Professional Documents
Culture Documents
Design of Isolated Footing Extract From Unni Krishnan Pillai Devdas Menon Book PDF
Design of Isolated Footing Extract From Unni Krishnan Pillai Devdas Menon Book PDF
14.1 INTRODUCTION
In a typical structure built on ground, that part of the structure which is located above
ground is generally referred to as the superstructure, and the part which lies below
ground is referred to as the substructure or the ‘foundation structure’ (or simply,
foundation). The purpose of the foundation is to effectively support the
superstructure by
1 transmitting the applied load effects (reactions in the form of vertical and
horizontal forces and moments) to the soil below, without exceeding the ‘safe
bearing capacity’ of the soil, and
2 ensuring that the settlement of the structure is within tolerable limits, and as
nearly uniform † as possible.
Further, the foundation should provide adequate safety against possible instability
due to overturning or sliding and/or possible pullout. Design against forces inducing
overturning and sliding are of special importance in the design of retaining walls,
whose very purpose is to provide lateral support to earthfill/embankment in order to
retain the side of the earthfill in a vertical position. The choice of the type of
foundation depends not only on the type of the superstructure and the magnitudes
and types of reactions induced at the base of the superstructure, but also on the nature
of the soil strata on top of which the substructure is to be founded. This comes under
†
Non-uniform (differential) settlement of a structure generally results in significant stresses in
the superstructure, which are usually not foreseen in design. In order to avoid this, it is
necessary to ensure that the different footings in a building are proportioned in such a way as
to result in soil pressures of nearly equal magnitude under their bases (under permanent loads).
In those exceptional situations where differential settlements are unavoidable, it is necessary to
consider this in the analysis of the structure itself; this will involve a trial-and-adjustment
process, as the settlements are not known a priori.
656 REINFORCED CONCRETE DESIGN
†
The design of pile caps is not included in this chapter.
‡
Shear forces are also induced in columns, which may result in significant horizontal forces at
column bases, under lateral loads. These are resisted by friction between the underside of the
footing and the soil below, and also by passive resistance of the soil adjoining the sides of the
footing, and in some cases, by ‘keys’ cast integrally with the footing.
DESIGN OF FOOTINGS AND RETAINING WALLS 657
P P P
P1 P2 P1 P2
central beam
(if required)
P1 P2
masonry or
beam r c wall
P/unit length
†
Tie beams are also sometimes provided (for this purpose), interconnecting different columns
at the top of pedestal level (about 150 mm below ground level). Plinth beams also serve as tie
beams.
‡
The raft foundation consists of a thick slab which may be (i) of uniform thickness (flat plate),
(ii) with locally thicker panels near column bases (flat slab), or (iii) with stiffening beams
interconnecting the columns.
DESIGN OF FOOTINGS AND RETAINING WALLS 659
†
It is more common to have stepped masonry (stone or brick) foundation for masonry walls.
‡
The soil bearing capacity, according to soil mechanics theory, depends on the size of the
footing, and this is to be accounted for (approximately) in the recommendation made in the
Soil Report.
660 REINFORCED CONCRETE DESIGN
WL/EL) should, therefore, be those applicable for the serviceability limit state and
not the ‘ultimate limit state’ [refer Section 3.6.3] when used in association with qa.
Another point to be noted is that the prescribed allowable soil pressure qa at a
given depth is generally the gross pressure, which includes the pressure due to the
existing overburden (soil up to the founding depth), and not the net pressure (in
excess of the existing overburden pressure). Hence, the total load to be considered in
calculating the maximum soil pressure q (≤ qa) must include the weight of the footing
itself and that of the backfill. Often, in preliminary calculations these weights are
accounted for approximately as 10 – 15 percent of the axial load on the column;
however, this assumption should be verified subsequently.
