Characteristics:
– Pilot controlled 2 stage control valve
– Closed loop control of size and direction of a flow
– Suitable for control of position, velocity, pressure and force
– Pilot control valve:
direct operated control valve, position controlled, with
pressure return of control pressures
– Main stage:
Self-centering, position controlled
– Integrated open and closed loop control
– For subplate mounting:
Interfaces to DIN 24 340 Form A
Subplates to data sheet RE 45 054 to 45 060 (separate
order), see pages 12 to 15
H/A 4601/95
Type 4WRTE10...-3X/6BG24.Z31…
List of contents
Symbols
Type WRTE..-3X/... A B
a 0 b
X P T Y
Type WRTE..-3X/..E. A B b a
a 0 b
P T Y
Type WRTE..-3X/..ET.A B
a 0 b
P T X A P T B Y
Type WRTE..-3X/..T. A B
a 0 b
X P T
1/16
RE 29 082/03.95
Structure, function description, section
Structure:
The valve consists of 3 main component groups:
• Housing (1) with main spool (2)
• Integrated electronics with inductive transducer (3) of main
stage
• Pilot control valve (4) with spool sleeve unit (5),
inductive transducer (6) and pressure return for neutral
setting of main spool (2)
12 7 5 4 8 13 6
A C
ST1
A C
B B D D
Setting
transducer zero
point
X T A P B T Y
9 10 1 2 11 3
Type 4 WRTE 10…-3X/… Section drawing see page 16
Function description:
• With proportional solenoid (7,8) at rest, neutral position of main Interruption of supply voltage:
spool (2) through centralising spring (9) and pressure return • Integrated electronics switches the solenoid off when supply
• Control of main spool (2) via the pilot control valve (4) - the main voltage is interrupted or with cable break
spool is positioned in closed loop control • Independent pressure control on same level in the control
• Control of spool of pilot control valve (4) through alteration of chambers (10 and 11) through the pilot control valve
solenoid force of proportional solenoid (7,8) • When pressure supply is interrupted centralising of main
• Connection of command and actual values in the integrated spool by centralising spring (9) occurs
control electronics • Neutral position of main spool (2)
• Pilot oil supply to pilot control valve internally via port P or
externally via port X Warning: The interruption of supply voltage leads to abrupt
Pilot oil drain internally via port T or externally via Y to tank standstill of the control axis.
• When command value is at 0 V the electronics moves the main The accelerations occurring may cause machine
spool (2) into neutral position damage.
Valves with the spool symbol "V" do not align
accurately in the hydraulic neutral position!
2/16
RE 29 082/03.95
Ordering code
4 WRTE – 3X / 6B G24 / *
Electrically operated Further
2-stage directional control valve details
in 4-way design with in clear text
integrated control electronics
w/o code = O-rings
Size 10 = 10 R= R-rings
Size 16 = 16
Size 25 = 25 M= NBR-seals,
Size 32 = 32 suitable for mineral oil
to DIN 51 524
Symbols V= Viton seals,
A B suitable for
a 0 b a 0 b phosphate ester
3/16
RE 29 082/03.95
Technical data (For application outside these parameters please consult us!)
