Professional Documents
Culture Documents
Keywords— Triplen harmonics, magnetizing current, finite Figure 1: Asymmetrical saturation on 3p5L transformer.
element method.
Under GIC bias, the saturated core becomes a much
I. INTRODUCTION higher reluctance path which requires more ampere-turns to
Geomagnetically induced currents (GIC) are quasi-dc produce the same amount of flux in order to sustain the
currents with frequencies that range between 0.001~0.1 Hz system sinusoidal voltage level. Also, the core nonlinearity
[1]. GICs are not the sole source of DC currents in power demands extremely large harmonic components in the
grids. DC current may be injected from HVDC lines exciting currents. Reduced core permeability and increased
operating near ac grids, photovoltaic systems connected to exciting magnetic gradient result in a large amount of stray
the grid via inverters, and ac and dc drives. Their effects on flux being generated. As a consequence, stray flux heating
the power system are costly to power utilities. In South could occur in windings, structural metallic parts, winding
Africa, several transformers were damaged during the supports, and the tank plate. Local hot spots could develop
Halloween Storm [2]. The primary effect of GIC current to which could damage paper insulation and cause gassing and
transformers is asymmetrical saturation. Asymmetrical transformer oil combustion.
saturation lead to increased harmonics, noise, magnetization
current, voltage drop, hot spot temperature rise and reactive B. Hypothetical Mitigation Strategies
power demand. Large excitation currents flowing in the
power system under dc-bias have also been found to cause Different methods have been proposed to mitigate the
false tripping of relays especially in capacitor banks and effects of GIC [3]. The methods proposed vary in the
static var compensators. Tripping of these reactive power techniques used: GIC blocking devices and monitoring and
reserves may lead to catastrophic events such as blackouts control techniques. The GIC blocking devices proposed can
or even permanent damage to insulators, capacitors, static either be installed in the phases or on the neutrals of
var compensator (SVC) firing thyristors and transformers. grounded transformers. Transmission line series capacitors
Mal-operation of relays is also linked to even and odd can be used to block the flow of GIC on power lines – this
harmonics generated by saturated transformers conducting method has been found to be ineffective in the US power
GIC. The main focus of this paper thus dwells on the grid [4]. A capacitor can be installed in the neutral of the
harmonic content of transformers under GIC attack, and the transformer to block GIC currents from entering the
levels of dc current causing such damages. High magnitudes transformer. The drawbacks of this method are that it would
of magnetizing current that is rich in harmonics results in bring considerable uncertainty and risk of impedance
high flux in the core and its surroundings. The increase in changes and ferroresonance concerns on the network. Partial
flux results in increased core losses and hotspot temperature GIC blocking can also be done by installing a resistor in
within structural parts of the transformer. This additional neutral of the transformers. The neutral GIC blocking
heating causes insulation degradation that may cause resistor can reduce overall GIC levels by approximately 60
premature failure of the transformer. to 70% [4]. Monitoring and control techniques involves
measuring the dc current and relates them to known network
II. LITERATURE REVIEW parameters that changes under dc conditions. The
parameters that can be used are:
A. Asymmetrical Saturation Caused by GIC
The primary effect of GIC current to transformers is • Voltage and/or var swings.
asymmetrical saturation. DC flowing in power transformers • Abnormal temperature rise and transformer noise
causes an upward shift in the voltage and this drives the • Dissolved gases
transformer in saturation region. In deep saturation, the • GIC related harmonics
transformer’s inductance is lowered, allowing more
magnetizing current to flow in the transformer. Figure 1 Accurate modelling of these indicators of the presence of
shows a waveform for an asymmetrically saturated GIC is required in the power system industry. That is why it
transformer, measured on a 15 kVA five-limb used in this is very important to find thresholds and trends of harmonics,
investigation. reactive power, dissolved gases and temperature rise under
dc-bias.
C. 3p5L Transformer Structure and its Response to GIC parameters of the real transformer. The equivalent circuit
The 3p5L transformer is mostly used in European parameter are shown in Table 1.
networks but it is also available in the South African
network. The transformer has two return paths for flux, this TABLE 1: THE EXACT EQUIVALENT PARAMETERS OF THE
is not the case in a three-phase three-limb (3p3L) TRANSFORMER.