GROUND LEVEL
backfill
ΔP
footing
FOUNDING
LEVEL GROSS SOIL PRESSURE
q = (P+ΔP)/A
area A = BL
B
DESIGN OF FOOTINGS AND RETAINING WALLS 661
Fig. 14.2 Assumed uniform base pressure distribution under concentric loading
Limiting q to the allowable soil pressure qa will give the minimum required area of
footing:
P + ΔP
Areqd = (14.1a)
qa
e = M/P
e P
ΔP ΔP
C FOOTING C FOOTING
(a) (b)
P
H
e
resultant thrust
P
H
C FOOTING
(c)
662 REINFORCED CONCRETE DESIGN
If the resultant loading eccentricity e = M/(P + ΔP) lies within the “middle third” of
the footing (i.e., e ≤ L 6 ), it is seen that the entire contact area of the footing is
subject to a (nonuniform) pressure which varies linearly from qmin to qmax
[Fig. 14.4(a)]. These pressures are easily obtained by superposing the separate
effects due to the direct load (P + ΔP) and the bending moment M = (P + ΔP) e:
( P + ΔP ) ( P + Δ P )e
q max,min = ± (14.2a)
A Z
with area A = BL and section modulus Z = BL2/6, where L is the length of the footing
in the direction of the eccentricity e, and B the width of the footing. Accordingly,
( P + ΔP ) ⎛ 6e ⎞
qmax,min = ⎜1 ± ⎟ for e ≤L6 (14.2b)
A ⎝ L⎠
In the limiting case of e = L 6 , qmin = 0 and qmax = 2(P + ΔP)/A, resulting in a
triangular pressure distribution. The uniform pressure distribution q = (P + ΔP)/A
[Eq. 14.1] is obtained as special case of Eq. 14.2b, with e = 0.
This limiting case of e = L 6 , is valid only for uniaxial bending. In case of bi-
axial bending, the limiting case shall be taken as
†
Eccentricities in loading can be quite significant in footings which support columns that form
part of a lateral load resisting frame. However, as the lateral loads are generally assumed to
act (with maximum values) in only one direction at a time, the problem is essentially one of
uniaxial eccentricity . Eccentricities in both directions should be considered, but usually only
one at a time.
DESIGN OF FOOTINGS AND RETAINING WALLS 663
ex ey
+ ≤1 (14.2c)
Lx / 6 L y / 6
Case 2: e >L6
When the resultant eccentricity e exceeds L/6, Eq. 14.2 becomes invalid because it
will yield a negative value for qmin, implying a tensile force at the interface.
However, such tension resisting capacity cannot be practically expected from soil † .
Assuming a triangular pressure distribution (considering the soil under compression
alone), and considering a collinear line of action of the resultant soil reaction R with
the eccentric load P + ΔP, with R = P + ΔP (for static equilibrium), [Fig. 14.4(b)],
2( P + ΔP)
qmax = (14.3)
BL′
†
In fact, it can be expected that the soil will tend to separate from the footing base, thereby
offering no pressure whatsoever in the base regions farthest removed from qmax.
664 REINFORCED CONCRETE DESIGN
P P
M M
P + ΔP P + ΔP
M
M e=
e= P + ΔP
P + ΔP c = 0.5L – e
ΔP ΔP
qmax
qmax
qmin
R = P + ΔP
R = P + ΔP
L′ = 3c
L
L
(a) e < L/6 (b) e > L/6
P
M
H
resultant thrust
M/P
ΔP
q = (P + ΔP) / (BL)
L/2 L/2
P + ΔP
(c) e =0
Fig. 14.4 Assumed linear base pressure distributions under uniaxially eccentric
loading on rectangular footings
L ′ = 3c ⎫
⎬ (14.4)
c = 0.5 L − e ⎭
Thus, it is seen that the effective length of contact is reduced from L to L ′ = 3c,
and the maximum soil pressure qmax is increased from (P + ΔP)/A to twice the load
(P + ΔP) divided by the effective area BL′ . In order to limit qmax to the allowable
bearing pressure qa, and also to maximise the effective bearing area ratio L ′ L , it
may be necessary to design a footing with a large base area. Such footings are
commonly encountered in industrial buildings where columns are relatively lightly
loaded axially, but subject to high bending moments due to lateral wind loads or
eccentric gantry crane loads.
It may be noted that highly nonuniform base pressures (especially under sustained
eccentric loads) are undesirable as this can result in possible tilting of the footing.
DESIGN OF FOOTINGS AND RETAINING WALLS 665
Hence, proportioning of the footing base should be such as to make the contact
pressure as uniform as possible.
†
Against overturning, the Code (Cl. 20.1) permits a reduced minimum factor of safety of 1.2 if
the overturning moment is entirely due to dead loads. However, it is advisable to apply a
uniform minimum factor safety of 1.4 in all cases of loading.
666 REINFORCED CONCRETE DESIGN
transfer of horizontal shear forces (due to lateral loads) at the base of the
wall/column.
The restoring moment, counterbalancing the overturning moment due to
lateral/eccentric loads is generally derived from the weight of the footing plus
backfill. In some cases, this may call for footings with large base area [refer
Fig. 14.4(b)] and large depths of foundation. However, in cases where the
overturning moment (not due to wind or earthquake) is not reversible, the problem
can be more economically solved by suitably making the column/wall eccentric to
the centre of the footing [refer Fig. 14.4(c)].
