.647 3782.61 2173.37 2841.52 1228.99 11688.92 8940.42 0.00
3500.00
B 46.647 3782.61 2151.02 2841.52 1267.70 -5844.46 -8940.42 -10122.90
3500.00
C 46.234 3779.26 -2166.44 2821.23 1276.72 -5802.73 9004.29 10050.62
3500.00
C 46.234 3779.26 -2188.90 2821.23 1237.83 11605.45 -9004.29 0.00
3500.00
Sum: -30.95 16943.26 -79.45 92.49 -0.00 -72.28
342.523 A 46.536 3744.73 -25.64 2797.30 -2489.48 -5753.51 8921.49 -9965.37
3500.00
A 46.536 3744.73 25.64 2797.30 -2489.48 -5753.51 -8921.49 9965.37
3500.00
B 48.478 3725.62 2086.81 2855.25 1171.78 11745.42 8584.33 0.00
3500.00
B 48.478 3725.62 2058.19 2855.25 1221.34 -5872.71 -8584.33 -10171.84
3500.00
C 48.308 3724.28 -2064.69 2847.15 1225.19 -5856.05 8611.41 10142.98
3500.00
C 48.308 3724.28 -2093.39 2847.15 1175.47 11712.10 -8611.41 0.00
3500.00
Sum: -13.08 16999.40 -185.17 221.74 0.00 -28.86
259.385 A 39.167 3688.99 0.00 2419.48 -2784.74 -4772.70 0.00 0.00
3500.00
B 40.371 3669.88 2363.96 2452.95 1364.83 2419.36 0.00 -4190.45
3500.00
C 40.148 3668.54 -2371.36 2441.39 1369.11 2407.96 -0.00 4170.71
3500.00
Sum: -7.40 7313.82 -50.80 54.62 -0.00 -19.74
179.385 A 55.095 3631.67 0.00 3004.52 -2040.07 -5926.76 0.00 0.00
3500.00
B 52.203 3617.59 1888.55 2886.42 1090.36 2846.90 0.00 -4930.97
3500.00
C 51.782 3616.25 -1906.00 2869.40 1100.43 2830.11 -0.00 4901.90
3500.00
Sum: -17.45 8760.35 150.72 -249.75 -0.00 -29.07
119.385 A 44.865 2760.46 0.00 1972.38 -1931.28 -3890.75 0.00 0.00
2690.00
B 40.306 2749.61 1796.01 1805.39 1036.93 1780.67 0.00 -3084.22
2690.00
C 39.709 2748.57 -1811.44 1783.13 1045.84 1758.71 -0.00 3046.18
2690.00
Sum: -15.43 5560.91 151.49 -351.36 -0.00 -38.03
59.3854 A 29.137 2110.45 0.00 1051.42 -1829.90 -2074.04 0.00 0.00
2080.00
B 22.154 2102.08 1677.04 817.79 968.24 806.59 0.00 -1397.06
2080.00
C 21.357 2101.28 -1686.07 790.55 973.45 779.72 -0.00 1350.52
Job Page
tnxTower Apex (BU 871394) 15 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Guy Guy Chord Guy Tension Fx Fy Fz Mx My Mz


Elevation Location Angle Top
Bottom
lb
ft ° lb lb lb lb-ft lb-ft lb-ft
2080.00
Sum: -9.02 2659.76 111.79 -487.72 -0.00 -46.53

Guy-Mast Forces (Excluding Wind) - Ice


Guy Guy Chord Guy Tension Fx Fy Fz Mx My Mz
Elevation Location Angle Top
Bottom
lb
ft ° lb lb lb lb-ft lb-ft lb-ft
479.385 A 49.151 13128.57 0.00 10604.43 -7739.85 -20918.45 0.00 0.00
10712.37
B 50.239 12795.91 6386.84 10456.88 3687.44 10313.69 0.00 -17863.83
10430.15
C 49.872 12805.13 -6447.26 10418.65 3722.33 10275.99 -0.00 17798.53
10460.63
Sum: -60.43 31479.97 -330.08 -328.77 -0.00 -65.30
422.523 A 45.639 11474.87 -61.14 8873.55 -7275.23 -18251.21 26043.77 -31612.03
9490.25
A 45.639 11474.87 61.14 8873.55 -7275.23 -18251.21 -26043.77 31612.03
9490.25
B 46.647 11172.40 6054.10 8743.60 3423.44 35967.87 24904.25 0.00
9234.38
B 46.647 11172.40 5991.83 8743.60 3531.28 -17983.93 -24904.25 -31149.09
9234.38
C 46.234 11182.20 -6049.48 8702.63 3565.07 -17899.67 25143.18 31003.13
9263.85
C 46.234 11182.20 -6112.18 8702.63 3456.47 35799.33 -25143.18 0.00
9263.85
Sum: -115.73 52639.58 -574.21 -618.83 -0.00 -145.95
342.523 A 46.536 10156.54 -65.85 7890.30 -6394.85 -16228.86 22917.11 -28109.21
8545.80
A 46.536 10156.54 65.85 7890.30 -6394.85 -16228.86 -22917.11 28109.21
8545.80
B 48.478 9559.37 5063.89 7592.98 2843.46 31234.64 20830.92 0.00
8055.52
B 48.478 9559.37 4994.45 7592.98 2963.73 -15617.32 -20830.92 -27049.99
8055.52
C 48.308 9558.32 -5012.83 7575.26 2974.63 -15580.87 20907.56 26986.85
8062.15
C 48.308 9558.32 -5082.52 7575.26 2853.92 31161.74 -20907.56 0.00
8062.15
Sum: -37.01 46117.08 -1153.97 -1259.53 0.00 -63.14
259.385 A 39.167 9719.52 0.00 6700.10 -7041.15 -13216.70 0.00 0.00
8528.88
B 40.371 9166.64 5665.77 6420.74 3271.14 6332.82 0.00 -10968.77
8078.47
C 40.148 9167.11 -5687.40 6395.87 3283.62 6308.29 -0.00 10926.28
8086.35
Sum: -21.63 19516.71 -486.40 -575.59 -0.00 -42.48
179.385 A 55.095 6706.95 0.00 5655.82 -3604.84 -11156.75 0.00 0.00
5920.76
B 52.203 6686.11 3352.31 5451.61 1935.46 5376.96 0.00 -9313.17
5971.68
Job Page
tnxTower Apex (BU 871394) 16 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Guy Guy Chord Guy Tension Fx Fy Fz Mx My Mz


Elevation Location Angle Top
Bottom
lb
ft ° lb lb lb lb-ft lb-ft lb-ft
C 51.782 6690.82 -3388.42 5427.57 1956.31 5353.25 -0.00 9272.10
5983.44
Sum: -36.11 16535.00 286.92 -426.54 -0.00 -41.07
119.385 A 44.865 5283.98 0.00 3896.04 -3569.49 -7685.38 0.00 0.00
4807.29
B 40.306 5288.73 3350.19 3606.34 1934.23 3556.96 0.00 -6160.83
4874.17
C 39.709 5295.42 -3386.15 3571.20 1954.99 3522.29 -0.00 6100.79
4887.07
Sum: -35.96 11073.58 319.73 -606.13 -0.00 -60.04
59.3854 A 29.137 4083.48 0.00 2159.04 -3466.03 -4258.95 0.00 0.00
3864.61
B 22.154 4133.07 3242.75 1749.78 1872.20 1725.82 0.00 -2989.21
3964.47
C 21.357 4142.27 -3270.35 1702.39 1888.14 1679.08 -0.00 2908.26
3978.99
Sum: -27.60 5611.21 294.31 -854.04 -0.00 -80.96

Guy-Mast Forces (Excluding Wind) - Service


Guy Guy Chord Guy Tension Fx Fy Fz Mx My Mz
Elevation Location Angle Top
Bottom
lb
ft ° lb lb lb lb-ft lb-ft lb-ft
479.385 A 49.151 4638.36 0.00 3620.47 -2899.41 -7141.79 0.00 0.00
4240.00
B 50.239 4628.61 2452.96 3660.79 1416.22 3610.66 0.00 -6253.85
4240.00
C 49.872 4624.55 -2470.69 3639.70 1426.45 3589.86 -0.00 6217.82
4240.00
Sum: -17.73 10920.95 -56.74 58.73 -0.00 -36.03
422.523 A 45.639 3790.66 -21.39 2808.89 -2545.35 -5777.35 9111.79 -10006.66
3500.00
A 45.639 3790.66 21.39 2808.89 -2545.35 -5777.35 -9111.79 10006.66
3500.00
B 46.647 3782.61 2173.37 2841.52 1228.99 11688.92 8940.42 0.00
3500.00
B 46.647 3782.61 2151.02 2841.52 1267.70 -5844.46 -8940.42 -10122.90
3500.00
C 46.234 3779.26 -2166.44 2821.23 1276.72 -5802.73 9004.29 10050.62
3500.00
C 46.234 3779.26 -2188.90 2821.23 1237.83 11605.45 -9004.29 0.00
3500.00
Sum: -30.95 16943.26 -79.45 92.49 -0.00 -72.28
342.523 A 46.536 3744.73 -25.64 2797.30 -2489.48 -5753.51 8921.49 -9965.37
3500.00
A 46.536 3744.73 25.64 2797.30 -2489.48 -5753.51 -8921.49 9965.37
3500.00
B 48.478 3725.62 2086.81 2855.25 1171.78 11745.42 8584.33 0.00
3500.00
B 48.478 3725.62 2058.19 2855.25 1221.34 -5872.71 -8584.33 -10171.84
3500.00
C 48.308 3724.28 -2064.69 2847.15 1225.19 -5856.05 8611.41 10142.98
Job Page
tnxTower Apex (BU 871394) 17 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Guy Guy Chord Guy Tension Fx Fy Fz Mx My Mz


Elevation Location Angle Top
Bottom
lb
ft ° lb lb lb lb-ft lb-ft lb-ft
3500.00
C 48.308 3724.28 -2093.39 2847.15 1175.47 11712.10 -8611.41 0.00
3500.00
Sum: -13.08 16999.40 -185.17 221.74 0.00 -28.86
259.385 A 39.167 3688.99 0.00 2419.48 -2784.74 -4772.70 0.00 0.00
3500.00
B 40.371 3669.88 2363.96 2452.95 1364.83 2419.36 0.00 -4190.45
3500.00
C 40.148 3668.54 -2371.36 2441.39 1369.11 2407.96 -0.00 4170.71
3500.00
Sum: -7.40 7313.82 -50.80 54.62 -0.00 -19.74
179.385 A 55.095 3631.67 0.00 3004.52 -2040.07 -5926.76 0.00 0.00
3500.00
B 52.203 3617.59 1888.55 2886.42 1090.36 2846.90 0.00 -4930.97
3500.00
C 51.782 3616.25 -1906.00 2869.40 1100.43 2830.11 -0.00 4901.90
3500.00
Sum: -17.45 8760.35 150.72 -249.75 -0.00 -29.07
119.385 A 44.865 2760.46 0.00 1972.38 -1931.28 -3890.75 0.00 0.00
2690.00
B 40.306 2749.61 1796.01 1805.39 1036.93 1780.67 0.00 -3084.22
2690.00
C 39.709 2748.57 -1811.44 1783.13 1045.84 1758.71 -0.00 3046.18
2690.00
Sum: -15.43 5560.91 151.49 -351.36 -0.00 -38.03
59.3854 A 29.137 2110.45 0.00 1051.42 -1829.90 -2074.04 0.00 0.00
2080.00
B 22.154 2102.08 1677.04 817.79 968.24 806.59 0.00 -1397.06
2080.00
C 21.357 2101.28 -1686.07 790.55 973.45 779.72 -0.00 1350.52
2080.00
Sum: -9.02 2659.76 111.79 -487.72 -0.00 -46.53

Guy-Tensioning Information
Temperature At Time Of Tensioning

0F 20 F 40 F 60 F 80 F 100 F 120 F
Guy H V Initial Intercept Initial Intercept Initial Intercept Initial Intercept Initial Intercept Initial Intercept Initial Intercept
Elevation Tension Tension Tension Tension Tension Tension Tension
ft ft ft lb ft lb ft lb ft lb ft lb ft lb ft lb ft
479.385 A 424.03 490.39 4839 33.89 4631 35.36 4431 36.90 4240 38.49 4058 40.15 3885 41.86 3721 43.61
B 398.03 478.39 4837 31.28 4630 32.62 4431 34.03 4240 35.51 4057 37.04 3884 38.62 3718 40.26
C 399.03 473.39 4845 30.92 4635 32.27 4434 33.68 4240 35.16 4055 36.70 3879 38.29 3712 39.93
422.523 A 423.96 433.52 4067 29.27 3869 30.72 3680 32.25 3500 33.85 3330 35.51 3170 37.23 3020 39.01
B 397.96 421.52 4069 26.76 3871 28.09 3681 29.49 3500 30.97 3328 32.51 3166 34.11 3013 35.77
C 398.96 416.52 4077 26.45 3876 27.78 3684 29.19 3500 30.67 3326 32.21 3162 33.82 3007 35.49
342.523 A 345.96 365.02 4119 20.00 3904 21.06 3698 22.21 3500 23.42 3311 24.71 3133 26.08 2964 27.51
B 297.96 336.52 4113 16.03 3903 16.87 3698 17.78 3500 18.76 3310 19.80 3128 20.92 2955 22.10
C 297.96 334.52 4118 15.91 3905 16.75 3699 17.66 3500 18.63 3309 19.68 3125 20.80 2952 21.98
259.385 A 346.03 281.89 4293 15.22 4016 16.25 3751 17.37 3500 18.59 3264 19.90 3044 21.30 2841 22.78
B 298.03 253.39 4319 11.65 4035 12.45 3762 13.34 3500 14.32 3252 15.38 3019 16.54 2803 17.79
C 298.03 251.39 4324 11.56 4039 12.36 3763 13.25 3500 14.23 3250 15.29 3016 16.45 2799 17.70
179.385 A 137.03 196.39 4041 4.68 3859 4.90 3679 5.13 3500 5.39 3323 5.67 3148 5.98 2975 6.32
B 136.03 175.39 4122 3.95 3913 4.16 3706 4.39 3500 4.64 3298 4.92 3098 5.23 2901 5.58
C 136.53 173.39 4133 3.89 3920 4.10 3709 4.33 3500 4.59 3293 4.87 3089 5.19 2889 5.54
119.385 A 137.03 136.39 3332 2.87 3116 3.06 2902 3.29 2690 3.54 2482 3.84 2278 4.18 2079 4.57
B 136.03 115.39 3435 2.37 3184 2.56 2935 2.77 2690 3.02 2449 3.32 2214 3.66 1987 4.08
C 136.53 113.39 3448 2.34 3193 2.52 2940 2.74 2690 2.99 2445 3.29 2206 3.64 1976 4.06
59.3854 A 137.03 76.39 2837 1.72 2582 1.89 2329 2.09 2080 2.34 1837 2.65 1603 3.03 1382 3.51
Job Page
tnxTower Apex (BU 871394) 18 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Temperature At Time Of Tensioning

0F 20 F 40 F 60 F 80 F 100 F 120 F
Guy H V Initial Intercept Initial Intercept Initial Intercept Initial Intercept Initial Intercept Initial Intercept Initial Intercept
Elevation Tension Tension Tension Tension Tension Tension Tension
ft ft ft lb ft lb ft lb ft lb ft lb ft lb ft lb ft
B 136.03 55.39 2934 1.46 2646 1.62 2360 1.81 2080 2.06 1807 2.37 1546 2.76 1303 3.28
C 136.53 53.39 2943 1.45 2652 1.61 2363 1.80 2080 2.05 1804 2.36 1540 2.76 1296 3.28

Feed Line/Linear Appurtenances - Entered As Round Or Flat


Description Face Allow Exclude Component Placement Face Lateral # # Clear Width or Perimeter Weight
or Shield From Type Offset Offset Per Spacing Diameter
Leg Torque ft in (Frac FW) Row in in in plf
Calculation
*** A-Face
***
LDF12-50( A No No Ar (CaAa) 494' - 0' 0.000 0.3 1 1 0.500 2.350 1.220
2-1/4'')
AVA7-50(1-5/ A No No Ar (CaAa) 198' - 0' 0.000 0.4 2 2 0.500 2.010 0.700
8'')
3/8'' Cable A No No Ar (CaAa) 131' - 0' 0.000 0.49 1 1 0.375 0.375 0.220
(Lights)
1'' Feedline A No No Ar (CaAa) 500' - 0' 0.000 0.48 1 1 1.000 1.000 0.200
(Cable Lights)
Step Pegs A No No Ar (CaAa) 500' - 0' 0.000 0.5 1 1 0.350 0.350 0.487
(5/8'' SR) 7-in.
w/30'' step
Safety Line A No No Ar (CaAa) 500' - 0' 0.000 0.5 1 1 0.375 0.375 0.220
3/8
*** B-Face
***
LCF158-50JA B No No Ar (CaAa) 190' - 0' 0.000 -0.2 8 7 0.500 1.980 0.080
-A0(1 5/8'')
((6) TBR +
(1E) + (1P)
1-3/8)
**
1'' Metal B No No Ar (CaAa) 251' - 0' 0.000 0.35 1 1 1.000 1.000 1.130
Conduit
1'' Metal B No No Ar (CaAa) 372' - 251' 0.000 0.35 1 1 1.000 1.000 1.130
Conduit
**
LDF7-50A(1- B No No Ar (CaAa) 471' - 0' 0.000 0.4 1 1 0.500 1.980 0.820
5/8'')
LDF7-50A(1- B No No Ar (CaAa) 485' - 471' 0.000 0.4 1 1 0.500 1.980 0.820
5/8'')
(Abandoned)
AVA6-50(1-1/ B No No Ar (CaAa) 444' - 0' 0.000 0.45 1 1 1.560 1.560 0.460
4)
Rung C1 B No No Af (CaAa) 191' - 0' 0.000 -0.05 1 1 1.071 0.994 0.725
3/4x3/4x1/8
(29'' width,
51'' step)
**C Face**
Rung L1 C No No Af (CaAa) 165' - 0' 0.000 -0.05 1 1 0.890 1.148 1.334
7/8x3 3.8x1/8
(35.5'' width,
58'' step)
(Abandoned)
1/2'' Ground B No No Ar (CaAa) 372' - 0' 0.000 0.37 1 1 0.500 0.500 0.517
Job Page
tnxTower Apex (BU 871394) 19 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Description Face Allow Exclude Component Placement Face Lateral # # Clear Width or Perimeter Weight
or Shield From Type Offset Offset Per Spacing Diameter
Leg Torque ft in (Frac FW) Row in in in plf
Calculation
1/2'' Ground A No No Ar (CaAa) 500' - 0' 0.000 0.26 1 1 0.500 0.500 0.517
** Mods **
A-Leg Plate A No No Af (CaAa) 102' - 60' 0.000 0.5 1 1 0.000 0.625 4.253
mod
A-Leg Plate B No No Af (CaAa) 102' - 60' 0.000 -0.5 1 1 0.000 0.625 4.253
mod
***
***
***

Feed Line/Linear Appurtenances - Entered As Area


Description Face Allow Exclude Component Placement Total CAAA Weight
or Shield From Type Number
Leg Torque ft ft2/ft plf
Calculation
***
***
***

Feed Line/Linear Appurtenances Section Areas


Tower Tower Face AR AF CAAA CAAA Weight
Section Elevation In Face Out Face
ft ft2 ft2 ft2 ft2 lb
T1 500'-480' A 0.000 0.000 7.740 0.000 45.56
B 0.000 0.000 0.990 0.000 4.10
C 0.000 0.000 0.000 0.000 0.00
T2 480'-460' A 0.000 0.000 9.150 0.000 52.88
B 0.000 0.000 3.960 0.000 16.40
C 0.000 0.000 0.000 0.000 0.00
T3 460'-440' A 0.000 0.000 9.150 0.000 52.88
B 0.000 0.000 4.584 0.000 18.24
C 0.000 0.000 0.000 0.000 0.00
T4 440'-420' A 0.000 0.000 9.150 0.000 52.88
B 0.000 0.000 7.080 0.000 25.60
C 0.000 0.000 0.000 0.000 0.00
T5 420'-400' A 0.000 0.000 9.150 0.000 52.88
B 0.000 0.000 7.080 0.000 25.60
C 0.000 0.000 0.000 0.000 0.00
T6 400'-380' A 0.000 0.000 9.150 0.000 52.88
B 0.000 0.000 7.080 0.000 25.60
C 0.000 0.000 0.000 0.000 0.00
T7 380'-360' A 0.000 0.000 9.150 0.000 52.88
B 0.000 0.000 8.880 0.000 45.36
C 0.000 0.000 0.000 0.000 0.00
T8 360'-340' A 0.000 0.000 9.150 0.000 52.88
B 0.000 0.000 10.080 0.000 58.54
C 0.000 0.000 0.000 0.000 0.00
T9 340'-320' A 0.000 0.000 9.150 0.000 52.88
Job Page
tnxTower Apex (BU 871394) 20 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Tower Tower Face AR AF CAAA CAAA Weight


Section Elevation In Face Out Face
ft ft2 ft2 ft2 ft2 lb
B 0.000 0.000 10.080 0.000 58.54
C 0.000 0.000 0.000 0.000 0.00
T10 320'-300' A 0.000 0.000 9.150 0.000 52.88
B 0.000 0.000 10.080 0.000 58.54
C 0.000 0.000 0.000 0.000 0.00
T11 300'-280' A 0.000 0.000 9.150 0.000 52.88
B 0.000 0.000 10.080 0.000 58.54
C 0.000 0.000 0.000 0.000 0.00
T12 280'-260' A 0.000 0.000 9.150 0.000 52.88
B 0.000 0.000 10.080 0.000 58.54
C 0.000 0.000 0.000 0.000 0.00
T13 260'-240' A 0.000 0.000 9.150 0.000 52.88
B 0.000 0.000 10.080 0.000 58.54
C 0.000 0.000 0.000 0.000 0.00
T14 240'-220' A 0.000 0.000 9.150 0.000 52.88
B 0.000 0.000 10.080 0.000 58.54
C 0.000 0.000 0.000 0.000 0.00
T15 220'-200' A 0.000 0.000 9.150 0.000 52.88
B 0.000 0.000 10.080 0.000 58.54
C 0.000 0.000 0.000 0.000 0.00
T16 200'-180' A 0.000 0.000 16.386 0.000 78.08
B 0.000 0.000 27.742 0.000 72.91
C 0.000 0.000 0.000 0.000 0.00
T17 180'-160' A 0.000 0.000 17.190 0.000 80.88
B 0.000 0.000 45.073 0.000 85.84
C 0.000 0.000 0.957 0.000 6.67
T18 160'-140' A 0.000 0.000 17.190 0.000 80.88
B 0.000 0.000 45.073 0.000 85.84
C 0.000 0.000 3.827 0.000 26.68
T19 140'-120' A 0.000 0.000 17.602 0.000 83.30
B 0.000 0.000 45.073 0.000 85.84
C 0.000 0.000 3.827 0.000 26.68
T20 120'-100' A 0.000 0.000 18.148 0.000 93.79
B 0.000 0.000 45.282 0.000 94.35
C 0.000 0.000 3.827 0.000 26.68
T21 100'-80' A 0.000 0.000 20.023 0.000 170.34
B 0.000 0.000 47.157 0.000 170.90
C 0.000 0.000 3.827 0.000 26.68
T22 80'-60' A 0.000 0.000 20.023 0.000 170.34
B 0.000 0.000 47.157 0.000 170.90
C 0.000 0.000 3.827 0.000 26.68
T23 60'-40' A 0.000 0.000 17.940 0.000 85.28
B 0.000 0.000 45.073 0.000 85.84
C 0.000 0.000 3.827 0.000 26.68
T24 40'-20' A 0.000 0.000 17.940 0.000 85.28
B 0.000 0.000 45.073 0.000 85.84
C 0.000 0.000 3.827 0.000 26.68
T25 20'-4'9-27/32'' A 0.000 0.000 13.619 0.000 64.74
B 0.000 0.000 34.216 0.000 65.16
C 0.000 0.000 2.905 0.000 20.25
T26 4'9-27/32''-0' A 0.000 0.000 4.321 0.000 20.54
B 0.000 0.000 10.858 0.000 20.68
C 0.000 0.000 0.922 0.000 6.43

Feed Line/Linear Appurtenances Section Areas - With Ice


Job Page
tnxTower Apex (BU 871394) 21 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Tower Tower Face Ice AR AF CAAA CAAA Weight


Section Elevation or Thickness In Face Out Face
ft Leg in ft2 ft2 ft2 ft2 lb
T1 500'-480' A 1.670 0.000 0.000 39.133 0.000 523.69
B 0.000 0.000 2.660 0.000 41.33
C 0.000 0.000 0.000 0.000 0.00
T2 480'-460' A 1.663 0.000 0.000 42.408 0.000 576.62
B 0.000 0.000 10.612 0.000 164.42
C 0.000 0.000 0.000 0.000 0.00
T3 460'-440' A 1.656 0.000 0.000 42.264 0.000 572.88
B 0.000 0.000 12.531 0.000 191.35
C 0.000 0.000 0.000 0.000 0.00
T4 440'-420' A 1.648 0.000 0.000 42.114 0.000 569.01
B 0.000 0.000 20.265 0.000 300.92
C 0.000 0.000 0.000 0.000 0.00
T5 420'-400' A 1.640 0.000 0.000 41.957 0.000 564.99
B 0.000 0.000 20.203 0.000 298.98
C 0.000 0.000 0.000 0.000 0.00
T6 400'-380' A 1.632 0.000 0.000 41.793 0.000 560.80
B 0.000 0.000 20.137 0.000 296.97
C 0.000 0.000 0.000 0.000 0.00
T7 380'-360' A 1.624 0.000 0.000 41.622 0.000 556.44
B 0.000 0.000 29.662 0.000 427.62
C 0.000 0.000 0.000 0.000 0.00
T8 360'-340' A 1.615 0.000 0.000 41.442 0.000 551.87
B 0.000 0.000 35.914 0.000 512.18
C 0.000 0.000 0.000 0.000 0.00
T9 340'-320' A 1.605 0.000 0.000 41.253 0.000 547.09
B 0.000 0.000 35.762 0.000 508.03
C 0.000 0.000 0.000 0.000 0.00
T10 320'-300' A 1.595 0.000 0.000 41.053 0.000 542.06
B 0.000 0.000 35.602 0.000 503.67
C 0.000 0.000 0.000 0.000 0.00
T11 300'-280' A 1.585 0.000 0.000 40.840 0.000 536.75
B 0.000 0.000 35.432 0.000 499.07
C 0.000 0.000 0.000 0.000 0.00
T12 280'-260' A 1.573 0.000 0.000 40.615 0.000 531.14
B 0.000 0.000 35.252 0.000 494.20
C 0.000 0.000 0.000 0.000 0.00
T13 260'-240' A 1.561 0.000 0.000 40.374 0.000 525.17
B 0.000 0.000 35.059 0.000 489.02
C 0.000 0.000 0.000 0.000 0.00
T14 240'-220' A 1.548 0.000 0.000 40.114 0.000 518.80
B 0.000 0.000 34.851 0.000 483.48
C 0.000 0.000 0.000 0.000 0.00
T15 220'-200' A 1.534 0.000 0.000 39.834 0.000 511.95
B 0.000 0.000 34.627 0.000 477.53
C 0.000 0.000 0.000 0.000 0.00
T16 200'-180' A 1.519 0.000 0.000 59.978 0.000 714.10
B 0.000 0.000 66.126 0.000 853.61
C 0.000 0.000 0.000 0.000 0.00
T17 180'-160' A 1.502 0.000 0.000 61.797 0.000 726.58
B 0.000 0.000 96.487 0.000 1209.64
C 0.000 0.000 2.459 0.000 31.44
T18 160'-140' A 1.483 0.000 0.000 61.294 0.000 714.67
B 0.000 0.000 95.993 0.000 1192.73
C 0.000 0.000 9.760 0.000 123.73
T19 140'-120' A 1.462 0.000 0.000 64.356 0.000 739.88
B 0.000 0.000 95.435 0.000 1173.77
C 0.000 0.000 9.676 0.000 121.44
T20 120'-100' A 1.438 0.000 0.000 67.360 0.000 770.87
B 0.000 0.000 95.579 0.000 1168.70
C 0.000 0.000 9.579 0.000 118.85
T21 100'-80' A 1.410 0.000 0.000 73.414 0.000 897.17
Job Page
tnxTower Apex (BU 871394) 22 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Tower Tower Face Ice AR AF CAAA CAAA Weight