Size 10 Size 16 Size 25 Size 25 1) Size 32
General
Weight kg 8,7 11,2 16,8 17 31,5
Installation position optional, preferrably horizontal (commissioning instructions see RE 07 700)
Ambient temperature range °C 0 to + 60
Hydraulic (measured at p = 100 bar, ν = 32 mm2/s, t = 40 °C)
Operating pressure: – Pilot control valve Pilot oil supply bar 25 to 315
– Main valve, ports P, A, B bar up to 315 up to 350 up to 350 up to 210 up to 350
Return pressure: – Port T Pilot oil supply internal bar static < 10
Pilot oil supply external bar up to 315 up to 250 up to 250 up to 210 up to 250
– Port Y bar static < 10
Nominal flow qV N ± 10 % at ∆p = 10 bar 2) L/min 25
50 125 220
100 200 350 500 600
Flow of main valve (max. permissible) L/min 170 460 870 1000 1600
Control spool stroke (3. stage) mm ± 3,5 ±5 ±6 ±6 ±9
Pilot control flow at port X or Y with jump-like
input signal from 0 to 100% (315 bar) L/min 6,3 13,7 25,5 25,5 26,5
Pressure fluid Mineral oil (HL, HLP) to DIN 51 524
Fluid cleanliness Maximum permissible degree of contamination of pressure fluid
to NAS 1638, Class 7 (pilot stage) and class 9 (main stage)
Recommendation:Filter with a minimum retention rate of
ß5 ≥ 75 with pilot stage; ß15 ≥ 75 with main stage
Pressure fluid temperature range °C 10 to 80; preferrably 40 to 50
Viscosity range mm2/s 20 to 380; preferrably 30 to 45
Hysteresis % ≤ 0,2
Response sensitivity % ≤ 0,1
Electrical
Insulation of valve to DIN 40 050 IP 65
Type of voltage direct voltage
Type of signal analogue
Power W 72
Control electronics VT 13 060 (integrated into valve, see below and page 5)
1) Type 4WRTE25…500.-3XH/… (High Flow-design)
2) ∆p = Valve pressure difference
Electrical connection
Plug position Signal
A Supply voltage A 24 VDC (18 to 30 VDC)
B Imax = 3 A
C Impulse load = 4 A B 0V
D
Release input 1) C 4 to 24 VDC
E Differential D Command value ± 10 V 3)
F input E 0 V reference potential
PE Measuring output F ± 10 V actual value 2) against B
Integrated 1) Before adding the release signal (commissioning, restart after fault) the command
electronics value must be set at 0 V.
(see page 5) 2) Signal > 14 V means valve not ready for operation, i.e. no release signal is present or a
monitoring unit signals an error (RL≥100 kΩ).
3) Current input ± 10 mA as option, input resistance 1 kΩ;
to be specified in the ordering code -280 under "further details"
Command value: Reference potential at E and positive command value at D causes flow from P to A and B to T
Reference potential at E and negative command value at D causes flow from P to B and A to T
Conn. cable: Recommendation: up to 25 m cable length type LiYCY 7 x 0,75 mm2; up to 50 m cable length type LiYCY 7 x 1 mm2
External diameter 6,5 to 9,5 mm; connect screen to ⊥ only on supply side.
Note: Electrical signals (i.e. actual value) emitted by a valve electronics must not be used to switch off safety-
related machinery functions!
(Please not the "Security requirements for hydraulically operated fluid power machinery and parts -
Hydraulics" prEN 982!)