Another possibility, relatively rare in practice, is the case of pullout of a
foundation supporting a tension member. Such a situation is encountered, for
example, in an overhead tank (or silo) structure (supported on multiple columns),
subjected to a very severe lateral wind load. Under minimal gravity load conditions
(tank empty), the windward columns are likely to be under tension, with the result
that the forces acting on these column foundations will tend to pull out the column-
footing from the soil. The counteracting forces, comprising the self weight of the
footing and the weight of the overburden, should be sufficiently large to prevent such
a ‘pullout’. If the tensile forces are excessive, it may be necessary to resort to tension
piles for proper anchorage.
†
As mentioned in Section 3.6.3, the partial load factor may be taken as unity in general —
except for the load combination DL + LL + WL/EL, where a partial load factor of 0.8 is
applicable for live loads (LL) and for wind loads (WL)/earthquake loads (EL).
DESIGN OF FOOTINGS AND RETAINING WALLS 667
P
M
ΔP
qmin
qmax
gross soil
pressure
=
ΔP/A
+
P M
+
P M A Z
− net soil
A Z pressure
(a)
Pu
Mu
Pu M u
qu, min qu,max = +
A Z
(b)
Fig. 14.5 Net soil pressure causing stresses in a footing
limit the crack-width to 0.3 mm in a majority of footings, and for this the general
detailing requirements will serve the purpose of crack-width control [Ref. 14.1].
Although the minimum cover prescribed in the Code (Cl. 26.4.2.2) is 50 mm, it
is desirable to provide a clear cover of 75 mm to the flexural reinforcement in
all footings.
critical sections
for moment
L
a a
d/2
B
b b b+d
d/2
Pu
critical section for a+d
Mu one–way shear critical section (all
d
around) for two–
way shear Vu2
Vu1
d (b)
qu
(a) C
wall
critical sections for
moment t/4
one-way t d masonry
shear wall
two-way
d/2 shear
d/2
Pu Pu
Mu
Mu d
critical section for
moment
d2 critical section
d1 for shear
d
d
qu qu
(c) (d)
‡
For the purpose of calculating the design shear strength τ c of concrete, a nominal
percentage of flexural tensile reinforcement (pt = 0.25) may be assumed (in preliminary
calculations).
DESIGN OF FOOTINGS AND RETAINING WALLS 671
2
Reinforcement in central band width = Ast ,short × (14.5)
β +1
where
Ast , short ≡ total flexural reinforcement required in the short direction
and β ≡ ratio of the longside (L) to the short side (B) of the footing.
This reinforcement is to be uniformly distributed within the central band width
(equal to width B), and the remainder of the reinforcement distributed uniformly in
the outer portions of the footing, as shown in Fig. 14.7. This is done to account
(approximately) for the observed variation of the transverse bending moment along
the length of the footing.
β = L/B
B
X X
B
s2 s1 s2
SECTION ‘XX’
These special detailing requirements are strictly intended for footings with
uniform slab thickness. In the case of sloped footings, it usually suffices to provide
uniformly distributed reinforcement in the short direction also, as the reduced
bending moment in the outer portions is coupled with reduced effective depths in
these regions. In the long direction also, the common practice is to provide
uniformly spaced reinforcement throughout the width of the footing, despite the
variations in depth.
In general, the percentage flexural reinforcement requirement in footing base slabs
is low, owing to the relatively large thickness provided on shear considerations. At
any rate, the reinforcement should not be less than the minimum prescribed for slabs
[refer Chapter 5], unless the footing is designed as a plain concrete (pedestal)
footing. Furthermore, the percentage reinforcement provided should be adequate to
mobilise the required one-way shear strength in concrete.
It is advisable to select small bar diameters with small spacings, in order to reduce
crackwidths and development length requirements.
Development length requirements for flexural reinforcement in a footing should
be satisfied at the sections of maximum moment, and also at other sections where the
depth is altered. Shortfall in required development length can be made up by
bending up the bars near the edges of the footings. This may be required in footings
with small plan dimensions.
Furthermore, the longitudinal reinforcement in the column/pedestal must also
have the required development length, measured from the interface between the
column/pedestal and the footing. When the column is subjected to compression
alone (without the bars being subject to tension), it is possible to achieve a full
transfer of forces from the column/pedestal to the footing by bearing, as discussed in
the next section (Section 14.4.7). Where this is not possible, and the transfer of force
is accomplished by reinforcement, such reinforcement must also have adequate
development length on each side.
where A2 is the loaded area at the column base, and A1 the maximum area of the
portion of the supporting surface that is geometrically similar to and concentric with
the loaded area. In the case of stepped or sloping footings, the area A1 is to be taken
as that of the lower base of the largest frustrum of a pyramid (or cone) contained
†
This is equally applicable in the case of force transfer from the column base to the pedestal
(if provided) and from the pedestal base to the footing.
