You are on page 1of 11

Science and Technology for the Built Environment

ISSN: 2374-4731 (Print) 2374-474X (Online) Journal homepage: http://www.tandfonline.com/loi/uhvc21

Literature review of building peak cooling load


methods in the United States

Chunliu Mao, Juan-Carlos Baltazar & Jeff S. Haberl

To cite this article: Chunliu Mao, Juan-Carlos Baltazar & Jeff S. Haberl (2017): Literature review
of building peak cooling load methods in the United States, Science and Technology for the Built
Environment, DOI: 10.1080/23744731.2017.1373700

To link to this article: https://doi.org/10.1080/23744731.2017.1373700

Accepted author version posted online: 31


Aug 2017.
Published online: 31 Aug 2017.

Submit your article to this journal

Article views: 56

View related articles

View Crossmark data

Full Terms & Conditions of access and use can be found at


http://www.tandfonline.com/action/journalInformation?journalCode=uhvc21

Download by: [RMIT University Library] Date: 09 December 2017, At: 05:29
Science and Technology for the Built Environment (2017) 0, 1–10
Copyright C 2017 ASHRAE.
ISSN: 2374-4731 print / 2374-474X online
DOI: 10.1080/23744731.2017.1373700

Literature review of building peak cooling load methods in


the United States
CHUNLIU MAO1,∗ , JUAN-CARLOS BALTAZAR2 , and JEFF S. HABERL2
1
Department of Building Science, Tsinghua University, Beijing City, 100084, China
2
Department of Architecture, Texas A&M University, College Station, TX, USA
Downloaded by [RMIT University Library] at 05:29 09 December 2017

Today, sizing HVAC systems plays an important role in the building design process, requiring an accurate method in order to avoid
problems from over- or under-sized systems. To date, there have been five peak cooling load methods published by ASHRAE,
including: the Total Equivalent Temperature Difference/Time Averaging Method, the Transfer Function Method, the Cooling Load
Temperature Difference/Solar Cooling Load/Cooling Load Factor Method, the Heat Balance Method, and the Radiant Time Series
Method. This study provides a thorough review of the five methods with respect to their history and summarizes the method differ-
ences that can lead to inaccurate sensible cooling load calculations.

Introduction Many design tools are available in the market to help the
engineers design buildings more efficiently. Five different peak
Buildings consume a large portion of the total energy use in cooling load methodologies are used by these tools, includ-
the United States. A recent study (EIA 2017) showed that the ing: the Total Equivalent Temperature Difference/Time
residential and commercial buildings sector accounted for Averaging Method (TETD/TA), the Transfer Function
almost 40% of the end-use energy use in the United States Method (TFM), the Cooling Load Temperature Differ-
in 2015. This has reinforced the interest and efforts of the ence/Solar Cooling Load /Cooling Load Factor Method
HVAC community to analyze, design, and construct new (CLTD/SCL/CLF), the Heat Balance Method (HBM), and
high-performance buildings that will consume less energy, the Radiant Time Series Method (RTSM)1 . A recent survey
look appealing, and provide acceptable indoor air conditions. showed design engineers calculate commercial building peak
However, in many cities in the United States, developers are cooling loads using, not the most recently published, but their
asked to try to reuse some portion of an existing structure, or preferred tools (Mao 2016). Unfortunately, discrepancies in
add-on to an existing structure without really knowing how the peak sensible cooling load calculations exist due to the
that previous building was designed, especially the HVAC different analysis methods. Therefore, there is a need for a
systems. Often, older buildings have existing HVAC systems better understanding of what the differences are and how the
that are significantly over- or under-sized, which makes them different tools should be selected.
inappropriate for meeting the heating and cooling loads A previous study provided broad historical discussions of
they must supply. In some cases, the thermal mass of these the early science, important people and events that included a
older buildings has never been adequately taken into account timeline of the significant contributions to current peak heat-
during the HVAC design process, which may have led to large ing and cooling load design methods (Mao et al. 2012, 2013).
errors in the thermal load sizing calculations that produces The current study aims to provide a detailed review of build-
inefficient over-sized systems. ing peak cooling load methods with the focus on sensible
cooling load calculations and includes a comparison of the
calculation procedures.

Received March 8, 2017; accepted July 30, 2017


Chunliu Mao, PhD, is a Postdoctoral Fellow. Juan-Carlos
Baltazar, PhD, Member ASHRAE, is an Associate Professor.
1
Jeff S. Haberl, PhD, Fellow ASHRAE, is a Professor. The Residential Heat Balance Method (RHB) and the Residen-

Corresponding author e-mail: maocl2008@gmail.com tial Load Factor Method (RLF) that are particularly used by res-
Color versions of one or more of the figures in the article can be idential buildings (Barnaby et al. 2004) are not covered in the
found online at www.tandfonline.com/uhvc. present article.
2 Science and Technology for the Built Environment