Section Elevation or Thickness In Face Out Face
ft Leg in ft2 ft2 ft2 ft2 lb
B 0.000 0.000 101.762 0.000 1289.62
C 0.000 0.000 9.465 0.000 115.83
T22 80'-60' A 1.375 0.000 0.000 72.193 0.000 869.85
B 0.000 0.000 100.697 0.000 1255.66
C 0.000 0.000 9.325 0.000 112.20
T23 60'-40' A 1.329 0.000 0.000 63.205 0.000 679.91
B 0.000 0.000 91.914 0.000 1057.01
C 0.000 0.000 9.143 0.000 107.59
T24 40'-20' A 1.263 0.000 0.000 61.159 0.000 636.73
B 0.000 0.000 90.167 0.000 1001.00
C 0.000 0.000 8.878 0.000 101.10
T25 20'-4'9-27/32'' A 1.156 0.000 0.000 43.923 0.000 432.89
B 0.000 0.000 66.309 0.000 693.42
C 0.000 0.000 6.416 0.000 69.22
T26 4'9-27/32''-0' A 0.981 0.000 0.000 12.637 0.000 113.17
B 0.000 0.000 19.931 0.000 187.27
C 0.000 0.000 1.867 0.000 18.40

Feed Line Center of Pressure


Section Elevation CPX CPZ CPX CPZ
Ice Ice
ft in in in in
T1 500'-480' -0.116 -3.533 -0.316 -6.455
T2 480'-460' 0.905 -2.959 0.684 -5.475
T3 460'-440' 1.259 -3.041 1.021 -5.656
T4 440'-420' 1.920 -2.054 1.339 -3.111
T5 420'-400' 2.087 -2.232 2.000 -4.641
T6 400'-380' 2.087 -2.232 2.003 -4.642
T7 380'-360' 2.618 -1.938 2.996 -3.942
T8 360'-340' 2.595 -1.540 2.418 -2.369
T9 340'-320' 2.953 -1.753 3.597 -3.522
T10 320'-300' 2.953 -1.753 3.601 -3.523
T11 300'-280' 2.953 -1.753 3.604 -3.524
T12 280'-260' 2.953 -1.753 3.608 -3.525
T13 260'-240' 2.728 -1.640 3.393 -3.325
T14 240'-220' 2.595 -1.540 2.479 -2.417
T15 220'-200' 2.595 -1.540 2.491 -2.427
T16 200'-180' 2.890 -5.517 2.653 -4.565
T17 180'-160' 3.389 -6.926 3.635 -6.377
T18 160'-140' 3.523 -7.085 3.764 -6.190
T19 140'-120' 3.505 -7.151 3.702 -6.477
T20 120'-100' 3.322 -7.001 3.469 -6.562
T21 100'-80' 2.606 -6.406 3.145 -7.518
T22 80'-60' 2.532 -6.259 3.085 -7.406
T23 60'-40' 2.493 -5.745 3.161 -6.192
T24 40'-20' 2.568 -5.887 3.280 -6.424
T25 20'-4'9-27/32'' 3.359 -6.967 3.622 -6.771
T26 4'9-27/32''-0' 0.000 0.000 0.000 0.000

Shielding Factor Ka
Job Page
tnxTower Apex (BU 871394) 23 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Tower Feed Line Description Feed Line Ka Ka


Section Record No. Segment Elev. No Ice Ice
T1 2 LDF12-50( 2-1/4") 480.00 - 0.6000 0.5588
494.00
T1 5 1" Feedline 480.00 - 0.6000 0.5588
500.00
T1 6 Step Pegs (5/8" SR) 7-in. 480.00 - 0.6000 0.5588
w/30" step 500.00
T1 7 Safety Line 3/8 480.00 - 0.6000 0.5588
500.00
T1 16 LDF7-50A(1-5/8") 480.00 - 0.6000 0.5588
485.00
T1 22 1/2" Ground 480.00 - 0.6000 0.5588
500.00
T2 2 LDF12-50( 2-1/4") 460.00 - 0.6000 0.5328
480.00
T2 5 1" Feedline 460.00 - 0.6000 0.5328
480.00
T2 6 Step Pegs (5/8" SR) 7-in. 460.00 - 0.6000 0.5328
w/30" step 480.00
T2 7 Safety Line 3/8 460.00 - 0.6000 0.5328
480.00
T2 15 LDF7-50A(1-5/8") 460.00 - 0.6000 0.5328
471.00
T2 16 LDF7-50A(1-5/8") 471.00 - 0.6000 0.5328
480.00
T2 22 1/2" Ground 460.00 - 0.6000 0.5328
480.00
T3 2 LDF12-50( 2-1/4") 440.00 - 0.6000 0.5609
460.00
T3 5 1" Feedline 440.00 - 0.6000 0.5609
460.00
T3 6 Step Pegs (5/8" SR) 7-in. 440.00 - 0.6000 0.5609
w/30" step 460.00
T3 7 Safety Line 3/8 440.00 - 0.6000 0.5609
460.00
T3 15 LDF7-50A(1-5/8") 440.00 - 0.6000 0.5609
460.00
T3 17 AVA6-50(1-1/4) 440.00 - 0.6000 0.5609
444.00
T3 22 1/2" Ground 440.00 - 0.6000 0.5609
460.00
T4 2 LDF12-50( 2-1/4") 420.00 - 0.6000 0.4001
440.00
T4 5 1" Feedline 420.00 - 0.6000 0.4001
440.00
T4 6 Step Pegs (5/8" SR) 7-in. 420.00 - 0.6000 0.4001
w/30" step 440.00
T4 7 Safety Line 3/8 420.00 - 0.6000 0.4001
440.00
T4 15 LDF7-50A(1-5/8") 420.00 - 0.6000 0.4001
440.00
T4 17 AVA6-50(1-1/4) 420.00 - 0.6000 0.4001
440.00
T4 22 1/2" Ground 420.00 - 0.6000 0.4001
440.00
T5 2 LDF12-50( 2-1/4") 400.00 - 0.6000 0.5491
420.00
T5 5 1" Feedline 400.00 - 0.6000 0.5491
420.00
T5 6 Step Pegs (5/8" SR) 7-in. 400.00 - 0.6000 0.5491
w/30" step 420.00
T5 7 Safety Line 3/8 400.00 - 0.6000 0.5491
Job Page
tnxTower Apex (BU 871394) 24 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Tower Feed Line Description Feed Line Ka Ka


Section Record No. Segment Elev. No Ice Ice
420.00
T5 15 LDF7-50A(1-5/8") 400.00 - 0.6000 0.5491
420.00
T5 17 AVA6-50(1-1/4) 400.00 - 0.6000 0.5491
420.00
T5 22 1/2" Ground 400.00 - 0.6000 0.5491
420.00
T6 2 LDF12-50( 2-1/4") 380.00 - 0.6000 0.5503
400.00
T6 5 1" Feedline 380.00 - 0.6000 0.5503
400.00
T6 6 Step Pegs (5/8" SR) 7-in. 380.00 - 0.6000 0.5503
w/30" step 400.00
T6 7 Safety Line 3/8 380.00 - 0.6000 0.5503
400.00
T6 15 LDF7-50A(1-5/8") 380.00 - 0.6000 0.5503
400.00
T6 17 AVA6-50(1-1/4) 380.00 - 0.6000 0.5503
400.00
T6 22 1/2" Ground 380.00 - 0.6000 0.5503
400.00
T7 2 LDF12-50( 2-1/4") 360.00 - 0.6000 0.5515
380.00
T7 5 1" Feedline 360.00 - 0.6000 0.5515
380.00
T7 6 Step Pegs (5/8" SR) 7-in. 360.00 - 0.6000 0.5515
w/30" step 380.00
T7 7 Safety Line 3/8 360.00 - 0.6000 0.5515
380.00
T7 13 1" Metal Conduit 360.00 - 0.6000 0.5515
372.00
T7 15 LDF7-50A(1-5/8") 360.00 - 0.6000 0.5515
380.00
T7 17 AVA6-50(1-1/4) 360.00 - 0.6000 0.5515
380.00
T7 21 1/2" Ground 360.00 - 0.6000 0.5515
372.00
T7 22 1/2" Ground 360.00 - 0.6000 0.5515
380.00
T8 2 LDF12-50( 2-1/4") 340.00 - 0.6000 0.3967
360.00
T8 5 1" Feedline 340.00 - 0.6000 0.3967
360.00
T8 6 Step Pegs (5/8" SR) 7-in. 340.00 - 0.6000 0.3967
w/30" step 360.00
T8 7 Safety Line 3/8 340.00 - 0.6000 0.3967
360.00
T8 13 1" Metal Conduit 340.00 - 0.6000 0.3967
360.00
T8 15 LDF7-50A(1-5/8") 340.00 - 0.6000 0.3967
360.00
T8 17 AVA6-50(1-1/4) 340.00 - 0.6000 0.3967
360.00
T8 21 1/2" Ground 340.00 - 0.6000 0.3967
360.00
T8 22 1/2" Ground 340.00 - 0.6000 0.3967
360.00
T9 2 LDF12-50( 2-1/4") 320.00 - 0.6000 0.5542
340.00
T9 5 1" Feedline 320.00 - 0.6000 0.5542
340.00
T9 6 Step Pegs (5/8" SR) 7-in. 320.00 - 0.6000 0.5542
Job Page
tnxTower Apex (BU 871394) 25 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Tower Feed Line Description Feed Line Ka Ka


Section Record No. Segment Elev. No Ice Ice
w/30" step 340.00
T9 7 Safety Line 3/8 320.00 - 0.6000 0.5542
340.00
T9 13 1" Metal Conduit 320.00 - 0.6000 0.5542
340.00
T9 15 LDF7-50A(1-5/8") 320.00 - 0.6000 0.5542
340.00
T9 17 AVA6-50(1-1/4) 320.00 - 0.6000 0.5542
340.00
T9 21 1/2" Ground 320.00 - 0.6000 0.5542
340.00
T9 22 1/2" Ground 320.00 - 0.6000 0.5542
340.00
T10 2 LDF12-50( 2-1/4") 300.00 - 0.6000 0.5556
320.00
T10 5 1" Feedline 300.00 - 0.6000 0.5556
320.00
T10 6 Step Pegs (5/8" SR) 7-in. 300.00 - 0.6000 0.5556
w/30" step 320.00
T10 7 Safety Line 3/8 300.00 - 0.6000 0.5556
320.00
T10 13 1" Metal Conduit 300.00 - 0.6000 0.5556
320.00
T10 15 LDF7-50A(1-5/8") 300.00 - 0.6000 0.5556
320.00
T10 17 AVA6-50(1-1/4) 300.00 - 0.6000 0.5556
320.00
T10 21 1/2" Ground 300.00 - 0.6000 0.5556
320.00
T10 22 1/2" Ground 300.00 - 0.6000 0.5556
320.00
T11 2 LDF12-50( 2-1/4") 280.00 - 0.6000 0.5572
300.00
T11 5 1" Feedline 280.00 - 0.6000 0.5572
300.00
T11 6 Step Pegs (5/8" SR) 7-in. 280.00 - 0.6000 0.5572
w/30" step 300.00
T11 7 Safety Line 3/8 280.00 - 0.6000 0.5572
300.00
T11 13 1" Metal Conduit 280.00 - 0.6000 0.5572
300.00
T11 15 LDF7-50A(1-5/8") 280.00 - 0.6000 0.5572
300.00
T11 17 AVA6-50(1-1/4) 280.00 - 0.6000 0.5572
300.00
T11 21 1/2" Ground 280.00 - 0.6000 0.5572
300.00
T11 22 1/2" Ground 280.00 - 0.6000 0.5572
300.00
T12 2 LDF12-50( 2-1/4") 260.00 - 0.6000 0.5588
280.00
T12 5 1" Feedline 260.00 - 0.6000 0.5588
280.00
T12 6 Step Pegs (5/8" SR) 7-in. 260.00 - 0.6000 0.5588
w/30" step 280.00
T12 7 Safety Line 3/8 260.00 - 0.6000 0.5588
280.00
T12 13 1" Metal Conduit 260.00 - 0.6000 0.5588
280.00
T12 15 LDF7-50A(1-5/8") 260.00 - 0.6000 0.5588
280.00
T12 17 AVA6-50(1-1/4) 260.00 - 0.6000 0.5588
Job Page
tnxTower Apex (BU 871394) 26 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Tower Feed Line Description Feed Line Ka Ka


Section Record No. Segment Elev. No Ice Ice
280.00
T12 21 1/2" Ground 260.00 - 0.6000 0.5588
280.00
T12 22 1/2" Ground 260.00 - 0.6000 0.5588
280.00
T13 2 LDF12-50( 2-1/4") 240.00 - 0.6000 0.5348
260.00
T13 5 1" Feedline 240.00 - 0.6000 0.5348
260.00
T13 6 Step Pegs (5/8" SR) 7-in. 240.00 - 0.6000 0.5348
w/30" step 260.00
T13 7 Safety Line 3/8 240.00 - 0.6000 0.5348
260.00
T13 12 1" Metal Conduit 240.00 - 0.6000 0.5348
251.00
T13 13 1" Metal Conduit 251.00 - 0.6000 0.5348
260.00
T13 15 LDF7-50A(1-5/8") 240.00 - 0.6000 0.5348
260.00
T13 17 AVA6-50(1-1/4) 240.00 - 0.6000 0.5348
260.00
T13 21 1/2" Ground 240.00 - 0.6000 0.5348
260.00
T13 22 1/2" Ground 240.00 - 0.6000 0.5348
260.00
T14 2 LDF12-50( 2-1/4") 220.00 - 0.6000 0.4103
240.00
T14 5 1" Feedline 220.00 - 0.6000 0.4103
240.00
T14 6 Step Pegs (5/8" SR) 7-in. 220.00 - 0.6000 0.4103
w/30" step 240.00
T14 7 Safety Line 3/8 220.00 - 0.6000 0.4103
240.00
T14 12 1" Metal Conduit 220.00 - 0.6000 0.4103
240.00
T14 15 LDF7-50A(1-5/8") 220.00 - 0.6000 0.4103
240.00
T14 17 AVA6-50(1-1/4) 220.00 - 0.6000 0.4103
240.00
T14 21 1/2" Ground 220.00 - 0.6000 0.4103
240.00
T14 22 1/2" Ground 220.00 - 0.6000 0.4103
240.00
T15 2 LDF12-50( 2-1/4") 200.00 - 0.6000 0.4132
220.00
T15 5 1" Feedline 200.00 - 0.6000 0.4132
220.00
T15 6 Step Pegs (5/8" SR) 7-in. 200.00 - 0.6000 0.4132
w/30" step 220.00
T15 7 Safety Line 3/8 200.00 - 0.6000 0.4132
220.00
T15 12 1" Metal Conduit 200.00 - 0.6000 0.4132
220.00
T15 15 LDF7-50A(1-5/8") 200.00 - 0.6000 0.4132
220.00
T15 17 AVA6-50(1-1/4) 200.00 - 0.6000 0.4132
220.00
T15 21 1/2" Ground 200.00 - 0.6000 0.4132
220.00
T15 22 1/2" Ground 200.00 - 0.6000 0.4132
220.00
T16 2 LDF12-50( 2-1/4") 180.00 - 0.6000 0.4164
Job Page
tnxTower Apex (BU 871394) 27 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Tower Feed Line Description Feed Line Ka Ka


Section Record No. Segment Elev. No Ice Ice
200.00
T16 3 AVA7-50(1-5/8") 180.00 - 0.6000 0.4164
198.00
T16 5 1" Feedline 180.00 - 0.6000 0.4164
200.00
T16 6 Step Pegs (5/8" SR) 7-in. 180.00 - 0.6000 0.4164
w/30" step 200.00
T16 7 Safety Line 3/8 180.00 - 0.6000 0.4164
200.00
T16 9 LCF158-50JA-A0(1 5/8") 180.00 - 0.6000 0.4164
190.00
T16 12 1" Metal Conduit 180.00 - 0.6000 0.4164
200.00
T16 15 LDF7-50A(1-5/8") 180.00 - 0.6000 0.4164
200.00
T16 17 AVA6-50(1-1/4) 180.00 - 0.6000 0.4164
200.00
T16 18 Rung C1 3/4x3/4x1/8 (29" 180.00 - 0.6000 0.4164
width, 51" step) 191.00
T16 21 1/2" Ground 180.00 - 0.6000 0.4164
200.00
T16 22 1/2" Ground 180.00 - 0.6000 0.4164
200.00
T17 2 LDF12-50( 2-1/4") 160.00 - 0.6000 0.5172
180.00
T17 3 AVA7-50(1-5/8") 160.00 - 0.6000 0.5172
180.00
T17 5 1" Feedline 160.00 - 0.6000 0.5172
180.00
T17 6 Step Pegs (5/8" SR) 7-in. 160.00 - 0.6000 0.5172
w/30" step 180.00
T17 7 Safety Line 3/8 160.00 - 0.6000 0.5172
180.00
T17 9 LCF158-50JA-A0(1 5/8") 160.00 - 0.6000 0.5172
180.00
T17 12 1" Metal Conduit 160.00 - 0.6000 0.5172
180.00
T17 15 LDF7-50A(1-5/8") 160.00 - 0.6000 0.5172
180.00
T17 17 AVA6-50(1-1/4) 160.00 - 0.6000 0.5172
180.00
T17 18 Rung C1 3/4x3/4x1/8 (29" 160.00 - 0.6000 0.5172
width, 51" step) 180.00
T17 20 Rung L1 7/8x3 3.8x1/8 (35.5" 160.00 - 0.6000 0.5172
width, 58" step) 165.00
T17 21 1/2" Ground 160.00 - 0.6000 0.5172
180.00
T17 22 1/2" Ground 160.00 - 0.6000 0.5172
180.00
T18 2 LDF12-50( 2-1/4") 140.00 - 0.6000 0.5453
160.00
T18 3 AVA7-50(1-5/8") 140.00 - 0.6000 0.5453
160.00
T18 5 1" Feedline 140.00 - 0.6000 0.5453
160.00
T18 6 Step Pegs (5/8" SR) 7-in. 140.00 - 0.6000 0.5453
w/30" step 160.00
T18 7 Safety Line 3/8 140.00 - 0.6000 0.5453
160.00
T18 9 LCF158-50JA-A0(1 5/8") 140.00 - 0.6000 0.5453
160.00
T18 12 1" Metal Conduit 140.00 - 0.6000 0.5453
Job Page
tnxTower Apex (BU 871394) 28 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Tower Feed Line Description Feed Line Ka Ka


Section Record No. Segment Elev. No Ice Ice
160.00
T18 15 LDF7-50A(1-5/8") 140.00 - 0.6000 0.5453
160.00
T18 17 AVA6-50(1-1/4) 140.00 - 0.6000 0.5453
160.00
T18 18 Rung C1 3/4x3/4x1/8 (29" 140.00 - 0.6000 0.5453
width, 51" step) 160.00
T18 20 Rung L1 7/8x3 3.8x1/8 (35.5" 140.00 - 0.6000 0.5453
width, 58" step) 160.00
T18 21 1/2" Ground 140.00 - 0.6000 0.5453
160.00
T18 22 1/2" Ground 140.00 - 0.6000 0.5453
160.00
T19 2 LDF12-50( 2-1/4") 120.00 - 0.6000 0.5484
140.00
T19 3 AVA7-50(1-5/8") 120.00 - 0.6000 0.5484
140.00
T19 4 3/8" Cable (Lights) 120.00 - 0.6000 0.5484
131.00
T19 5 1" Feedline 120.00 - 0.6000 0.5484
140.00
T19 6 Step Pegs (5/8" SR) 7-in. 120.00 - 0.6000 0.5484
w/30" step 140.00
T19 7 Safety Line 3/8 120.00 - 0.6000 0.5484
140.00
T19 9 LCF158-50JA-A0(1 5/8") 120.00 - 0.6000 0.5484
140.00
T19 12 1" Metal Conduit 120.00 - 0.6000 0.5484
140.00
T19 15 LDF7-50A(1-5/8") 120.00 - 0.6000 0.5484
140.00
T19 17 AVA6-50(1-1/4) 120.00 - 0.6000 0.5484
140.00
T19 18 Rung C1 3/4x3/4x1/8 (29" 120.00 - 0.6000 0.5484
width, 51" step) 140.00
T19 20 Rung L1 7/8x3 3.8x1/8 (35.5" 120.00 - 0.6000 0.5484
width, 58" step) 140.00
T19 21 1/2" Ground 120.00 - 0.6000 0.5484
140.00
T19 22 1/2" Ground 120.00 - 0.6000 0.5484
140.00
T20 2 LDF12-50( 2-1/4") 100.00 - 0.6000 0.5269
120.00
T20 3 AVA7-50(1-5/8") 100.00 - 0.6000 0.5269
120.00
T20 4 3/8" Cable (Lights) 100.00 - 0.6000 0.5269
120.00
T20 5 1" Feedline 100.00 - 0.6000 0.5269
120.00
T20 6 Step Pegs (5/8" SR) 7-in. 100.00 - 0.6000 0.5269
w/30" step 120.00
T20 7 Safety Line 3/8 100.00 - 0.6000 0.5269
120.00
T20 9 LCF158-50JA-A0(1 5/8") 100.00 - 0.6000 0.5269
120.00
T20 12 1" Metal Conduit 100.00 - 0.6000 0.5269
120.00
T20 15 LDF7-50A(1-5/8") 100.00 - 0.6000 0.5269
120.00
T20 17 AVA6-50(1-1/4) 100.00 - 0.6000 0.5269
120.00
T20 18 Rung C1 3/4x3/4x1/8 (29" 100.00 - 0.6000 0.5269
Job Page
tnxTower Apex (BU 871394) 29 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Tower Feed Line Description Feed Line Ka Ka


Section Record No. Segment Elev. No Ice Ice
width, 51" step) 120.00
T20 20 Rung L1 7/8x3 3.8x1/8 (35.5" 100.00 - 0.6000 0.5269
width, 58" step) 120.00
T20 21 1/2" Ground 100.00 - 0.6000 0.5269
120.00
T20 22 1/2" Ground 100.00 - 0.6000 0.5269
120.00
T20 24 A-Leg Plate mod 100.00 - 0.6000 0.5269
102.00
T20 25 A-Leg Plate mod 100.00 - 0.6000 0.5269
102.00
T21 2 LDF12-50( 2-1/4") 80.00 - 100.00 0.6000 0.5791
T21 3 AVA7-50(1-5/8") 80.00 - 100.00 0.6000 0.5791
T21 4 3/8" Cable (Lights) 80.00 - 100.00 0.6000 0.5791
T21 5 1" Feedline 80.00 - 100.00 0.6000 0.5791
T21 6 Step Pegs (5/8" SR) 7-in. 80.00 - 100.00 0.6000 0.5791
w/30" step
T21 7 Safety Line 3/8 80.00 - 100.00 0.6000 0.5791
T21 9 LCF158-50JA-A0(1 5/8") 80.00 - 100.00 0.6000 0.5791
T21 12 1" Metal Conduit 80.00 - 100.00 0.6000 0.5791
T21 15 LDF7-50A(1-5/8") 80.00 - 100.00 0.6000 0.5791
T21 17 AVA6-50(1-1/4) 80.00 - 100.00 0.6000 0.5791
T21 18 Rung C1 3/4x3/4x1/8 (29" 80.00 - 100.00 0.6000 0.5791
width, 51" step)
T21 20 Rung L1 7/8x3 3.8x1/8 (35.5" 80.00 - 100.00 0.6000 0.5791
width, 58" step)
T21 21 1/2" Ground 80.00 - 100.00 0.6000 0.5791
T21 22 1/2" Ground 80.00 - 100.00 0.6000 0.5791
T21 24 A-Leg Plate mod 80.00 - 100.00 0.6000 0.5791
T21 25 A-Leg Plate mod 80.00 - 100.00 0.6000 0.5791
T22 2 LDF12-50( 2-1/4") 60.00 - 80.00 0.6000 0.5738
T22 3 AVA7-50(1-5/8") 60.00 - 80.00 0.6000 0.5738
T22 4 3/8" Cable (Lights) 60.00 - 80.00 0.6000 0.5738
T22 5 1" Feedline 60.00 - 80.00 0.6000 0.5738
T22 6 Step Pegs (5/8" SR) 7-in. 60.00 - 80.00 0.6000 0.5738
w/30" step
T22 7 Safety Line 3/8 60.00 - 80.00 0.6000 0.5738
T22 9 LCF158-50JA-A0(1 5/8") 60.00 - 80.00 0.6000 0.5738
T22 12 1" Metal Conduit 60.00 - 80.00 0.6000 0.5738
T22 15 LDF7-50A(1-5/8") 60.00 - 80.00 0.6000 0.5738
T22 17 AVA6-50(1-1/4) 60.00 - 80.00 0.6000 0.5738
T22 18 Rung C1 3/4x3/4x1/8 (29" 60.00 - 80.00 0.6000 0.5738
width, 51" step)
T22 20 Rung L1 7/8x3 3.8x1/8 (35.5" 60.00 - 80.00 0.6000 0.5738
width, 58" step)
T22 21 1/2" Ground 60.00 - 80.00 0.6000 0.5738
T22 22 1/2" Ground 60.00 - 80.00 0.6000 0.5738
T22 24 A-Leg Plate mod 60.00 - 80.00 0.6000 0.5738
T22 25 A-Leg Plate mod 60.00 - 80.00 0.6000 0.5738
T23 2 LDF12-50( 2-1/4") 40.00 - 60.00 0.6000 0.5545
T23 3 AVA7-50(1-5/8") 40.00 - 60.00 0.6000 0.5545
T23 4 3/8" Cable (Lights) 40.00 - 60.00 0.6000 0.5545
T23 5 1" Feedline 40.00 - 60.00 0.6000 0.5545
T23 6 Step Pegs (5/8" SR) 7-in. 40.00 - 60.00 0.6000 0.5545
w/30" step
T23 7 Safety Line 3/8 40.00 - 60.00 0.6000 0.5545
T23 9 LCF158-50JA-A0(1 5/8") 40.00 - 60.00 0.6000 0.5545
T23 12 1" Metal Conduit 40.00 - 60.00 0.6000 0.5545
T23 15 LDF7-50A(1-5/8") 40.00 - 60.00 0.6000 0.5545
T23 17 AVA6-50(1-1/4) 40.00 - 60.00 0.6000 0.5545
T23 18 Rung C1 3/4x3/4x1/8 (29" 40.00 - 60.00 0.6000 0.5545
width, 51" step)
Job Page
tnxTower Apex (BU 871394) 30 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Tower Feed Line Description Feed Line Ka Ka