DESIGN OF FOOTINGS AND RETAINING WALLS 673
wholly within the footing (with area A2 on top) with a side slope of 1 in 2, as shown
in Fig. 14.8(a). The factor A1 A2 in Eq. 14.6 allows for the increase in concrete
strength in the bearing area in the footing due to confinement offered by the
surrounding concrete. This factor A1 A2 is limited to 2.0. A limitation on the
bearing stress is imposed because very high axial compressive stresses give rise to
transverse tensile strains which may lead to spalling, lateral splitting or bursting of
concrete. This possibility, however, can be countered by providing suitable
transverse and confinement reinforcement.
area A1 geometrically
similar to A2
A2
A2
1 1
2 2
A1
column or
pedestal
column
column bars
or
dev. length for
development pedestal construction joint column bars
length
dowel bar
(b) reinforcement across column–footing interface
It should be noted that fbr, max may be governed by the bearing resistance of the
concrete in the column at the interface (for which A1 A2 is obviously unity),
rather than that of the concrete in the footing (for which 1 < A1 A2 ≤ 2). If the
actual compressive stress exceeds fbr,max, then the excess force is transferred by
reinforcement, dowels or mechanical connectors. For transferring a moment at the
column base (involving tension in the reinforcement), it may be necessary to provide
the same amount of reinforcement in the footing as in the column, although some
relief in the compression reinforcement is obtainable on account of transfer through
674 REINFORCED CONCRETE DESIGN
bearing. This may be achieved by either continuing the column/pedestal bars into the
footing or by providing separate dowel bars across the interface as depicted in
Fig. 14.8(b). The diameter of dowels should not exceed the diameter of the column
bars by 3 mm. Furthermore, the reinforcement provided across the interface must
comprise at least four bars, with a total area not less than 0.5 percent of the cross-
sectional area of the supported column or pedestal [refer Cl. 34.4.3 of the Code].
Finally, it should be ensured that all reinforcement provided across the interface
(whether by extension of column bars or dowels) must have the necessary
development length in compression or tension, (as applicable) on both sides of the
interface.
Where pedestals are provided, and full force transfer is possible at the interface of
column and pedestal, no reinforcement is theoretically required in the pedestal.
However, the Code (Cl. 26.5.3.1h) specifies that nominal longitudinal reinforcement
(i.e., in a direction parallel to the column load) of not less than 0.15 percent of the
cross-sectional area should be provided, for reasons similar to those pertaining to
minimum reinforcement in columns [refer Section 13.3.3].
†
This is only a convenient idealisation; the actual state of stress is difficult to assess.
DESIGN OF FOOTINGS AND RETAINING WALLS 675
where qmax is the maximum soil pressure under service loads, as defined earlier
[Eq. 14.2a, Fig. 14.4a].
(L–b)/2 b
plain concrete
pedestal
D strut action
α
tie force
nominal reinforcement for tie action
(and temp. and shrinkage effects)
L
(a) (b)
An expression for the thickness D of the footing block is obtainable [Fig. 14.9] as:
D = ( L − b )(tan α ) 2
where b is the width of the column and the expression for tanα in Eq. 14.7 governs
the minimum thickness of the footing.
The design of a plain concrete footing is demonstrated in Example 14.1.
Design a plain concrete footing for a column, 300 mm × 300 mm, carrying an axial
load of 330 kN (under service loads, due to dead and live loads). Assume an
676 REINFORCED CONCRETE DESIGN
allowable soil bearing pressure of 360 kN/m2 at a depth of 1.0 m below ground.
Assume M 20 concrete and Fe 415 steel.
SOLUTION
Transfer of axial force at base of column
• In order to provide a plain concrete block footing, full force transfer must be
possible at the column base, without the need for reinforcement at the interface.
That is, the factored axial load Pu must be less than the limiting bearing resistance
Fbr.
• Assuming a load factor of 1.5, Pu = 330 × 1.5 = 495 kN
Limiting bearing stress fbr, max = 0.45fck A1 A2
At the column-footing interface, fbr, max will be governed by the column face in
this case (and not the footing face), with A1 = A2 = (300 × 300) mm2
⇒ Fbr = 0.45 × 20 × 3002 = 810 × 103 N
> Pu = 495 kN
Hence, full force transfer is possible without the need for reinforcement.
Size of footing
• Assuming the weight of footing + backfill to comprise 10 percent of the axial
330 × 11
.
load, base area required = = 1.01 m2
360
Provide 1 m × 1 m footing, as shown in Fig. 4.10.