Early building peak load calculation methods sponsored project and is regarded as the first time that the
heat balance calculation and the thermal network method
The development of most engineering methods is often were used together in a well-documented analog building
inspired by the need to solve problems that are relevant and simulation.
practical during that period. Early building peak load cal-
culation methods that provided solutions to moist air and
dynamic heat transfer problems began to be developed during Current building peak cooling load methods
the period from 1900 to 1945 as the air-conditioning industry
developed (Mao et al. 2013). TETD/TA
In 1948, James Stewart, a design engineer at Carrier Corpo-
Sol-air temperature method ration, published the Equivalent Temperature Differentials
Method (ETD), which was based on Mackey and Wright’s
The sol-air calculation method was one of the earliest meth- earlier work. This method was intended to be an easy-to-use,
ods that was successfully used to solve the dynamic heat tabulated design method that would calculate the dynamic
transfer through a multi-layer opaque wall. The sol-air sensible heat gains through opaque walls and roofs. To
Downloaded by [RMIT University Library] at 05:29 09 December 2017

temperature was defined as: accomplish this, Stewart’s ETD tables were generated under
specific conditions: (1) July at 40° N Latitude; (2) maximum
the temperature of the outdoor air that, in the absence
and minimum outdoor temperatures of 95°F and 75°F,
of all radiation changes, gives the same rate of heat entry
respectively; and (3) a room temperature of 80°F. For tem-
into the surface as would the combination of incident solar
radiation, radiant energy exchange with the sky and other
perature differences between the outdoor maximum design
outdoor surroundings, and convective heat exchanges with temperature and the room temperature that were larger
the outdoor air. (ASHRAE 2013) than15°F, it was suggested to use the published ETD and
add (or subtract) the difference (Stewart 1948). The ETD
This concept was originally introduced by Mackey and tables were adopted for use in the 1951 ASHVE Guide and
Wright in 1944. Figure 1 shows a graph of the decrement the 1961 ASHRAE Guide and Data Book (ASHRAE 1961;
factor developed by Mackey and Wright. They proposed ASHVE 1951). The TETD/TA was later tabulated in the
an equation to calculate the inside surface temperature of 1967 ASHRAE Handbook of Fundamentals (ASHRAE
a homogeneous wall using a daily average sol-air tempera- 1967), which added the TA procedure to allow the method
ture, a decrement factor and a lag angle. In 1967, sol-air tem- to be suitable for calculating extended hourly profiles when
perature was adopted by ASHRAE and later became part the radiant heat gain components were averaged over the
of the ASHRAE simplified peak cooling load methods to representative period for all the thermal mass of the building.
calculate building sensible cooling loads for exterior opaque The TETD is formulated by (ASHRAE 1997):
surfaces.
T ET D = tea − ti + DF (te,T L − tea ), (1)

Thermal networks which allows the conduction heat gains through walls and
Beginning in the 1940s, several authors investigated the use roofs to be calculated by (ASHRAE 1997):
of thermal R/C network models for analyzing dynamic heat
transfer. The thermal R/C network method was first pub- qT ET D/TA = UA(T ET D). (2)
lished by Victor Paschkis in 1942 to calculate the dynamic
heat transfer through building walls (Paschkis 1942). Shortly In the TETD/TA method, hourly averaged sol-air tem-
after this, in 1944, John Linvill and John Hess Jr. published peratures are used in the TETD calculation and thermal
their article “Studying Thermal Behavior of Houses,” which mass effects are calculated in TETD factors by applying
was an undergraduate student project at M.I.T. Their article the appropriate decrement factors and time lags published
showed how the thermal R/C network method could be used in the ASHRAE tables which define specific wall and
to calculate the dynamic heat transfer of an entire house roof group numbers for a total of 41 wall and 42 roof
(Linvill and Hess 1944). Later, in 1958, Harry Buchberg at the types from which to choose. The solar heat gains through
University of California at Los Angeles (UCLA) developed a fenestration are calculated using a shading coefficient (SC)
complete R/C thermal network model for a house using heat and the published double-strength sheet glass (DSA) coef-
balance calculations at each node that were simulated on an ficients shown in the most recent updates for TETD/TA
analog computer, as shown in Figure 2 (Buchberg 1958). The Method (ASHRAE 1997). The fenestration conduction
test house consisted of four opaque walls, two colored roofs heat gains can be obtained through steady-state calculation
(e.g., green and white), a glass window mounted in the south UAT. Any significant internal heat gains need to be con-
wall, a floor and an overhang that could shade the window. sidered individually. The peak cooling load is then finalized
This network represented the conduction paths for the wall, by applying the TA process. Unfortunately, this requires a
roof and floor sectors, as well as the transmitted and diffuse subjective decision to determine the time period for aver-
solar radiation through the window that were absorbed aging, which varies from one designer to the next. This is
by the interior surfaces. This project was an ASHRAE because judging the amount of thermal mass in a building
Downloaded by [RMIT University Library] at 05:29 09 December 2017

Fig. 1. Decrement factor graph (Mackey and Wright 1944). Reprinted from periodic heat flow—homogeneous walls or roofs, Mackey, C.O. and Wright, L.T., Jr. 1944,
ASHVE Journal, 16(9), 546–55.

3
4 Science and Technology for the Built Environment

In the TFM, the transient conduction heat gain through


the walls and roofs is formulated by (ASHRAE 1997):

 
  
(qe,θ )T F M = A bnte,θ−nδ − dn (qe,θ−nδ /A) − tr cn .
n=0 n=1 n=0
(3)
To determine the space sensible cooling load, the room
transfer functions (RTFs) concept (also called weighting fac-
tors [WF]) is used, where the cooling load is formulated by
(ASHRAE 1997):

(Qθ )T F M = ν0 qθ + ν1 qθ−δ + ν2 qθ−2δ − w1 Qθ −δ − w2 Qθ −2δ .


(4)
Downloaded by [RMIT University Library] at 05:29 09 December 2017

The TFM is a two-step, simplified method that incorpo-


rates the concepts of conduction transfer functions (CTFs)
and the RTFs (also called WFs). The conduction heat gains
of the walls and roofs are calculated using sol-air tempera-
Fig. 2. Thermal network for a test house (Buchberg 1958).
tures and CTFs. The fenestration solar heat gain is calculated
Reprinted from cooling load from thermal network solutions, as the same fashion of TETD/TA Method. Any internal heat
Buchberg, H., 1958, ASHRAE Transactions, 64, 111–28. gains need to be calculated individually. The peak sensible
cooling loads from solar heat gains, conduction heat gains,
and internal heat gains are obtained by applying the solar WF,
conduction WF, lighting WF, and occupant/equipment WF,
is a difficult job, which ultimately made the method useful respectively. The infiltration heat gains directly contribute to
only in the hands of an experienced engineer. Typically, the the cooling load. Summing up all types of peak sensible cool-
recommended time period for the TETD/TA Method was ing load yields the total sensible cooling load for the space.
3 hours (ASHRAE 1997). The following are the limitations of the TFM:
r The construction layer thermal properties and code num-
bers are pre-defined. The TFM relies on tables of pre-
TFM
defined material layers. Therefore, the users who apply the
The TFM can trace its roots back to the Response Factor TFM must choose only from the material layers provided
Method (RFM). The RFM was first introduced for transient by the TFM tables, which uses the published values in 1997
heat flow calculation by André Nessi and Léon Nisolle in ASHRAE Handbook of Fundamentals (ASHRAE 1997).
France (Nessi and Nisolle 1925). In the mid-1950s, Brisken, r The layer groups for walls and roofs are fixed. In the TFM,
Reque, and Hill laid the foundations of the current RFM there are 41 wall groups and 42 roof groups available for
based on Nessi and Nisolle’s work. In 1956, Brisken and calculation. The TFM has its own procedure to guide users
Reque published their heat load calculations using the RFM to select the closest wall and roof group numbers. This is
(Brisken and Reque 1956). In this method, they proposed because the CTFs are only calculated for those layer com-
using “square waves” to represent a time-varying “curve” of binations and tabulated in the TFM tables. This can cause
dynamic temperature response. One year later, Hill developed discrepancies in building sensible cooling load analysis if
a more accurate “unit triangle” method for calculating the they do not exactly match the values in the table. However,
time-varying one-dimensional (1D) surface temperature (Hill an adjustment procedure is provided to reduce this discrep-
1957). Based on these works, in 1967, Gintas Mitalas and ancy, which uses Uactual /Utabulatedfactor to multiply the tab-
Don Stephenson developed the thermal RFM, which allowed ulated CTF coefficientsbn and cn for modifications. In
for the solution to the dynamic heat transfer problem (Mitalas this way, the overall U-values can be approximated to the
and Stephenson 1967; Stephenson and Mitalas 1967). Later, actual building U-values. As a simplified method, engineers
this method became part of the TFM that has also been are only required to pick the numbers from the tables and
called the Weighting Factor Method (ASHRAE 1981; Mita- perform the peak sensible cooling load calculations.
las 1972). r An iterative calculation was required in order to achieve
In 1972, the ASHRAE Task Group on Energy Require- steady periodic results. When converting heat gains into
ments (TGER) first introduced the TFM for peak cooling the peak sensible cooling load, historical
 terms of the pre-
load calculation, which was based on Mitalas and Stephen- vious peak sensible cooling loads n=1 dn (qe,θ−nδ /A) are
son’s earlier work (ASHRAE 1972). The TFM is considered required. When calculating the cooling load for the first
the first, wide-spread, computer-oriented method for solving hour on the very first day, the historical terms are assumed
dynamic heat transfer problems in buildings in the United to be zero. Therefore, an iterative calculation should be
States (Mitalas 1972). applied until the peak cooling load calculations converge.
Volume 0, Number 0, XXXX 2017 5

Usually, for heavy-weight thermal mass, this requires cal- For IP Unit, CLT D = CLT DT + (78 − tr ) + (tm − 85).
culations for several more days with steady periodic input (7)
parameters to achieve convergence compared to the light-
weight thermal mass.
There are several limitations with the CLTD/SCL/CLF
Finally, when using the TFM, the design engineers should Method:
be aware of the method’s limitations in order to obtain the r All the limitations of TFM are included in this method.
reasonable peak sensible cooling load results.
The tables of CLTD, SCL, and CLF were generated based
on the TFM. Once the cooling load was obtained by the
CLTD/SCL/CLF TFM, the values of CLTD, SCL, and CLF could then be
calculated by dividing the surface area and overall U-factor
As new computer-based methods were being developed
for the tabulated wall and roof combination groups.
during 1970s, manual and tabulated methods continued r There is less flexibility for users to change parameters. Dif-
to be updated and used because many HVAC engineers
ferent from the TFM, the principal material layers of walls
could not justify the time and expense required by the new
and roofs were further regrouped, from 41 wall groups and
computer methods. One such method, based on the princi-
42 roof groups reduced to 16 wall and 10 roof groups. In
Downloaded by [RMIT University Library] at 05:29 09 December 2017

ples of TFM, was the CLTD/CLF, which was developed by


addition, since all the tables are built in, it is difficult to
William Rudoy and Fernando Duran in 1974 at University
change parameters for cooling load calculations, such as
of Pittsburgh (Rudoy and Duran 1974). It included tabulated
the exterior surface solar radiation and fenestration solar
results of controlled-variable tests summarized in ASHRAE
model. In addition, solar radiation at the exterior surfaces
research project RP-138 for peak cooling load calculations.
relied on the ASHRAE (1967) clear-sky model that uti-
The CLTD/CLF Method attempted to simplify the two-step
lizes A, B, and C coefficients as the default according to
TFM and TETD/TA Method into a single-step technique,
the available updates for CLTD/SCL/CLF Method at the
which was later published in the 1977 ASHRAE Handbook
time it was published. Therefore, the 2009 clear-sky model
of Fundamentals (ASHRAE 1977). Eleven years later, in
update was not implemented in the CLTD tables. Fur-
1988, the CLTD/CLF Method was modified by Edward Sow-
thermore, the fenestration solar model was based on SCs
ell at California State University who ran 200,640 simulations
and the published DSA coefficients. Therefore, the angular-
to provide new tabulated values (Sowell 1988). That same
based solar heat gain coefficient (SHGC) model was not
year, motivated by the limited wall and roof categories used in
implemented in the published SCL tables.
the CLTD/CLF Method, Steven Harries and Faye McQuis-
ton proposed additional CTFs to cover more roof and wall In summary, the CLTD/SCL/CLF Method is quite easy-
construction groups in ASHRAE research project RP-472 at to-use compared to other methods, which can shorten the
Oklahoma State University (Harries and McQuiston 1988). design time and save the design efforts and cost. However, as
In 1993, Jeffery Spitler at Oklahoma State University lead a simplified method, the calculation accuracy is not as good
the efforts to update the CLTD/CLF Method to become the as the detailed methods (Mao 2016).
CLTD/SCL/CLF Method by introducing the term “Solar
Cooling Load (SCL)” for an improved solar heat gain cal-
culation through fenestration (Spitler et al. 1993). This new HBM
CLTD/SCL/CLF Method was later incorporated into the
As mentioned previously, the earliest heat balance calcula-
1993 ASHRAE Handbook of Fundamentals (ASHRAE
tions using a thermal network, can be tracked back to 1958
1993). As a one-step method, it relied on the CLTD, SCL, and
for house modeling (Buchberg 1958). The complete heat bal-
CLF tables to calculate cooling loads from exterior opaque
ance equations were first implemented in energy simulation
surfaces, fenestration as well as the occupancy, lighting, and
programs, such as NBSLD, BLAST, and TARP (Hittle 1979;
the equipment.
Kusuda 1976; Sowell and Walton 1980; Walton 1983). In
Different from the TFM, in the CLTD/SCL/CLF
1997, Curtis Pedersen and colleagues at the University of Illi-
Method, the principal material layers of walls and roofs were
nois further developed the HBM for load calculation using a
further regrouped, which resulted in a reduced number of wall
twelve-surface model, including four walls, four windows, one
and roof groups from which to choose.
roof, one skylight, one floor, and thermal mass, as shown in
In the CLTD/SCL/CLF Method, the sensible cooling
Figure 3. Their published work included a complete descrip-
load is estimated by (ASHRAE 1997):
tion of the mathematical calculations for the heat balance
procedures (Pedersen et al. 1997). This HBM is considered
QCLT D/SCL/CLF = UA(CLT D). (5) the most accurate method among all the methods (Fisher and
Spitler 2002; Pedersen et al. 1997; Smith 2011). It utilizes an
The tabulated CLTD needs to be adjusted if the actual out- iterative procedure to perform the heat balance calculations
door and indoor conditions do not match with the default for the outside surfaces, wall conductions, and the inside sur-
conditions, which is calculated by (ASHRAE 1997): faces as well as zone air, instead of using superposition and
calculating each cooling load component in the simplified
For SI unit, CLT D = CLT DT + (25.5 − tr ) + (tm − 29.4), methods. Therefore, due to its complexity, a computer pro-
(6) gram is required to solve the heat balance equations.
6 Science and Technology for the Built Environment

or using the CTSFs,


23
(qθ )RT SM = c j UA(te,θ− jδ − tr ). (9)
j=0

The RTSM utilizes two sets of the RTFs to convert all heat
gains into the cooling loads, which are the solar RTFs and the
nonsolar RTFs. The beam solar heat gain is assumed to be
distributed on the floor only, while other types of heat gains
are distributed uniformly to the interior surfaces, including
the radiative portion of conduction heat gains and internal
heat gains as well as diffuse solar radiation heat gains. There-
Fig. 3. Schematic view of general heat balance zone (Adapted fore, the solar RTFs are applied to the beam solar heat gains
from ASHRAE 2013). while the nonsolar RTFs are applied onto the diffuse solar
radiation heat gains and the radiative portion of other types
Downloaded by [RMIT University Library] at 05:29 09 December 2017

of heat gains to calculate the cooling loads, which gives,


In 2001, the ASHRAE building load calculation toolkit
(LOADS Toolkits) was developed and distributed by (Qr,θ )RT SM = r0 qr,θ + r1 qr,θ−1 + r2 qr,θ−2
ASHRAE (Pedersen et al. 2001), which provided FORTRAN + r3 qr,θ−3 + · · · + r23 qr,θ−23 . (10)
source code, detailed documentation, and an executable file
for the heat balance calculations. In addition, in the RTSM, the window solar heat gain cal-
However, there are limitations in the ASHRAE LOADS culation model was also improved using an angular SHGC
Toolkit Output. For example, the sensible cooling load pro- instead of the original SC. These two fenestration solar heat
duced by the ASHRAE LOADS Toolkit does not provide gain calculation models are shown in Figure 4.
a detailed breakdown of each component that contributes In the first fenestration solar heat gain model, the transmit-
to the total cooling load, which is useful for diagnosing the tance and absorptance of beam and diffuse solar radiation are
results. In order to obtain a detailed output, the source code determined by DSA coefficients, which are used to calculate
would need to be modified, tested, and recompiled. Thereby, the transmitted solar heat gain factor (TSHGF) and absorbed
a user-friendly interface is desired for people who are not code solar heat gain factor (ASHGF), respectively. The total fen-
developers to use. estration solar heat gains can be obtained accordingly using
solar heat gain factors, SC, and glazing area. In the second
fenestration solar heat gain model, instead of default DSA
RTSM coefficients, the angular SHGC is used to calculate the beam
and diffuse solar heat gains. As one improvement, the glass
The most current simplified cooling load method is the RTSM properties are input as variables based on the solar incidence
that was first developed in 1997. The RTSM is an improve- angle at different times of the day. Also, by introducing the
ment over all previous simplified methods (Spitler et al. 1997). indoor attenuation coefficient (IAC), the interior shading that
In response to a research proposed by ASHRAE Technical was not considered in the first model is now covered in the
Committee TC 4.1, the RTSM was derived directly from, calculation (Nigusse and Spitler 2010). Therefore, the total
but in a simpler manner than, the HBM. In the RTSM, the solar heat gains can be determined by multiplying the solar
1D time, varying heat conduction is calculated using a 24- heat gains, IAC, and the glazing area. By contrast, the SC is
term periodic response factors (PRFs). The radiant portion defined by normal incidence SHGC divided by 0.87, which is
of hourly heat gains are converted to hourly cooling loads a fixed value for each type of glass.
using radiant time factors (RTFs). The convection portion of
heat gains directly contributes to the cooling load. In 2007,
the RTSM was improved by Nigusse and Spitler at Oklahoma
State University (Nigusse 2007; Nigusse and Spitler 2010). Differences between the five methods
The improved RTSM introduced conduction time series fac-
tors (CTSFs), which are a set of dimensionless factors that For a typical building during cooling conditions, different
can be determined by the PRFs divided by the U-factor, to types of sensible heat gains can enter a space. In general,
perform the dynamic conduction heat gain calculations. the convective heat gains directly impact the space sensible
For the walls and roofs, the conduction heat gain qθ can be cooling load, while, the radiative heat gains must first be
determined using the PRFs, absorbed by the interior structures and then transferred by
convection to the zone air in the space after a time delay, as
shown in Figure 5.

23 In short, the five building peak cooling load methods are
(qθ )RT SM = A YP j (te,θ− jδ − tr ), (8) differentiated by their cooling load calculation procedures for
j=0 building opaque surfaces and the fenestration models that
Downloaded by [RMIT University Library] at 05:29 09 December 2017

Fig. 4. Relationship and connections between the two fenestration solar heat gain calculation models used by the RTSM.

7
8 Science and Technology for the Built Environment

methods. Four of these methods are considered simplified


methods, including the TETD/TA method, the TFM, the
CLTD/SCL/CLF method and the RTSM. All the methods
utilize a superposition principle to obtain the sensible cool-
ing load for a given space. The remaining HBM is a detailed
method that lays out the heat balance equations through the
entire heat transfer process of a twelve-surface model and per-
forms iterative calculations to converge on an answer.
Historically, the foundation of all the simplified methods
can be traced back to 1944 sol-air temperature method devel-
oped by Mackey and Wright. Around the same time, the ther-
Fig. 5. Peak cooling load method comparison (Adapted from mal R/C network started to arise, which was used to calculate
ASHRAE Handbook of Fundamentals2 ). dynamic heat transfer through the building walls by Paschkis
(1942), to model the house by Linvill and Hess (1944), and by
were adopted by the methods. Two ways are used to catego- Buchberg (1958). In Buchberg’s ASHRAE project, the heat
rize the methods. One is based on the degree of simplification, balance calculations were performed at each node of the ther-
Downloaded by [RMIT University Library] at 05:29 09 December 2017

while the other one relies on the number of the steps to achieve mal network, which required one of the first analog computer
the cooling load calculation. simulations.
Regarding the degree of simplification, the HBM is consid- During the same time period, the ETD tables were pub-
ered the “detailed method,” while the other four are regarded lished by Stewart (1948), based on Mackey and Wright’s
as the “simplified methods.” The HBM contains equation- work, to calculate the dynamic heat gains through the walls
based descriptions for each essential calculation process. By and roofs. This method helped formulate the TETD/TA
contrast, the simplified methods hide the corresponding equa- method that was later introduced in the 1967 ASHRAE
tions behind the tabulated factors, for instance, TETD, CTFs, Handbook of Fundamentals. In this method, a decrement
WFs, CLTD, SCL, CLF, CTSFs, and RTFs. factor and a time lag were used in the heat gain calculations
In light of the calculation steps, as one-step methods, the of the opaque surfaces. Later, the TETD/TA method added
HBM and the CLTD/SCL/CLF Method directly calculate a time-averaging (TA) process to improve the calculation of
the building peak sensible cooling load. To accomplish this, the dynamic cooling load from multiple surfaces. However,
the HBM uses an iterative analysis, while, the CLTD/SCL/ the representative time-averaging period was subjective.
CLF depends on the CLTD, SCL, and CLF tables to cal- Therefore, the experience and skills of the design engineer
culate cooling loads from wall/roof conduction heat gains, were crucial to the calculation accuracy.
fenestration solar heat gains, and internal heat gains. The thermal RFM was introduced in 1967 by Mitalas and
The remaining three methods are two-step methods. In Stephenson, based on the previous work done by Nessi and
general, for these methods, all types of sensible heat gains Nisolle (1925), Brisken and Reque (1956), and Hill (1957).
have to be determined in the first step. Different methods rely In 1972, ASHRAE Task Group published the TFM for cal-
on the different factors to calculate the heat gains through the culating dynamic heat transfer. Compared to the TETD/TA
opaque surfaces while the fenestration and internal heat gain method, the TFM used the CTFs and WFs for more accurate
calculations remain the same. For example, the TETD/TA heat gain and cooling load calculations, respectively. How-
method uses the TETD tables to perform the wall/roof ever, with pre-defined construction layer thermal properties
one-dimensional transient conduction calculations, whereas and limited wall and roof groups, the accuracy of this method
the TFM uses the CTFs, and the RTSM relies on the PRFs or depends significantly on the proper user input and appropri-
the CTSFs for the calculations. Second, all sensible heat gains ate factor adjustment in order to match the simulated building
need to be converted into the space sensible cooling load. as close as possible. Furthermore, iterative pre-calculations
In the TETD/TA method, this is accomplished by applying needed to be performed under the same boundary conditions
the time-averaging process to mimic the dynamic thermal to improve the convergence of the answer.
changes. The summation of all time-averaged sensible heat The TFM laid the basis for the CLTD/CLF method devel-
gains yield the total sensible cooling load. Whereas, the TFM oped by Rudoy and Duran (1974). This was later modi-
depends on the WFs for the calculations, and the RTSM fied by Sowell (1988), Harries (1988), McQuiston (1988),
applies the RTFs. and Spitler (1993) to become the CLTD/SCL/CLF method
by introducing the SCL term. Compared to the TFM, the
CLTD/SCL/CLF method further regrouped the wall and
Summary and conclusions roof types. Unfortunately, the same limitations of the TFM
remain in the CLTD/SCL/CLF method. Finally, since the
This study reviewed the five building peak cooling load meth- method relied on tabulated values, it left limited room for
ods that have been published by ASHRAE, and includes users to change any of the pre-determined simulation input
a history of the methods and the procedures used in the parameters.
Early heat balance calculations appeared in the previously
mentioned thermal network analysis (Buchberg 1958). Later,
2 the formulas were implemented in energy simulation pro-
This diagram combines the information from 1997 and 2001
ASHRAE Handbook of Fundamentals. gram, including NBSLD, BLAST as well as TARP. In 1997,
Volume 0, Number 0, XXXX 2017 9

the HBM was further developed for stand-alone load cal- QCLT D/SCL/CLF = cooling load by CLTD/SCL/CLF
culation by Pedersen. Today, this method is regarded as the Method, W in SI or Btu/h in IP;
most accurate method. Currently, the LOADS Toolkit, devel- (Qr,θ )RT SM = cooling load by RTSM, W in SI or Btu/h
oped by ASHRAE, is the only published toolkit that pro- in IP;
vides the FORTRAN source code, detailed documentation, Qθ −δ = cooling load at time θ − δ, W in SI or
and an executable file to run the simulation. Unfortunately, Btu/h in IP;
the output from the LOADS Toolkit does not provide a Qθ −2δ = cooling load at time θ − 2δ, W in SI or
detailed breakdown of each cooling load component. In addi- Btu/h in IP;
tion, the source code would need to be modified, tested and qT ET D/TA = wall and roof conduction heat gains by
recompiled before component-level cooling loads could be TETD/TA Method, W in SI or Btu/h in
obtained. Therefore, a user-friendly interface is highly desired IP;
for those who are not code developers. (qe,θ )T F M = wall and roof conduction heat gains by
In 1997, Spitler et al. published the RTSM for dynamic TFM, W in SI or Btu/h in IP;
peak cooling load calculations, which was derived from the (qθ )RT SM = wall and roof conduction heat gains by
HBM. Compared to the TETD/TA method and the TFM, RTSM, W in SI or Btu/h in IP;
the RTSM used the PRFs and RTFs to perform the heat gain qθ = heat gain at time θ , W in SI or Btu/h in
Downloaded by [RMIT University Library] at 05:29 09 December 2017

and cooling load calculations, respectively. Ten years later, IP;