Section Record No. Segment Elev. No Ice Ice
T23 20 Rung L1 7/8x3 3.8x1/8 (35.5" 40.00 - 60.00 0.6000 0.5545
width, 58" step)
T23 21 1/2" Ground 40.00 - 60.00 0.6000 0.5545
T23 22 1/2" Ground 40.00 - 60.00 0.6000 0.5545
T24 2 LDF12-50( 2-1/4") 20.00 - 40.00 0.6000 0.5864
T24 3 AVA7-50(1-5/8") 20.00 - 40.00 0.6000 0.5864
T24 4 3/8" Cable (Lights) 20.00 - 40.00 0.6000 0.5864
T24 5 1" Feedline 20.00 - 40.00 0.6000 0.5864
T24 6 Step Pegs (5/8" SR) 7-in. 20.00 - 40.00 0.6000 0.5864
w/30" step
T24 7 Safety Line 3/8 20.00 - 40.00 0.6000 0.5864
T24 9 LCF158-50JA-A0(1 5/8") 20.00 - 40.00 0.6000 0.5864
T24 12 1" Metal Conduit 20.00 - 40.00 0.6000 0.5864
T24 15 LDF7-50A(1-5/8") 20.00 - 40.00 0.6000 0.5864
T24 17 AVA6-50(1-1/4) 20.00 - 40.00 0.6000 0.5864
T24 18 Rung C1 3/4x3/4x1/8 (29" 20.00 - 40.00 0.6000 0.5864
width, 51" step)
T24 20 Rung L1 7/8x3 3.8x1/8 (35.5" 20.00 - 40.00 0.6000 0.5864
width, 58" step)
T24 21 1/2" Ground 20.00 - 40.00 0.6000 0.5864
T24 22 1/2" Ground 20.00 - 40.00 0.6000 0.5864
T25 2 LDF12-50( 2-1/4") 4.82 - 20.00 0.6000 0.5778
T25 3 AVA7-50(1-5/8") 4.82 - 20.00 0.6000 0.5778
T25 4 3/8" Cable (Lights) 4.82 - 20.00 0.6000 0.5778
T25 5 1" Feedline 4.82 - 20.00 0.6000 0.5778
T25 6 Step Pegs (5/8" SR) 7-in. 4.82 - 20.00 0.6000 0.5778
w/30" step
T25 7 Safety Line 3/8 4.82 - 20.00 0.6000 0.5778
T25 9 LCF158-50JA-A0(1 5/8") 4.82 - 20.00 0.6000 0.5778
T25 12 1" Metal Conduit 4.82 - 20.00 0.6000 0.5778
T25 15 LDF7-50A(1-5/8") 4.82 - 20.00 0.6000 0.5778
T25 17 AVA6-50(1-1/4) 4.82 - 20.00 0.6000 0.5778
T25 18 Rung C1 3/4x3/4x1/8 (29" 4.82 - 20.00 0.6000 0.5778
width, 51" step)
T25 20 Rung L1 7/8x3 3.8x1/8 (35.5" 4.82 - 20.00 0.6000 0.5778
width, 58" step)
T25 21 1/2" Ground 4.82 - 20.00 0.6000 0.5778
T25 22 1/2" Ground 4.82 - 20.00 0.6000 0.5778
T26 2 LDF12-50( 2-1/4") 0.00 - 4.82 0.0000 0.0000
T26 3 AVA7-50(1-5/8") 0.00 - 4.82 0.0000 0.0000
T26 4 3/8" Cable (Lights) 0.00 - 4.82 0.0000 0.0000
T26 5 1" Feedline 0.00 - 4.82 0.0000 0.0000
T26 6 Step Pegs (5/8" SR) 7-in. 0.00 - 4.82 0.0000 0.0000
w/30" step
T26 7 Safety Line 3/8 0.00 - 4.82 0.0000 0.0000
T26 9 LCF158-50JA-A0(1 5/8") 0.00 - 4.82 0.0000 0.0000
T26 12 1" Metal Conduit 0.00 - 4.82 0.0000 0.0000
T26 15 LDF7-50A(1-5/8") 0.00 - 4.82 0.0000 0.0000
T26 17 AVA6-50(1-1/4) 0.00 - 4.82 0.0000 0.0000
T26 18 Rung C1 3/4x3/4x1/8 (29" 0.00 - 4.82 0.0000 0.0000
width, 51" step)
T26 20 Rung L1 7/8x3 3.8x1/8 (35.5" 0.00 - 4.82 0.0000 0.0000
width, 58" step)
T26 21 1/2" Ground 0.00 - 4.82 0.0000 0.0000
T26 22 1/2" Ground 0.00 - 4.82 0.0000 0.0000
Job Page
tnxTower Apex (BU 871394) 31 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Discrete Tower Loads


Description Face Offset Offsets: Azimuth Placement CAAA CAAA Weight
or Type Horz Adjustment Front Side
Leg Lateral
Vert
ft ° ft ft2 ft2 lb
ft
ft
5/8''x6-ft LRod C From Leg 0.00 0.000 500' No Ice 0.38 0.38 6.26
0' 1/2'' Ice 0.99 0.99 10.45
3' 1'' Ice 1.62 1.62 18.52
2'' Ice 2.46 2.46 46.92
16'' Dia. x 30'' Beacon C From Leg 1.00 0.000 500' No Ice 1.67 1.67 30.00
0' 1/2'' Ice 2.56 2.56 62.55
1' 1'' Ice 2.80 2.80 98.42
2'' Ice 3.31 3.31 180.68
16'' Dia. x 30'' Beacon B From Face 1.00 0.000 500' No Ice 1.67 1.67 30.00
0' 1/2'' Ice 2.56 2.56 62.55
1' 1'' Ice 2.80 2.80 98.42
2'' Ice 3.31 3.31 180.68
3'' x 6'' SideLight A From Leg 1.00 0.000 372' No Ice 0.09 0.09 0.98
0' 1/2'' Ice 0.14 0.14 2.46
0' 1'' Ice 0.19 0.19 4.70
2'' Ice 0.34 0.34 12.08
3'' x 6'' SideLight B From Leg 1.00 0.000 372' No Ice 0.09 0.09 0.98
0' 1/2'' Ice 0.14 0.14 2.46
0' 1'' Ice 0.19 0.19 4.70
2'' Ice 0.34 0.34 12.08
3'' x 6'' SideLight C From Leg 1.00 0.000 372' No Ice 0.09 0.09 0.98
0' 1/2'' Ice 0.14 0.14 2.46
0' 1'' Ice 0.19 0.19 4.70
2'' Ice 0.34 0.34 12.08
16'' Dia. x 30'' Beacon B From Leg 1.00 0.000 252' No Ice 1.67 1.67 30.00
0' 1/2'' Ice 2.56 2.56 62.55
0' 1'' Ice 2.80 2.80 98.42
2'' Ice 3.31 3.31 180.68
16'' Dia. x 30'' Beacon C From Leg 1.00 0.000 252' No Ice 1.67 1.67 30.00
0' 1/2'' Ice 2.56 2.56 62.55
0' 1'' Ice 2.80 2.80 98.42
2'' Ice 3.31 3.31 180.68
3'' x 6'' SideLight A From Leg 1.00 0.000 131' No Ice 0.09 0.09 0.98
0' 1/2'' Ice 0.14 0.14 2.46
0' 1'' Ice 0.19 0.19 4.70
2'' Ice 0.34 0.34 12.08
3'' x 6'' SideLight B From Leg 1.00 0.000 131' No Ice 0.09 0.09 0.98
0' 1/2'' Ice 0.14 0.14 2.46
0' 1'' Ice 0.19 0.19 4.70
2'' Ice 0.34 0.34 12.08
3'' x 6'' SideLight C From Leg 1.00 0.000 131' No Ice 0.09 0.09 0.98
0' 1/2'' Ice 0.14 0.14 2.46
0' 1'' Ice 0.19 0.19 4.70
2'' Ice 0.34 0.34 12.08
*** 500' ***
BCR12-A C None 0.000 510' No Ice 6.63 6.63 92.00
(Abandoned) 1/2'' Ice 15.32 15.32 180.59
1'' Ice 17.40 17.40 282.23
2'' Ice 20.80 20.80 525.25
*** 494' ***
750 10074 A From Leg 1.00 0.000 494' No Ice 1.75 1.75 17.60
0' 1/2'' Ice 2.64 2.64 31.15
4' 1'' Ice 3.55 3.55 50.37
2'' Ice 4.72 4.72 106.42
Job Page
tnxTower Apex (BU 871394) 32 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Description Face Offset Offsets: Azimuth Placement CAAA CAAA Weight


or Type Horz Adjustment Front Side
Leg Lateral
Vert
ft ° ft ft2 ft2 lb
ft
ft
Side Arm Mount [SO 309-1] A From Leg 0.50 0.000 494' No Ice 2.82 2.20 40.00
0' 1/2'' Ice 4.07 3.16 61.95
0' 1'' Ice 5.32 4.12 83.89
2'' Ice 7.82 6.04 127.79
*** 485' ***
PG1N0F-0090-310 A From Leg 5.00 0.000 485' No Ice 3.00 3.00 28.00
(Abandoned) 0' 1/2'' Ice 4.03 4.03 49.79
5' 1'' Ice 5.03 5.03 78.14
2'' Ice 6.26 6.26 155.16
490114 A From Face 0.50 0.000 485' No Ice 2.53 1.43 57.00
(Abandoned) 0' 1/2'' Ice 2.73 1.58 78.52
5' 1'' Ice 2.94 1.75 103.08
2'' Ice 3.37 2.11 162.13
Side Arm Mount [SO 303-1] A From Leg 2.50 0.000 485' No Ice 2.24 5.32 115.00
(Abandoned) 0' 1/2'' Ice 3.19 7.69 158.73
0' 1'' Ice 4.14 10.06 202.46
2'' Ice 6.04 14.80 289.92
*** 471' ***
DB420 A From Leg 5.00 0.000 471' No Ice 3.33 3.33 34.00
(Abandoned) 0' 1/2'' Ice 5.99 5.99 44.20
10' 1'' Ice 8.66 8.66 54.40
2'' Ice 13.99 13.99 74.80
Side Arm Mount [SO 303-1] A From Leg 2.50 0.000 471' No Ice 2.24 5.32 115.00
(Abandoned) 0' 1/2'' Ice 3.19 7.69 158.73
0' 1'' Ice 4.14 10.06 202.46
2'' Ice 6.04 14.80 289.92
**444**
784-70 B From Leg 4.00 0.000 444' No Ice 2.52 2.52 30.00
0' 1/2'' Ice 3.60 3.60 48.90
5' 1'' Ice 4.69 4.69 74.60
2'' Ice 6.33 6.33 147.06
Side Arm Mount [SO 303-1] B From Leg 2.50 0.000 444' No Ice 2.24 5.32 115.00
0' 1/2'' Ice 3.19 7.69 158.73
0' 1'' Ice 4.14 10.06 202.46
2'' Ice 6.04 14.80 289.92
2.4'' dia. x 10' stabilizer A From Face 0.50 0.000 444' No Ice 2.37 2.38 36.51
0' 1/2'' Ice 3.41 3.41 62.85
0' 1'' Ice 4.46 4.46 91.88
2'' Ice 5.97 5.97 162.69
** 198 **
HG2409U-PRO A From Leg 3.00 0.000 198' No Ice 0.38 0.38 2.76
0' 1/2'' Ice 0.54 0.54 6.21
2' 1'' Ice 0.72 0.72 11.60
2'' Ice 1.10 1.10 28.84
Side Arm Mount [SO 305-1] A From Leg 1.50 0.000 198' No Ice 0.94 1.41 30.00
0' 1/2'' Ice 1.48 2.17 43.27
0' 1'' Ice 2.02 2.93 56.54
2'' Ice 3.10 4.45 83.07
**190**
***
NHH-65C-R2B w/ Mount A From Leg 4.00 0.000 190' No Ice 11.63 9.79 84.45
Pipe 0' 1/2'' Ice 12.35 11.31 173.76
0' 1'' Ice 13.07 12.85 273.01
2'' Ice 14.44 15.19 505.64
NHH-65C-R2B w/ Mount B From Leg 4.00 0.000 190' No Ice 11.63 9.79 84.45
Pipe 0' 1/2'' Ice 12.35 11.31 173.76
0' 1'' Ice 13.07 12.85 273.01
Job Page
tnxTower Apex (BU 871394) 33 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Description Face Offset Offsets: Azimuth Placement CAAA CAAA Weight


or Type Horz Adjustment Front Side
Leg Lateral
Vert
ft ° ft ft2 ft2 lb
ft
ft
2'' Ice 14.44 15.19 505.64
NHH-65C-R2B w/ Mount C From Leg 4.00 0.000 190' No Ice 11.63 9.79 84.45
Pipe 0' 1/2'' Ice 12.35 11.31 173.76
0' 1'' Ice 13.07 12.85 273.01
2'' Ice 14.44 15.19 505.64
(2) LNX-6515DS-A1M w/ A From Leg 4.00 0.000 190' No Ice 11.72 10.28 100.61
Mount Pipe 0' 1/2'' Ice 12.44 11.81 194.42
(Existing) 0' 1'' Ice 13.15 13.16 299.33
2'' Ice 14.52 15.49 539.68
(2) LNX-6515DS-A1M w/ B From Leg 4.00 0.000 190' No Ice 11.72 10.28 100.61
Mount Pipe 0' 1/2'' Ice 12.44 11.81 194.42
(Existing) 0' 1'' Ice 13.15 13.16 299.33
2'' Ice 14.52 15.49 539.68
(2) LNX-6515DS-A1M w/ C From Leg 4.00 0.000 190' No Ice 11.72 10.28 100.61
Mount Pipe 0' 1/2'' Ice 12.44 11.81 194.42
(Existing) 0' 1'' Ice 13.15 13.16 299.33
2'' Ice 14.52 15.49 539.68
HBXX-6516DS-A2M w/ A From Leg 4.00 0.000 190' No Ice 5.66 4.53 49.73
Mount Pipe 0' 1/2'' Ice 6.06 5.20 98.97
(Existing) 0' 1'' Ice 6.47 5.86 154.42
2'' Ice 7.32 7.20 286.98
HBXX-6516DS-A2M w/ B From Leg 4.00 0.000 190' No Ice 5.66 4.53 49.73
Mount Pipe 0' 1/2'' Ice 6.06 5.20 98.97
(Existing) 0' 1'' Ice 6.47 5.86 154.42
2'' Ice 7.32 7.20 286.98
HBXX-6516DS-A2M w/ C From Leg 4.00 0.000 190' No Ice 5.66 4.53 49.73
Mount Pipe 0' 1/2'' Ice 6.06 5.20 98.97
(Existing) 0' 1'' Ice 6.47 5.86 154.42
2'' Ice 7.32 7.20 286.98
(2) RADIO 4449 A From Leg 4.00 0.000 190' No Ice 3.50 2.36 85.00
0' 1/2'' Ice 3.74 2.57 114.30
0' 1'' Ice 3.99 2.78 147.22
2'' Ice 4.51 3.24 224.74
RADIO 4449 B From Leg 4.00 0.000 190' No Ice 3.50 2.36 85.00
0' 1/2'' Ice 3.74 2.57 114.30
0' 1'' Ice 3.99 2.78 147.22
2'' Ice 4.51 3.24 224.74
(3) RADIO 8843 B From Leg 4.00 0.000 190' No Ice 3.50 2.36 85.00
0' 1/2'' Ice 3.74 2.57 114.30
0' 1'' Ice 3.99 2.78 147.22
2'' Ice 4.51 3.24 224.74
RVZDC-6627-PF-48 A From Leg 4.00 0.000 190' No Ice 3.79 2.51 32.00
0' 1/2'' Ice 4.04 2.73 63.48
0' 1'' Ice 4.30 2.95 98.72
2'' Ice 4.84 3.42 181.25
RRFDC-3315-PF-48 A From Leg 4.00 0.000 190' No Ice 3.36 2.19 32.00
(Existing) 0' 1/2'' Ice 3.60 2.39 60.54
0' 1'' Ice 3.84 2.61 92.61
2'' Ice 4.34 3.05 168.17
Sector Mount [SM 405-3] C None 0.000 190' No Ice 18.73 18.73 860.80
1/2'' Ice 27.19 27.19 1262.42
1'' Ice 35.65 35.65 1664.04
2'' Ice 52.57 52.57 2467.28
** Mods **
Knife Plate 1/2''x4''x33'' A From Leg 0.25 90.000 120' No Ice 0.23 1.32 18.70
6'' 1/2'' Ice 0.55 1.54 24.82
0' 1'' Ice 0.78 1.75 33.58
Job Page
tnxTower Apex (BU 871394) 34 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Description Face Offset Offsets: Azimuth Placement CAAA CAAA Weight


or Type Horz Adjustment Front Side
Leg Lateral
Vert
ft ° ft ft2 ft2 lb
ft
ft
2'' Ice 1.21 2.19 59.73
Knife Plate 1/2''x4''x33'' A From Leg 0.25 -90.000 120' No Ice 0.23 1.32 18.70
-6'' 1/2'' Ice 0.55 1.54 24.82
0' 1'' Ice 0.78 1.75 33.58
2'' Ice 1.21 2.19 59.73
Knife Plate 1/2''x4''x33'' B From Leg 0.25 90.000 120' No Ice 0.23 1.32 18.70
6'' 1/2'' Ice 0.55 1.54 24.82
0' 1'' Ice 0.78 1.75 33.58
2'' Ice 1.21 2.19 59.73
Knife Plate 1/2''x4''x33'' B From Leg 0.25 -90.000 120' No Ice 0.23 1.32 18.70
-6'' 1/2'' Ice 0.55 1.54 24.82
0' 1'' Ice 0.78 1.75 33.58
2'' Ice 1.21 2.19 59.73
Knife Plate 1/2''x4''x33'' C From Leg 0.25 90.000 120' No Ice 0.23 1.32 18.70
6'' 1/2'' Ice 0.55 1.54 24.82
0' 1'' Ice 0.78 1.75 33.58
2'' Ice 1.21 2.19 59.73
Knife Plate 1/2''x4''x33'' C From Leg 0.25 -90.000 120' No Ice 0.23 1.32 18.70
-6'' 1/2'' Ice 0.55 1.54 24.82
0' 1'' Ice 0.78 1.75 33.58
2'' Ice 1.21 2.19 59.73
*
Knife Plate (Apex) A From Leg 0.25 45.000 100' No Ice 0.58 1.40 39.40
0' 1/2'' Ice 0.99 1.67 49.32
0' 1'' Ice 1.25 1.94 62.54
2'' Ice 1.79 2.48 99.68
Knife Plate (Apex) B From Leg 0.25 -45.000 100' No Ice 0.58 1.40 39.40
0' 1/2'' Ice 0.99 1.67 49.32
0' 1'' Ice 1.25 1.94 62.54
2'' Ice 1.79 2.48 99.68
Knife Plate (Apex) C From Leg 0.25 -45.000 100' No Ice 0.58 1.40 39.40
0' 1/2'' Ice 0.99 1.67 49.32
0' 1'' Ice 1.25 1.94 62.54
2'' Ice 1.79 2.48 99.68
*
Knife Plate (Apex) A From Leg 0.25 45.000 80' No Ice 0.58 1.40 39.40
0' 1/2'' Ice 0.99 1.67 49.32
0' 1'' Ice 1.25 1.94 62.54
2'' Ice 1.79 2.48 99.68
Knife Plate (Apex) B From Leg 0.25 -45.000 80' No Ice 0.58 1.40 39.40
0' 1/2'' Ice 0.99 1.67 49.32
0' 1'' Ice 1.25 1.94 62.54
2'' Ice 1.79 2.48 99.68
Knife Plate (Apex) C From Leg 0.25 -45.000 80' No Ice 0.58 1.40 39.40
0' 1/2'' Ice 0.99 1.67 49.32
0' 1'' Ice 1.25 1.94 62.54
2'' Ice 1.79 2.48 99.68
*
Knife Plate (Apex) A From Leg 0.25 45.000 60' No Ice 0.58 1.40 39.40
0' 1/2'' Ice 0.99 1.67 49.32
0' 1'' Ice 1.25 1.94 62.54
2'' Ice 1.79 2.48 99.68
Knife Plate (Apex) B From Leg 0.25 -45.000 60' No Ice 0.58 1.40 39.40
0' 1/2'' Ice 0.99 1.67 49.32
0' 1'' Ice 1.25 1.94 62.54
2'' Ice 1.79 2.48 99.68
Knife Plate (Apex) C From Leg 0.25 -45.000 60' No Ice 0.58 1.40 39.40
Job Page
tnxTower Apex (BU 871394) 35 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Description Face Offset Offsets: Azimuth Placement CAAA CAAA Weight


or Type Horz Adjustment Front Side
Leg Lateral
Vert
ft ° ft ft2 ft2 lb
ft
ft
0' 1/2'' Ice 0.99 1.67 49.32
0' 1'' Ice 1.25 1.94 62.54
2'' Ice 1.79 2.48 99.68
*
Knife Plate (Apex) A From Leg 0.25 45.000 40' No Ice 0.58 1.40 39.40
0' 1/2'' Ice 0.99 1.67 49.32
0' 1'' Ice 1.25 1.94 62.54
2'' Ice 1.79 2.48 99.68
Knife Plate (Apex) B From Leg 0.25 -45.000 40' No Ice 0.58 1.40 39.40
0' 1/2'' Ice 0.99 1.67 49.32
0' 1'' Ice 1.25 1.94 62.54
2'' Ice 1.79 2.48 99.68
Knife Plate (Apex) C From Leg 0.25 -45.000 40' No Ice 0.58 1.40 39.40
0' 1/2'' Ice 0.99 1.67 49.32
0' 1'' Ice 1.25 1.94 62.54
2'' Ice 1.79 2.48 99.68
*
Knife Plate (Apex) A From Leg 0.25 45.000 20' No Ice 0.58 1.40 39.40
0' 1/2'' Ice 0.99 1.67 49.32
0' 1'' Ice 1.25 1.94 62.54
2'' Ice 1.79 2.48 99.68
Knife Plate (Apex) B From Leg 0.25 -45.000 20' No Ice 0.58 1.40 39.40
0' 1/2'' Ice 0.99 1.67 49.32
0' 1'' Ice 1.25 1.94 62.54
2'' Ice 1.79 2.48 99.68
Knife Plate (Apex) C From Leg 0.25 -45.000 20' No Ice 0.58 1.40 39.40
0' 1/2'' Ice 0.99 1.67 49.32
0' 1'' Ice 1.25 1.94 62.54
2'' Ice 1.79 2.48 99.68
***
***

Bolt Design Data


Section Elevation Component Bolt Bolt Size Number Maximum Allowable Ratio Allowable Criteria
No. Type Grade Of Load Load Load Ratio
ft in Bolts per Bolt per Bolt Allowable
lb lb
T1 500 Leg A325X 0.750 4 2001.01 30101.40 0.066 1.05 Bolt Tension
Diagonal A325X 0.500 1 2262.19 5919.48 0.382 1.05 Member Bearing
Top Girt A325X 0.500 1 212.72 5919.48 0.036 1.05 Member Bearing
Bottom Girt A325X 0.500 1 1235.04 5919.48 0.209 1.05 Member Bearing
T2 480 Leg A325X 0.750 4 1174.08 30101.40 0.039 1 Bolt Tension
Diagonal A325X 0.500 1 1642.80 5919.48 0.278 1.05 Member Bearing
Top Girt A325X 0.500 1 591.88 5919.48 0.100 1.05 Member Bearing
Bottom Girt A325X 0.500 1 672.42 5919.48 0.114 1.05 Member Bearing
Top Guy A325N 0.750 2 1900.65 19880.40 0.096 1.05 Bolt Shear
Pull-Off@479.38
5
T3 460 Leg A325X 0.750 4 1410.47 30101.40 0.047 1.05 Bolt Tension
Diagonal A325X 0.500 1 2153.90 5919.48 0.364 1.05 Member Bearing
Job Page
tnxTower Apex (BU 871394) 36 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Section Elevation Component Bolt Bolt Size Number Maximum Allowable Ratio Allowable Criteria
No. Type Grade Of Load Load Load Ratio
ft in Bolts per Bolt per Bolt Allowable
lb lb
Top Girt A325X 0.500 1 680.77 5919.48 0.115 1.05 Member Bearing
Bottom Girt A325X 0.500 1 1115.81 5919.48 0.188 1.05 Member Bearing
T4 440 Leg A325X 0.750 4 2889.27 30101.40 0.096 1.05 Bolt Tension
Diagonal A325X 0.500 1 2238.64 5919.48 0.378 1.05 Member Bearing
Top Girt A325X 0.500 1 237.09 5919.48 0.040 1.05 Member Bearing
Bottom Girt A325X 0.500 1 760.18 5919.48 0.128 1.05 Member Bearing
Torque Arm A325X 0.625 2 2653.57 15701.80 0.169 1.05 Member Bearing
Top@422.523
T5 420 Leg A325X 0.750 4 2679.38 30101.40 0.089 1 Bolt Tension
Diagonal A325X 0.500 1 1685.85 5919.48 0.285 1.05 Member Bearing
Top Girt A325X 0.500 1 876.97 5919.48 0.148 1.05 Member Bearing
Bottom Girt A325X 0.500 1 340.62 5919.48 0.058 1.05 Member Bearing
T6 400 Leg A325X 0.750 4 2787.33 30101.40 0.093 1 Bolt Tension
Diagonal A325X 0.500 1 776.82 7015.68 0.111 1.05 Member Bearing
Top Girt A325X 0.500 1 306.44 5919.48 0.052 1.05 Member Bearing
Bottom Girt A325X 0.500 1 243.91 5919.48 0.041 1.05 Member Bearing
T7 380 Leg A325X 0.750 4 3120.43 30101.40 0.104 1.05 Bolt Tension
Diagonal A325X 0.500 1 1471.11 5919.48 0.249 1.05 Member Bearing
Top Girt A325X 0.500 1 305.91 5919.48 0.052 1.05 Member Bearing
Bottom Girt A325X 0.500 1 639.43 5919.48 0.108 1.05 Member Bearing
T8 360 Leg A325X 0.750 4 4517.14 30101.40 0.150 1.05 Bolt Tension
Diagonal A325X 0.500 1 2577.54 7015.68 0.367 1.05 Member Bearing
Top Girt A325X 0.500 1 370.60 5919.48 0.063 1 Member Bearing
Bottom Girt A325X 0.500 1 743.72 5919.48 0.126 1.05 Member Bearing
Torque Arm A325X 0.625 2 2676.59 15701.80 0.170 1.05 Member Bearing
Top@342.523
T9 340 Leg A325X 0.750 4 4384.21 30101.40 0.146 1 Bolt Tension
Diagonal A325X 0.500 1 2851.25 5919.48 0.482 1.05 Member Bearing
Top Girt A325X 0.500 1 1246.45 5919.48 0.211 1.05 Member Bearing
Bottom Girt A325X 0.500 1 711.08 5919.48 0.120 1.05 Member Bearing
T10 320 Leg A325X 0.750 4 4468.55 30101.40 0.148 1 Bolt Tension
Diagonal A325X 0.500 1 1823.88 5919.48 0.308 1.05 Member Bearing
Top Girt A325X 0.500 1 712.21 5919.48 0.120 1.05 Member Bearing
Bottom Girt A325X 0.500 1 384.20 5919.48 0.065 1.05 Member Bearing
T11 300 Leg A325X 0.750 4 4520.83 30101.40 0.150 1 Bolt Tension
Diagonal A325X 0.500 1 1504.00 5919.48 0.254 1.05 Member Bearing
Top Girt A325X 0.500 1 383.55 5919.48 0.065 1.05 Member Bearing
Bottom Girt A325X 0.500 1 547.25 5919.48 0.092 1.05 Member Bearing
T12 280 Leg A325X 0.750 4 4545.27 30101.40 0.151 1 Bolt Tension
Diagonal A325X 0.500 1 2122.49 5919.48 0.359 1.05 Member Bearing
Top Girt A325X 0.500 1 598.00 5919.48 0.101 1.05 Member Bearing
Bottom Girt A325X 0.500 1 993.27 5919.48 0.168 1.05 Member Bearing
T13 260 Leg A325X 0.750 4 5291.00 30101.40 0.176 1.05 Bolt Tension
Diagonal A325X 0.500 1 3752.51 5919.48 0.634 1.05 Member Bearing
Top Girt A325X 0.500 1 622.67 5919.48 0.105 1.05 Member Bearing
Bottom Girt A325X 0.500 1 1099.67 5919.48 0.186 1.05 Member Bearing
Top Guy A325N 0.750 2 1999.52 19880.40 0.101 1.05 Bolt Shear
Pull-Off@259.38
5
T14 240 Leg A325X 0.750 4 5636.18 30101.40 0.187 1.05 Bolt Tension
Diagonal A325X 0.500 1 2028.06 7015.68 0.289 1.05 Member Bearing
Top Girt A325X 0.500 1 598.15 5919.48 0.101 1.05 Member Bearing
Bottom Girt A325X 0.500 1 596.73 5919.48 0.101 1.05 Member Bearing
T15 220 Leg A325X 0.750 4 5793.31 30101.40 0.192 1.05 Bolt Tension
Diagonal A325X 0.500 1 1198.79 7015.68 0.171 1.05 Member Bearing
Top Girt A325X 0.500 1 584.65 5919.48 0.099 1.05 Member Bearing
Bottom Girt A325X 0.500 1 568.27 5919.48 0.096 1 Member Bearing
T16 200 Leg A325X 0.750 4 5992.96 30101.40 0.199 1 Bolt Tension
Diagonal A325X 0.500 1 2988.96 7015.68 0.426 1.05 Member Bearing
Top Girt A325X 0.500 1 604.03 5919.48 0.102 1.05 Member Bearing
Job Page
tnxTower Apex (BU 871394) 37 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Section Elevation Component Bolt Bolt Size Number Maximum Allowable Ratio Allowable Criteria
No. Type Grade Of Load Load Load Ratio
ft in Bolts per Bolt per Bolt Allowable
lb lb
Bottom Girt A325X 0.500 1 813.88 5919.48 0.137 1.05 Member Bearing
T17 180 Leg A325X 0.750 4 6491.18 30101.40 0.216 1 Bolt Tension
Diagonal A325X 0.500 1 976.85 5919.48 0.165 1.05 Member Bearing
Top Girt A325X 0.500 1 613.71 5919.48 0.104 1.05 Member Bearing
Bottom Girt A325X 0.500 1 325.46 5919.48 0.055 1.05 Member Bearing
Top Guy A325N 0.750 2 1970.75 19880.40 0.099 1.05 Bolt Shear
Pull-Off@179.38
5
T18 160 Leg A325X 0.750 4 6536.00 30101.40 0.217 1 Bolt Tension
Diagonal A325X 0.500 1 2235.35 5919.48 0.378 1.05 Member Bearing
Top Girt A325X 0.500 1 316.56 5919.48 0.053 1.05 Member Bearing
Bottom Girt A325X 0.500 1 720.99 5919.48 0.122 1.05 Member Bearing
T19 140 Diagonal A325X 0.500 1 3424.24 5919.48 0.578 1.05 Member Bearing
Top Girt A325X 0.500 1 672.42 5919.48 0.114 1.05 Member Bearing
Bottom Girt A325X 0.500 1 1475.40 5919.48 0.249 1.05 Member Bearing
T20 120 Leg A325X 0.750 4 6915.39 30101.40 0.230 1 Bolt Tension
Diagonal A325X 0.500 1 2211.81 5919.48 0.374 1.05 Member Bearing
Top Girt A325X 0.500 1 600.53 5919.48 0.101 1.05 Member Bearing
Bottom Girt A325X 0.500 1 530.10 5919.48 0.090 1.05 Member Bearing
Top Guy A325N 0.750 2 1928.43 19880.40 0.097 1.05 Bolt Shear
Pull-Off@119.38
5
T21 100 Leg A325X 0.875 4 6985.74 41556.00 0.168 1 Bolt Tension
Diagonal A325X 0.500 1 1526.57 5919.48 0.258 1.05 Member Bearing
Top Girt A325X 0.500 1 469.26 5919.48 0.079 1.05 Member Bearing
Bottom Girt A325X 0.500 1 430.39 5919.48 0.073 1.05 Member Bearing
T22 80 Leg A325X 0.875 4 7026.90 41556.00 0.169 1 Bolt Tension
Diagonal A325X 0.500 1 2790.85 5919.48 0.471 1.05 Member Bearing
Top Girt A325X 0.500 1 494.15 5919.48 0.083 1.05 Member Bearing
Bottom Girt A325X 0.500 1 961.22 5919.48 0.162 1.05 Member Bearing
T23 60 Leg A325X 0.875 4 7315.03 41556.00 0.176 1 Bolt Tension
Diagonal A325X 0.500 1 3083.44 5919.48 0.521 1.05 Member Bearing
Top Girt A325X 0.500 1 437.71 5919.48 0.074 1.05 Member Bearing
Bottom Girt A325X 0.500 1 638.45 5919.48 0.108 1.05 Member Bearing
Top Guy A325N 0.750 2 1561.76 19880.40 0.079 1.05 Bolt Shear
Pull-Off@59.385
4
T24 40 Leg A325X 0.875 4 7393.49 41556.00 0.178 1 Bolt Tension
Diagonal A325X 0.500 1 2328.59 5919.48 0.393 1.05 Member Bearing
Top Girt A325X 0.500 1 612.23 5919.48 0.103 1.05 Member Bearing
Bottom Girt A325X 0.500 1 580.11 5919.48 0.098 1.05 Member Bearing
T25 20 Leg A325X 0.875 4 7440.40 41556.00 0.179 1 Bolt Tension
Diagonal A325X 0.500 1 2269.44 5919.48 0.383 1.05 Member Bearing
Top Girt A325X 0.500 1 621.83 5919.48 0.105 1.05 Member Bearing
Bottom Girt A325X 0.500 1 1429.89 5919.48 0.242 1 Member Bearing

Guy Design Data


Section Elevation Size Initial Breaking Actual Allowable Required Actual
No. Tension Load Tu φTn S.F. S.F.
ft lb lb lb lb
T2 479'4-11/16'' 5/8 EHS 4240.00 42399.99 12779.10 26711.49 0.952 1.991
(A) (960)
479'4-11/16'' 5/8 EHS 4240.00 42399.99 13015.40 26711.49 0.952 1.955
Job Page
tnxTower Apex (BU 871394) 38 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Section Elevation Size Initial Breaking Actual Allowable Required Actual


No. Tension Load Tu φTn S.F. S.F.
ft lb lb lb lb
(B) (959)
479'4-11/16'' 5/8 EHS 4240.00 42399.99 12945.50 26711.49 0.952 1.965
(C) (955)
T4 422'6-1/4'' (A) 9/16 EHS 3500.00 35000.04 11088.40 22049.58 0.952 1.894
(969)
422'6-1/4'' (A) 9/16 EHS 3500.00 35000.04 11071.30 22049.58 0.952 1.897
(970)
422'6-1/4'' (B) 9/16 EHS 3500.00 35000.04 11283.80 22049.58 0.952 1.861
(965)
422'6-1/4'' (B) 9/16 EHS 3500.00 35000.04 11359.20 22049.58 0.952 1.849
(966)
422'6-1/4'' (C) 9/16 EHS 3500.00 35000.04 11279.20 22049.58 0.952 1.862
(961)
422'6-1/4'' (C) 9/16 EHS 3500.00 35000.04 11223.10 22049.58 0.952 1.871
(962)
T8 342'6-1/4'' (A) 9/16 EHS 3500.00 35000.04 9427.86 22049.58 0.952 2.227
(981)
342'6-1/4'' (A) 9/16 EHS 3500.00 35000.04 9397.91 22049.58 0.952 2.235
(982)
342'6-1/4'' (B) 9/16 EHS 3500.00 35000.04 9630.20 22049.58 0.952 2.181
(977)
342'6-1/4'' (B) 9/16 EHS 3500.00 35000.04 9724.05 22049.58 0.952 2.160
(978)
342'6-1/4'' (C) 9/16 EHS 3500.00 35000.04 9659.23 22049.58 0.952 2.174
(973)
342'6-1/4'' (C) 9/16 EHS 3500.00 35000.04 9603.34 22049.58 0.952 2.187
(974)
T13 259'4-11/16'' 9/16 EHS 3500.00 35000.04 10401.10 22049.58 0.952 2.019
(A) (990)
259'4-11/16'' 9/16 EHS 3500.00 35000.04 10751.20 22049.58 0.952 1.953
(B) (989)
259'4-11/16'' 9/16 EHS 3500.00 35000.04 10766.50 22049.58 0.952 1.950
(C) (985)
T17 179'4-11/16'' 9/16 EHS 3500.00 35000.04 14246.80 22049.58 0.952 1.474
(A) (996)
179'4-11/16'' 9/16 EHS 3500.00 35000.04 13774.40 22049.58 0.952 1.525
(B) (995)
179'4-11/16'' 9/16 EHS 3500.00 35000.04 13720.40 22049.58 0.952 1.531
(C) (991)
T20 119'4-11/16'' 1/2 EHS 2690.00 26900.04 10882.90 16946.68 0.952 1.483
(A) (1002)
119'4-11/16'' 1/2 EHS 2690.00 26900.04 10180.90 16946.68 0.952 1.585
(B) (1001)
119'4-11/16'' 1/2 EHS 2690.00 26900.04 10058.30 16946.68 0.952 1.605
(C) (997)
T23 59'4-11/16'' (A) 7/16 EHS 2080.00 20800.02 6791.60 13103.75 0.952 1.838
(1008)
59'4-11/16'' (B) 7/16 EHS 2080.00 20800.02 6303.27 13103.75 0.952 1.980
(1007)
59'4-11/16'' (C) 7/16 EHS 2080.00 20800.02 6217.06 13103.75 0.952 2.007
(1003)

Compression Checks
Job Page
tnxTower Apex (BU 871394) 39 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Leg Design Data (Compression)


Section Elevation Size L Lu Kl/r A Pu φPn Ratio
No. Pu
ft ft ft in2 lb lb φPn
T1 500 - 480 ROHN 2 EH 20' 2'4-29/3 75.4 1.477 -7959.61 43855.60 0.181 1
2'' K=2.00
T2 480 - 460 ROHN 2 EH 20' 2'4-29/3 75.4 1.477 -14010.40 43855.60 0.319*1
2'' K=2.00
T3 460 - 440 ROHN 2 EH 20' 2'4-29/3 75.4 1.477 -16410.60 43855.60 0.374 1
2'' K=2.00
T4 440 - 420 ROHN 2 EH 20' 2'4-29/3 37.7 1.477 -34365.70 59911.20 0.574 1
2'' K=1.00
T5 420 - 400 ROHN 2.5 STD 20' 2'4-29/3 61.0 1.704 -34595.00 58405.60 0.592 1
2'' K=2.00
T6 400 - 380 ROHN 2.5 STD 20' 2'4-29/3 61.0 1.704 -33228.90 58405.60 0.569*1
2'' K=2.00
T7 380 - 360 ROHN 2.5 STD 20' 2'4-29/3 61.0 1.704 -37214.00 58405.60 0.637 1
2'' K=2.00
T8 360 - 340 ROHN 2.5 STD 20' 2'4-29/3 30.5 1.704 -53621.40 71636.60 0.749 1
2'' K=1.00
T9 340 - 320 ROHN 2.5 EH 20' 2'4-29/3 62.6 2.254 -54085.40 76169.70 0.710 1
2'' K=2.00
T10 320 - 300 ROHN 2.5 EH 20' 2'4-29/3 62.6 2.254 -53444.10 76169.70 0.702*1
2'' K=2.00
T11 300 - 280 ROHN 2.5 EH 20' 2'4-29/3 62.6 2.254 -54166.40 76169.70 0.711*1
2'' K=2.00
T12 280 - 260 ROHN 2.5 EH 20' 2'4-29/3 62.6 2.254 -54529.00 76169.70 0.716*1
2'' K=2.00
T13 260 - 240 ROHN 2.5 EH 20' 2'4-29/3 62.6 2.254 -61292.50 76169.70 0.805*1
2'' K=2.00
T14 240 - 220 ROHN 2.5 EH 20' 2'4-29/3 31.3 2.254 -67330.50 94406.90 0.713 1
2'' K=1.00
T15 220 - 200 ROHN 2.5 EH 20' 2'4-29/3 31.3 2.254 -69720.70 94406.90 0.739 1
2'' K=1.00
T16 200 - 180 ROHN 2.5 EH 20' 2'4-29/3 31.3 2.254 -71849.00 94406.90 0.761*1
2'' K=1.00
T17 180 - 160 2.5 XH w/ 3 STD Half 20' 2'4-29/3 62.5 3.368 -77754.90 113939.00 0.682*1
Sleeve 2'' K=2.00
T18 160 - 140 2.5 XH w/ 3 STD Half 20' 2'4-29/3 62.5 3.368 -78478.70 113939.00 0.689*1
Sleeve 2'' K=2.00
T19 140 - 120 2.5 XH w/ 3 STD Half 20' 2'4-29/3 62.5 3.368 -82503.00 113939.00 0.724 1
Sleeve 2'' K=2.00
T20 120 - 100 2.5 XH w/ 3 STD Half 20' 2'4-29/3 62.5 3.368 -82908.80 113939.00 0.728*1
Sleeve 2'' K=2.00
T21 100 - 80 Rohn 2.5 EH w/ L3x3x1/4 20' 2'4-29/3 57.3 3.706 -83795.00 131141.00 0.639*1
2'' K=2.00
T22 80 - 60 Rohn 3 STD w/ L3x3x1/4 20' 2'4-29/3 49.9 3.681 -84381.60 138078.00 0.611*1
2'' K=2.00
T23 60 - 40 Rohn 3 STD w/ L3x3x1/4 20' 2'4-29/3 49.9 3.681 -87590.90 138078.00 0.634*1
2'' K=2.00
T24 40 - 20 Rohn 3 STD w/ L3x3x1/4 20' 2'4-29/3 49.9 3.681 -88617.40 138078.00 0.642*1
2'' K=2.00
T25 20 - 4.81771 3 STD w/ 3.5 STD Half 15'2-5/3 2'4-29/3 50.7 3.568 -89168.00 133021.00 0.670*1
Sleeve 2'' 2'' K=2.00
T26 4.81771 - 0 ROHN 3 X-STR 5'2-17/3 1'3-19/3 13.7 3.016 -96077.30 133855.00 0.718*1
2'' 2'' K=1.00

*
DL controls
1
Pu / φPn controls
Job Page
tnxTower Apex (BU 871394) 40 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Diagonal Design Data (Compression)


Section Elevation Size L Lu Kl/r A Pu φPn Ratio
No. Pu
ft ft ft in2 lb lb φPn
T1 500 - 480 ROHN 1.5 x 16GA 4'2-5/32' 3'11-9/3 92.6 0.263 -2255.53 5864.10 0.385 1
' 2'' K=1.00
T2 480 - 460 ROHN 1.5 x 16GA 4'2-5/32' 3'11-9/3 92.6 0.263 -1720.12 5864.10 0.293 1
' 2'' K=1.00
T3 460 - 440 ROHN 1.5 x 16GA 4'2-5/32' 3'11-9/3 92.6 0.263 -2455.42 5864.10 0.419 1
' 2'' K=1.00
T4 440 - 420 ROHN 1.5 x 16GA 4'2-5/32' 3'11-9/3 92.6 0.263 -2083.60 5864.10 0.355 1
' 2'' K=1.00
T5 420 - 400 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 -1691.54 5944.12 0.285 1
' 16'' K=1.00
T6 400 - 380 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 -776.82 5944.12 0.131 1
' 16'' K=1.00
T7 380 - 360 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 -1625.30 5944.12 0.273 1
' 16'' K=1.00
T8 360 - 340 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 -2577.54 5944.12 0.434 1
' 16'' K=1.00
T9 340 - 320 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 -3007.65 5944.12 0.506 1
' 16'' K=1.00
T10 320 - 300 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 -2062.10 5944.12 0.347 1
' 16'' K=1.00
T11 300 - 280 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 -1736.03 5944.12 0.292 1
' 16'' K=1.00
T12 280 - 260 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 -2317.72 5944.12 0.390 1
' 16'' K=1.00
T13 260 - 240 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 -3693.79 5944.12 0.621 1
' 16'' K=1.00
T14 240 - 220 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 -2028.06 5944.12 0.341 1
' 16'' K=1.00
T15 220 - 200 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 -1198.79 5944.12 0.202 1
' 16'' K=1.00
T16 200 - 180 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 -2988.96 5944.12 0.503 1
' 16'' K=1.00
T17 180 - 160 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 -1092.74 5944.12 0.184 1
' 16'' K=1.00
T18 160 - 140 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 -2619.40 5944.12 0.441 1
' 16'' K=1.00
T19 140 - 120 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 -3676.50 5944.12 0.619 1
' 16'' K=1.00
T20 120 - 100 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 -2091.45 5944.12 0.352 1
' 16'' K=1.00
T21 100 - 80 ROHN 1.5 x 16GA 4'2-5/32' 3'9'' 88.1 0.263 -1794.64 6164.23 0.291 1
' K=1.00
T22 80 - 60 ROHN 1.5 x 16GA 4'2-5/32' 3'9'' 88.1 0.263 -3008.01 6164.23 0.488 1
' K=1.00
T23 60 - 40 ROHN 1.5 x 16GA 4'2-5/32' 3'9'' 88.1 0.263 -3037.35 6164.23 0.493 1
' K=1.00
T24 40 - 20 ROHN 1.5 x 16GA 4'2-5/32' 3'9'' 88.1 0.263 -2689.29 6164.23 0.436 1
' K=1.00
T25 20 - 4.81771 ROHN 1.5 x 16GA 4'2-5/32' 3'9-1/4'' 88.7 0.263 -2362.03 6124.22 0.386 1
' K=1.00

1
Pu / φPn controls
Job Page
tnxTower Apex (BU 871394) 41 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Horizontal Design Data (Compression)


Section Elevation Size L Lu Kl/r A Pu φPn Ratio
No. Pu
ft ft ft in2 lb lb φPn
T26 4.81771 - 0 C14x2-3/8x3/16 (BP) 1'8-17/3 1'5-1/32' 38.7 3.445 -148.42 103173.00 0.001*1
2'' ' K=1.00

*
DL controls
1
Pu / φPn controls

Top Girt Design Data (Compression)


Section Elevation Size L Lu Kl/r A Pu φPn Ratio
No. Pu
ft ft ft in2 lb lb φPn
T1 500 - 480 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/8'' 75.7 0.263 -202.97 6985.23 0.029 1
' K=1.00
T3 460 - 440 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/8'' 75.7 0.263 -709.15 6985.23 0.102 1
' K=1.00
T4 440 - 420 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/8'' 75.7 0.263 -101.86 6985.23 0.015 1
' K=1.00
T5 420 - 400 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -624.68 7048.75 0.089 1
' ' K=1.00
T6 400 - 380 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -209.59 7048.75 0.030 1
' ' K=1.00
T7 380 - 360 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -188.41 7048.75 0.027 1
' ' K=1.00
T9 340 - 320 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -929.32 7048.75 0.132 1
' ' K=1.00
T10 320 - 300 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -539.49 7048.75 0.077 1
' ' K=1.00
T11 300 - 280 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -253.79 7048.75 0.036 1
' ' K=1.00
T12 280 - 260 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -438.01 7048.75 0.062 1
' ' K=1.00
T14 240 - 220 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -57.46 7048.75 0.008 1
' ' K=1.00
T17 180 - 160 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -25.00 7048.75 0.004 1
' ' K=1.00
T18 160 - 140 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -207.43 7048.75 0.029 1
' ' K=1.00
T19 140 - 120 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -609.16 7048.75 0.086 1
' ' K=1.00
T20 120 - 100 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -5.53 7048.75 0.001 1
' ' K=1.00
T21 100 - 80 ROHN 1.5 x 16GA 3'5-1/32' 3'23/32'' 72.0 0.263 -274.00 7222.05 0.038 1
' K=1.00
T22 80 - 60 ROHN 1.5 x 16GA 3'5-1/32' 3'23/32'' 72.0 0.263 -244.54 7222.05 0.034 1
' K=1.00
T24 40 - 20 ROHN 1.5 x 16GA 3'5-1/32' 3'23/32'' 72.0 0.263 -271.71 7222.05 0.038 1
' K=1.00
T25 20 - 4.81771 ROHN 1.5 x 16GA 3'5-1/32' 3'31/32'' 72.5 0.263 -286.64 7190.71 0.040 1
' K=1.00
Job Page
tnxTower Apex (BU 871394) 42 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

1
Pu / φPn controls

Bottom Girt Design Data (Compression)


Section Elevation Size L Lu Kl/r A Pu φPn Ratio
No. Pu
2
ft ft ft in lb lb φPn
T1 500 - 480 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/8'' 75.7 0.263 -1149.35 6985.23 0.165 1
' K=1.00
T2 480 - 460 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/8'' 75.7 0.263 -651.39 6985.23 0.093 1
' K=1.00
T3 460 - 440 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/8'' 75.7 0.263 -955.69 6985.23 0.137 1
' K=1.00
T4 440 - 420 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/8'' 75.7 0.263 -759.76 6985.23 0.109 1
' K=1.00
T5 420 - 400 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -248.16 7048.75 0.035 1
' ' K=1.00
T6 400 - 380 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -183.66 7048.75 0.026 1
' ' K=1.00
T7 380 - 360 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -557.40 7048.75 0.079 1
' ' K=1.00
T8 360 - 340 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -472.63 7048.75 0.067 1
' ' K=1.00
T9 340 - 320 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -626.98 7048.75 0.089 1
' ' K=1.00
T10 320 - 300 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -306.70 7048.75 0.044 1
' ' K=1.00
T11 300 - 280 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -445.64 7048.75 0.063 1
' ' K=1.00
T12 280 - 260 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -803.64 7048.75 0.114 1
' ' K=1.00
T13 260 - 240 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -1142.36 7048.75 0.162 1
' ' K=1.00
T16 200 - 180 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -94.15 7048.75 0.013 1
' ' K=1.00
T17 180 - 160 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -98.81 7048.75 0.014 1
' ' K=1.00
T18 160 - 140 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -432.36 7048.75 0.061 1
' ' K=1.00
T19 140 - 120 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -971.21 7048.75 0.138 1
' ' K=1.00
T20 120 - 100 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 -269.37 7048.75 0.038 1
' ' K=1.00
T21 100 - 80 ROHN 1.5 x 16GA 3'5-1/32' 3'23/32'' 72.0 0.263 -209.83 7222.05 0.029 1
' K=1.00
T22 80 - 60 ROHN 1.5 x 16GA 3'5-1/32' 3'23/32'' 72.0 0.263 -483.05 7222.05 0.067 1
' K=1.00
T23 60 - 40 ROHN 1.5 x 16GA 3'5-1/32' 3'23/32'' 72.0 0.263 -303.16 7222.05 0.042 1
' K=1.00
T24 40 - 20 ROHN 1.5 x 16GA 3'5-1/32' 3'23/32'' 72.0 0.263 -220.61 7222.05 0.031 1
' K=1.00

1
Pu / φPn controls

Top Guy Pull-Off Design Data (Compression)


Job Page
tnxTower Apex (BU 871394) 43 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Section Elevation Size L Lu Kl/r A Pu φPn Ratio


No. Pu
ft ft ft in2 lb lb φPn
T17 180 - 160 4 1/2x3/8 3'5-1/32' 3'2-5/32' 352.2 1.688 -160.54 3073.58 0.052 1
' ' K=1.00
KL/R > 200 (C) - 994
T20 120 - 100 4 1/2x3/8 3'5-1/32' 3'2-5/32' 352.2 1.688 -35.54 3073.58 0.012 1
' ' K=1.00
KL/R > 200 (C) - 998

1
Pu / φPn controls

Top Guy Pull-Off Bending Design Data


Section Elevation Size Mux φMnx Ratio Muy φMny Ratio
No. Mux Muy
ft lb-ft lb-ft φMnx lb-ft lb-ft φMny
T17 180 - 160 4 1/2x3/8 0.00 5125.78 0.000 0.00 427.15 0.000
T20 120 - 100 4 1/2x3/8 0.00 5125.78 0.000 0.00 427.15 0.000

Top Guy Pull-Off Interaction Design Data


Section Elevation Size Ratio Ratio Ratio Comb. Allow. Criteria
No. Pu Mux Muy Stress Stress
ft φPn φMnx φMny Ratio Ratio
T17 180 - 160 4 1/2x3/8 0.052 0.000 0.000 0.052 1 1.050 4.8.1
T20 120 - 100 4 1/2x3/8 0.012 0.000 0.000 0.012 1 1.050 4.8.1