Thickness of footing
1000 − 300 ⎞
• D = ⎛⎜ ⎟ tan α
⎝ 2 ⎠
where tan α ≥ 0.9 100qmax fck + 1
qmax = 360 kN/m2 = 0.360 N/mm2
fck = 20 N/mm2
⇒ D ≥ 350 × 0.9 100 × 0.36 20 + 1
= 527 mm
Provide 530 mm.
Hence, provide a concrete block 1000 × 1000 × 530 mm.
• Further, it is necessary to provide minimum reinforcement to provide for ‘tie
action’, and to account for temperature and shrinkage effects:
Ast,min = 0.0012BD = 0.0012 × 1000 × 530 = 636 mm2
Provide 6 – 12 mm φ bars (Ast = 678 mm2) both ways with a clear cover of
75 mm, as shown in Fig. 4.10. The spacing is within limits (< 5d or 450 mm).
Check gross base pressure
• Assuming unit weight of concrete and soil as 24 kN/m3 and 18 kN/m3
respectively,
330
actual gross soil pressure qmax = + (24 × 0.53) + (18 × 0.47)
1.0 × 1.0
DESIGN OF FOOTINGS AND RETAINING WALLS 677
470
300 350
α
530
6 – 12 φ bars both ways
(nominal reinforcement)
75
1000
300
300
1000
Design an isolated footing for a square column, 450 mm × 450 mm, reinforced with
8–25 φ bars, and carrying a service load of 2300 kN. Assume soil with a safe bearing
capacity of 300 kN/m2 at a depth of 1.5 m below ground. Assume M 20 grade
concrete and Fe 415 grade steel for the footing, and M 25 concrete and Fe 415 steel
for the column.
SOLUTION
Size of footing
• Given: P = 2300 kN, qa = 300 kN/m2 at h = 1.5 m
678 REINFORCED CONCRETE DESIGN
†
This assumption is verified subsequently.
†
Actual effective depth provided will not be less than this value; hence, the use of this value in
this context can only be on a slightly conservative side; such an assumption simplifies
calculations.
DESIGN OF FOOTINGS AND RETAINING WALLS 679
Provide D = 750 mm. The effective depths in the two directions will differ by
one bar diameter, which is not significant in relatively deep square footings. For
the purpose of flexural reinforcement calculations, an average value of d may be
assumed:
⇒ d = 750 – 75 – 16 = 659 mm
• Assuming unit weights of concrete and soil as 24 kN/m3 and 18 kN/m3
respectively, actual gross pressure at footing base (under service loads)
450
750 75
dav = 659
75
3000
SECTION ‘XX’
section for
one-way shear
section for
two-way shear
d/2
X X
d/2
450
3000 d
d/2 450
(3000 – 450)/2
= 1275
PLAN
Mu 933.9 × 10 6
⇒R≡ = = 0.717 MPa
Bd 2
3000 × 659 2
[ ]
( pt )reqd 20
⇒ = 1 − 1 − 4.598 × 0.717 20 = 0.207 × 10–2
100 2 × 415
Ast,min = 0.0012BD = 0.0012 × 3000 × 750 = 2700 mm2
⇒ pt,min = 100 × 2700/(3000 × 659) = 0.137 < 0.207
• However, this reinforcement is less than assumed for one-way shear design ‡ ,
( τ c = 0.36 MPa).
for which pt = 0.25 (for M 20 concrete)
⇒ Ast,reqd = 0.25 × 3000 × 659/100 = 4943 mm2
Using 16 mm φ bars, number of bars required = 4943/201 = 25
[corresponding spacing s = {3000 – (75 × 2) – 16}/(25 –1) = 118 mm — is
acceptable.]
Provide 25 nos 16 φ bars both ways as shown in Fig. 14.11
φ (0.87 f y )
Required development length Ld = [refer Cl. 26.2.1 of Code]
4τ bd
For M 20 concrete and Fe 415 steel, Ld = φ (0.87 × 415)/(4 × 1.2 × 1.6) = 47.0 φ
For 16 φ bars in footing, Ld =47.0 × 16 = 752 mm
Length available = 1275 – 75 = 1200 mm > 752 mm — Hence, OK.
Transfer of force at column base
• Factored compressive force at column base: Pu = 2300 × 1.5 = 3450 kN
Limiting bearing stress at column-footing interface, fbr, max = 0.45 fck A1 A2 .