an improved RTSM was proposed by Nigusse and Spitler in qθ−δ = heat gain at time θ − δ, W in SI or Btu/h
2007. In this work, a set of dimensionless CTSFs were intro- in IP;
duced and the fenestration model was updated. The new fen- qθ−2δ = heat gain at time θ − 2δ, W in SI or
estration model used the solar incidence angle-based SHGC Btu/h in IP;
instead of older SC method. Today, the RTSM is considered qr,θ−n = radiant heat gain n hours ago, n =
the most accurate simplified method, 0,1,2, …23, W in SI or Btu/h in IP;
The differences between the five methods can be found in qe,θ−nδ = heat gain through walls or roofs, at time
the procedures used to calculate sensible heat gains and cool- θ − nδ, W in SI or Btu/h in IP;
ing loads for opaque surfaces. If additional time and cost are RFM = response factor method;
allowed on a project, the tools, such as ASHRAE LOADS RTSM = radiant time series method;
Toolkit, that use the HBM algorithms should be used as it RTFs = room transfer functions or radiant time
provides the most accurate peak cooling load calculations. factors;
Otherwise, one of the other simplified methods should be con- r0 , r1 , …, r23 = radiant time factors, dimensionless;
sidered, whose accuracies are acceptable under certain cir- SCL = solar cooling load, W/m2 in SI or
cumstances. In some cases, there is a tradeoff between calcu- Btu/(h- ft2 ) in IP;
lation accuracy and the degree of complexity of the methods. SC = shading coefficient, dimensionless;
Finally, the experience of design engineers is a significant fac- SHGC = solar heat gain coefficient, dimensionless;
tor for providing a reliable peak cooling load estimation. TA = time averaging;
TARP = thermal analysis research program;
Nomenclature TETD = total equivalent temperature difference,
°C in SI or °F in IP;
A = surface area, m2 in SI or ft2 in IP; TFM = transfer function method;
ASHGF = absorbed solar heat gain factor, W/m2 in TGER = ASHRAE task group on energy require-
SI or Btu/(h- ft2 ) in IP; ments;
BLAST = building load analysis and system ther- TSHGF = transmitted solar heat gain factor, W/m2
modynamics program; in SI or Btu/(h- ft2 ) in IP;
CLF = cooling load factor, dimensionless; tea = daily average sol-air temperature, °C in
CLTD = cooling load temperature difference, °C SI or °F in IP;
in SI or °F in IP; ti = indoor air temperature, °C in SI or °F in
CTFs = conduction transfer functions; IP;
CTSFs = conduction time series factors; te,T L = sol-air temperature at time lag (TL)
CLTDT = tabulated CLTD, °C in SI or °F in IP; hours ago, °C in SI or °F in IP;
c j = conduction time series factor (CTSFs), te,θ−nδ = sol-air temperature at time θ − nδ, °C in
dimensionless; SI or °F in IP;
DF = decrement factor, dimensionless; te,θ− jδ = sol-air temperature at time θ − jδ, °C in
DSA = double-strength sheet glass; SI or °F in IP;
ETD = equivalent temperature differentials; tr = indoor room temperature, °C in SI or °F
HBM = heat balance method; in IP;
NBSLD = national bureau of standards load deter- tm = mean outdoor temperature, °C in SI or
mination program; °F in IP;
PRFs = periodic response factors; U = overall heat transfer coefficient, W/ (m2 -
(Qθ )T F M = cooling load by TFM Method, W in SI K) in SI or Btu/(h-ft2 -°F) in IP;
or Btu/h in IP; WF = weighting factors;
10 Science and Technology for the Built Environment

θ = current hour, h; Kusuda, T. 1976. NBSLD, the computer program for heating and cool-
δ = time interval, h; ing loads in building. NBS Building Science Series 69, National
n = summation index, dimensionless; Bureau of Standards.
Linvill, J.G., and J.J. Hess. 1944. Studying thermal behavior of houses.
bn , cn = conduction transfer function coefficients,
Electronics 117–9.
W/(m2 -K) in SI or Btu/(h-ft2 -°F) in IP; Mackey, C.O., and L.T. Wright. 1944. Periodic heat flow—
dn = conduction transfer function coefficients, Homogeneous walls or roofs. ASHVE Journal 16(9):
dimensionless; 546–55.
ν0 , ν1 , ν2 , w1 , w2 = room transfer function coefficients Mao, C. 2016. Analysis of building peak cooling load calculation meth-
(weighting factors), dimensionless; ods for commercial buildings in the United States. Ph.D. Disserta-
YP j = periodic response factor (PRFs), tion. Department of Architecture. Texas A&M University.
Mao, C., J.S. Haberl, and J.C. Baltazar. 2012. Literature review on
W/(m2 -K) in SI or Btu/(h-ft2 -°F) in the history of building peak load and annual energy use cal-
IP. culation methods in the U.S. ESL-TR-12-12-02. Energy Systems
Laboratory. Report ESL–TR-12-12-02.
Mao, C., J.S. Haberl, and J.C. Baltazar. 2013. Peak heating/cooling load
Acknowledgments design methods: How we got to where we are today in the U.S. Pro-
ceedings of 13th International Conference of the IBPSA, Chambery,
Downloaded by [RMIT University Library] at 05:29 09 December 2017