1
Pu / φPn controls

Torque-Arm Top Design Data


Section Elevation Size L Lu Kl/r A Pu φPn Ratio
No. Pu
2
ft ft ft in lb lb φPn
T4 440 - 420 (963) C12x20.7 3'6-23/3 3'5-17/3 52.0 6.090 -191.50 171105.00 0.001
2'' 2'' K=1.00
T4 440 - 420 (964) C12x20.7 3'6-23/3 3'5-17/3 52.0 6.090 -631.03 171105.00 0.004
2'' 2'' K=1.00
T4 440 - 420 (967) C12x20.7 3'6-23/3 3'5-17/3 52.0 6.090 -356.04 171105.00 0.002
2'' 2'' K=1.00
T4 440 - 420 (968) C12x20.7 3'6-23/3 3'5-17/3 52.0 6.090 -343.89 171105.00 0.002
2'' 2'' K=1.00
T4 440 - 420 (971) C12x20.7 3'6-23/3 3'5-17/3 52.0 6.090 -313.49 171105.00 0.002
2'' 2'' K=1.00
T4 440 - 420 (972) C12x20.7 3'6-23/3 3'5-17/3 52.0 6.090 -130.83 171105.00 0.001
2'' 2'' K=1.00
T8 360 - 340 (975) C12x20.7 3'6-23/3 3'5-9/32' 51.7 6.090 -520.81 171397.00 0.003
2'' ' K=1.00
T8 360 - 340 (976) C12x20.7 3'6-23/3 3'5-9/32' 51.7 6.090 -319.88 171397.00 0.002
Job Page
tnxTower Apex (BU 871394) 44 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Section Elevation Size L Lu Kl/r A Pu φPn Ratio


No. Pu
ft ft ft in2 lb lb φPn
2'' ' K=1.00
T8 360 - 340 (979) C12x20.7 3'6-23/3 3'5-9/32' 51.7 6.090 -165.54 171397.00 0.001
2'' ' K=1.00
T8 360 - 340 (980) C12x20.7 3'6-23/3 3'5-9/32' 51.7 6.090 -345.77 171397.00 0.002
2'' ' K=1.00
T8 360 - 340 (983) C12x20.7 3'6-23/3 3'5-9/32' 51.7 6.090 -718.92 171397.00 0.004
2'' ' K=1.00
T8 360 - 340 (984) C12x20.7 3'6-23/3 3'5-9/32' 51.7 6.090 -723.68 171397.00 0.004
2'' ' K=1.00

Torque-Arm Top Bending Design Data


Section Elevation Size Mux φMnx Ratio Muy φMny Ratio
No. Mux Muy
ft lb-ft lb-ft φMnx lb-ft lb-ft φMny
T4 440 - 420 (963) C12x20.7 -24814.92 58050.00 0.427 -0.00 9423.00 0.000
T4 440 - 420 (964) C12x20.7 -22011.25 58050.00 0.379 -0.00 9423.00 0.000
T4 440 - 420 (967) C12x20.7 -23138.50 58050.00 0.399 0.00 9423.00 0.000
T4 440 - 420 (968) C12x20.7 -22911.00 58050.00 0.395 -0.00 9423.00 0.000
T4 440 - 420 (971) C12x20.7 -25051.58 58050.00 0.432 0.00 9423.00 0.000
T4 440 - 420 (972) C12x20.7 -23958.75 58050.00 0.413 -0.00 9423.00 0.000
T8 360 - 340 (975) C12x20.7 -24141.83 58050.00 0.416 -0.00 9423.00 0.000
T8 360 - 340 (976) C12x20.7 -22439.17 58050.00 0.387 -0.00 9423.00 0.000
T8 360 - 340 (979) C12x20.7 -24362.08 58050.00 0.420 0.00 9423.00 0.000
T8 360 - 340 (980) C12x20.7 -24117.50 58050.00 0.415 -0.00 9423.00 0.000
T8 360 - 340 (983) C12x20.7 -24339.42 58050.00 0.419 0.00 9423.00 0.000
T8 360 - 340 (984) C12x20.7 -22500.17 58050.00 0.388 -0.00 9423.00 0.000

Torque-Arm Top Interaction Design Data


Section Elevation Size Ratio Ratio Ratio Comb. Allow. Criteria
No. Pu Mux Muy Stress Stress
ft φPn φMnx φMny Ratio Ratio
T4 440 - 420 (963) C12x20.7 0.001 0.427 0.000 0.428 1.050 4.8.1
T4 440 - 420 (964) C12x20.7 0.004 0.379 0.000 0.381 1.050 4.8.1
T4 440 - 420 (967) C12x20.7 0.002 0.399 0.000 0.400 1.050 4.8.1
T4 440 - 420 (968) C12x20.7 0.002 0.395 0.000 0.396 1.050 4.8.1
T4 440 - 420 (971) C12x20.7 0.002 0.432 0.000 0.432 1.050 4.8.1
T4 440 - 420 (972) C12x20.7 0.001 0.413 0.000 0.413 1.050 4.8.1
T8 360 - 340 (975) C12x20.7 0.003 0.416 0.000 0.417 1.050 4.8.1
T8 360 - 340 (976) C12x20.7 0.002 0.387 0.000 0.387 1.050 4.8.1
T8 360 - 340 (979) C12x20.7 0.001 0.420 0.000 0.420 1.050 4.8.1
T8 360 - 340 (980) C12x20.7 0.002 0.415 0.000 0.416 1.050 4.8.1
T8 360 - 340 (983) C12x20.7 0.004 0.419 0.000 0.421 1.050 4.8.1
T8 360 - 340 (984) C12x20.7 0.004 0.388 0.000 0.390 1.050 4.8.1

Tension Checks
Job Page
tnxTower Apex (BU 871394) 45 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Leg Design Data (Tension)


Section Elevation Size L Lu Kl/r A Pu φPn Ratio
No. Pu
ft ft ft in2 lb lb φPn
T1 500 - 480 ROHN 2 EH 20' 1-5/16'' 1.8 1.477 8004.02 66476.60 0.120 1
T2 480 - 460 ROHN 2 EH 20' 7-5/16'' 9.6 1.477 8003.41 66476.60 0.120 1
T3 460 - 440 ROHN 2 EH 20' 2'4-29/3 37.7 1.477 475.70 66476.60 0.007 1
2''
T4 440 - 420 ROHN 2 EH 20' 2'4-29/3 37.7 1.477 6649.48 66476.60 0.100 1
2''
T8 360 - 340 ROHN 2.5 STD 20' 2'4-29/3 30.5 1.704 2582.66 76682.30 0.034 1
2''
T14 240 - 220 ROHN 2.5 EH 20' 1-5/16'' 1.5 2.254 2323.31 101409.00 0.023 1
T15 220 - 200 ROHN 2.5 EH 20' 2'4-29/3 31.3 2.254 6580.78 101409.00 0.065 1
2''
T16 200 - 180 ROHN 2.5 EH 20' 2'4-29/3 31.3 2.254 6451.11 101409.00 0.064 1
2''

1
Pu / φPn controls

Diagonal Design Data (Tension)


Section Elevation Size L Lu Kl/r A Pu φPn Ratio
No. Pu
ft ft ft in2 lb lb φPn
T1 500 - 480 ROHN 1.5 x 16GA 4'2-5/32' 3'11-9/3 92.6 0.263 2262.19 9931.96 0.228 1
' 2''
T2 480 - 460 ROHN 1.5 x 16GA 4'2-5/32' 3'11-9/3 92.6 0.263 1642.80 9931.96 0.165 1
' 2''
T3 460 - 440 ROHN 1.5 x 16GA 4'2-5/32' 3'11-9/3 92.6 0.263 2153.90 9931.96 0.217 1
' 2''
T4 440 - 420 ROHN 1.5 x 16GA 4'2-5/32' 3'11-9/3 92.6 0.263 2238.64 9931.96 0.225 1
' 2''
T5 420 - 400 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 1685.85 9931.96 0.170 1
' 16''
T6 400 - 380 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 651.26 9931.96 0.066 1
' 16''
T7 380 - 360 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 1471.11 9931.96 0.148 1
' 16''
T8 360 - 340 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 1908.88 9931.96 0.192 1
' 16''
T9 340 - 320 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 2851.25 9931.96 0.287 1
' 16''
T10 320 - 300 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 1823.88 9931.96 0.184 1
' 16''
T11 300 - 280 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 1504.00 9931.96 0.151 1
' 16''
T12 280 - 260 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 2122.49 9931.96 0.214 1
' 16''
T13 260 - 240 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 3752.51 9931.96 0.378 1
' 16''
T14 240 - 220 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 1561.39 9931.96 0.157 1
' 16''
T15 220 - 200 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 852.76 9931.96 0.086 1
' 16''
T16 200 - 180 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 2497.86 9931.96 0.251 1
Job Page
tnxTower Apex (BU 871394) 46 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Section Elevation Size L Lu Kl/r A Pu φPn Ratio


No. Pu
ft ft ft in2 lb lb φPn
' 16''
T17 180 - 160 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 976.85 9931.96 0.098 1
' 16''
T18 160 - 140 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 2235.35 9931.96 0.225 1
' 16''
T19 140 - 120 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 3424.24 9931.96 0.345 1
' 16''
T20 120 - 100 ROHN 1.5 x 16GA 4'2-5/32' 3'10-11/ 91.4 0.263 2211.81 9931.96 0.223 1
' 16''
T21 100 - 80 ROHN 1.5 x 16GA 4'2-5/32' 3'9'' 88.1 0.263 1526.57 9931.96 0.154 1
'
T22 80 - 60 ROHN 1.5 x 16GA 4'2-5/32' 3'9'' 88.1 0.263 2790.85 9931.96 0.281 1
'
T23 60 - 40 ROHN 1.5 x 16GA 4'2-5/32' 3'9'' 88.1 0.263 3083.44 9931.96 0.310 1
'
T24 40 - 20 ROHN 1.5 x 16GA 4'2-5/32' 3'9'' 88.1 0.263 2328.59 9931.96 0.234 1
'
T25 20 - 4.81771 ROHN 1.5 x 16GA 4'2-5/32' 3'9-1/4'' 88.7 0.263 2269.44 9931.96 0.228 1
'

1
Pu / φPn controls

Horizontal Design Data (Tension)


Section Elevation Size L Lu Kl/r A Pu φPn Ratio
No. Pu
ft ft ft in2 lb lb φPn
T26 4.81771 - 0 C14x2-3/8x3/16 (BP) 2'6-23/3 2'3-1/4'' 62.0 3.445 860.89 111628.00 0.008*1
2''

*
DL controls
1
Pu / φPn controls

Top Girt Design Data (Tension)


Section Elevation Size L Lu Kl/r A Pu φPn Ratio
No. Pu
ft ft ft in2 lb lb φPn
T1 500 - 480 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/8'' 75.7 0.263 212.72 9931.96 0.021 1
'
T2 480 - 460 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/8'' 75.7 0.263 591.88 9931.96 0.060 1
'
T3 460 - 440 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/8'' 75.7 0.263 680.77 9931.96 0.069 1
'
T4 440 - 420 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/8'' 75.7 0.263 237.09 9931.96 0.024 1
'
T5 420 - 400 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 876.97 9931.96 0.088 1
' '
T6 400 - 380 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 306.44 9931.96 0.031 1
' '
T7 380 - 360 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 305.91 9931.96 0.031 1
Job Page
tnxTower Apex (BU 871394) 47 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Section Elevation Size L Lu Kl/r A Pu φPn Ratio


No. Pu
ft ft ft in2 lb lb φPn
' '
T8 360 - 340 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 370.60 9931.96 0.037*1
' '
T9 340 - 320 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 1246.45 9931.96 0.125 1
' '
T10 320 - 300 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 712.21 9931.96 0.072 1
' '
T11 300 - 280 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 383.55 9931.96 0.039 1
' '
T12 280 - 260 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 598.00 9931.96 0.060 1
' '
T13 260 - 240 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 622.67 9931.96 0.063 1
' '
T14 240 - 220 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 598.15 9931.96 0.060 1
' '
T15 220 - 200 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 584.65 9931.96 0.059 1
' '
T16 200 - 180 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 604.03 9931.96 0.061 1
' '
T17 180 - 160 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 613.71 9931.96 0.062 1
' '
T18 160 - 140 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 316.56 9931.96 0.032 1
' '
T19 140 - 120 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 672.42 9931.96 0.068 1
' '
T20 120 - 100 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 600.53 9931.96 0.060 1
' '
T21 100 - 80 ROHN 1.5 x 16GA 3'5-1/32' 3'23/32'' 72.0 0.263 469.26 9931.96 0.047 1
'
T22 80 - 60 ROHN 1.5 x 16GA 3'5-1/32' 3'23/32'' 72.0 0.263 494.15 9931.96 0.050 1
'
T23 60 - 40 ROHN 1.5 x 16GA 3'5-1/32' 3'23/32'' 72.0 0.263 437.71 9931.96 0.044 1
'
T24 40 - 20 ROHN 1.5 x 16GA 3'5-1/32' 3'23/32'' 72.0 0.263 612.23 9931.96 0.062 1
'
T25 20 - 4.81771 ROHN 1.5 x 16GA 3'5-1/32' 3'31/32'' 72.5 0.263 621.83 9931.96 0.063 1
'
T26 4.81771 - 0 C14x2-3/8x3/16 (BP) 3'5-1/32' 3'31/32'' 84.2 3.445 17918.20 111628.00 0.161*1
'

*
DL controls
1
Pu / φPn controls

Bottom Girt Design Data (Tension)


Section Elevation Size L Lu Kl/r A Pu φPn Ratio
No. Pu
ft ft ft in2 lb lb φPn
T1 500 - 480 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/8'' 75.7 0.263 1235.04 9931.96 0.124 1
'
T2 480 - 460 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/8'' 75.7 0.263 672.42 9931.96 0.068 1
'
T3 460 - 440 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/8'' 75.7 0.263 1115.81 9931.96 0.112 1
'
T4 440 - 420 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/8'' 75.7 0.263 760.18 9931.96 0.077 1
'
Job Page
tnxTower Apex (BU 871394) 48 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Section Elevation Size L Lu Kl/r A Pu φPn Ratio


No. Pu
ft ft ft in2 lb lb φPn
T5 420 - 400 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 340.62 9931.96 0.034 1
' '
T6 400 - 380 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 243.91 9931.96 0.025 1
' '
T7 380 - 360 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 639.43 9931.96 0.064 1
' '
T8 360 - 340 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 743.72 9931.96 0.075 1
' '
T9 340 - 320 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 711.08 9931.96 0.072 1
' '
T10 320 - 300 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 384.20 9931.96 0.039 1
' '
T11 300 - 280 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 547.25 9931.96 0.055 1
' '
T12 280 - 260 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 993.27 9931.96 0.100 1
' '
T13 260 - 240 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 1099.67 9931.96 0.111 1
' '
T14 240 - 220 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 596.73 9931.96 0.060 1
' '
T15 220 - 200 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 568.27 9931.96 0.057*1
' '
T16 200 - 180 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 813.88 9931.96 0.082 1
' '
T17 180 - 160 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 325.46 9931.96 0.033 1
' '
T18 160 - 140 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 720.99 9931.96 0.073 1
' '
T19 140 - 120 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 1475.40 9931.96 0.149 1
' '
T20 120 - 100 ROHN 1.5 x 16GA 3'5-1/32' 3'2-5/32' 74.7 0.263 530.10 9931.96 0.053 1
' '
T21 100 - 80 ROHN 1.5 x 16GA 3'5-1/32' 3'23/32'' 72.0 0.263 430.39 9931.96 0.043 1
'
T22 80 - 60 ROHN 1.5 x 16GA 3'5-1/32' 3'23/32'' 72.0 0.263 961.22 9931.96 0.097 1
'
T23 60 - 40 ROHN 1.5 x 16GA 3'5-1/32' 3'23/32'' 72.0 0.263 638.45 9931.96 0.064 1
'
T24 40 - 20 ROHN 1.5 x 16GA 3'5-1/32' 3'23/32'' 72.0 0.263 580.11 9931.96 0.058 1
'
T25 20 - 4.81771 ROHN 1.5 x 16GA 3'5-1/32' 3'31/32'' 72.5 0.263 1429.89 9931.96 0.144*1
'

*
DL controls
1
Pu / φPn controls

Top Guy Pull-Off Design Data (Tension)


Section Elevation Size L Lu Kl/r A Pu φPn Ratio
No. Pu
2
ft ft ft in lb lb φPn
T2 480 - 460 4 1/2x3/8 3'5-1/32' 3'2-5/8'' 356.8 1.688 3801.31 54675.00 0.070 1
'
T13 260 - 240 4 1/2x3/8 3'5-1/32' 3'2-5/32' 352.2 1.688 3999.04 54675.00 0.073 1
' '
T17 180 - 160 4 1/2x3/8 3'5-1/32' 3'2-5/32' 352.2 1.688 3941.50 54675.00 0.072 1
Job Page
tnxTower Apex (BU 871394) 49 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Section Elevation Size L Lu Kl/r A Pu φPn Ratio


No. Pu
ft ft ft in2 lb lb φPn
' '
T20 120 - 100 4 1/2x3/8 3'5-1/32' 3'2-5/32' 352.2 1.688 3856.86 54675.00 0.071 1
' '
T23 60 - 40 5x3/8 3'5-1/32' 3'23/32'' 339.5 1.875 3123.51 60750.00 0.051 1
'

1
Pu / φPn controls

Top Guy Pull-Off Bending Design Data


Section Elevation Size Mux φMnx Ratio Muy φMny Ratio
No. Mux Muy
ft lb-ft lb-ft φMnx lb-ft lb-ft φMny
T2 480 - 460 4 1/2x3/8 0.00 5125.78 0.000 0.00 427.15 0.000
T13 260 - 240 4 1/2x3/8 0.00 5125.78 0.000 0.00 427.15 0.000
T17 180 - 160 4 1/2x3/8 0.00 5125.78 0.000 0.00 427.15 0.000
T20 120 - 100 4 1/2x3/8 0.00 5125.78 0.000 0.00 427.15 0.000
T23 60 - 40 5x3/8 0.00 6328.13 0.000 0.00 474.61 0.000

Top Guy Pull-Off Interaction Design Data


Section Elevation Size Ratio Ratio Ratio Comb. Allow. Criteria
No. Pu Mux Muy Stress Stress
ft φPn φMnx φMny Ratio Ratio
T2 480 - 460 4 1/2x3/8 0.070 0.000 0.000 0.070 1 1.050 4.8.1
T13 260 - 240 4 1/2x3/8 0.073 0.000 0.000 0.073 1 1.050 4.8.1
T17 180 - 160 4 1/2x3/8 0.072 0.000 0.000 0.072 1 1.050 4.8.1
T20 120 - 100 4 1/2x3/8 0.071 0.000 0.000 0.071 1 1.050 4.8.1
T23 60 - 40 5x3/8 0.051 0.000 0.000 0.051 1 1.050 4.8.1

1
Pu / φPn controls

Torque-Arm Top Design Data


Section Elevation Size L Lu Kl/r A Pu φPn Ratio
No. Pu
ft ft ft in2 lb lb φPn
T4 440 - 420 (963) C12x20.7 3'6-23/3 3'5-17/3 52.0 4.409 3013.01 191786.00 0.016
2'' 2''
T4 440 - 420 (964) C12x20.7 3'6-23/3 3'5-17/3 52.0 4.409 3219.10 191786.00 0.017
2'' 2''
T4 440 - 420 (967) C12x20.7 3'6-23/3 3'5-17/3 52.0 4.409 3208.69 191786.00 0.017
2'' 2''
T4 440 - 420 (968) C12x20.7 3'6-23/3 3'5-17/3 52.0 4.409 3168.73 191786.00 0.017
2'' 2''
T4 440 - 420 (971) C12x20.7 3'6-23/3 3'5-17/3 52.0 4.409 3004.23 191786.00 0.016
2'' 2''
Job Page
tnxTower Apex (BU 871394) 50 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Section Elevation Size L Lu Kl/r A Pu φPn Ratio


No. Pu
ft ft ft in2 lb lb φPn
T4 440 - 420 (972) C12x20.7 3'6-23/3 3'5-17/3 52.0 4.409 3169.72 191786.00 0.017
2'' 2''
T8 360 - 340 (975) C12x20.7 3'6-23/3 3'5-9/32' 51.7 4.409 2457.46 191786.00 0.013
2'' '
T8 360 - 340 (976) C12x20.7 3'6-23/3 3'5-9/32' 51.7 4.409 2524.63 191786.00 0.013
2'' '
T8 360 - 340 (979) C12x20.7 3'6-23/3 3'5-9/32' 51.7 4.409 2545.35 191786.00 0.013
2'' '
T8 360 - 340 (980) C12x20.7 3'6-23/3 3'5-9/32' 51.7 4.409 2526.62 191786.00 0.013
2'' '
T8 360 - 340 (983) C12x20.7 3'6-23/3 3'5-9/32' 51.7 4.409 2424.40 191786.00 0.013
2'' '
T8 360 - 340 (984) C12x20.7 3'6-23/3 3'5-9/32' 51.7 4.409 2470.78 191786.00 0.013
2'' '

Torque-Arm Top Bending Design Data


Section Elevation Size Mux φMnx Ratio Muy φMny Ratio
No. Mux Muy
ft lb-ft lb-ft φMnx lb-ft lb-ft φMny
T4 440 - 420 (963) C12x20.7 -31577.50 58050.00 0.544 -0.00 9423.00 0.000
T4 440 - 420 (964) C12x20.7 -31114.33 58050.00 0.536 -0.00 9423.00 0.000
T4 440 - 420 (967) C12x20.7 -31955.00 58050.00 0.550 0.00 9423.00 0.000
T4 440 - 420 (968) C12x20.7 -31582.42 58050.00 0.544 -0.00 9423.00 0.000
T4 440 - 420 (971) C12x20.7 -31906.50 58050.00 0.550 0.00 9423.00 0.000
T4 440 - 420 (972) C12x20.7 -31135.42 58050.00 0.536 -0.00 9423.00 0.000
T8 360 - 340 (975) C12x20.7 -27398.92 58050.00 0.472 -0.00 9423.00 0.000
T8 360 - 340 (976) C12x20.7 -26496.33 58050.00 0.456 -0.00 9423.00 0.000
T8 360 - 340 (979) C12x20.7 -27632.58 58050.00 0.476 0.00 9423.00 0.000
T8 360 - 340 (980) C12x20.7 -27398.42 58050.00 0.472 -0.00 9423.00 0.000
T8 360 - 340 (983) C12x20.7 -27569.42 58050.00 0.475 0.00 9423.00 0.000
T8 360 - 340 (984) C12x20.7 -26534.75 58050.00 0.457 -0.00 9423.00 0.000

Torque-Arm Top Interaction Design Data


Section Elevation Size Ratio Ratio Ratio Comb. Allow. Criteria
No. Pu Mux Muy Stress Stress
ft φPn φMnx φMny Ratio Ratio
T4 440 - 420 (963) C12x20.7 0.016 0.544 0.000 0.552 1.050 4.8.1
T4 440 - 420 (964) C12x20.7 0.017 0.536 0.000 0.544 1.050 4.8.1
T4 440 - 420 (967) C12x20.7 0.017 0.550 0.000 0.559 1.050 4.8.1
T4 440 - 420 (968) C12x20.7 0.017 0.544 0.000 0.552 1.050 4.8.1
T4 440 - 420 (971) C12x20.7 0.016 0.550 0.000 0.557 1.050 4.8.1
T4 440 - 420 (972) C12x20.7 0.017 0.536 0.000 0.545 1.050 4.8.1
T8 360 - 340 (975) C12x20.7 0.013 0.472 0.000 0.478 1.050 4.8.1
T8 360 - 340 (976) C12x20.7 0.013 0.456 0.000 0.463 1.050 4.8.1
T8 360 - 340 (979) C12x20.7 0.013 0.476 0.000 0.483 1.050 4.8.1
T8 360 - 340 (980) C12x20.7 0.013 0.472 0.000 0.479 1.050 4.8.1
T8 360 - 340 (983) C12x20.7 0.013 0.475 0.000 0.481 1.050 4.8.1
T8 360 - 340 (984) C12x20.7 0.013 0.457 0.000 0.464 1.050 4.8.1
Job Page
tnxTower Apex (BU 871394) 51 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Section Capacity Table


Section Elevation Component Size Critical P øPallow % Pass
No. ft Type Element lb lb Capacity Fail
T1 500 - 480 Leg ROHN 2 EH 1 -7959.61 46048.38 17.3 Pass
T2 480 - 460 Leg ROHN 2 EH 36 -14010.40 43855.60 31.9 Pass
T3 460 - 440 Leg ROHN 2 EH 67 -16410.60 46048.38 35.6 Pass
T4 440 - 420 Leg ROHN 2 EH 102 -34365.70 62906.76 54.6 Pass
T5 420 - 400 Leg ROHN 2.5 STD 159 -34595.00 61325.88 56.4 Pass
T6 400 - 380 Leg ROHN 2.5 STD 191 -33228.90 58405.60 56.9 Pass
T7 380 - 360 Leg ROHN 2.5 STD 223 -37214.00 61325.88 60.7 Pass
T8 360 - 340 Leg ROHN 2.5 STD 256 -53621.40 75218.43 71.3 Pass
T9 340 - 320 Leg ROHN 2.5 EH 313 -54085.40 79978.18 67.6 Pass
T10 320 - 300 Leg ROHN 2.5 EH 346 -53444.10 76169.70 70.2 Pass
T11 300 - 280 Leg ROHN 2.5 EH 379 -54166.40 76169.70 71.1 Pass
T12 280 - 260 Leg ROHN 2.5 EH 412 -54529.00 76169.70 71.6 Pass
T13 260 - 240 Leg ROHN 2.5 EH 445 -61292.50 76169.70 80.5 Pass
T14 240 - 220 Leg ROHN 2.5 EH 480 -67330.50 99127.24 67.9 Pass
T15 220 - 200 Leg ROHN 2.5 EH 537 -69720.70 99127.24 70.3 Pass
T16 200 - 180 Leg ROHN 2.5 EH 594 -71849.00 94406.90 76.1 Pass
T17 180 - 160 Leg 2.5 XH w/ 3 STD Half Sleeve Note 1 Note 1 Note 1 73.2 Pass
T18 160 - 140 Leg 2.5 XH w/ 3 STD Half Sleeve Note 1 Note 1 Note 1 69.6 Pass
T19 140 - 120 Leg 2.5 XH w/ 3 STD Half Sleeve Note 1 Note 1 Note 1 73.2 Pass
T20 120 - 100 Leg 2.5 XH w/ 3 STD Half Sleeve Note 1 Note 1 Note 1 77.9 Pass
T21 100 - 80 Leg Rohn 2.5 EH w/ L3x3x1/4 Note 1 Note 1 Note 1 78.7 Pass
T22 80 - 60 Leg Rohn 3 STD w/ L3x3x1/4 Note 1 Note 1 Note 1 80.1 Pass
T23 60 - 40 Leg Rohn 3 STD w/ L3x3x1/4 Note 1 Note 1 Note 1 83.2 Pass
T24 40 - 20 Leg Rohn 3 STD w/ L3x3x1/4 Note 1 Note 1 Note 1 84.2 Pass
T25 20 - 4.81771 Leg 3 STD w/ 3.5 STD Half Sleeve Note 1 Note 1 Note 1 67.4 Pass
T26 4.81771 - 0 Leg ROHN 3 X-STR 942 -96077.30 133855.00 71.8 Pass
T1 500 - 480 Diagonal ROHN 1.5 x 16GA 12 -2255.53 6157.30 36.6 Pass
T2 480 - 460 Diagonal ROHN 1.5 x 16GA 44 -1720.12 6157.30 27.9 Pass
T3 460 - 440 Diagonal ROHN 1.5 x 16GA 77 -2455.42 6157.30 39.9 Pass
T4 440 - 420 Diagonal ROHN 1.5 x 16GA 109 -2083.60 6157.30 33.8 Pass
36.0 (b)
T5 420 - 400 Diagonal ROHN 1.5 x 16GA 188 -1691.54 6241.33 27.1 Pass
27.1 (b)
T6 400 - 380 Diagonal ROHN 1.5 x 16GA 220 -776.82 6241.33 12.4 Pass
T7 380 - 360 Diagonal ROHN 1.5 x 16GA 233 -1625.30 6241.33 26.0 Pass
T8 360 - 340 Diagonal ROHN 1.5 x 16GA 267 -2577.54 6241.33 41.3 Pass
T9 340 - 320 Diagonal ROHN 1.5 x 16GA 344 -3007.65 6241.33 48.2 Pass
T10 320 - 300 Diagonal ROHN 1.5 x 16GA 377 -2062.10 6241.33 33.0 Pass
T11 300 - 280 Diagonal ROHN 1.5 x 16GA 388 -1736.03 6241.33 27.8 Pass
T12 280 - 260 Diagonal ROHN 1.5 x 16GA 421 -2317.72 6241.33 37.1 Pass
T13 260 - 240 Diagonal ROHN 1.5 x 16GA 476 -3693.79 6241.33 59.2 Pass
60.4 (b)
T14 240 - 220 Diagonal ROHN 1.5 x 16GA 532 -2028.06 6241.33 32.5 Pass
T15 220 - 200 Diagonal ROHN 1.5 x 16GA 589 -1198.79 6241.33 19.2 Pass
T16 200 - 180 Diagonal ROHN 1.5 x 16GA 604 -2988.96 6241.33 47.9 Pass
T17 180 - 160 Diagonal ROHN 1.5 x 16GA 659 -1092.74 6241.33 17.5 Pass
T18 160 - 140 Diagonal ROHN 1.5 x 16GA 692 -2619.40 6241.33 42.0 Pass
T19 140 - 120 Diagonal ROHN 1.5 x 16GA 725 -3676.50 6241.33 58.9 Pass
T20 120 - 100 Diagonal ROHN 1.5 x 16GA 772 -2091.45 6241.33 33.5 Pass
35.6 (b)
T21 100 - 80 Diagonal ROHN 1.5 x 16GA 811 -1794.64 6472.44 27.7 Pass
T22 80 - 60 Diagonal ROHN 1.5 x 16GA 824 -3008.01 6472.44 46.5 Pass
T23 60 - 40 Diagonal ROHN 1.5 x 16GA 874 -3037.35 6472.44 46.9 Pass
49.6 (b)
T24 40 - 20 Diagonal ROHN 1.5 x 16GA 910 -2689.29 6472.44 41.5 Pass
T25 20 - 4.81771 Diagonal ROHN 1.5 x 16GA 938 -2362.03 6430.43 36.7 Pass
T26 4.81771 - 0 Horizontal C14x2-3/8x3/16 (BP) 947 -146.04 110250.00 28.5 Pass
Job Page
tnxTower Apex (BU 871394) 52 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Section Elevation Component Size Critical P øPallow % Pass


No. ft Type Element lb lb Capacity Fail
T1 500 - 480 Top Girt ROHN 1.5 x 16GA 6 -202.97 7334.49 2.8 Pass
3.4 (b)
T2 480 - 460 Top Girt ROHN 1.5 x 16GA 38 591.88 10428.56 5.7 Pass
9.5 (b)
T3 460 - 440 Top Girt ROHN 1.5 x 16GA 71 -709.15 7334.49 9.7 Pass
11.0 (b)
T4 440 - 420 Top Girt ROHN 1.5 x 16GA 105 237.09 10428.56 2.3 Pass
3.8 (b)
T5 420 - 400 Top Girt ROHN 1.5 x 16GA 161 -624.68 7401.19 8.4 Pass
14.1 (b)
T6 400 - 380 Top Girt ROHN 1.5 x 16GA 193 306.44 10428.56 2.9 Pass
4.9 (b)
T7 380 - 360 Top Girt ROHN 1.5 x 16GA 228 305.91 10428.56 2.9 Pass
4.9 (b)
T8 360 - 340 Top Girt ROHN 1.5 x 16GA 260 370.60 9931.96 3.7 Pass
6.0 (b)
T9 340 - 320 Top Girt ROHN 1.5 x 16GA 317 -929.32 7401.19 12.6 Pass
20.1 (b)
T10 320 - 300 Top Girt ROHN 1.5 x 16GA 350 -539.49 7401.19 7.3 Pass
11.5 (b)
T11 300 - 280 Top Girt ROHN 1.5 x 16GA 383 383.55 10428.56 3.7 Pass
6.2 (b)
T12 280 - 260 Top Girt ROHN 1.5 x 16GA 415 -438.01 7401.19 5.9 Pass
9.6 (b)
T13 260 - 240 Top Girt ROHN 1.5 x 16GA 450 622.67 10428.56 6.0 Pass
10.0 (b)
T14 240 - 220 Top Girt ROHN 1.5 x 16GA 483 598.15 10428.56 5.7 Pass
9.6 (b)
T15 220 - 200 Top Girt ROHN 1.5 x 16GA 538 584.65 10428.56 5.6 Pass
9.4 (b)
T16 200 - 180 Top Girt ROHN 1.5 x 16GA 597 604.03 10428.56 5.8 Pass
9.7 (b)
T17 180 - 160 Top Girt ROHN 1.5 x 16GA 652 613.71 10428.56 5.9 Pass
9.9 (b)
T18 160 - 140 Top Girt ROHN 1.5 x 16GA 686 316.56 10428.56 3.0 Pass
5.1 (b)
T19 140 - 120 Top Girt ROHN 1.5 x 16GA 719 -609.16 7401.19 8.2 Pass
10.8 (b)
T20 120 - 100 Top Girt ROHN 1.5 x 16GA 752 600.53 10428.56 5.8 Pass
9.7 (b)
T21 100 - 80 Top Girt ROHN 1.5 x 16GA 784 469.26 10428.56 4.5 Pass
7.5 (b)
T22 80 - 60 Top Girt ROHN 1.5 x 16GA 818 494.15 10428.56 4.7 Pass
8.0 (b)
T23 60 - 40 Top Girt ROHN 1.5 x 16GA 851 437.71 10428.56 4.2 Pass
7.0 (b)
T24 40 - 20 Top Girt ROHN 1.5 x 16GA 883 612.23 10428.56 5.9 Pass
9.9 (b)
T25 20 - 4.81771 Top Girt ROHN 1.5 x 16GA 917 621.83 10428.56 6.0 Pass
10.0 (b)
T26 4.81771 - 0 Top Girt C14x2-3/8x3/16 (BP) 944 17918.20 111628.00 16.1 Pass
T1 500 - 480 Bottom Girt ROHN 1.5 x 16GA 8 -1149.35 7334.49 15.7 Pass
19.9 (b)
T2 480 - 460 Bottom Girt ROHN 1.5 x 16GA 42 -651.39 7334.49 8.9 Pass
10.8 (b)
T3 460 - 440 Bottom Girt ROHN 1.5 x 16GA 74 -955.69 7334.49 13.0 Pass
18.0 (b)
T4 440 - 420 Bottom Girt ROHN 1.5 x 16GA 107 -759.76 7334.49 10.4 Pass
12.2 (b)
T5 420 - 400 Bottom Girt ROHN 1.5 x 16GA 163 -248.16 7401.19 3.4 Pass
5.5 (b)
Job Page
tnxTower Apex (BU 871394) 53 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Section Elevation Component Size Critical P øPallow % Pass


No. ft Type Element lb lb Capacity Fail
T6 400 - 380 Bottom Girt ROHN 1.5 x 16GA 198 -183.66 7401.19 2.5 Pass
3.9 (b)
T7 380 - 360 Bottom Girt ROHN 1.5 x 16GA 230 -557.40 7401.19 7.5 Pass
10.3 (b)
T8 360 - 340 Bottom Girt ROHN 1.5 x 16GA 264 743.72 10428.56 7.1 Pass
12.0 (b)
T9 340 - 320 Bottom Girt ROHN 1.5 x 16GA 320 -626.98 7401.19 8.5 Pass
11.4 (b)
T10 320 - 300 Bottom Girt ROHN 1.5 x 16GA 353 -306.70 7401.19 4.1 Pass
6.2 (b)
T11 300 - 280 Bottom Girt ROHN 1.5 x 16GA 385 -445.64 7401.19 6.0 Pass
8.8 (b)
T12 280 - 260 Bottom Girt ROHN 1.5 x 16GA 418 -803.64 7401.19 10.9 Pass
16.0 (b)
T13 260 - 240 Bottom Girt ROHN 1.5 x 16GA 452 -1142.36 7401.19 15.4 Pass
17.7 (b)
T14 240 - 220 Bottom Girt ROHN 1.5 x 16GA 486 596.73 10428.56 5.7 Pass
9.6 (b)
T15 220 - 200 Bottom Girt ROHN 1.5 x 16GA 543 568.27 9931.96 5.7 Pass
9.1 (b)
T16 200 - 180 Bottom Girt ROHN 1.5 x 16GA 600 813.88 10428.56 7.8 Pass
13.1 (b)
T17 180 - 160 Bottom Girt ROHN 1.5 x 16GA 656 325.46 10428.56 3.1 Pass
5.2 (b)
T18 160 - 140 Bottom Girt ROHN 1.5 x 16GA 689 720.99 10428.56 6.9 Pass
11.6 (b)
T19 140 - 120 Bottom Girt ROHN 1.5 x 16GA 722 1475.40 10428.56 14.1 Pass
23.7 (b)
T20 120 - 100 Bottom Girt ROHN 1.5 x 16GA 754 530.10 10428.56 5.1 Pass
8.5 (b)
T21 100 - 80 Bottom Girt ROHN 1.5 x 16GA 788 430.39 10428.56 4.1 Pass
6.9 (b)
T22 80 - 60 Bottom Girt ROHN 1.5 x 16GA 821 961.22 10428.56 9.2 Pass
15.5 (b)
T23 60 - 40 Bottom Girt ROHN 1.5 x 16GA 853 638.45 10428.56 6.1 Pass
10.3 (b)
T24 40 - 20 Bottom Girt ROHN 1.5 x 16GA 888 580.11 10428.56 5.6 Pass
9.3 (b)
T25 20 - 4.81771 Bottom Girt ROHN 1.5 x 16GA 920 1429.89 9931.96 14.4 Pass
23.0 (b)
T2 480 - 460 Guy A@479.385 5/8 960 12779.10 26711.49 47.8 Pass
T4 440 - 420 Guy A@422.523 9/16 969 11088.40 22049.58 50.3 Pass
T8 360 - 340 Guy A@342.523 9/16 981 9427.86 22049.58 42.8 Pass
T13 260 - 240 Guy A@259.385 9/16 990 10401.10 22049.58 47.2 Pass
T17 180 - 160 Guy A@179.385 9/16 996 14246.80 22049.58 64.6 Pass
T20 120 - 100 Guy A@119.385 1/2 1002 10882.90 16946.68 64.2 Pass
T23 60 - 40 Guy A@59.3854 7/16 1008 6791.60 13103.75 51.8 Pass
T2 480 - 460 Guy B@479.385 5/8 959 13015.40 26711.49 48.7 Pass
T4 440 - 420 Guy B@422.523 9/16 966 11359.20 22049.58 51.5 Pass
T8 360 - 340 Guy B@342.523 9/16 978 9724.05 22049.58 44.1 Pass
T13 260 - 240 Guy B@259.385 9/16 989 10751.20 22049.58 48.8 Pass
T17 180 - 160 Guy B@179.385 9/16 995 13774.40 22049.58 62.5 Pass
T20 120 - 100 Guy B@119.385 1/2 1001 10180.90 16946.68 60.1 Pass
T23 60 - 40 Guy B@59.3854 7/16 1007 6303.27 13103.75 48.1 Pass
T2 480 - 460 Guy C@479.385 5/8 955 12945.50 26711.49 48.5 Pass
T4 440 - 420 Guy C@422.523 9/16 961 11279.20 22049.58 51.2 Pass
T8 360 - 340 Guy C@342.523 9/16 973 9659.23 22049.58 43.8 Pass
T13 260 - 240 Guy C@259.385 9/16 985 10766.50 22049.58 48.8 Pass
T17 180 - 160 Guy C@179.385 9/16 991 13720.40 22049.58 62.2 Pass
T20 120 - 100 Guy C@119.385 1/2 997 10058.30 16946.68 59.4 Pass
T23 60 - 40 Guy C@59.3854 7/16 1003 6217.06 13103.75 47.4 Pass
Job Page
tnxTower Apex (BU 871394) 54 of 54
Project Date
Tower Engineering
Professionals TEP No. 33537.193933 11:10:01 11/02/18
326 Tryon Road
Raleigh, NC 27603 Client Designed by
Phone: (919) 661-6351 Crown Castle jbalk
FAX: (919) 661-6350

Section Elevation Component Size Critical P øPallow % Pass


No. ft Type Element lb lb Capacity Fail
T2 480 - 460 Top Guy 4 1/2x3/8 957 3801.31 57408.75 6.6 Pass
Pull-Off@479.385 9.1 (b)
T13 260 - 240 Top Guy 4 1/2x3/8 988 3999.04 57408.75 7.0 Pass
Pull-Off@259.385 9.6 (b)
T17 180 - 160 Top Guy 4 1/2x3/8 992 3941.50 57408.75 6.9 Pass
Pull-Off@179.385 9.4 (b)
T20 120 - 100 Top Guy 4 1/2x3/8 999 3856.86 57408.75 6.7 Pass
Pull-Off@119.385 9.2 (b)
T23 60 - 40 Top Guy 5x3/8 1005 3123.51 63787.50 4.9 Pass
Pull-Off@59.3854 7.5 (b)
T4 440 - 420 Torque Arm C12x20.7 967 3208.69 201375.29 53.2 Pass
Top@422.523
T8 360 - 340 Torque Arm C12x20.7 979 2545.35 201375.29 46.0 Pass
Top@342.523
Summary
Leg (T24) 84.2 Pass
Diagonal 60.4 Pass
(T13)
Horizontal 28.5 Pass
(T26)
Top Girt 20.1 Pass
(T9)
Bottom Girt 23.7 Pass
(T19)
Guy A (T17) 64.6 Pass
Guy B (T17) 62.5 Pass
Guy C (T17) 62.2 Pass
Top Guy 9.6 Pass
Pull-Off
(T13)
Torque Arm 53.2 Pass
Top (T4)
Bolt Checks 60.4 Pass
Rating = 84.2 Pass
Notes:
1) See additional documentation in “Appendix C - Additional Calculations” for calculations supporting the % capacity listed.

Program Version 8.0.4.0 - 8/15/2018 File:C:/Users/jbalk/Desktop/Work In Progress/Week of 10-29-2018/33537/P-163302_L-193933_871394_Apex_Structural


Analysis/tnxTower/871394_LC5.eri
November 2, 2018
500-ft Guyed Tower Structural Analysis Report CCI BU No 871394
TEP Project Number 33537.193933, Order 464886, Revision 0 Page 12

APPENDIX B

BASE LEVEL DRAWING

tnxTower Report - version 8.0.4.0


November 2, 2018
500-ft Guyed Tower Structural Analysis Report CCI BU No 871394
TEP Project Number 33537.193933, Order 464886, Revision 0 Page 13

APPENDIX C

ADDITIONAL CALCULATIONS

tnxTower Report - version 8.0.4.0


ASCE 7 Hazards Report
Address: Standard: ASCE/SEI 7-10 Elevation: 479.01 ft (NAVD 88)
No Address at This Risk Category: II Latitude: 35.731111
Location
Soil Class: D - Stiff Soil Longitude: -78.837806

Wind
Results:
Wind Speed: 115 Vmph
10-year MRI 76 Vmph
25-year MRI 84 Vmph
50-year MRI 90 Vmph
100-year MRI 96 Vmph
Data Source: ASCE/SEI 7-10, Fig. 26.5-1A and Figs. CC-1–CC-4, incorporating errata of
March 12, 2014
Date Accessed: Mon Oct 29 2018

Value provided is 3-second gust wind speeds at 33 ft above ground for Exposure C Category, based on linear
interpolation between contours. Wind speeds are interpolated in accordance with the 7-10 Standard. Wind speeds
correspond to approximately a 7% probability of exceedance in 50 years (annual exceedance probability =
0.00143, MRI = 700 years).

Mountainous terrain, gorges, ocean promontories, and special wind regions should be examined for unusual wind
conditions.

https://asce7hazardtool.online/ Page 1 of 3 Mon Oct 29 2018


Seismic

Site Soil Class: D - Stiff Soil


Results:

SS : 0.162 S DS : 0.172
S1 : 0.079 S D1 : 0.127
Fa : 1.600 TL : 8.000
Fv : 2.400 PGA : 0.076
S MS : 0.259 PGA M : 0.122
S M1 : 0.191 F PGA : 1.600
Ie : 1
Seismic Design Category B

MCER Response Spectrum Design Response Spectrum

Sa (g) vs T(s) Sa (g) vs T(s)

Data Accessed: Mon Oct 29 2018


Date Source: USGS Seismic Design Maps based on ASCE/SEI 7-10, incorporating
Supplement 1 and errata of March 31, 2013, and ASCE/SEI 7-10 Table 1.5-2.
Additional data for site-specific ground motion procedures in accordance with
ASCE/SEI 7-10 Ch. 21 are available from USGS.

https://asce7hazardtool.online/ Page 2 of 3 Mon Oct 29 2018


Ice
Results:
Ice Thickness: 0.75 in.
Concurrent Temperature: 15 F
Gust Speed: 30 mph
Data Source: Standard ASCE/SEI 7-10, Figs. 10-2 through 10-8
Date Accessed: Mon Oct 29 2018
Ice thicknesses on structures in exposed locations at elevations higher than the surrounding terrain and in valleys
and gorges may exceed the mapped values.
Values provided are equivalent radial ice thicknesses due to freezing rain with concurrent 3-second gust speeds,
for a 50-year mean recurrence interval, and temperatures concurrent with ice thicknesses due to freezing rain.
Thicknesses for ice accretions caused by other sources shall be obtained from local meteorological studies. Ice
thicknesses in exposed locations at elevations higher than the surrounding terrain and in valleys and gorges may
exceed the mapped values.

The ASCE 7 Hazard Tool is provided for your convenience, for informational purposes only, and is provided “as is” and without warranties of
any kind. The location data included herein has been obtained from information developed, produced, and maintained by third party providers;
or has been extrapolated from maps incorporated in the ASCE 7 standard. While ASCE has made every effort to use data obtained from
reliable sources or methodologies, ASCE does not make any representations or warranties as to the accuracy, completeness, reliability,
currency, or quality of any data provided herein. Any third-party links provided by this Tool should not be construed as an endorsement,
affiliation, relationship, or sponsorship of such third-party content by or from ASCE.

ASCE does not intend, nor should anyone interpret, the results provided by this Tool to replace the sound judgment of a competent
professional, having knowledge and experience in the appropriate field(s) of practice, nor to substitute for the standard of care required of such
professionals in interpreting and applying the contents of this Tool or the ASCE 7 standard.

In using this Tool, you expressly assume all risks associated with your use. Under no circumstances shall ASCE or its officers, directors,
employees, members, affiliates, or agents be liable to you or any other person for any direct, indirect, special, incidental, or consequential
damages arising from or related to your use of, or reliance on, the Tool or any information obtained therein. To the fullest extent permitted by
law, you agree to release and hold harmless ASCE from any and all liability of any nature arising out of or resulting from any use of data
provided by the ASCE 7 Hazard Tool.

https://asce7hazardtool.online/ Page 3 of 3 Mon Oct 29 2018


Project Name: Apex Engineer: EBS
Project Number: TEP No. 33537.193933 Check: JWB
Client Site Number: BU 871394 Date: 11/2/2018
Elevation: 160 - 180 CODE: TIA-H

Grouted/Un-Grouted Pipe Leg + Half Sleeve R/F

Φc = 0.90 - LRFD strength reduction factor (compression) Mast St.: 1.00 - from tnxTower

Φt = 0.90 - LRFD strength reduction factor (tension)

Φw = 0.75 - LRFD strength reduction factor (weld shear)

Φv = 0.75 - LRFD strength reduction factor (shear)

Input - Loads Quick Check

Pinitial: 27.6 kips - force from initial load (no wind) Weld Size: OK
Pwind: 77.8 kips - force due to final loading including reinforcement Weld Connection: 15.8%
Tu: 0.0 kips - maximum load on leg Crushing Check: 73.2%
Leg Comp. Check: 58.2%
Input - Tower Leg 2.5 XS Sleeve Check: 35.6%
Built-up Check: 68.9%
K: 2.00 - effective length factor for leg Slenderness Check: OK
Lu : 2.41 ft - unbraced length of tower leg Leg Tension Check: 0.0%
Fy_leg: 50.00 ksi - minimum specified yield strength of tower leg

Fu_leg: 65.00 ksi - minimum specified ultimate strength of tower leg

r: 0.92 in - minimum radius of gyration of tower leg


Aleg: 2.25 in2 - area of tower leg
Di: 2.32 in - inside diameter of tower leg
tleg: 0.28 in - thickness of tower leg

f`c: 0.00 ksi - minimum specified compressive strength of grout (If ungrouted enter 0)

Input - Sleeve R/F 3 STD Gap Check: OK

Fy_sleeve: 46.00 ksi - minimum specified yield strength of sleeve r/f


Fu_sleeve: 62.00 ksi - minimum specified ultimate strength of sleeve r/f
rx_sleeve: 0.51 in - minimum radius of gyration of sleeve r/f about the x-axis
ry_sleeve: 1.16 in - minimum radius of gyration of sleeve r/f about the y-axis
Asleeve: 1.11 in2 - area of sleeve r/f
tsleeve: 0.22 in - thickness of tower leg
Termination: Connected to Leg ONLY

Input - Sleeve Connection to Leg

a: 12.00 in - spacing of connectors connecting the sleeve to the leg


D: 3.00 - weld size for the weld connecting the sleeve to the leg (unit = # of 16ths)
Length //: 12.00 in - length of weld on each side of the leg at the termination
Length ⊥: 0.00 in - length of weld at the bottom/top of the leg sleeve at termination (πD/2)
No: 2.00 - number of longitudinal welds per end of the leg (typically near side & far side, so 2)
FEXX: 70.00 ksi - weld electrode classification

Width: 3.50 in - maximum width of the built-up leg


Gap: 6.00 in - length of leg considered for crushing

Input - Built-up Leg Section 2.5 XS w/3 STD Half Sleeve

rx_bu: 0.93 in - minimum radius of gyration of the built-up section about the x-axis

ry_bu: 1.01 in - minimum radius of gyration of the built-up section about the y-axis

Input - Grouted Leg


Ec: 0 ksi - Modulus of Elasticity of Grout
E_leg: 29,000 ksi - Modulus of Elasticity of Leg
E_sleeve: 29,000 ksi - Modulus of Elasticity of Sleeve

C:\Users\jbalk\Desktop\Work In Progress\Week of 10-29-2018\33537\P-163302_L-193933_871394_Apex_Structural Analysis\Add Calcs\Leg Mods\Built-Up Leg Calculations - 160-180


Project Name: Apex Engineer: EBS
Project Number: TEP No. 33537.193933 Check: JWB
Client Site Number: BU 871394 Date: 11/2/2018
Elevation: 140 - 160 CODE: TIA-H

Grouted/Un-Grouted Pipe Leg + Half Sleeve R/F

Φc = 0.90 - LRFD strength reduction factor (compression) Mast St.: 1.00 - from tnxTower

Φt = 0.90 - LRFD strength reduction factor (tension)

Φw = 0.75 - LRFD strength reduction factor (weld shear)

Φv = 0.75 - LRFD strength reduction factor (shear)

Input - Loads Quick Check

Pinitial: 27.9 kips - force from initial load (no wind) Weld Size: OK
Pwind: 78.5 kips - force due to final loading including reinforcement Weld Connection: 11.8%
Tu: 0.0 kips - maximum load on leg Crushing Check: 58.0%
Leg Comp. Check: 58.7%
Input - Tower Leg 2.5 XS Sleeve Check: 35.9%
Built-up Check: 69.6%
K: 2.00 - effective length factor for leg Slenderness Check: OK
Lu : 2.41 ft - unbraced length of tower leg Leg Tension Check: 0.0%
Fy_leg: 50.00 ksi - minimum specified yield strength of tower leg

Fu_leg: 65.00 ksi - minimum specified ultimate strength of tower leg

r: 0.92 in - minimum radius of gyration of tower leg


Aleg: 2.25 in2 - area of tower leg
Di: 2.32 in - inside diameter of tower leg
tleg: 0.28 in - thickness of tower leg

f`c: 0.00 ksi - minimum specified compressive strength of grout (If ungrouted enter 0)

Input - Sleeve R/F 3 STD Gap Check: OK

Fy_sleeve: 46.00 ksi - minimum specified yield strength of sleeve r/f


Fu_sleeve: 62.00 ksi - minimum specified ultimate strength of sleeve r/f
rx_sleeve: 0.51 in - minimum radius of gyration of sleeve r/f about the x-axis
ry_sleeve: 1.16 in - minimum radius of gyration of sleeve r/f about the y-axis
Asleeve: 1.11 in2 - area of sleeve r/f
tsleeve: 0.22 in - thickness of tower leg
Termination: Connected to Flange

Input - Sleeve Connection to Leg

a: 12.00 in - spacing of connectors connecting the sleeve to the leg


D: 3.00 - weld size for the weld connecting the sleeve to the leg (unit = # of 16ths)
Length //: 12.00 in - length of weld on each side of the leg at the termination
Length ⊥: 5.50 in - length of weld at the bottom/top of the leg sleeve at termination (πD/2)
No: 2.00 - number of longitudinal welds per end of the leg (typically near side & far side, so 2)
FEXX: 70.00 ksi - weld electrode classification

Width: 3.50 in - maximum width of the built-up leg


Gap: 0.00 in - length of leg considered for crushing

Input - Built-up Leg Section 2.5 XS w/3 STD Half Sleeve

rx_bu: 0.93 in - minimum radius of gyration of the built-up section about the x-axis

ry_bu: 1.01 in - minimum radius of gyration of the built-up section about the y-axis

Input - Grouted Leg


Ec: 0 ksi - Modulus of Elasticity of Grout
E_leg: 29,000 ksi - Modulus of Elasticity of Leg
E_sleeve: 29,000 ksi - Modulus of Elasticity of Sleeve

C:\Users\jbalk\Desktop\Work In Progress\Week of 10-29-2018\33537\P-163302_L-193933_871394_Apex_Structural Analysis\Add Calcs\Leg Mods\Built-Up Leg Calculations - 140-160


Project Name: Apex Engineer: EBS
Project Number: TEP No. 33537.193933 Check: JWB
Client Site Number: BU 871394 Date: 11/2/2018
Elevation: 120 - 140 CODE: TIA-H

Grouted/Un-Grouted Pipe Leg + Half Sleeve R/F

Φc = 0.90 - LRFD strength reduction factor (compression) Mast St.: 1.00 - from tnxTower

Φt = 0.90 - LRFD strength reduction factor (tension)

Φw = 0.75 - LRFD strength reduction factor (weld shear)

Φv = 0.75 - LRFD strength reduction factor (shear)

Input - Loads Quick Check

Pinitial: 28.1 kips - force from initial load (no wind) Weld Size: OK
Pwind: 82.5 kips - force due to final loading including reinforcement Weld Connection: 12.7%
T u: 0.0 kips - maximum load on leg Crushing Check: 60.6%
Leg Comp. Check: 61.3%
Input - Tower Leg 2.5 XS Sleeve Check: 38.6%
Built-up Check: 73.2%
K: 2.00 - effective length factor for leg Slenderness Check: OK
Lu: 2.41 ft - unbraced length of tower leg Leg Tension Check: 0.0%
Fy_leg: 50.00 ksi - minimum specified yield strength of tower leg

Fu_leg: 65.00 ksi - minimum specified ultimate strength of tower leg

r: 0.92 in - minimum radius of gyration of tower leg

Aleg: 2.25 in2 - area of tower leg


Di: 2.32 in - inside diameter of tower leg

tleg: 0.28 in - thickness of tower leg

f`c: 0.00 ksi - minimum specified compressive strength of grout (If ungrouted enter 0)

Input - Sleeve R/F 3 STD Gap Check: OK

Fy_sleeve: 46.00 ksi - minimum specified yield strength of sleeve r/f


Fu_sleeve: 62.00 ksi - minimum specified ultimate strength of sleeve r/f
rx_sleeve: 0.51 in - minimum radius of gyration of sleeve r/f about the x-axis
ry_sleeve: 1.16 in - minimum radius of gyration of sleeve r/f about the y-axis
Asleeve: 1.11 in2 - area of sleeve r/f
tsleeve: 0.22 in - thickness of tower leg
Termination: Connected to Flange

Input - Sleeve Connection to Leg

a: 12.00 in - spacing of connectors connecting the sleeve to the leg


D: 3.00 - weld size for the weld connecting the sleeve to the leg (unit = # of 16ths)
Length //: 12.00 in - length of weld on each side of the leg at the termination
Length ⊥: 5.50 in - length of weld at the bottom/top of the leg sleeve at termination ( πD/2)
No: 2.00 - number of longitudinal welds per end of the leg (typically near side & far side, so 2)

FEXX: 70.00 ksi - weld electrode classification


Width: 3.50 in - maximum width of the built-up leg
Gap: 0.00 in - length of leg considered for crushing

Input - Built-up Leg Section 2.5 XS w/3 STD Half Sleeve

rx_bu: 0.93 in - minimum radius of gyration of the built-up section about the x-axis

ry_bu: 1.01 in - minimum radius of gyration of the built-up section about the y-axis

Input - Grouted Leg


Ec: 0 ksi - Modulus of Elasticity of Grout
E_leg: 29,000 ksi - Modulus of Elasticity of Leg
E_sleeve: 29,000 ksi - Modulus of Elasticity of Sleeve

C:\Users\jbalk\Desktop\Work In Progress\Week of 10-29-2018\33537\P-163302_L-193933_871394_Apex_Structural Analysis\Add Calcs\Leg Mods\Built-Up Leg Calculations - 120-140


Project Name: Apex Design: EBS
Project Number: TEP No. 33537.193933 Check: JWB
Client Site Number: BU 871394 Date: 11/2/18

Elevation: 120-ft

Knife plate connection design:

Pwind: 82.50 kips Existing Legs: Pipe 2.5 XS


Pflange jump, each: 41.25 kips Area: 2.250 in^2
Tu: 0.00 kips
Reinforcing Half Sleeve: Pipe 3 STD
Tower Leg Properties: Area: 1.110 in^2
Pipe Diameter: 2.875 in Fy: 42 ksi
Fy: 50.0 ksi Fu: 58 ksi

Knife Plate Properties:


Width: 4.00 in
Thickness: 0.50 in
Area: 2.00 in
Span: 9.0 in
Plate Eccentricity 5.5 in
Fy: 36.0 ksi
Fu: 58.0 ksi
K: 1.0
# of knife plates: 2

Design Calculations:

1) Check Knife Plate in Tension

ФTn: 64.80 kips - allowable tension in plate 0.0%

2) Check Stress on Knife Plate subject to Bending

rx: 1.155 in

ry: 0.144 in

KLr_x: 7.79
KLr_y: 62.35
Fe: 73.62 ksi
Fcr: 29.34 ksi
Fa: 29.34 ksi
ФPn: 52.81 kips 74.4%

3) Check Plate Weld to Leg

e: 5.5 in
D: 3 (16ths)
l: 12 in
a: 0.458
C: 2.073
Φ: 0.75
ΦRn: 55.96 kips 70.2%

4) Check Base Metal Weld Check Leg-Stiffener

FyBM Leg: 50 ksi FyBM Stiffener: 36 ksi

FuBM Leg: 65 ksi FuBM Stiffener: 58 ksi

tBM Leg: 0.276 in tBM Stiffener: 0.50 in

ABM Leg: 3.312 in2 ABM Stiffener: 6 in2

ΦVy: 1.00
ΦVr: 0.75
ΦRn: 96.88 kips 40.6%
Project Name: Apex Engineer: EBS
Project Number: TEP No. 33537.193933 Check: JWB
Client Site Number: BU 871394 Date: 11/2/2018
Elevation: 100 - 120 CODE: TIA-H

Grouted/Un-Grouted Pipe Leg + Half Sleeve R/F

Φc = 0.90 - LRFD strength reduction factor (compression) Mast St.: 1.00 - from tnxTower

Φt = 0.90 - LRFD strength reduction factor (tension)

Φw = 0.75 - LRFD strength reduction factor (weld shear)

Φv = 0.75 - LRFD strength reduction factor (shear)

Input - Loads Quick Check

Pinitial: 30.5 kips - force from initial load (no wind) Weld Size: OK
Pwind: 82.9 kips - force due to final loading including reinforcement Weld Connection: 16.5%
Tu: 0.0 kips - maximum load on leg Crushing Check: 77.9%
Leg Comp. Check: 62.3%
Input - Tower Leg 2.5 XS Sleeve Check: 37.2%
Built-up Check: 73.5%
K: 2.00 - effective length factor for leg Slenderness Check: OK
Lu : 2.41 ft - unbraced length of tower leg Leg Tension Check: 0.0%
Fy_leg: 50.00 ksi - minimum specified yield strength of tower leg

Fu_leg: 65.00 ksi - minimum specified ultimate strength of tower leg

r: 0.92 in - minimum radius of gyration of tower leg


Aleg: 2.25 in2 - area of tower leg
Di: 2.32 in - inside diameter of tower leg
tleg: 0.28 in - thickness of tower leg

f`c: 0.00 ksi - minimum specified compressive strength of grout (If ungrouted enter 0)

Input - Sleeve R/F 3 STD Gap Check: OK

Fy_sleeve: 46.00 ksi - minimum specified yield strength of sleeve r/f


Fu_sleeve: 62.00 ksi - minimum specified ultimate strength of sleeve r/f
rx_sleeve: 0.51 in - minimum radius of gyration of sleeve r/f about the x-axis
ry_sleeve: 1.16 in - minimum radius of gyration of sleeve r/f about the y-axis
Asleeve: 1.11 in2 - area of sleeve r/f
tsleeve: 0.22 in - thickness of tower leg
Termination: Connected to Leg ONLY

Input - Sleeve Connection to Leg

a: 12.00 in - spacing of connectors connecting the sleeve to the leg


D: 3.00 - weld size for the weld connecting the sleeve to the leg (unit = # of 16ths)
Length //: 12.00 in - length of weld on each side of the leg at the termination
Length ⊥: 0.00 in - length of weld at the bottom/top of the leg sleeve at termination (πD/2)
No: 2.00 - number of longitudinal welds per end of the leg (typically near side & far side, so 2)
FEXX: 70.00 ksi - weld electrode classification

Width: 3.50 in - maximum width of the built-up leg


Gap: 0.50 in - length of leg considered for crushing

Input - Built-up Leg Section 2.5 XS w/3 STD Half Sleeve

rx_bu: 0.93 in - minimum radius of gyration of the built-up section about the x-axis

ry_bu: 1.01 in - minimum radius of gyration of the built-up section about the y-axis

Input - Grouted Leg


Ec: 0 ksi - Modulus of Elasticity of Grout
E_leg: 29,000 ksi - Modulus of Elasticity of Leg
E_sleeve: 29,000 ksi - Modulus of Elasticity of Sleeve

C:\Users\jbalk\Desktop\Work In Progress\Week of 10-29-2018\33537\P-163302_L-193933_871394_Apex_Structural Analysis\Add Calcs\Leg Mods\Built-Up Leg Calculations - 100-120


Project Name: Apex Engineer: EBS
Project Number: TEP No. 33537.193933 Check: JWB
Client Site Number: BU 871394 Date: 11/2/2018
Elevation: 80 - 100 CODE: TIA-H

Grouted/Un-Grouted Pipe Leg + Half Sleeve R/F

Φc = 0.90 - LRFD strength reduction factor (compression) Mast St.: 1.00 - from tnxTower

Φt = 0.90 - LRFD strength reduction factor (tension)

Φw = 0.75 - LRFD strength reduction factor (weld shear)

Φv = 0.75 - LRFD strength reduction factor (shear)

Input - Loads Quick Check

Pinitial: 31.1 kips - force from initial load (no wind) Weld Size: OK
Pwind: 83.8 kips - force due to final loading including reinforcement Weld Connection: 9.4%
Tu: 0.0 kips - maximum load on leg Crushing Check: 78.7%
Leg Comp. Check: 60.0%
Input - Tower Leg 2.5 XS Sleeve Check: 31.0%
Built-up Check: 62.7%
K: 2.00 - effective length factor for leg Slenderness Check: OK
Lu : 2.41 ft - unbraced length of tower leg Leg Tension Check: 0.0%
Fy_leg: 50.00 ksi - minimum specified yield strength of tower leg

Fu_leg: 65.00 ksi - minimum specified ultimate strength of tower leg

r: 0.92 in - minimum radius of gyration of tower leg


Aleg: 2.25 in2 - area of tower leg
Di: 2.32 in - inside diameter of tower leg
tleg: 0.28 in - thickness of tower leg

f`c: 0.00 ksi - minimum specified compressive strength of grout (If ungrouted enter 0)

Input - Sleeve R/F L3x3x1/4 Gap Check: NG

Fy_sleeve: 50.00 ksi - minimum specified yield strength of sleeve r/f


Fu_sleeve: 65.00 ksi - minimum specified ultimate strength of sleeve r/f
rx_sleeve: 0.59 in - minimum radius of gyration of sleeve r/f about the x-axis
ry_sleeve: 1.15 in - minimum radius of gyration of sleeve r/f about the y-axis
Asleeve: 1.45 in2 - area of sleeve r/f
tsleeve: 0.00 in - thickness of tower leg
Termination: Connected to Leg ONLY

Input - Sleeve Connection to Leg

a: 12.00 in - spacing of connectors connecting the sleeve to the leg


D: 5.00 - weld size for the weld connecting the sleeve to the leg (unit = # of 16ths)
Length //: 15.00 in - length of weld on each side of the leg at the termination
Length ⊥: 0.00 in - length of weld at the bottom/top of the leg sleeve at termination (πD/2)
No: 2.00 - number of longitudinal welds per end of the leg (typically near side & far side, so 2)
FEXX: 70.00 ksi - weld electrode classification

Width: 0.00 in - maximum width of the built-up leg


Gap: 0.50 in - length of leg considered for crushing

Input - Built-up Leg Section 2.5 XS w/L3x3x1/4 Half Sleeve

rx_bu: 1.01 in - minimum radius of gyration of the built-up section about the x-axis

ry_bu: 1.02 in - minimum radius of gyration of the built-up section about the y-axis

Input - Grouted Leg


Ec: 0 ksi - Modulus of Elasticity of Grout
E_leg: 29,000 ksi - Modulus of Elasticity of Leg
E_sleeve: 29,000 ksi - Modulus of Elasticity of Sleeve

C:\Users\jbalk\Desktop\Work In Progress\Week of 10-29-2018\33537\P-163302_L-193933_871394_Apex_Structural Analysis\Add Calcs\Leg Mods\Built-Up Leg Calculations - 80-100


Project Name: Apex Engineer: EBS
Project Number: TEP No. 33537.193933 Check: JWB
Client Site Number: BU 871394 Date: 11/2/2018
Elevation: 60 - 80 CODE: TIA-H

Grouted/Un-Grouted Pipe Leg + Half Sleeve R/F

Φc = 0.90 - LRFD strength reduction factor (compression) Mast St.: 1.00 - from tnxTower

Φt = 0.90 - LRFD strength reduction factor (tension)

Φw = 0.75 - LRFD strength reduction factor (weld shear)

Φv = 0.75 - LRFD strength reduction factor (shear)

Input - Loads Quick Check

Pinitial: 31.6 kips - force from initial load (no wind) Weld Size: OK
Pwind: 84.4 kips - force due to final loading including reinforcement Weld Connection: 9.5%
Tu: 0.0 kips - maximum load on leg Crushing Check: 80.1%
Leg Comp. Check: 60.8%
Input - Tower Leg 3 STD Sleeve Check: 31.3%
Built-up Check: 58.3%
K: 2.00 - effective length factor for leg Slenderness Check: OK
Lu : 2.41 ft - unbraced length of tower leg Leg Tension Check: 0.0%
Fy_leg: 50.00 ksi - minimum specified yield strength of tower leg

Fu_leg: 65.00 ksi - minimum specified ultimate strength of tower leg

r: 1.16 in - minimum radius of gyration of tower leg


Aleg: 2.23 in2 - area of tower leg
Di: 3.07 in - inside diameter of tower leg
tleg: 0.22 in - thickness of tower leg

f`c: 0.00 ksi - minimum specified compressive strength of grout (If ungrouted enter 0)

Input - Sleeve R/F L3x3x1/4 Gap Check: NG

Fy_sleeve: 50.00 ksi - minimum specified yield strength of sleeve r/f


Fu_sleeve: 65.00 ksi - minimum specified ultimate strength of sleeve r/f
rx_sleeve: 0.59 in - minimum radius of gyration of sleeve r/f about the x-axis
ry_sleeve: 1.15 in - minimum radius of gyration of sleeve r/f about the y-axis
Asleeve: 1.45 in2 - area of sleeve r/f
tsleeve: 0.00 in - thickness of tower leg
Termination: Connected to Leg ONLY

Input - Sleeve Connection to Leg

a: 12.00 in - spacing of connectors connecting the sleeve to the leg


D: 5.00 - weld size for the weld connecting the sleeve to the leg (unit = # of 16ths)
Length //: 15.00 in - length of weld on each side of the leg at the termination
Length ⊥: 0.00 in - length of weld at the bottom/top of the leg sleeve at termination (πD/2)
No: 2.00 - number of longitudinal welds per end of the leg (typically near side & far side, so 2)
FEXX: 70.00 ksi - weld electrode classification

Width: 0.00 in - maximum width of the built-up leg


Gap: 0.50 in - length of leg considered for crushing

Input - Built-up Leg Section 3 STD w/L3x3x1/4 Half Sleeve

rx_bu: 1.27 in - minimum radius of gyration of the built-up section about the x-axis

ry_bu: 1.16 in - minimum radius of gyration of the built-up section about the y-axis

Input - Grouted Leg


Ec: 0 ksi - Modulus of Elasticity of Grout
E_leg: 29,000 ksi - Modulus of Elasticity of Leg
E_sleeve: 29,000 ksi - Modulus of Elasticity of Sleeve

C:\Users\jbalk\Desktop\Work In Progress\Week of 10-29-2018\33537\P-163302_L-193933_871394_Apex_Structural Analysis\Add Calcs\Leg Mods\Built-Up Leg Calculations - 60-80


Project Name: Apex Engineer: EBS
Project Number: TEP No. 33537.193933 Check: JWB
Client Site Number: BU 871394 Date: 11/2/2018
Elevation: 40 - 60 CODE: TIA-H

Grouted/Un-Grouted Pipe Leg + Half Sleeve R/F

Φc = 0.90 - LRFD strength reduction factor (compression) Mast St.: 1.00 - from tnxTower

Φt = 0.90 - LRFD strength reduction factor (tension)

Φw = 0.75 - LRFD strength reduction factor (weld shear)

Φv = 0.75 - LRFD strength reduction factor (shear)

Input - Loads Quick Check

Pinitial: 33.2 kips - force from initial load (no wind) Weld Size: OK
Pwind: 87.6 kips - force due to final loading including reinforcement Weld Connection: 9.8%
Tu: 0.0 kips - maximum load on leg Crushing Check: 83.2%
Leg Comp. Check: 63.3%
Input - Tower Leg 3 STD Sleeve Check: 32.2%
Built-up Check: 60.6%
K: 2.00 - effective length factor for leg Slenderness Check: OK
Lu : 2.41 ft - unbraced length of tower leg Leg Tension Check: 0.0%
Fy_leg: 50.00 ksi - minimum specified yield strength of tower leg

Fu_leg: 65.00 ksi - minimum specified ultimate strength of tower leg

r: 1.16 in - minimum radius of gyration of tower leg


Aleg: 2.23 in2 - area of tower leg
Di: 3.07 in - inside diameter of tower leg
tleg: 0.22 in - thickness of tower leg

f`c: 0.00 ksi - minimum specified compressive strength of grout (If ungrouted enter 0)

Input - Sleeve R/F L3x3x1/4 Gap Check: NG

Fy_sleeve: 50.00 ksi - minimum specified yield strength of sleeve r/f


Fu_sleeve: 65.00 ksi - minimum specified ultimate strength of sleeve r/f
rx_sleeve: 0.59 in - minimum radius of gyration of sleeve r/f about the x-axis
ry_sleeve: 1.15 in - minimum radius of gyration of sleeve r/f about the y-axis
Asleeve: 1.45 in2 - area of sleeve r/f
tsleeve: 0.00 in - thickness of tower leg
Termination: Connected to Leg ONLY

Input - Sleeve Connection to Leg

a: 12.00 in - spacing of connectors connecting the sleeve to the leg


D: 5.00 - weld size for the weld connecting the sleeve to the leg (unit = # of 16ths)
Length //: 15.00 in - length of weld on each side of the leg at the termination
Length ⊥: 0.00 in - length of weld at the bottom/top of the leg sleeve at termination (πD/2)
No: 2.00 - number of longitudinal welds per end of the leg (typically near side & far side, so 2)
FEXX: 70.00 ksi - weld electrode classification

Width: 0.00 in - maximum width of the built-up leg


Gap: 0.50 in - length of leg considered for crushing

Input - Built-up Leg Section 3 STD w/L3x3x1/4 Half Sleeve

rx_bu: 1.27 in - minimum radius of gyration of the built-up section about the x-axis

ry_bu: 1.16 in - minimum radius of gyration of the built-up section about the y-axis

Input - Grouted Leg


Ec: 0 ksi - Modulus of Elasticity of Grout
E_leg: 29,000 ksi - Modulus of Elasticity of Leg
E_sleeve: 29,000 ksi - Modulus of Elasticity of Sleeve

C:\Users\jbalk\Desktop\Work In Progress\Week of 10-29-2018\33537\P-163302_L-193933_871394_Apex_Structural Analysis\Add Calcs\Leg Mods\Built-Up Leg Calculations - 40-60


Project Name: Apex Engineer: EBS
Project Number: TEP No. 33537.193933 Check: JWB
Client Site Number: BU 871394 Date: 11/2/2018
Elevation: 20 - 40 CODE: TIA-H

Grouted/Un-Grouted Pipe Leg + Half Sleeve R/F

Φc = 0.90 - LRFD strength reduction factor (compression) Mast St.: 1.00 - from tnxTower

Φt = 0.90 - LRFD strength reduction factor (tension)

Φw = 0.75 - LRFD strength reduction factor (weld shear)

Φv = 0.75 - LRFD strength reduction factor (shear)

Input - Loads Quick Check

Pinitial: 33.7 kips - force from initial load (no wind) Weld Size: OK
Pwind: 88.6 kips - force due to final loading including reinforcement Weld Connection: 9.9%
Tu: 0 kips - maximum load on leg Crushing Check: 84.2%
Leg Comp. Check: 64.1%
Input - Tower Leg 3 STD Sleeve Check: 32.5%
Built-up Check: 61.3%
K: 2.00 - effective length factor for leg Slenderness Check: OK
Lu : 2.41 ft - unbraced length of tower leg Leg Tension Check: 0.0%
Fy_leg: 50.00 ksi - minimum specified yield strength of tower leg

Fu_leg: 65.00 ksi - minimum specified ultimate strength of tower leg

r: 1.16 in - minimum radius of gyration of tower leg


Aleg: 2.23 in2 - area of tower leg
Di: 3.07 in - inside diameter of tower leg
tleg: 0.22 in - thickness of tower leg

f`c: 0.00 ksi - minimum specified compressive strength of grout (If ungrouted enter 0)

Input - Sleeve R/F L3x3x1/4 Gap Check: NG

Fy_sleeve: 50.00 ksi - minimum specified yield strength of sleeve r/f


Fu_sleeve: 65.00 ksi - minimum specified ultimate strength of sleeve r/f
rx_sleeve: 0.59 in - minimum radius of gyration of sleeve r/f about the x-axis
ry_sleeve: 1.15 in - minimum radius of gyration of sleeve r/f about the y-axis
Asleeve: 1.45 in2 - area of sleeve r/f
tsleeve: 0.00 in - thickness of tower leg
Termination: Connected to Leg ONLY

Input - Sleeve Connection to Leg

a: 12.00 in - spacing of connectors connecting the sleeve to the leg


D: 5.00 - weld size for the weld connecting the sleeve to the leg (unit = # of 16ths)
Length //: 15.00 in - length of weld on each side of the leg at the termination
Length ⊥: 0.00 in - length of weld at the bottom/top of the leg sleeve at termination (πD/2)
No: 2.00 - number of longitudinal welds per end of the leg (typically near side & far side, so 2)
FEXX: 70.00 ksi - weld electrode classification

Width: 0.00 in - maximum width of the built-up leg


Gap: 0.50 in - length of leg considered for crushing

Input - Built-up Leg Section 3 STD w/L3x3x1/4 Half Sleeve

rx_bu: 1.27 in - minimum radius of gyration of the built-up section about the x-axis

ry_bu: 1.16 in - minimum radius of gyration of the built-up section about the y-axis

Input - Grouted Leg


Ec: 0 ksi - Modulus of Elasticity of Grout
E_leg: 29,000 ksi - Modulus of Elasticity of Leg
E_sleeve: 29,000 ksi - Modulus of Elasticity of Sleeve

C:\Users\jbalk\Desktop\Work In Progress\Week of 10-29-2018\33537\P-163302_L-193933_871394_Apex_Structural Analysis\Add Calcs\Leg Mods\Built-Up Leg Calculations - 20-40


Project Name: Apex Engineer: EBS
Project Number: TEP No. 33537.193933 Check: JWB
Client Site Number: BU 871394 Date: 11/2/2018
Elevation: 4.8 - 20 CODE: TIA-H

Grouted/Un-Grouted Pipe Leg + Half Sleeve R/F

Φc = 0.90 - LRFD strength reduction factor (compression) Mast St.: 1.00 - from tnxTower

Φt = 0.90 - LRFD strength reduction factor (tension)

Φw = 0.75 - LRFD strength reduction factor (weld shear)

Φv = 0.75 - LRFD strength reduction factor (shear)

Input - Loads Quick Check

Pinitial: 34.1 kips - force from initial load (no wind) Weld Size: OK
Pwind: 89.2 kips - force due to final loading including reinforcement Weld Connection: 14.1%
Tu: 0.0 kips - maximum load on leg Crushing Check: 65.0%
Leg Comp. Check: 65.6%
Input - Tower Leg 3 STD Sleeve Check: 36.5%
Built-up Check: 67.4%
K: 2.00 - effective length factor for leg Slenderness Check: OK
Lu : 2.41 ft - unbraced length of tower leg Leg Tension Check: 0.0%
Fy_leg: 50.00 ksi - minimum specified yield strength of tower leg

Fu_leg: 65.00 ksi - minimum specified ultimate strength of tower leg

r: 1.16 in - minimum radius of gyration of tower leg


Aleg: 2.23 in2 - area of tower leg
Di: 3.07 in - inside diameter of tower leg
tleg: 0.22 in - thickness of tower leg

f`c: 0.00 ksi - minimum specified compressive strength of grout (If ungrouted enter 0)

Input - Sleeve R/F 3.5 STD Gap Check: OK

Fy_sleeve: 46.00 ksi - minimum specified yield strength of sleeve r/f


Fu_sleeve: 62.00 ksi - minimum specified ultimate strength of sleeve r/f
rx_sleeve: 0.58 in - minimum radius of gyration of sleeve r/f about the x-axis
ry_sleeve: 1.34 in - minimum radius of gyration of sleeve r/f about the y-axis
Asleeve: 1.34 in2 - area of sleeve r/f
tsleeve: 0.23 in - thickness of tower leg
Termination: Connected to Flange

Input - Sleeve Connection to Leg

a: 12.00 in - spacing of connectors connecting the sleeve to the leg


D: 3.00 - weld size for the weld connecting the sleeve to the leg (unit = # of 16ths)
Length //: 12.00 in - length of weld on each side of the leg at the termination
Length ⊥: 6.28 in - length of weld at the bottom/top of the leg sleeve at termination (πD/2)
No: 2.00 - number of longitudinal welds per end of the leg (typically near side & far side, so 2)
FEXX: 70.00 ksi - weld electrode classification

Width: 4.00 in - maximum width of the built-up leg


Gap: 0.00 in - length of leg considered for crushing

Input - Built-up Leg Section 3 STD w/3.5 STD Half Sleeve

rx_bu: 1.14 in - minimum radius of gyration of the built-up section about the x-axis

ry_bu: 1.23 in - minimum radius of gyration of the built-up section about the y-axis

Input - Grouted Leg


Ec: 0 ksi - Modulus of Elasticity of Grout
E_leg: 29,000 ksi - Modulus of Elasticity of Leg
E_sleeve: 29,000 ksi - Modulus of Elasticity of Sleeve

C:\Users\jbalk\Desktop\Work In Progress\Week of 10-29-2018\33537\P-163302_L-193933_871394_Apex_Structural Analysis\Add Calcs\Leg Mods\Built-Up Leg Calculations - 4.8-20


Pier and Pad Foundation
BU # : 871394
Site Name: Apex
App. Number: 464886 Rev. 0

TIA-222 Revision: H
Tower Type: Guyed Block Foundation?:

Superstructure Analysis Reactions Foundation Analysis Checks


Compression, Pcomp: 270.452 kips Capacity Demand Rating* Check
Base Shear, Vu_comp: 0.883 kips Uplift (kips) 70.59 0.00 0.0% Pass
Uplift, Puplift: Lateral (Sliding) (kips) 90.70 0.88 0.9% Pass
Uplift Shear, Vu_uplift: Bearing Pressure (ksf) 3.60 3.02 79.9% Pass
Moment, Mu: ft-kips Overturning (kip*ft) 422.42 4.42 1.0% Pass
Tower Height, H: 500 ft Pier Flexure (Comp.) (kip*ft) 627.15 2.65 0.4% Pass
Base Face Width, BW: ft Pier Flexure (Tension) (kip*ft) 607.50 0.00 0.0% Pass
BP Dist. Above Fdn, bpdist: 0 in Pier Compression (kip) 4296.24 275.31 6.1% Pass
Bolt Circle / Bearing Plate Width, BC: 12 in Pad Flexure (kip*ft) 498.46 198.88 38.0% Pass
Pad Shear - 1-way (kips) 215.54 58.28 25.8% Pass
Pier Properties Pad Shear - 2-way (Comp) (ksi) 0.164 0.045 26.0% Pass
Pier Shape: Square Flexural 2-way (Comp) (kip*ft) 397.03 1.59 0.4% Pass
Pier Diameter, dpier: 3 ft Pad Shear - 2-way (Uplift) (ksi) 0.164 0.000 0.0% Pass
Ext. Above Grade, E: 0.1667 ft Flexural 2-way (Tension) (kip*ft) 397.03 0.00 0.0% Pass
Pier Rebar Size, Sc: 6 *Rating per TIA-222-H Section
Pier Rebar Quantity, mc: 15 15.5

Pier Tie/Spiral Size, St: 4 Soil Rating*: 79.9%


Pier Tie/Spiral Quantity, mt: 3 Structural Rating*: 38.0%
Pier Reinforcement Type: Tie
Pier Clear Cover, ccpier: 3 in

Pad Properties
Depth, D: 4.83 ft
Pad Width, W: 11 ft
Pad Thickness, T: 2 ft
Pad Rebar Size, Sp: 6
Pad Rebar Quantity, mp: 13
Pad Clear Cover, ccpad: 3 in

Material Properties
Rebar Grade, Fy: 60000 psi
Concrete Compressive Strength, F'c: 3000 psi
Dry Concrete Density, δc: 150 pcf

Soil Properties
Total Soil Unit Weight, γ: 120 pcf
Ultimate Gross Bearing, Qult: 6.000 ksf <--Toggle between Gross and Net
Cohesion, Cu: 0.000 ksf
Friction Angle, : 0 degrees
SPT Blow Count, Nblows: 11
Base Friction, µ: 0.4
Neglected Depth, N: 0.00 ft
Foundation Bearing on Rock? No
Groundwater Depth, gw: 12 ft

Version 3.0.2
Anchor Block Foundation
Checks capacity of anchor blocks for a guyed tower.

BU#: 871394
Site Name: Apex
Order Number: 464886 Rev. 0
Location: Inner A

TIA-222 Revision: H

Design Reactions Design Checks


Shear, S: 21.85 kips
Uplift, Ua: 22.24 kips Capacity Demand Rating* Check
Resultant Force, Rf: 31.2 kips Lateral Capacity (kips): 92.12 21.85 22.6% Pass
Tower Height, H: 500.00 ft Uplift Capacity (kips): 115.78 22.24 18.3% Pass
Guy Anchor Radius, R: 139.00 ft Lateral Flexural Capacity (ft*kips): #N/A 43.70 #N/A #N/A
Resultant Angle to Horizontal, θ: 45.5 deg Uplift Flexural Capacity (ft*kips): #N/A 44.49 #N/A #N/A
Anchor Shaft (kips): 70.69 31.18 42.0% Pass
Guy Anchor Properties *Rating per TIA-222-H Section 15.5
Depth to Bottom of Deadman, Da: 6.2 ft
Anchor Width, Wa: 4.9 ft Frost Depth, Fd: 0.8333 ft
Anchor Thickness, Ta: 2.0 ft Groundwater Level, gw: N/A ft
Anchor Length, La: 16.0 ft
Concrete Volume, Vc: 5.8 yd3 Warning: Maximum soil depth is not equal to bottom of deadman.
Toe Width, toe: 0 ft Soil Properties: No. of Soil Layers? 2
Guyed Anchor Top Rebar Size, Sat: Layer φ, deg cu, ksf δ, kcf d, ft Ultimate fs (ksf) N (blows/ft)
No. of Bars in Top of Block: 1 0 0.750 0.120 3.00 0.413
Guyed Anchor Front Rebar Size, Saf: 2 0 0.900 0.115 6.20 0.495
No. of Bars in Front of Block:
Stirrup Size:
Anchor Shaft Diameter, ds: 1.5 in
Anchor Shaft Quantity. n: 1
Anchor Shaft Area Override: in2
Shear Lag Factor, u: 1
Section Type (Reference Only):
*key: φ = Internal Angle of Friction
Material Properties cu = Cohesion / Undrained Shear Strength
Rebar Grade, Fy: psi δ = Buoyant Soil Unit Weight
Concrete Strength, F'c: psi d = Depth to Bottom of Layer
Wt. Avg.Concrete Density, δx: 0.150 kcf Ultimate fs = Geotechnical Report-provided skin friction / adhesion
Clear Cover, cc: in N = SPT Blow Count
Anchor Shaft Grade, Fy': 50 ksi
Anchor Shaft Ultimate Strength, Fu': 65 ksi

Version 3.0.3
Anchor Block Foundation
Checks capacity of anchor blocks for a guyed tower.

BU#: 871394
Site Name: Apex
Order Number: 464886 Rev. 0
Location: Inner B

TIA-222 Revision: H

Design Reactions Design Checks


Shear, S: 22.07 kips
Uplift, Ua: 19.47 kips Capacity Demand Rating* Check
Resultant Force, Rf: 29.4 kips Lateral Capacity (kips): 103.17 22.07 20.4% Pass
Tower Height, H: 500.00 ft Uplift Capacity (kips): 184.71 19.47 10.0% Pass
Guy Anchor Radius, R: 138.00 ft Lateral Flexural Capacity (ft*kips): #N/A 46.34 #N/A #N/A
Resultant Angle to Horizontal, θ: 41.4 deg Uplift Flexural Capacity (ft*kips): #N/A 40.90 #N/A #N/A
Anchor Shaft (kips): 70.69 29.43 39.7% Pass
Guy Anchor Properties *Rating per TIA-222-H Section 15.5
Depth to Bottom of Deadman, Da: 8.6 ft
Anchor Width, Wa: 5.3 ft Frost Depth, Fd: 0.8333 ft
Anchor Thickness, Ta: 1.9 ft Groundwater Level, gw: N/A ft
Anchor Length, La: 16.8 ft
Concrete Volume, Vc: 6.3 yd3 Warning: Maximum soil depth is not equal to bottom of deadman.
Toe Width, toe: 0 ft Soil Properties: No. of Soil Layers? 2
Guyed Anchor Top Rebar Size, Sat: Layer φ, deg cu, ksf δ, kcf d, ft Ultimate fs (ksf) N (blows/ft)
No. of Bars in Top of Block: 1 0 0.750 0.120 3.00 0.413
Guyed Anchor Front Rebar Size, Saf: 2 0 0.900 0.115 8.60 0.495
No. of Bars in Front of Block:
Stirrup Size:
Anchor Shaft Diameter, ds: 1.5 in
Anchor Shaft Quantity. n: 1
Anchor Shaft Area Override: in2
Shear Lag Factor, u: 1
Section Type (Reference Only):
*key: φ = Internal Angle of Friction
Material Properties cu = Cohesion / Undrained Shear Strength
Rebar Grade, Fy: psi δ = Buoyant Soil Unit Weight
Concrete Strength, F'c: psi d = Depth to Bottom of Layer
Wt. Avg.Concrete Density, δx: 0.150 kcf Ultimate fs = Geotechnical Report-provided skin friction / adhesion
Clear Cover, cc: in N = SPT Blow Count
Anchor Shaft Grade, Fy': 50 ksi
Anchor Shaft Ultimate Strength, Fu': 65 ksi

Version 3.0.3
Anchor Block Foundation
Checks capacity of anchor blocks for a guyed tower.

BU#: 871394
Site Name: Apex
Order Number: 464886 Rev. 0
Location: Inner C

TIA-222 Revision: H

Design Reactions Design Checks


Shear, S: 22.03 kips
Uplift, Ua: 19.09 kips Capacity Demand Rating* Check
Resultant Force, Rf: 29.1 kips Lateral Capacity (kips): 53.43 22.03 39.3% Pass
Tower Height, H: 500.00 ft Uplift Capacity (kips): 91.69 19.09 19.8% Pass
Guy Anchor Radius, R: 138.50 ft Lateral Flexural Capacity (ft*kips): #N/A 22.03 #N/A #N/A
Resultant Angle to Horizontal, θ: 40.9 deg Uplift Flexural Capacity (ft*kips): #N/A 19.09 #N/A #N/A
Anchor Shaft (kips): 70.69 29.15 39.3% Pass
Guy Anchor Properties *Rating per TIA-222-H Section 15.5
Depth to Bottom of Deadman, Da: 8.4 ft
Anchor Width, Wa: 4.8 ft Frost Depth, Fd: 0.8333 ft
Anchor Thickness, Ta: 2.1 ft Groundwater Level, gw: N/A ft
Anchor Length, La: 8.0 ft
Concrete Volume, Vc: 3.0 yd3 Warning: Maximum soil depth is not equal to bottom of deadman.
Toe Width, toe: 0 ft Soil Properties: No. of Soil Layers? 2
Guyed Anchor Top Rebar Size, Sat: Layer φ, deg cu, ksf δ, kcf d, ft Ultimate fs (ksf) N (blows/ft)
No. of Bars in Top of Block: 1 0 0.750 0.120 3.00 0.413
Guyed Anchor Front Rebar Size, Saf: 2 0 0.900 0.115 8.40 0.495
No. of Bars in Front of Block:
Stirrup Size:
Anchor Shaft Diameter, ds: 1.5 in
Anchor Shaft Quantity. n: 1
2
Anchor Shaft Area Override: in
Shear Lag Factor, u: 1
Section Type (Reference Only):
*key: φ = Internal Angle of Friction
Material Properties cu = Cohesion / Undrained Shear Strength
Rebar Grade, Fy: psi δ = Buoyant Soil Unit Weight
Concrete Strength, F'c: psi d = Depth to Bottom of Layer
Wt. Avg.Concrete Density, δx: 0.150 kcf Ultimate fs = Geotechnical Report-provided skin friction / adhesion
Clear Cover, cc: in N = SPT Blow Count
Anchor Shaft Grade, Fy': 50 ksi
Anchor Shaft Ultimate Strength, Fu': 65 ksi

Version 3.0.3
Anchor Block Foundation
Checks capacity of anchor blocks for a guyed tower.

BU#: 871394
Site Name: Apex
Order Number: 464886 Rev. 0
Location: Middle A

TIA-222 Revision: H

Design Reactions Design Checks


Shear, S: 20.06 kips
Uplift, Ua: 17.98 kips Capacity Demand Rating* Check
Resultant Force, Rf: 26.9 kips Lateral Capacity (kips): 114.46 20.06 16.7% Pass
Tower Height, H: 500.00 ft Uplift Capacity (kips): 170.85 17.98 10.0% Pass
Guy Anchor Radius, R: 348.00 ft Lateral Flexural Capacity (ft*kips): #N/A 41.61 #N/A #N/A
Resultant Angle to Horizontal, θ: 41.9 deg Uplift Flexural Capacity (ft*kips): #N/A 37.31 #N/A #N/A
Anchor Shaft (kips): 70.69 26.94 36.3% Pass
Guy Anchor Properties *Rating per TIA-222-H Section 15.5
Depth to Bottom of Deadman, Da: 7.6 ft
Anchor Width, Wa: 6.0 ft Frost Depth, Fd: 0.8333 ft
Anchor Thickness, Ta: 2.2 ft Groundwater Level, gw: N/A ft
Anchor Length, La: 16.6 ft
Concrete Volume, Vc: 8.1 yd3 Warning: Maximum soil depth is not equal to bottom of deadman.
Toe Width, toe: 0 ft Soil Properties: No. of Soil Layers? 2
Guyed Anchor Top Rebar Size, Sat: Layer φ, deg cu, ksf δ, kcf d, ft Ultimate fs (ksf) N (blows/ft)
No. of Bars in Top of Block: 1 0 0.750 0.120 3.00 0.413
Guyed Anchor Front Rebar Size, Saf: 2 0 0.900 0.115 7.60 0.495
No. of Bars in Front of Block:
Stirrup Size:
Anchor Shaft Diameter, ds: 1.5 in
Anchor Shaft Quantity. n: 1
Anchor Shaft Area Override: in2
Shear Lag Factor, u: 1
Section Type (Reference Only):
*key: φ = Internal Angle of Friction
Material Properties cu = Cohesion / Undrained Shear Strength
Rebar Grade, Fy: psi δ = Buoyant Soil Unit Weight
Concrete Strength, F'c: psi d = Depth to Bottom of Layer
Wt. Avg.Concrete Density, δx: 0.150 kcf Ultimate fs = Geotechnical Report-provided skin friction / adhesion
Clear Cover, cc: in N = SPT Blow Count
Anchor Shaft Grade, Fy': 50 ksi
Anchor Shaft Ultimate Strength, Fu': 65 ksi

Version 3.0.3
Anchor Block Foundation
Checks capacity of anchor blocks for a guyed tower.

BU#: 871394
Site Name: Apex
Order Number: 464886 Rev. 0
Location: Middle B

TIA-222 Revision: H

Design Reactions Design Checks


Shear, S: 20.38 kips
Uplift, Ua: 19.53 kips Capacity Demand Rating* Check
Resultant Force, Rf: 28.2 kips Lateral Capacity (kips): 128.25 20.38 15.1% Pass
Tower Height, H: 500.00 ft Uplift Capacity (kips): 208.34 19.53 8.9% Pass
Guy Anchor Radius, R: 300.00 ft Lateral Flexural Capacity (ft*kips): #N/A 49.17 #N/A #N/A
Resultant Angle to Horizontal, θ: 43.8 deg Uplift Flexural Capacity (ft*kips): #N/A 47.12 #N/A #N/A
Anchor Shaft (kips): 70.69 28.23 38.0% Pass
Guy Anchor Properties *Rating per TIA-222-H Section 15.5
Depth to Bottom of Deadman, Da: 8.2 ft
Anchor Width, Wa: 5.8 ft Frost Depth, Fd: 0.8333 ft
Anchor Thickness, Ta: 2.1 ft Groundwater Level, gw: N/A ft
Anchor Length, La: 19.3 ft
Concrete Volume, Vc: 8.7 yd3 Warning: Maximum soil depth is not equal to bottom of deadman.
Toe Width, toe: 0 ft Soil Properties: No. of Soil Layers? 2
Guyed Anchor Top Rebar Size, Sat: Layer φ, deg cu, ksf δ, kcf d, ft Ultimate fs (ksf) N (blows/ft)
No. of Bars in Top of Block: 1 0 0.750 0.120 3.00 0.413
Guyed Anchor Front Rebar Size, Saf: 2 0 0.900 0.115 8.20 0.495
No. of Bars in Front of Block:
Stirrup Size:
Anchor Shaft Diameter, ds: 1.5 in
Anchor Shaft Quantity. n: 1
Anchor Shaft Area Override: in2
Shear Lag Factor, u: 1
Section Type (Reference Only):
*key: φ = Internal Angle of Friction
Material Properties cu = Cohesion / Undrained Shear Strength
Rebar Grade, Fy: psi δ = Buoyant Soil Unit Weight
Concrete Strength, F'c: psi d = Depth to Bottom of Layer
Wt. Avg.Concrete Density, δx: 0.150 kcf Ultimate fs = Geotechnical Report-provided skin friction / adhesion
Clear Cover, cc: in N = SPT Blow Count
Anchor Shaft Grade, Fy': 50 ksi
Anchor Shaft Ultimate Strength, Fu': 65 ksi

Version 3.0.3
Anchor Block Foundation
Checks capacity of anchor blocks for a guyed tower.

BU#: 871394
Site Name: Apex
Order Number: 464886 Rev. 0
Location: Middle C

TIA-222 Revision: H

Design Reactions Design Checks


Shear, S: 20.40 kips
Uplift, Ua: 19.41 kips Capacity Demand Rating* Check
Resultant Force, Rf: 28.2 kips Lateral Capacity (kips): 112.47 20.40 17.3% Pass
Tower Height, H: 500.00 ft Uplift Capacity (kips): 156.79 19.41 11.8% Pass
Guy Anchor Radius, R: 300.00 ft Lateral Flexural Capacity (ft*kips): #N/A 42.57 #N/A #N/A
Resultant Angle to Horizontal, θ: 43.6 deg Uplift Flexural Capacity (ft*kips): #N/A 40.52 #N/A #N/A
Anchor Shaft (kips): 70.69 28.16 37.9% Pass
Guy Anchor Properties *Rating per TIA-222-H Section 15.5
Depth to Bottom of Deadman, Da: 8.2 ft
Anchor Width, Wa: 4.5 ft Frost Depth, Fd: 0.8333 ft
Anchor Thickness, Ta: 2.4 ft Groundwater Level, gw: N/A ft
Anchor Length, La: 16.7 ft
Concrete Volume, Vc: 6.7 yd3 Warning: Maximum soil depth is not equal to bottom of deadman.
Toe Width, toe: 0 ft Soil Properties: No. of Soil Layers? 2
Guyed Anchor Top Rebar Size, Sat: Layer φ, deg cu, ksf δ, kcf d, ft Ultimate fs (ksf) N (blows/ft)
No. of Bars in Top of Block: 1 0 0.750 0.120 3.00 0.413
Guyed Anchor Front Rebar Size, Saf: 2 0 0.900 0.115 8.20 0.495
No. of Bars in Front of Block:
Stirrup Size:
Anchor Shaft Diameter, ds: 1.5 in
Anchor Shaft Quantity. n: 1
Anchor Shaft Area Override: in2
Shear Lag Factor, u: 1
Section Type (Reference Only):
*key: φ = Internal Angle of Friction
Material Properties cu = Cohesion / Undrained Shear Strength
Rebar Grade, Fy: psi δ = Buoyant Soil Unit Weight
Concrete Strength, F'c: psi d = Depth to Bottom of Layer
Wt. Avg.Concrete Density, δx: 0.150 kcf Ultimate fs = Geotechnical Report-provided skin friction / adhesion
Clear Cover, cc: in N = SPT Blow Count
Anchor Shaft Grade, Fy': 50 ksi
Anchor Shaft Ultimate Strength, Fu': 65 ksi

Version 3.0.3
Anchor Block Foundation
Checks capacity of anchor blocks for a guyed tower.

BU#: 871394
Site Name: Apex
Order Number: 464886 Rev. 0
Location: Outer A

TIA-222 Revision: H

Design Reactions Design Checks


Shear, S: 20.99 kips
Uplift, Ua: 20.62 kips Capacity Demand Rating* Check
Resultant Force, Rf: 29.4 kips Lateral Capacity (kips): 107.09 20.99 18.7% Pass
Tower Height, H: 500.00 ft Uplift Capacity (kips): 192.80 20.62 10.2% Pass
Guy Anchor Radius, R: 426.00 ft Lateral Flexural Capacity (ft*kips): #N/A 39.36 #N/A #N/A
Resultant Angle to Horizontal, θ: 44.5 deg Uplift Flexural Capacity (ft*kips): #N/A 38.66 #N/A #N/A
Anchor Shaft (kips): 70.69 29.42 39.6% Pass
Guy Anchor Properties *Rating per TIA-222-H Section 15.5
Depth to Bottom of Deadman, Da: 8.7 ft
Anchor Width, Wa: 6.5 ft Frost Depth, Fd: 0.8333 ft
Anchor Thickness, Ta: 2.1 ft Groundwater Level, gw: N/A ft
Anchor Length, La: 15.0 ft
Concrete Volume, Vc: 7.6 yd3 Warning: Maximum soil depth is not equal to bottom of deadman.
Toe Width, toe: 0 ft Soil Properties: No. of Soil Layers? 2
Guyed Anchor Top Rebar Size, Sat: Layer φ, deg cu, ksf δ, kcf d, ft Ultimate fs (ksf) N (blows/ft)
No. of Bars in Top of Block: 1 0 0.750 0.120 3.00 0.413
Guyed Anchor Front Rebar Size, Saf: 2 0 0.900 0.115 8.70 0.495
No. of Bars in Front of Block:
Stirrup Size:
Anchor Shaft Diameter, ds: 1.5 in
Anchor Shaft Quantity. n: 1
Anchor Shaft Area Override: in2
Shear Lag Factor, u: 1
Section Type (Reference Only):
*key: φ = Internal Angle of Friction
Material Properties cu = Cohesion / Undrained Shear Strength
Rebar Grade, Fy: psi δ = Buoyant Soil Unit Weight
Concrete Strength, F'c: psi d = Depth to Bottom of Layer
Wt. Avg.Concrete Density, δx: 0.150 kcf Ultimate fs = Geotechnical Report-provided skin friction / adhesion
Clear Cover, cc: in N = SPT Blow Count
Anchor Shaft Grade, Fy': 50 ksi
Anchor Shaft Ultimate Strength, Fu': 65 ksi

Version 3.0.3
Anchor Block Foundation
Checks capacity of anchor blocks for a guyed tower.

BU#: 871394
Site Name: Apex
Order Number: 464886 Rev. 0
Location: Outer B

TIA-222 Revision: H

Design Reactions Design Checks


Shear, S: 21.35 kips
Uplift, Ua: 21.86 kips Capacity Demand Rating* Check
Resultant Force, Rf: 30.6 kips Lateral Capacity (kips): 126.94 21.35 16.0% Pass
Tower Height, H: 500.00 ft Uplift Capacity (kips): 183.94 21.86 11.3% Pass
Guy Anchor Radius, R: 400.00 ft Lateral Flexural Capacity (ft*kips): #N/A 42.70 #N/A #N/A
Resultant Angle to Horizontal, θ: 45.7 deg Uplift Flexural Capacity (ft*kips): #N/A 43.71 #N/A #N/A
Anchor Shaft (kips): 70.69 30.55 41.2% Pass
Guy Anchor Properties *Rating per TIA-222-H Section 15.5
Depth to Bottom of Deadman, Da: 8.8 ft
Anchor Width, Wa: 5.5 ft Frost Depth, Fd: 0.8333 ft
Anchor Thickness, Ta: 2.7 ft Groundwater Level, gw: N/A ft
Anchor Length, La: 16.0 ft
Concrete Volume, Vc: 8.8 yd3 Warning: Maximum soil depth is not equal to bottom of deadman.
Toe Width, toe: 0 ft Soil Properties: No. of Soil Layers? 2
Guyed Anchor Top Rebar Size, Sat: Layer φ, deg cu, ksf δ, kcf d, ft Ultimate fs (ksf) N (blows/ft)
No. of Bars in Top of Block: 1 0 0.750 0.120 3.00 0.413
Guyed Anchor Front Rebar Size, Saf: 2 0 0.900 0.115 8.80 0.495
No. of Bars in Front of Block:
Stirrup Size:
Anchor Shaft Diameter, ds: 1.5 in
Anchor Shaft Quantity. n: 1
Anchor Shaft Area Override: in2
Shear Lag Factor, u: 1
Section Type (Reference Only):
*key: φ = Internal Angle of Friction
Material Properties cu = Cohesion / Undrained Shear Strength
Rebar Grade, Fy: psi δ = Buoyant Soil Unit Weight
Concrete Strength, F'c: psi d = Depth to Bottom of Layer
Wt. Avg.Concrete Density, δx: 0.150 kcf Ultimate fs = Geotechnical Report-provided skin friction / adhesion
Clear Cover, cc: in N = SPT Blow Count
Anchor Shaft Grade, Fy': 50 ksi
Anchor Shaft Ultimate Strength, Fu': 65 ksi

Version 3.0.3
Anchor Block Foundation
Checks capacity of anchor blocks for a guyed tower.

BU#: 871394
Site Name: Apex
Order Number: 464886 Rev. 0
Location: Outer C

TIA-222 Revision: H

Design Reactions Design Checks


Shear, S: 21.41 kips
Uplift, Ua: 21.62 kips Capacity Demand Rating* Check
Resultant Force, Rf: 30.4 kips Lateral Capacity (kips): 97.27 21.41 21.0% Pass
Tower Height, H: 500.00 ft Uplift Capacity (kips): 153.39 21.62 13.4% Pass
Guy Anchor Radius, R: 401.00 ft Lateral Flexural Capacity (ft*kips): #N/A 43.88 #N/A #N/A
Resultant Angle to Horizontal, θ: 45.3 deg Uplift Flexural Capacity (ft*kips): #N/A 44.32 #N/A #N/A
Anchor Shaft (kips): 70.69 30.43 41.0% Pass
Guy Anchor Properties *Rating per TIA-222-H Section 15.5
Depth to Bottom of Deadman, Da: 8.0 ft
Anchor Width, Wa: 4.6 ft Frost Depth, Fd: 0.8333 ft
Anchor Thickness, Ta: 2.0 ft Groundwater Level, gw: N/A ft
Anchor Length, La: 16.4 ft
Concrete Volume, Vc: 5.6 yd3 Warning: Maximum soil depth is not equal to bottom of deadman.
Toe Width, toe: 0 ft Soil Properties: No. of Soil Layers? 2
Guyed Anchor Top Rebar Size, Sat: Layer φ, deg cu, ksf δ, kcf d, ft Ultimate fs (ksf) N (blows/ft)
No. of Bars in Top of Block: 1 0 0.750 0.120 3.00 0.413
Guyed Anchor Front Rebar Size, Saf: 2 0 0.900 0.115 8.00 0.495
No. of Bars in Front of Block:
Stirrup Size:
Anchor Shaft Diameter, ds: 1.5 in
Anchor Shaft Quantity. n: 1
Anchor Shaft Area Override: in2
Shear Lag Factor, u: 1
Section Type (Reference Only):
*key: φ = Internal Angle of Friction
Material Properties cu = Cohesion / Undrained Shear Strength
Rebar Grade, Fy: psi δ = Buoyant Soil Unit Weight
Concrete Strength, F'c: psi d = Depth to Bottom of Layer
Wt. Avg.Concrete Density, δx: 0.150 kcf Ultimate fs = Geotechnical Report-provided skin friction / adhesion
Clear Cover, cc: in N = SPT Blow Count
Anchor Shaft Grade, Fy': 50 ksi
Anchor Shaft Ultimate Strength, Fu': 65 ksi

Version 3.0.3