(i) for column face, fck = 25 MPa, A1 = A2 = 4502 mm2
⇒ fbr, max - col = 0.45 × 25 × 1 = 11.25 MPa
(ii) for footing face, fck = 20 MPa, A1 = 30002 mm2, A2 = 4502 mm2
⇒ A1 A2 = 3000/450 = 6.67, limited to 2.0
⇒ fbr, max- ftg = 0.45 × 20 × 2 = 18.0 MPa
• Evidently, the column face governs, and fbr, max = 11.25 MPa
⇒ Limiting bearing resistance Fbr = 11.25 × 4502 = 2278.1 × 103 N
< Pu = 3450 kN
⇒ Excess force (to be transferred by reinforcement):
ΔPu = 3450 – 2278 = 1172 kN
This may be transferred by reinforcement, dowels or mechanical connectors. In
this case, it is convenient to extend the column bars into the footing, as shown in
Fig. 14.11.
‡
Unless the footing dimensions are revised (to result in less shear stress), the reinforcement
requirement here will be governed by shear strength requirements, and not flexural strength
requirements. If the resulting pt is excessive, it may be more economical to revise the footing
dimensions, providing larger plan area and less depth of footing. In a practical design, this
should be investigated.
DESIGN OF FOOTINGS AND RETAINING WALLS 681
410
d = 659
750
340
75
3000
SECTION ‘XX’ critical section for
one-way shear
X X
450
1770
3000
450
1770
PLAN
• As the thickness of the footing near the column base is governed by shear (one-
way shear, in this example) and the effective area available at the critical section
is a truncated rectangle, the effective depth required is slightly larger than that for
a flat footing.
• Assuming a thickness D = 750 mm up to a distance of 660 mm (> d = 659 mm)
from the periphery of the column; and providing a slope of 1 in 1.5 over the
remaining distance of 1275 – 660 = 615 mm on all four sides [Fig. 14.12], the
edge thickness is obtained as 750 – 615/1.5 = 340 mm
⇒ Vu1 = 0.383 × (1275 – 659) × 3000 = 707784 N
⇒ τ v1 = 707784 / (3000 × 659 – 616 × 410) ‡ = 0.410 MPa
Providing pt = 0.35 ⇒ τ c = 0.413 MPa (for M 20 concrete) [refer Table 6.1]
τ c > τ v — Hence, OK.
⇒ (Ast)reqd = (0.35/100) × (3000 × 659 – 616 × 410) = 6036 mm2
‡
The area resisting the shear is polygonal in shape.
DESIGN OF FOOTINGS AND RETAINING WALLS 683
Redesign the footing for the column in Example 14.2, including a spatial restriction
of 2.5 m on one of the plan dimensions of the footing.
SOLUTION
Size of footing
• As in Example 14.2, required base area = 8.43 m2
Width B = 2.5 m, ⇒ length L = 8.43/2.5 = 3.37 m
⇒ Provide a rectangular footing 3.4 m × 2.5 m.
⇒ Net factored soil pressure = 2300 × 1.5/(3.4 × 2.5) = 406 kN/m2
= 0.406 N/mm2
Thickness required for shear
• An exact solution for the required depth for shear (one-way shear as well as two-
way shear) may be obtained using the conditions Vu1 ≤ Vc1 and Vu2 ≤ Vc2, as done
in Example 14.2. In this example, a trial-and-error procedure is used.
Assuming an overall depth (thickness) of footing D = 850 mm, with clear cover
of 75 mm and 20 mm φ bars in the long direction (placed at bottom) and 16 mm φ
bars in the short direction,
effective depth (long span) dx = 850 – 75 – 20/2 = 765 mm
effective depth (short span) dy = 850 – 75 – 20 – 16/2 = 747 mm
Average d for two-way shear calculations: d = (765 + 747)/2 = 756 mm
• One-way shear at dx = 765 mm away from column face in the long direction:
Vu1 = 0.406 × 2500 × (1475 – 765) = 720650 N
⇒ τ v1 = 720650/(2500 × 765) = 0.377 MPa
For τ c = τ v1 = 0.377 MPa, (pt)reqd = 0.28 [refer Table 6.1].
[In the short span direction, dy = 747 mm and Vu1 = 0.406 × 3400 × (1025 – 747)
= 383751 N ⇒ τ v1 =383751/(3400 × 747) = 0.151 MPa << τ c,min ; hence this is
not critical].
†
In this case, advantage may be availed of the reduction in one-way shear owing to the
inclination in the compressive force [refer Section 6.4.2].
684 REINFORCED CONCRETE DESIGN
450
1475
18 nos 20 φ
at uniform
spacing
3400
X
dx = 765
critical section for
one-way shear
critical section
for Mux
PLAN
[ ]
( pt )reqd 20
⇒ = 1 − 1 − 4.598 × 0.755 20 = 0.219 × 10–2
100 2 × 415
• This is less than pt = 0.28 required for one-way shear.