The authors would like to give special thanks to Profes- France, August 25–28.
sor Daniel E. Fisher at Oklahoma State University, who Mitalas, G.P. 1972. Transfer function method of calculating cooling
loads, heat extraction and space temperature. ASHRAE Journal
kindly and patiently answered many questions regarding the 14(12):54–6.
ASHRAE RP-1117, and for providing all the related files and Mitalas, G.P., and D.G. Stephenson. 1967. Room thermal response fac-
source code to complete this work. tors. ASHRAE Transactions 73(Pt.1).
Nessi, A., and L. Nisolle. 1925. Regimes Variables de Fonctionnement
dans les Installations de Chauffage Central [Regimes operating vari-
References ables in central heating installations]. Paris, France.
Nigusse, B.A. 2007. Improvements to the radiant time series method
ASHRAE. 1961. ASHRAE Guide and Data Book 1961: Fundamentals cooling load calculation procedure. Ph.D. Dissertation. Depart-
and Equipment. New York, NY: ASHRAE. ment of Mechanical Engineering. Oklahoma State University.
ASHRAE. 1967. ASHRAE Handbook of Fundamentals. Atlanta, GA: Nigusse, B.A., and J.D. Spitler. 2010. Refinements and improvements
ASHRAE. to the radiant time series method. ASHRAE Transactions 116(1):
ASHRAE. 1972. ASHRAE Handbook of Fundamentals. Atlanta, GA: 542–9.
ASHRAE. Paschkis, V. 1942. Periodic heat flow in building walls determined by
ASHRAE. 1977. ASHRAE Handbook of Fundamentals. Atlanta, GA: electrical analog method. ASHVE Transactions 48:75.
ASHRAE. Pedersen, C.O., D.E. Fisher, and R.J. Liesen. 1997. Development of
ASHRAE. 1981. ASHRAE Handbook of Fundamentals. Atlanta, GA: a heat balance procedure for calculating cooling loads. ASHRAE
ASHRAE. Transactions 103(Pt.2):459–68.
ASHRAE. 1993. ASHRAE Handbook of Fundamentals. Atlanta, GA: Pedersen, C.O., R.J. Liesen, R.K. Strand, D.E. Fisher, L. Dong, and P.G.
ASHRAE. Ellis. 2001. A Toolkit for Building Load Calculations. Atlanta, GA:
ASHRAE. 1997. ASHRAE Handbook of Fundamentals. Atlanta, GA: ASHRAE.
ASHRAE. Rudoy, W., and F. Duran. 1974. ASHRAE RP-138 development of an
ASHRAE. 2013. ASHRAE Handbook of Fundamentals. Atlanta, GA: improved cooling load calculation method. Final Report, Atlanta,
ASHRAE. GA: ASHRAE.
ASHVE. 1951. American Society of Heating and Ventilating Engineers Smith, B. 2011. HVAC peak load calculation methods—History
Guide. New York, NY: American Society of Heating and Ventilat- and comparisons. http://www.elitesoft.com/web/newsroom/
ing Engineers. loadcalcs.html
Barnaby, C.S., J.D. Spitler, and D. Xiao. 2004. Updating the Sowell, E.F. 1988. Classification of 200,640 parametric zones for cooling
ASHRAE/ACCA residential heating and cooling load calculation load calculations. ASHRAE Transactions 94(Pt.2):754–77.
procedures and data. ASHRAE Final Report 1199. Sowell, E.F., and G.N. Walton. 1980. Efficient computation of zone
Brisken, W.R., and S.G. Reque. 1956. Heat load calculations by thermal loads. ASHRAE Transactions 86(Pt.1):49–72.
response. ASHRAE Transactions 62:391–424. Spitler, J.D., F.C. McQuiston, and K.L. Lindsey. 1993. The
Buchberg, H. 1958. Cooling load from thermal network solutions. CLTD/SCL/CLF cooling load calculation method. ASHRAE
ASHRAE Transactions 64:111–28. Transactions 99(1):183–92.
Fisher, D.E., and J.D. Spitler. 2002. Experimental validation of heat bal- Spitler, J.D., D.E. Fisher, and C.O. Pedersen. 1997. The radiant time
ance/RTS cooling load calculation procedure. ASHRAE Research series cooling load calculation procedure. ASHRAE Transactions
Project Report RP-1117. 103(Pt.2):503–15.
Harries, S.M., and F.C. McQuiston. 1988. A study to categorize walls Stephenson, D.G., and G.P. Mitalas. 1967. Cooling load calculations by
and roofs on the basis of thermal response. ASHRAE Transactions thermal response factor method. ASHRAE Transactions 73(Pt.1):
94(Pt.2):688–715. III. 1.1–1.7.
Hill, P.R. 1957. A method of computing the transient temperature of Stewart, J.P. 1948. Solar heat gain through walls and roofs for cooling
thick walls from arbitrary variation of adiabatic-wall temperature load calculations. ASHVE Transactions 54:361–89.
and heat transfer coefficient. Nat. Advisory Committee for Aero- U.S. Energy Information Administration (EIA). 2017. Monthly
nautics, Tech. Note 4105. energy review. https://www.eia.gov/totalenergy/data/monthly/
Hittle, D.C. 1979. BLAST-The building loads analysis and system pdf/mer.pdf
thermodynamics program. Vol. I, User’s Manual. U.S. Army Walton, G.N. 1983. Thermal Analysis Research Program Reference
Construction Engineering Research Laboratory (CERL) Report Manual. NBSSIR 83–2655. Washington, DC: National Bureau of
CERL-TR-E-119. Standards.

You might also like