transformer. In a 3p3L transformer conducting GIC, the flux
must travel through a high reluctance path outside the core 3p5L, 380/380 V, 15 kVA Transformer
to complete its circuit. The stray flux is believed to cause Parameter Impedance (�)
heating of the tank and other structural parts of the 1800.1775
transformer. Most studies have reported that there is no stray j923.273
flux outside the core in a five-limb transformer. Thus, it is 0.2357
envisaged that, heating of the tank in the five-limb 0.2357
transformer cannot occur as a result of GIC flow. However,
j0.2357
this does not dismiss that heating of other structural parts of
the transformer does not occur. There was a fast rise in the j0.2357
flux in the core as measured using search coils tied around
the core in the investigation that we carried out in the
III. LABORATORY TESTING SYSTEM
laboratory. This rise in flux may cause heating of the core,
tie plates and core bolts in power transformers. This investigation was conducted on power
transformers through a series of laboratory experiments. The
voltage and current total harmonic distortion (THD)
measurements with a Yokogawa WT1800 power analyzer,
up to the 60th component, are shown below. Figure 3 is a
representation of the experimental setup. The system was
supplied from a power supply with 1.1% voltage THD,
much less than the standard limit of 5% according to IEEE
standards [5].
(1)
(2)
(3)
A 3p5L model was developed using the exact Figure 3: Test system for transformer response to GICs
dimensions provided by the manufacture. Short circuit and
open circuit tests were conducted to find the equivalent
circuit parameter of the transformer. The equivalent circuit
parameters are required for refining the model to match the
IV. EXPERIMENTAL RESULTS
The laboratory experiments have shown that there is
severe increase in harmonics in transformers conducting dc
current. The tests compared the effects of harmonics under
different load types. FEM simulations were also done and
they showed that there is a wide harmonic spectrum of both
odd and even harmonics under dc conditions.
A. Magnetizing Current
The transformer magnetization current waveforms at 0
A, 1 A and 6 A of dc current injected in the transformer
neutral showed an increase in the magnetizing current.
The transformer hysteresis loop represents the C. Total Harmonic Distortion (THD)
transformer’s inductance, and as it enters in saturation The results for the THD variation at the input side is
region the inductance drops heavily allowing more shown in Figure 6. Current and voltage THD with a load of
magnetizing current to flow. The current waveform is 1.5 kW is 1.2% and 1.1% with no dc injected into the
distorted as seen from Figure 4 above, which results in system. A dc current approximately 2.2 A is sufficient
harmonics generation in the transformer. enough to give a THD rise of current beyond the IEEE
threshold of 20% [5]. In contrast, voltage THD needs a
much higher current of to surpass the IEEE threshold of 5%.
B. Harmonics on Load
It can be seen that there is a very steep rise in current THD
Several researchers have said that triplen or third order between 1 A and 12 A in the neutral. At higher values of dc
harmonics are predominant in transformers conducting GIC the THD will stabilize because the inductance of the
[6, 7]. This research has shown that this is the case at no transformer will be almost constant in deep saturation. It is
load only for 3p5L transformers as seen from Figure 5. believed that as more dc current is injected, the transformer
When the transformer is loaded, both even and odd will reach air core saturation and that subsequently lead to
harmonics exist with no specific order being predominant. the THD to drop.
Figure 6: Current and voltage THD as measured from the input side
The input and output THD of voltage is shown in Figure Fast Fourier Transform (FFT) results showing increasing
7. As explained earlier, in both cases, a dc current of 25 A dc harmonic content for a 3p5L transformer, with magnitudes
in neutral is required to surpass the IEEE threshold of of harmonics decreasing at higher order.
voltage. This current is 36.71 percent of the rated current of
the transformer used in the investigations.
V. DISCUSSIONS
Figure 7: Input and output voltage THD This paper investigated the harmonics generated under
varying dc conditions. There is an increase in the harmonics
The voltage THD at varying loads was also investigated generated. This will lead to a number of effects which
in order to establish the effect of load type on THD. Three include: transformer heating, mal-operation of relays, static
different loads that were used are; THD r1 – at 1.5 kW load, var compensators tripping.
THD r2 – at 3 kW load, THD rl3 – at 6.4 kVA. The
conclusion is that voltage THD is lower for resistive loads
A. Considerations for Large Power Transformers
than inductive loads, while it is slightly maintained for
resistive loads. This means power utilities will suffer the The THD threshold for large power transformer is 1.5%
effects of GIC more when they have inductive loads. Figure [9] in accordance with IEEE standard. Using the results for
8, shows the variation of voltage THD at varying loads. smaller power transformer, it takes a current of 3 A to
surpass this standard. This result correlates with experiments
done on MVA range power transformers [10, 11]. The limit
for transmission transformers is very low because if the
supply has a higher THD, the resultant THD in distribution
systems will be very much high. The results have shown
that inductive loads cause an increase in the system THD.
This is why the THD becomes high in distribution networks.