⇒ (Ast,x)reqd = 0.28 × 2500 × 765/100 = 5355 mm2
Using 20 φ bars, number required = 5355/314 = 18
⇒ Corresponding spacing s = {2500 – (75 ×2) – 20}/17 = 137 mm — OK.
Provide 18 nos 20 φ bars at uniform spacing in the long direction.
• Development length required: Ld = 47.0 φ (for M 20 concrete, Fe 415 steel, as in
previous Example)
= 47.0 × 20 = 940 mm
Development length available = 1475 – 75 = 1400 mm > 940 mm — OK.
(b) short direction (section YY in Fig. 14.13)
• Muy = 0.406 × 3400 × 10252/2 = 725.1 × 106 Nmm
Mu 725.1 × 10 6
⇒R≡ = = 0.382 MPa
Bd y 2
3400 × 747 2
[ ]
( pt )reqd 20
⇒ = 1 − 1 − 4.598 × 0.382 20 = 0.108 × 10–2
100 2 × 415
• This is less than the minimum reinforcement required for slabs:
(Ast)min = 0.0012 bD = 0.0012 × 3400 × 850 = 3468 mm2
Using 16 φ bars, number required = 3468/201 = 18
• Ast to be provided within a central band width B = 2500 mm is:
2 2
3468 × = 3468 × = 2890 mm2
β +1 (3.5 2.5 + 1)
Using 16 φ bars, number required = 2890/201 = 15
• Provide 15 nos 16 φ bars at uniform spacing within the central band of width
2.5 m, and 2 nos 16 φ bars each in the two outer segments; making a total of 19
bars, as shown in Fig. 14.13. The spacings are within limits (3d, 300 mm).
• Required development length = 47.0 × 16 = 752 mm
Development length available = 1025 – 75 = 950 mm > 752 mm — OK.
Transfer of force at column base
The calculations are identical to those given in Example 14.2 (except that for the
footing face, A1 A2 = 2500/450 = 5.56, limited to 2.0). The excess force of
1171.9 kN may be transferred across the column-footing interface by simply
extending the column bars, as in the previous Example, and as indicated in
Fig. 14.13.
Alternative: As in the previous Example, a sloped footing may be designed; this is
likely to be more economical than a flat footing.
Design a reinforced concrete footing for a 230 mm thick masonry wall which
supports a load (inclusive of self-weight) of 200 kN/m under service loads. Assume
686 REINFORCED CONCRETE DESIGN
a safe soil bearing capacity of 150 kN/m2 at a depth of 1 m below ground. Assume
M 20 grade concrete and Fe 415 grade steel.
SOLUTION
Size of footing
• Given: P = 200 kN/m, qa = 150 kN/m 2 at a depth of 1 m.
• Assuming the weight of the footing + backfill to constitute 10 percent of the
applied load P, and considering a 1 m length of footing along the wall,
200 × 11.
required width of footing = = 1.47 m.
150
Provide 1.5 m wide footing.
Thickness of footing based on shear considerations
• Factored net soil pressure (assuming a load factor of 1.5) is:
200 × 1.5
qu = = 200 kN/m2 = 0.200 N/mm2
1.5 × 1.0
• The critical section for (one-way) shear is located at a distance d away from the
face of the wall
⇒ Vu = 0.200 × 1000 [(1500 – 230)/2 –d]
= (127000 – 200d) N
• Assuming nominal flexural reinforcement (pt = 0.25), τ c = 0.36 MPa for M 20
concrete, the shear resistance of concrete is:
Vuc = 0.36 × 1000 × d = (360d) N.
• Vu ≤ Vuc ⇒ 127000 – 200d ≤ 360d
⇒ d ≥ 227 mm
• Assuming a clear cover of 75 mm and 16 φ bars,
thickness D ≥ 227 + 75 + 16/2 = 310 mm
Provide D = 310 mm upto a distance of 250 mm from the face of the wall. At the
edge of the footing, a minimum thickness of 150 mm may be provided, and the
thickness linearly tapered upto 310 mm, as shown in Fig. 14.14.
DESIGN OF FOOTINGS AND RETAINING WALLS 687
C 230/4
critical section
for moment
7 –10 φ distributors 692.5
d = 227
75 critical section
310 for shear
150
12 φ @ 180 c/c
1500
SECTION A–A
A A
250 250
PLAN
= 47.0 × 12 = 564 mm †
Length available = 692.5 – 75 = 617.5 mm > 564 mm — OK.