4/16
Flow direction:
Positive signal at Pin D and reference
potential at Pin E causes flow P → A
Pilot current
Output
Flow controller stage
Zero point
U
Command value ± 10 D U I
E U Controller Controller Pulse output
main stage pilot stage stage Act. current Solenoid A
value
U
Option current input I
(ordering code -280 D I Pilot
under "further details") E U current Output
Command value ± 10 mA Flow controller stage
U
I
Interlock
Act. current Solenoid B
value
U
Actual value ± 10 V I
(error message U > 14 V) F
+ UH Cable break
+ UM
+ UM
Release 4 to 24 VDC C
Monitoring
Transducer
+ UL
pilot stage
Cable break
U + UH
U
0V B
PE Sensitivity
main stage
Original
Block circuit diagram / terminal connection of integrated electronics type VT 13 060
main stage
RE 29 082/03.95
5/16
RE 29 082/03.95
Operating curves (measured at ν = 32 mm2/s and t = 40 °C) all sizes
80
60
40
in % →
20
–5 –4 –3 –2 –1
∆p L
1 2 3 4 5
pS
– 20
←
– 40
– 60
– 80
– 100
UE
← in % →
UEN
Leakage flow 4WRTE…V with pilot control valve in neutral position of main spool
2 3 5
350
1
315
300
Operating pressure in bar →
250
4
210
200
150
100
1 = Size 10
2 = Size 16
3 = Size 25
50
4 = Size 25
(High Flow-type)
5 = Size 32
0 2 4 6 8 10 12 14 16 18 20
Leakage flow in L/min →
6/16
RE 29 082/03.95
Operating curves (measured at 10 bar valve pressure difference or 5 bar per control edge)
1 1
80 80
2 2
Flow in % →
Flow in % →
60 60
40 40
20 20
10 10
0 25 50 75 100 0 25 50 75 100
15 36,25 57,5 78,75 100 15 36,25 57,5 78,75 100
Command value in % 1) → Command value in % 1) →
100
80 A→T B→T
Flow in % →
60
P→A
40
20 P→B
0
– 100 – 80 – 60 – 40 – 20 0 20 40 60 80 100
Command value in % →
7/16
RE 29 082/03.95
Transition function with jump-like electrical input signals Size 10
Signal alteration in %
100 0 –100
75 0 – 75
measured at:
Stroke in % →
pS = 100 bar
ν = 32 mm2/s
50 0 – 50 t = 40 °C
25 0 – 25
0 10 20 0 10 20
Time in ms →
+5
Phase angle in ° →
–5
– 10 180
– 15
– 20 90
– 25
Signal ± 10 %
– 30
Signal ± 25 %
0
1 2 5 10 20 50 100 200 Signal ± 100 %
Frequency in Hz →
170 1
100
Flow in L/min →
50
25
20
10 20 50 100 200 300
Valve pressure difference in bar →
1 = recommended flow
limitation
8/16
RE 29 082/03.95
Transition function with jump-like electrical input signals Size 16
Signal alteration in %
100 0 –100
75 0 – 75
Stroke in % →
measured at:
pS = 100 bar
50 0 – 50 ν = 32 mm2/s
t = 40 °C
25 0 – 25
0 10 20 30 0 10 20 30
Time in ms →
+5
0 270
Pilot pressure pS = 100 bar
Amplitude ratio in dB →
Phase angle in ° →
–5
– 10 180
– 15
– 20 90
– 25
Signal ± 10 %
– 30 0 Signal ± 25 %
1 2 5 10 20 50 100 200 Signal ± 100 %
Frequency in Hz →
460 1
300
Flow in L/min →
200
125
100
10 20 50 100 200 300
Valve pressure difference in bar →
1 = recommended flow
limitation
9/16
RE 29 082/03.95
Transition function with jump-like electrical input signals Size 25
Signal alteration in %
100 0 –100
75 0 – 75
Stroke in % →
measured at:
pS = 100 bar
50 0 – 50 ν = 32 mm2/s
t = 40 °C
25 0 – 25
0 10 20 30 40 0 10 20 30 40
Time in ms →
+5
Phase angle in ° →
–5
– 10 180
– 15
– 20 90
– 25
Signal ± 10 %
– 30 0 Signal ± 25 %
1 2 5 10 20 50 100 200 Signal ± 100 %
Frequency in Hz →
H
1000 1
870 1
Flow in L/min →
500
350
220
200
10 20 50 100 200 300
Valve pressure difference in bar →
1 = recommended flow
limitation
H = High Flow-type
10/16
RE 29 082/03.95
Transition function with jump-like electrical input signals Size 32
Signal alteration in %
100 0 –100
measured at:
75 0 – 75 pS = 100 bar
ν = 32 mm2/s
Stroke in % →
t = 40 °C
50 0 – 50
25 0 – 25
0 20 40 60 80 0 20 40 60 80
Time in ms →
+5
270
Pilot pressure pS = 100 bar
0
Amplitude ratio in dB →
Phase angle in ° →
–5
– 10 180
– 15
– 20 90
– 25
Signal ± 10 %
Signal ± 25 %
– 30 0
1 2 5 10 20 50 100 200 Signal ± 100 %
Frequency in Hz →
1600 1
Flow in L/min →
1000
600
500
10 20 50 100 200 300
Valve pressure difference in bar →
1 = recommended flow
limitation
11/16
RE 29 082/03.95
Unit dimensions size 10 (Dimensions in mm)
1 2 3 4 5 11
50
176
170
T A P B T
86
6
35
42 105 70
243,5
311
9 7 10 12 8
7,9 61,9
13,5
0,01/100mm
P R max 4
X A B Y
11,1
46
73
T T
Required surface finish of mating
piece
27 54
108
1 Pilot control valve Subplates to data sheet RE 45 054 and valve fixing screws
2 Electrical connection must be ordered separately.
3 Cables and plugs Subplates: G 534/01 (3/4"BSP)
4 Inductive transducer (pilot control valve) G 535/01 (3/4"BSP) with ports X and Y
G 536/01 (1"BSP) with ports X and Y
5 Plug 6-pin +PE to DIN 43 563; order no. 021 267
Valve fixing screws:
6 Type label 4 off M6 x 45 DIN 912–10.9; MA = 15,5 Nm
7 Main valve
8 Control electronics and inductive
transducer (main valve)
9 R-ring 10,8 x 14,4 x 1,7 (O-ring 10,82 x 1,78)
Ports X, Y
10 R-ring 12 x 16 x 1,9 (O-ring 12 x 2)
Ports A, B, P, T
11 Space requirement for connection cable and
removal of plug
12 Machined valve mounting surface,
Position of ports to DIN 24 340 Form A
(Ports X, Y on request)
12/16
RE 29 082/03.95
Unit dimensions size 16 (Dimensions in mm)
1 2 3 4 5 11
50
186
A B Y
168
96
43
36 154 Ø3
3
294 91
357
7 10 6 9 12 8 13
29 101,6
12
0,01/100mm
R max 4
T P X
69,9
94
158
1 Pilot valve Subplates to data sheet RE 45 056 and valve fixing screws
2 Electrical connection must be ordered separately.
3 Cable connection and plug Subplates: G 172/01 (3/4"BSP)
4 Inductive transducer (pilot control valve) G 172/02 (M27 x 2)
5 Plug 6-pin +PE to DIN 43 563; order no. 021 267 G 174/01 (1"BSP)
G 174/02 (M33 x 2)
6 Type label Valve fixing screws:
7 Main valve 2 off M6 x 60 DIN 912–10.9; MA = 15,5 Nm
8 Control electronics and inductive 4 off M10 x 60 DIN 912–10.9; MA = 75 Nm
transducer (main valve)
9 R-ring 12 x 16 x 1,9 (ports X, Y)
10 R-ring 21,9 x 27,1 x 2,5 (ports A, B, P, T)
11 Space requirement for connection cable and
removal of plug
12 Machined valve mounting surface,
Position of ports to DIN 24 340 Form A
13 Locating pin (2 off)
13/16
RE 29 082/03.95
Unit dimensions size 25 (Dimensions in mm)
1 2 3 4 5 11
50
6
H1
180
H2
41
37 191 Ø6
4
L2 B1
L1
7 10 9 12 8 13
21 130 Type B1 H1 H2 L1 L2 L3
14
0,01/100mm
X A B
R max 4
4WRTE25…500.-3XH/…
Special connection holes for
ports P, T, A and B Required surface finish of
L3 mit d = 32 mm mating piece
1 Pilot valve Subplates to data sheet RE 45 058 and valve fixing screws
2 Electrical connection must be ordered separately.
3 Cable connection and plug Subplates: G 151/01 (1"BSP)
4 Inductive transducer (pilot control valve) G 154/01 (1 1/4"BSP)
G 156/01 (1 1/2"BSP)
5 Plug 6-pin +PE to DIN 43 563; order no. 021 267
Valve fixing screws:
6 Type label 6 off M12 x 60 DIN 912–10.9; MA = 130 Nm
7 Main valve
8 Control electronics and inductive
transducer (main valve)
9 R-ring 19 x 25,3 x 2,9 (O-ring 19 x 3)
10 R-ring 27 x 33 x 2,9 (O-ring 27 x 3)
11 Space requirement for connection cable and
removal of plug
12 Machined valve mounting surface,
Position of ports to DIN 24 340 Form A
13 Locating pin (2 off)
14/16
RE 29 082/03.95
Unit dimensions size 32 (Dimensions in mm)
1 2 3 4 5 11
50
6
242
191
152
49
59 254 Ø6
4
426,5 197
507
9 7 10 12 8 13
23 190,5
20,5
T P
Y
0,01/100mm
159
200
R max 4
X A B
Required surface finish of
mating piece
114,5
257
1 Pilot valve Subplates to data sheet RE 45 060 and valve fixing screws
2 Electrical connection must be ordered separately.
3 Cable connection and plug Subplates: G 157/01 (1 1/4"BSP)
4 Inductive transducer (pilot control valve) G 157/02 (M48 x 2)
G 158/10 (Flange)
5 Plug 6-pin +PE to DIN 43 563; order no. 021 267
Valve fixing screws:
6 Type label 6 off M20 x 80 DIN 912–10.9; MA = 430 Nm
7 Main valve
8 Control electronics and inductive
transducer (main valve)
9 R-ring 19 x 23 x 3 (O-ring 19 x 3)
10 R-ring 42,5 x 48,5 x 3 (O-ring 42 x 3)
11 Space requirement for connection cable and
removal of plug
12 Machined valve mounting surface,
Position of ports to DIN 24 340 Form A
13 Locating pin (2 off)
15/16
RE 29 082/03.95
Pilot oil supply
Type 4WRTE…-3X/… External pilot oil supply Type 4WRTE...-3X/...ET... Internal pilot oil supply
External pilot oil drain Internal pilot oil drain
With this type the pilot oil supply is from a separate control circuit With this type the pilot oil supply is from the P-channel of the main
(external). valve (internal).
The pilot oil drain is not conveyed into the T-channel of the main The pilot oil drain is conveyed directly into the T-channel of the
valve but separately into the tank via port Y (external). main valve (internal).
The ports X and Y should be closed on the connection plate.
Type 4WRTE…-3X/…E… Internal pilot oil supply Type 4WRTE…-3X/…T… Internal pilot oil supply
External pilot oil drain Internal pilot oil drain
With this type the pilot oil supply is from the P-channel of the main With this type the pilot oil supply is from a separate control circuit
valve (internal).. (external).
The pilot oil drain is not conveyed into the T-channel of the main The pilot oil drain is conveyed directly into the T-channel of the
valve but separately into the tank via port Y. main valve (internal).
Port X should be closed on the connection plate. Port Y should be closed on the connection plate.
Size 10 Size 16
Section A – A Section C – C Section D – D Section C – C
X Y Y T 1
1 Y 2
T P X
Pilot oil supply external: 1 closed Pilot oil supply external: P closed
internal: 1 open internal: P open
Pilot oil drain external: 2 closed Pilot oil drain external: 1 closed
internal: 2 open internal: 1 open
Size 25 Size 32
Section B – B Section A – A Section A – A Pilot valve
P T
1
Pilot control valve
P Y X
2 P 1
P T T
Main valve
XY
X
T 2
Cover Main valve
Pilot oil supply external: 1 closed Pilot oil supply external: 1 closed
internal: 1 open internal: 1 open
Pilot oil drain external: 2 closed Pilot oil drain external: 2 closed
internal: 2 open internal: 2 open