Pier Structural Engineering Corp. (P-SEC) is pleased to submit this “Structural Modification Report” to
determine the structural integrity of the above mentioned tower. This analysis has been performed in
accordance with the Crown Castle Structural ‘Statement of Work’ and the terms of Crown Castle Purchase
Order Number 813484, in accordance with application 290784, revision 8 pertaining to the recent upgrade
modifications package for this structure.
The purpose of the analysis is to determine acceptability of the tower stress level. Based on our analysis we
have determined the tower stress level for the structure and foundation, under the following load case, to be:
This analysis has been performed in accordance with the 2013 CBC based upon an ultimate 3-second gust
wind speed of 110 mph converted to a nominal 3-second gust wind speed of 85 mph per section 1609.3.1 as
required for use in the TIA-222-G Standard per Exception #5 of Section 1609.1.1. Exposure Category C with a
maximum topographic factor, Kzt, of 2.922, Risk Category II and Classification U was/were used in this analysis.
The seismic design category and site class are D, as determined in “Appendix C – Additional Calculations” of
this report.
All modifications and equipment proposed in this report shall be installed in accordance with the attached
drawings for the determined available structural capacity to be effective.
We at P-SEC appreciate the opportunity of providing our continuing professional services to you and Crown
Castle USA Inc. If you have any questions or need further assistance on this or any other projects please give
us a call.
TABLE OF CONTENTS
1) INTRODUCTION
2) ANALYSIS CRITERIA
Table 1 - Proposed Antenna and Cable Information
Table 2 - Existing and Reserved Antenna and Cable Information
Table 3 - Design Antenna and Cable Information
3) ANALYSIS PROCEDURE
Table 4 - Documents Provided
3.1) Analysis Method
3.2) Assumptions
4) ANALYSIS RESULTS
Table 5 - Section Capacity (Summary)
Table 6 - Tower Component Stresses vs. Capacity
4.1) Recommendations
5) APPENDIX A
tnxTower Output (for LC4)
6) APPENDIX B
Base Level Drawing
7) APPENDIX C
Additional Calculations
7) APPENDIX D
Upgrade Drawings
1) INTRODUCTION
This tower is a 60-ft Self Support tower originally designed by ANDREW in August of 1988 for a wind speed of
90 mph per EIA-222-D. The tower was reinforced per P-SEC modification drawings of 2013.
2) ANALYSIS CRITERIA
3) ANALYSIS PROCEDURE
tnxTower (6.1.4.1), a commercially available analysis software package, was used to create a three-
dimensional model of the tower and calculate member stresses for various loading cases. Selected
output from the analysis is included in Appendix A.
3.2) Assumptions
1) Tower and structures were built in accordance with the manufacturer’s specifications.
2) The tower\structures have been maintained in accordance with the manufacturer’s specification.
3) The configuration of antennas, transmission cables, mounts and other appurtenances are as
specified in Tables 1 and 2 and the referenced drawings.
4) P-SEC did not analyze antenna supporting mounts as part of this analysis report and assumed
they are structurally sufficient. It is the carrier’s responsibility to ensure structural compliance of
their existing and/or proposed antenna supporting mounts.
5) All equipment model numbers, quantities, and centerline elevations are as provided in the CCI
CAD package dated 6/19/2015 with any adjustments as noted below:
a) There are (2) existing sidearm mounts at the 50ft elevation that will be removed.
6) Minimum rebar content has been assumed in the original caisson foundations.
7) The proposed upgrade modifications are to be completed as soon as possible and before any
proposed loadings are added. See drawing package in Appendix D for details.
This analysis may be affected if any assumptions are not valid or have been made in error. P-SEC
should be notified to determine the effect on the structural integrity of the tower.
4) ANALYSIS RESULTS
4.1) Recommendations
Once the modifications outlined in Appendix D are completed, the existing 60-ft self-support tower located in
Solano County (VACAVILLE (REVISED)), CA will conform to the TIA-222-G Standard and the 2013 CBC
based upon an ultimate 3-second gust wind speed of 110 mph converted to a nominal 3-second gust wind
speed of 85 mph, exposure category C with a maximum topographic factor, Kzt of 2.922.
encl.
816137_PASSING SA Report_20150828.doc
APPENDIX A
4
P4F-21D
Lighting
(2)
Side
SBNHH-1D45B
Additional
CBC721-DF
PipeRCMDC-3315-PF-48
RRUS
Arm
Mount
Rod
(Carrier
Mount
12
Mount
[PM
(Carrier
3/4"
W/SOLAR
w/
601-1]
[SO
Area
x43'
Mount
4'302-3]
57'
50'
E)
(L-Rod
(Carrier
(Carrier
SHIELD
E)
(Carrier
Pipe
(Carrier
62'
50'
(Carrier
43'
E)
57'
P)
E) 43
62
57
50
(Carrier
P)
57'
50' E) 57' P)
P)
DESIGNED APPURTENANCE LOADING
TYPE ELEVATION TYPE ELEVATION
Lighting Rod 3/4" x 4' (L-Rod 62' E) 62 CBC721-DF (Carrier 57' E) 57
SBNHH-1D45B w/ Mount Pipe (Carrier 57 CBC721-DF (Carrier 57' E) 57
57' P) CBC721-DF (Carrier 57' E) 57
SBNHH-1D45B w/ Mount Pipe (Carrier 57 CBC721-DF (Carrier 57' E) 57
57' P)
Side Arm Mount [SO 302-3] (Carrier 57
SBNHH-1D45B w/ Mount Pipe (Carrier 57 57' E)
57' P)
L1 1/2x1 1/2x1/8
L1 3/4x1 3/4x1/8
57' P)
SBNHH-1D45B w/ Mount Pipe (Carrier 50
0.5
T1
SYMBOL LIST
N.A.
10 @ 4
40.0 ft
MATERIAL STRENGTH
GRADE Fy Fu GRADE Fy Fu
0.2
T2
0.2
T4
7. - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
8. E - Existing, R - Reserved, P - Proposed
28.0 ft 9. 57ft - Proposed loading revisions included
10. 50ft - Proposed loading revisions included
11. Considers end distances to be 2D per site pictures
0.2
T5
A
N.A.
20.0 ft
ALL REACTIONS
ARE FACTORED
L1 3/4x1 3/4x1/8
A500-42
P3x.437
1.1
T7
DOWN: 128 K
SHEAR: 10 K
UPLIFT: -124 K
SHEAR: 10 K
AXIAL
7K
SHEAR MOMENT
16 K 636 kip-ft
0.0 ft
5.8333
2.5
TORQUE 5 kip-ft
REACTIONS - 85 mph WIND
Sec. Horizontals
Diagonal Grade
# Panels @ (ft)
Face Width (ft)
Leg Grade
Weight (K)
Diagonals
Top Girts
Section
Legs
Pier Structural Engineer Corp. Job: PSEC Job 14083 [for UPGRADE PACKAGE]
Project: 816137 - VACAVILLE (REVISED) [for Verizon app 290784 rev 8
198-55 Northfield Drive East
Client:
Waterloo, Ontario, N2K 3T6 CROWN CASTLE USA Drawn by: shoffmeyer App'd:
Code: Date: Scale:
Phone: 519-885-3806 TIA-222-G 08/28/15 NTS
Path: Dwg No.
FAX: 519-884-3806 E-1
H:\PROJECTS\JOB 14000 - 14999\JOB 14000 - 14099\14083 - CCI - 816137 - VACAVILLE (REVISED) (MODs)\PASSING SA\816137_LC4_20150828.eri
Job Page
tnxTower PSEC Job 14083 [for UPGRADE PACKAGE] 1 of 12
Project Date
Pier Structural Engineer Corp.
198-55 Northfield Drive East 816137 - VACAVILLE (REVISED) [for Verizon app 290784 rev 14:45:29 08/28/15
8]
Waterloo, Ontario, N2K 3T6 Client Designed by
Phone: 519-885-3806 CROWN CASTLE USA
FAX: 519-884-3806 shoffmeyer
The main tower is a 3x free standing tower with an overall height of 60.00 ft above the ground line.
The base of the tower is set at an elevation of 0.00 ft above the ground line.
The face width of the tower is 4.00 ft at the top and 5.83 ft at the base.
This tower is designed using the TIA-222-G standard.
The following design criteria apply:
Tower is located in Solano County, California.
Basic wind speed of 85 mph.
Structure Class II.
Exposure Category C.
Topographic Category 5.
Crest Height 487.00 ft.
SEAW RSM-03 procedures for wind speed-up calculations are used.
Topographic Feature: Continuous Ridge.
Slope Distance L: 1430.00 ft.
Distance from Crest x: 41.00 ft.
Deflections calculated using a wind speed of 60 mph.
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -.
E - Existing, R - Reserved, P - Proposed.
57ft - Proposed loading revisions included.
50ft - Proposed loading revisions included.
Considers end distances to be 2D per site pictures.
Anchor Bolts considered to be A325 equivalent per Andrew drawings.
Includes all currently proposed PSEC 14083 modifications.
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -.
A non-linear (P-delta) analysis was used.
Pressures are calculated at each section.
Stress ratio used in tower member design is 1.
Local bending stresses due to climbing loads, feed line supports, and appurtenance mounts are not considered.
Options
Consider Moments - Legs Distribute Leg Loads As Uniform Treat Feedline Bundles As Cylinder
Consider Moments - Horizontals Assume Legs Pinned Use ASCE 10 X-Brace Ly Rules
Consider Moments - Diagonals √ Assume Rigid Index Plate √ Calculate Redundant Bracing Forces
Use Moment Magnification √ Use Clear Spans For Wind Area Ignore Redundant Members in FEA
√ Use Code Stress Ratios √ Use Clear Spans For KL/r SR Leg Bolts Resist Compression
√ Use Code Safety Factors - Guys Retension Guys To Initial Tension √ All Leg Panels Have Same Allowable
Escalate Ice √ Bypass Mast Stability Checks Offset Girt At Foundation
Always Use Max Kz √ Use Azimuth Dish Coefficients √ Consider Feedline Torque
Use Special Wind Profile √ Project Wind Area of Appurt. √ Include Angle Block Shear Check
√ Include Bolts In Member Capacity Autocalc Torque Arm Areas Poles
Leg Bolts Are At Top Of Section SR Members Have Cut Ends √ Include Shear-Torsion Interaction
√ Secondary Horizontal Braces Leg √ Sort Capacity Reports By Component Always Use Sub-Critical Flow
Use Diamond Inner Bracing (4 Sided) Triangulate Diamond Inner Bracing Use Top Mounted Sockets
Add IBC .6D+W Combination Use TIA-222-G Tension Splice Capacity
Exemption
Job Page
tnxTower PSEC Job 14083 [for UPGRADE PACKAGE] 2 of 12
Project Date
Pier Structural Engineer Corp.
198-55 Northfield Drive East 816137 - VACAVILLE (REVISED) [for Verizon app 290784 rev 14:45:29 08/28/15
8]
Waterloo, Ontario, N2K 3T6 Client Designed by
Phone: 519-885-3806 CROWN CASTLE USA
FAX: 519-884-3806 shoffmeyer
Description Face Allow Component Placement Face Lateral # # Clear Width or Perimeter Weight
or Shield Type Offset Offset Per Spacing Diameter
Leg ft in (Frac FW) Row in in in plf
(Carrier 50'/57' E)
T-Brackets (Af) B No Af (CaAa) 57.00 - 0.00 0.0000 -0.42 1 1 1.0000 0.5000 8.40
(Carrier 50'/57' E)
***
LDF5-50A(7/8'') B No Ar (CaAa) 57.00 - 0.00 0.0000 -0.32 6 2 0.7500 1.0900 0.33
(Carrier 57' E)
T-Brackets (Af) B No Af (CaAa) 57.00 - 0.00 0.0000 -0.32 1 1 1.0000 0.5000 8.40
(Carrier 57' E)
***
EW90(ELLIPTICAL) A No Ar (CaAa) 43.00 - 0.00 0.0000 0.35 1 1 0.7500 1.2800 0.32
(Carrier 43' E)
***
Dishes
Description Face Dish Offset Offsets: Azimuth 3 dB Elevation Outside Aperture Weight
or Type Type Horz Adjustment Beam Diameter Area
Leg Lateral Width
Vert
ft ° ° ft ft ft2 K
P4F-21D C Paraboloid w/o From 1.00 -15.0000 43.00 4.00 No Ice 12.57 0.10
(Carrier 43' E) Radome Leg 0.00
0.00
Load Combinations
Comb. Description
No.
1 Dead Only
2 1.2 Dead+1.6 Wind 0 deg - No Ice
3 0.9 Dead+1.6 Wind 0 deg - No Ice
4 1.2 Dead+1.6 Wind 30 deg - No Ice
5 0.9 Dead+1.6 Wind 30 deg - No Ice
6 1.2 Dead+1.6 Wind 60 deg - No Ice
7 0.9 Dead+1.6 Wind 60 deg - No Ice
8 1.2 Dead+1.6 Wind 90 deg - No Ice
Job Page
tnxTower PSEC Job 14083 [for UPGRADE PACKAGE] 7 of 12
Project Date
Pier Structural Engineer Corp.
198-55 Northfield Drive East 816137 - VACAVILLE (REVISED) [for Verizon app 290784 rev 14:45:29 08/28/15
8]
Waterloo, Ontario, N2K 3T6 Client Designed by
Phone: 519-885-3806 CROWN CASTLE USA
FAX: 519-884-3806 shoffmeyer
Comb. Description
No.
9 0.9 Dead+1.6 Wind 90 deg - No Ice
10 1.2 Dead+1.6 Wind 120 deg - No Ice
11 0.9 Dead+1.6 Wind 120 deg - No Ice
12 1.2 Dead+1.6 Wind 150 deg - No Ice
13 0.9 Dead+1.6 Wind 150 deg - No Ice
14 1.2 Dead+1.6 Wind 180 deg - No Ice
15 0.9 Dead+1.6 Wind 180 deg - No Ice
16 1.2 Dead+1.6 Wind 210 deg - No Ice
17 0.9 Dead+1.6 Wind 210 deg - No Ice
18 1.2 Dead+1.6 Wind 240 deg - No Ice
19 0.9 Dead+1.6 Wind 240 deg - No Ice
20 1.2 Dead+1.6 Wind 270 deg - No Ice
21 0.9 Dead+1.6 Wind 270 deg - No Ice
22 1.2 Dead+1.6 Wind 300 deg - No Ice
23 0.9 Dead+1.6 Wind 300 deg - No Ice
24 1.2 Dead+1.6 Wind 330 deg - No Ice
25 0.9 Dead+1.6 Wind 330 deg - No Ice
26 Dead+Wind 0 deg - Service
27 Dead+Wind 30 deg - Service
28 Dead+Wind 60 deg - Service
29 Dead+Wind 90 deg - Service
30 Dead+Wind 120 deg - Service
31 Dead+Wind 150 deg - Service
32 Dead+Wind 180 deg - Service
33 Dead+Wind 210 deg - Service
34 Dead+Wind 240 deg - Service
35 Dead+Wind 270 deg - Service
36 Dead+Wind 300 deg - Service
37 Dead+Wind 330 deg - Service
Maximum Reactions
Location Condition Gov. Vertical Horizontal, X Horizontal, Z
Load K K K
Comb.
Leg C Max. Vert 18 127.80 9.01 -5.09
Max. Hx 18 127.80 9.01 -5.09
Max. Hz 7 -123.76 -8.71 5.04
Min. Vert 7 -123.76 -8.71 5.04
Min. Hx 7 -123.76 -8.71 5.04
Min. Hz 18 127.80 9.01 -5.09
Leg B Max. Vert 10 122.15 -8.38 -5.39
Max. Hx 23 -112.67 7.83 5.01
Max. Hz 23 -112.67 7.83 5.01
Min. Vert 23 -112.67 7.83 5.01
Min. Hx 10 122.15 -8.38 -5.39
Min. Hz 10 122.15 -8.38 -5.39
Leg A Max. Vert 2 119.98 0.50 9.80
Max. Hx 22 53.31 0.93 4.28
Max. Hz 2 119.98 0.50 9.80
Min. Vert 15 -106.64 -0.46 -8.95
Min. Hx 11 -46.85 -1.06 -4.16
Min. Hz 15 -106.64 -0.46 -8.95
Job Page
tnxTower PSEC Job 14083 [for UPGRADE PACKAGE] 8 of 12
Project Date
Pier Structural Engineer Corp.
198-55 Northfield Drive East 816137 - VACAVILLE (REVISED) [for Verizon app 290784 rev 14:45:29 08/28/15
8]
Waterloo, Ontario, N2K 3T6 Client Designed by
Phone: 519-885-3806 CROWN CASTLE USA
FAX: 519-884-3806 shoffmeyer
Compression Checks
1
Pu / Pn controls
1
Pu / Pn controls
Job Page
tnxTower PSEC Job 14083 [for UPGRADE PACKAGE] 10 of 12
Project Date
Pier Structural Engineer Corp.
198-55 Northfield Drive East 816137 - VACAVILLE (REVISED) [for Verizon app 290784 rev 14:45:29 08/28/15
8]
Waterloo, Ontario, N2K 3T6 Client Designed by
Phone: 519-885-3806 CROWN CASTLE USA
FAX: 519-884-3806 shoffmeyer
1
Pu / Pn controls
1
Pu / Pn controls
Tension Checks
1
Pu / Pn controls
Job Page
tnxTower PSEC Job 14083 [for UPGRADE PACKAGE] 11 of 12
Project Date
Pier Structural Engineer Corp.
198-55 Northfield Drive East 816137 - VACAVILLE (REVISED) [for Verizon app 290784 rev 14:45:29 08/28/15
8]
Waterloo, Ontario, N2K 3T6 Client Designed by
Phone: 519-885-3806 CROWN CASTLE USA
FAX: 519-884-3806 shoffmeyer
1
Pu / Pn controls
1
Pu / Pn controls
1
Pu / Pn controls
Job Page
tnxTower PSEC Job 14083 [for UPGRADE PACKAGE] 12 of 12
Project Date
Pier Structural Engineer Corp.
198-55 Northfield Drive East 816137 - VACAVILLE (REVISED) [for Verizon app 290784 rev 14:45:29 08/28/15
8]
Waterloo, Ontario, N2K 3T6 Client Designed by
Phone: 519-885-3806 CROWN CASTLE USA
FAX: 519-884-3806 shoffmeyer
APPENDIX B
LEG A (~340°)
B
A
)
'E
60
o
(T
er
dd
La
ng
bi
lim
lC
al
Sm
Pier Structural Engineer Corp. Job: PSEC Job 14083 [for UPGRADE PACKAGE]
Project: 816137 - VACAVILLE (REVISED) [for Verizon app 290784 rev 8
198-55 Northfield Drive East
Client:
Waterloo, Ontario, N2K 3T6 CROWN CASTLE USA Drawn by: shoffmeyer App'd:
Code: Date: Scale:
Phone: 519-885-3806 TIA-222-G 08/28/15 NTS
Path: Dwg No.
FAX: 519-884-3806 E-7
H:\PROJECTS\JOB 14000 - 14999\JOB 14000 - 14099\14083 - CCI - 816137 - VACAVILLE (REVISED) (MODs)\PASSING SA\816137_LC4_20150828.eri
August 28, 2015
60-ft Self Support Tower Structural Analysis CCI BU No 816137
Project Number 14083, Application 290784, Revision 8 Page 9
APPENDIX C
ADDITIONAL CALCULATIONS
Input Parameters
Diags 0'-20' Diags 0'-20' Diags 0'-20' Diags 40'-60' Diags 40'-60' Diags 40'-60' Piece Description
Actual tnx Adjusted Actual tnx Adjusted Elevation (20-60ft)
1.75x1.75x1/8 1.75x1.75x1/8 1.75x1.75x1/8 1.50x1.50x1/8 1.50x1.50x1/8 1.50x1.50x1/8 Angle Size
1 1 1 1 1 1 No of Angles
1.7500 1.7500 1.7500 1.5000 1.5000 1.5000 H
1.7500 1.7500 1.7500 1.5000 1.5000 1.5000 V
0.1250 0.1250 0.1250 0.1250 0.1250 0.1250 T
A325N A325N A325N A325N A325N A325N Bolt Type
0.6250 0.6250 0.6250 0.5000 0.5000 0.5000 Bolt Size/Diameter
0.6875 0.6875 0.6875 0.5625 0.5625 0.5625 Bolt Hole Size (per cl 4.6.3.1)
0.7500 0.7500 0.7500 0.6250 0.6250 0.6250 Bolt Hole Size (1/16" larger per 3.1.5)
1.0000 1.0000 1.3350 1.0000 1.0000 1.3350 End Distance
0.8750 1.0000 1.0000 0.7500 0.8750 0.8750 Edge Distance (from heel)
36 36 36 36 36 36 Fy
58 58 58 58 58 58 Fu
1.0 1.0 1.0 1.0 1.0 1.0 Ubs = 1.0 for lattice connections
Input from RISA Output Ubs = 0.5 for cope beam conns w/ multiply rows
C 3.56 3.56 3.56 4.52 4.52 4.52 Software Reactions (kips) - COMPRESSION
T 3.31 3.31 3.31 4.36 4.36 4.36 Software Reactions (kips) - TENSION
0.063 0.047 0.047 0.055 0.039 0.039 Ant = net area perpendicular with force
0.109 0.094 0.094 0.094 0.078 0.078 Agt = gross area perpendicular with force
0.078 0.078 0.120 0.086 0.086 0.128 Anv = net area inline with force
0.125 0.125 0.167 0.125 0.125 0.167 Agv = gross area inline with force
0.125 0.125 0.125 0.109 0.109 0.109 Aen = wnt & U=1 if ignoring o/s leg member (4.6.3.2)
Tensile Rupture Check (cl 4.6.3)
0.75 0.75 0.75 0.75 0.75 0.75 φt = 0.75 for tensile rupture
7.25 7.25 7.25 6.34 6.34 6.34 Pn
5.44 5.44 5.44 4.76 4.76 4.76 φtPn
49.1% 49.1% 49.1% 71.3% 71.3% 71.3% Capacity (%)
Pass Pass Pass Pass Pass Pass
Block Shear Rupture Check (4.6.3)
0.75 0.75 0.75 0.75 0.75 0.75 φt = 0.75 for block shear rupture
6.34 5.44 6.89 6.16 5.26 6.71 Pn (eqn 1: 0.6FuAnv + UbsFuAnt)
6.33 5.42 6.32 5.87 4.97 5.87 Pn (eqn 2: 0.6FyAgv + UbsFuAnt)
4.74 4.06 4.74 4.40 3.72 4.40 φtPn (governing capacity)
69.8% 81.4% 69.8% 99.0% 117.1% 99.0% Capacity (%)
Pass Pass Pass Pass Fail Pass
Bearing Strength Check (4.9.6.2)
0.8 0.8 0.8 0.8 0.8 0.8 φ = 0.80 for bearing strength
7.07 7.07 9.98 7.34 7.34 10.26 Rn (eqn 1: 1.2 (Lc+d/4) t Fu)
10.88 10.88 10.88 8.70 8.70 8.70 Rn (eqn 1: 2.4 d t Fu)
5.66 5.66 7.99 5.87 5.87 6.96 φRn (governing capacity)
63.0% 63.0% 44.6% 77.0% 77.0% 64.9% Capacity (%)
Pass Pass Pass Pass Pass Pass
Bolt Shear Check (4.9.6.3)
0.75 0.75 0.75 0.75 0.75 0.75 φ = 0.75 for bolt shear
16.57 16.57 16.57 10.60 10.60 10.60 Rn (eqn: 0.45FubAb or 0.55FuAb)
12.43 12.43 12.43 7.95 7.95 7.95 φRn (governing capacity)
28.7% 28.7% 28.7% 56.8% 56.8% 56.8% Capacity (%)
Pass Pass Pass Pass Pass Pass
Site ID # 816137
STRUCTURAL REVIEW Site Name VACAVILLE (REVISED)
OF ANCHOR RODS PSEC # 14083
PER TIA-222-G CLAUSE 4.9.9 Date 28-Aug-2015
Pg 1 of 2
A) T OWER R EACTIONS
LRFD To Existing
Download = 128.0 kips 52.3 kips Anchor Rod Capacity
Shear = 10.0 kips 4.1 kips
43.4%
Uplift = 124.0 kips 50.6 kips
Shear = 10.0 kips 4.1 kips
B) A NCHOR R OD P ARAMETERS
Quantity = 4
Diameter = 0.750 in (OD)
Type = A193 B7 (used this as ≥ A325N)
Grade Fu = 125.0 ksi
Grade Fy = 105.0 ksi Distance from top of concrete to
Threads = 10 #/in (per UNC) bottom of base plate in field
[ Formula 1 ]
where:
φ= 0.80
φRnt = 33.45 kips Using cl 4.9.6.1 gives Fub = 125.0ksi and An =0.334in²
h= 0.55 ksi
ii. Cross Check to How tnxTower Calculates capacity (based on AISC 13th Ed)
A) T OWER R EACTIONS
LRFD To New
Download = 128.0 kips 75.7 kips Anchor Rod Capacity
Shear = 10.0 kips 5.9 kips
47.1%
Uplift = 124.0 kips 73.4 kips
Shear = 10.0 kips 5.9 kips
B) A NCHOR R OD P ARAMETERS
Quantity = 2
Diameter = 1.250 in (OD)
Type = A449 (≤ 1")
Grade Fu = 120.0 ksi
Grade Fy = 85.0 ksi Distance from top of concrete to
Threads = 7 #/in (per UNC) bottom of base plate in field
[ Formula 1 ]
where:
φ= 0.80
φRnt = 93.03 kips Using cl 4.9.6.1 gives Fub = 120.0ksi and An =0.969in²
h= 0.50 ksi
ii. Cross Check to How tnxTower Calculates capacity (based on AISC 13th Ed)
CALCULATIONS:
EPOXY/GROUT LENGTH:
Allowable Capacity = 450 psi Note, we used the allowable approach as the results provided
Hole Circumference = 4.712 in²/in slightly longer lengths, as such we feel it is slightly more conservative.
All Force Bond Length = 0.00 in
All Capacity Bond Length = 31.83 in
Proof Load Bond Length = 26.78 in
EMBEDMENT LENGTH:
Top Cover Length = 6.000 in
Development Length = 24.648 in
Engagement Length = 4.125 in
½ Capacity Bond Length = 15.914 in
Required Embedment Length = 50.687 in
Download (P) 128.00 kips cl. 9.4.1 0.750 ФEB (Bearing) Type ASTM Company FDH Velocitel
Uplift (U) 124.00 kips cl. 9.4.1 0.750 ФSF (Friction) Size 7 File No. 15BVNZ1600
Shear (V) 10.00 kips 0.900 ФPW (Weight) Qty (6) 7# @ 4.00'' (0.005%) Date 8/26/2015
# of Piles 1 per base
Pier OD 30.00 in Water table 15.00 ft
Tower Type SST DESIGN OUTPUT Soil Dry 0.110 kips/ft3
Conc. Dry 0.150 kips/ft3
DOWNLOAD= 201.7 kips 63.5% Soil Sub 0.048 kips/ft3
Face base width = 5.83 ft UPLIFT = 118.2 kips 104.9% Conc. Sub 0.088 kips/ft3
Required Length (L) - ft DEPTH = 12.1 ft Shaft Area 7.854 ft²/ft
3
Total Volume 5.0 ft (incl 1ft) Pier Area 4.909 ft²
Skin Friction (SF) End Bearing (EB) Pile weight (PW) Resistance Capacity
Depth z Ult. friction Force Accumulated All. Bearing Force Per layer Accumulated Uplift Download
0.00 (ft) (psf) (kips) (kips) (psf) (kips) (kips) (kips) (kips) (kips)
UPLIFT RESISTANCE
0.42 Above Grade 0.31 0.31
3.00 3.00 0.00 0.00 0.00 55.42 2.21 57.94 52.14
4.00 1.00 0.00 0.00 0.00 0.74 58.67 52.81
6.00 2.00 1120.00 17.59 17.59 1.47 60.14 67.33
8.00 2.00 1330.00 20.89 38.48 1.47 61.62 84.32
10.00 2.00 1330.00 20.89 59.38 1.47 63.09 101.31
11.00 1.00 1330.00 10.45 69.82 0.74 63.83 109.81
12.08 1.08 1200.00 10.18 80.00 0.80 64.62 118.16
ADDED NEW RAFT TO EXISTING CAISSONS
CONSIDERED "CoG AREA" TO EACH CAISSON TO BE
87.0ft² ‐ 4.9ft² = 82.1ft²
VOLUME = 82.1ft² x 4.5ft = 369.5ft³
WEIGHT = 369.5ft³ x 150pcf = 55.42 kips
Skin Friction (SF) End Bearing (EB) Pile weight (PW) Resistance Capacity
Depth z Ult. friction Force Accumulated Ult. Bearing Force Per layer Accumulated Uplift Download
0.00 (ft) (psf) (kips) (kips) (psf) (kips) (kips) (kips) (kips) (kips)
COMPRESSION RESISTANCE
3.00 3.00 0.00 0.00 0.00 0.00 2.21 2.21 0.00
4.00 1.00 0.00 0.00 0.00 0.00 0.74 2.95 0.00
6.00 2.00 1120.00 17.59 17.59 0.00 1.47 4.42 13.19
8.00 2.00 1330.00 20.89 38.48 0.00 1.47 5.89 28.86
10.00 2.00 1330.00 20.89 59.38 0.00 1.47 7.36 44.53
11.00 1.00 1330.00 10.45 69.82 0.00 0.74 8.10 52.37
12.08 1.08 1600.00 13.57 83.39 37800.00 185.55 0.80 8.89 201.71
DOWNLOAD / UPLIFT
NOTES FORMULAS
1. Used the geotech report for skin friction values.
2. Used the geotech for end bearing. Download Formula: P ≤ ФEB · EB + ФSF · SF
3. Used foundation mapping for 2.5' x 12.08' deep caisson. Uplift Formula: U ≤ ФSF · SF + ФPW · PW
Note: Used 1/3 of global shear
and half of the Caisson depth
to calculate moment.
Case 1 Case 2
Dist. From Edge to Neutral Axis: 2.71 in
Extreme Steel Strain, єt: 0.0259
Minimum Rho Check: єt > 0.0050, Tension Controlled
Actual Req'd Min. Rho: 0.33% Flexural Reduction Factor,φ: 0.900
Provided Rho: 0.50% OK
Drilled_Shaft_Moment_Capacity, DSMC, Version 1.1 - Effective 04/01/ 2010 Analysis Date: 28/08/2015
# #%"( "$
"!
>
>$
-7)0%66 ? @ 7-** 3-0A
"
#!
+
+
+
+
+
+
Seismic shear does not exceed 50% of wind shear. No further analysis is required per section 2.7.3 of TIA‐222‐G.
Home About This Site Lat/Long Finder Related Resources Sponsors About ATC Contact
Search Results
Latitude: 38.3286
Longitude: -121.9969
ASCE 7-05: 85
ASCE 7-93: 73
2015 Google Imagery 2015 , DigitalGlobe, Landsat, U.S. Geological Survey, USDA Farm
*MPH(Miles per hour) Service
Report Agency
a map error
**MRI Mean Recurrence Interval (years)
Sponsored by the ATC Endowment Fund • Applied Technology Council • 201 Redwood Shores Parkway, Suite 240 • Redwood City, California 94065 • (650) 595-1542
BU#: 816137
Site Name: VACAVILLE (REVISED)
App#: 290784 Rev 8 [PSEC Job 14083]
Exposure B
Continuous Ridge
Exposure C
Notes: 1)
Hill Feature is assumed to be isolated per section 1.8 of
the Crown Castle standard for the Determination of
Topographic Factors (ENG-PRC-10040).
Flat Topped Hill 2) Base Kzt may differ slightly from TNX value due
to differences in where the base line is established.
This does not effect the results in anyway.
Continuous Escarpment
Topographic Input
Crest Point Elevation (ft. AMSL) 739
Base Point Elevation (ft. AMSL) 252
Mid-Height Elevation (ft. AMSL) 495.5
Crest to Mid-Height Distance (L/2) (ft.) 715
Tower Point Elevation (ft. AMSL) 725
Structure Upwind/Downwind Distance (x)(ft.) 41
tnxTower Input KZT (RSM-03)
Topographic Category 5
Crest Height, H (ft.) 487 At Base:
Slope Distance, L (ft.) 1430 2.922²
Distance from Crest, x (ft.) 41
August 28, 2015
60-ft Self Support Tower Structural Analysis CCI BU No 816137
Project Number 14083, Application 290784, Revision 8 Page 10
APPENDIX D
UPGRADE DRAWINGS