Distributors
Some nominal bars may be provided, to account for possible secondary stresses
due to differential settlement.
Provide 10 φ distributors @ about 200 c/c (7 nos will be adequate) [Fig. 14.4].
Transfer of force at wall base
Assuming a load factor of 1.5, maximum bearing stress at wall/footing interface
(loaded area is 230 mm wide)
200 × 10 3 × 1.5
fbr = = 1.304 MPa
1000 × 230
which is relatively low and can be accommodated by the concrete
[fbr, max = 0.45 fck A1 A2 ] in the footing face; the masonry must also be capable of
providing this bearing resistance.
Design an isolated footing for a column, 300 mm × 500 mm, reinforced with 6–25 φ
bars with Fe 415 steel and M 25 concrete [refer Fig. 13.14(a), Example 13.5], subject
to a factored axial load Pu = 1000 kN and a factored uniaxial moment Mux = 120 kNm
(with respect to the major axis) at the column base. Assume that the moment is
reversible. The safe soil bearing capacity may be taken as 200 kN/m2 at a depth of
1.25 m. Assume M 20 concrete and Fe 415 steel for the footing.
SOLUTION
Size of footing
• Given: Pu = 1000 kN, Mux = 120 kNm, qa = 200 kN/m2 at a depth of 1.25 m.
• As the moment is reversible, the footing should be symmetric with respect to the
column. Assuming the weight of the footing plus backfill to constitute about 15
percent of Pu, resultant eccentricity of loading at footing base,
120 × 10 3
e=
1000 × 1.15
= 104 mm
• Assuming e < L/6 (i.e., L > 6 × 104 = 624 mm)
1000 × 1.15 120
+ 2 ≤ (200 × 1.5 ‡ ) kN/m2
BL BL 6
†
This is required with reference to the section of maximum moment. Strictly, development
length should also be checked at sections where the thickness is reduced. However, in this
case, it can be seen that in the region of tapered thickness, the drop in bending moment (due to
cantilever action) is steeper than the drop in effective depth, and hence there is no cause for
concern.
‡
Assuming an enhanced soil pressure under ultimate loads is equivalent to considering
allowable pressures at the serviceability limit state. A load factor of 1.5 is assumed here.
DESIGN OF FOOTINGS AND RETAINING WALLS 689
11 nos 16 φ
(uniform spacing) dx = 417
975 dy = 401
Y Y
2000 300
500
one–way
Mux shear
X
2450
†
In this problem, the variation in the soil pressure over the length from the edge to the critical
section is not very large. In such cases, it is sufficient and conservative to assume a uniform
pressure equal to the maximum at the edge.
DESIGN OF FOOTINGS AND RETAINING WALLS 691
Redesign the footing in Example 14.5 for a uniformly distributed base pressure,
considering that the applied moment at the column base is entirely due to dead loads
(and hence, irreversible).
SOLUTION
• Given: (as in the previous Example) Pu = 1000 kN, Mux = 120 kNm,
qa = 200 kN/m2 at a depth of 1.25 m, fck = 20 MPa, fy = 415 MPa
Size of footing
• Required eccentricity between column centroid and footing centroid = Mu/Pu
120 × 10 3
= = 120 mm
1000
• Assuming the weight of the footing + backfill to constitute 10 percent of Pu, and
assuming a load factor of 1.5,
1000 × 11.
base area required = = 3.67 m2
200 × 1.5
• For economical proportions, the cantilever projections (for flexural design)
should be approximately equal in the two directions.
⇒ Provide L = B = 1.95 m (Area = 3.80 m2 > 3.67 m2)
With the column offset by 120 mm, this results in cantilever projections of
845 mm and 825 mm in the two directions, as shown in Fig. 14.16.
Thickness of footing based on shear
1000
• Factored (net) soil prressure qu = = 263.0kN/m2
1.95 × 1.95
= 0.263 N/mm2
DESIGN OF FOOTINGS AND RETAINING WALLS 693
e = 120 mm
605 845
750 mm extension
(by making bar
incilined in plan)
450
uniform pressure
qu = 263.0 kN/m2
C COL. C FTG.
130
1950 150
150
500
975
975 975
1950
14.6.1 General
As mentioned in Section 14.2.2, a footing supporting more than a single column or
wall is called a combined footing, and when many columns (more than two) are
involved, terms such as continuous strip footing (if columns are aligned in one
direction only) and raft foundation or mat foundation are used. Multiple column
foundations become necessary in soils having very low bearing capacities. However,
even in soils having moderate or high ‘safe bearing capacity’ for the use of individual
footings, combined footings become necessary sometimes — as when: