EMCP 4.4 Generator Set Controller: Attachment
EMCP 4.4 Generator Set Controller: Attachment
EMCP 4.4
GENERATOR SET
CONTROLLER
LEHE0135-04 1
Attachment
Standard Features
Generator Monitoring Inputs & Outputs
Voltage (L-L, L-N) Eight dedicated digital inputs
Current (Phase) Four analogue inputs
Average Volt, Amp, Frequency Twelve programmable digital inputs
kW, kVAr, kVA (Average, Phase, %) Seventeen programmable digital outputs
Power Factor (Average, Phase) Communications
kW-hr, kVAr-hr (total)
Primary and accessory CAN data links
Excitation voltage and current (with CDVR)
RS-485 annunciator data link
Desired Voltage, Excitation Command, Operating
Mode (with IVR) Modbus TCP (10BT Ethernet)
Generator stator and bearing temp (with optional Modbus RTU (RS-485 Half duplex)
module) Webserver
kW load histogram Language Support
Arabic, Chinese, Danish, Dutch, English, Finnish,
Generator Protection French, German, Greek, Italian, Japanese, Polish,
Generator phase sequence Portuguese, Russian, Spanish, Swedish, Turkish
Over/Under voltage (27/59) Environmental
Over/Under frequency (81 O/U)
Control module operating temperature:
Reverse Power (kW) (32)
-40°C to 70°C
Reverse Reactive Power (kVAr) (32RV)
Display operating temperature: -20°C to 70°C
Overcurrent (50/51)
Current Balance (46) Humidity: 100% condensing 30°C to 60°C
Storage temperature: -40°C to 85°C
Engine Monitoring Vibration: Random profile, 24-1000 Hz, 6.0G rms
LEHE0135-04 2
Attachment
Paralleling Functions
LEHE0135-04 3
Attachment
Modes of Operation
Multi-generator set paralleling Peak Lopping Closed Transition: The EMCP 4.4
will parallel the generator set to the utility and soft
The EMCP 4.4 can operate as a multi-generator set load the generator set to the programmed utility
paralleling controller, with up to 16 generator sets disconnect level and then open the utility breaker.
synchronized and controlled on a common bus. When leaving this mode, the generator set will
Support is provided for both emergency standby and parallel back to the utility and soft unload the
prime power operation. Features include automatic generator set to the programmed disconnect level.
paralleling, dead bus arbitration, load sharing, and
load sense-load demand. Peak Lopping Open Transition: The EMCP 4.4
will open the utility circuit breaker and close the
Single Unit Utility Paralleling
generator breaker after a programmed time delay
The EMCP 4.4 can operate as a single generator set and take over the load. When leaving this mode,
paralleling to a single utility. Support is provided for the EMCP 4.4 opens the generator circuit breaker
controlling both a generator circuit breaker and utility and closes the utility breaker after a programmed
circuit breaker. Features provided include time delay.
Emergency, Baseload, Import, Export, Peak Lopping
Open Transition and Peak Lopping Closed Transition. Automatic paralleling
Soft loading during closed transitions is automatically In the automatic paralleling mode, the EMCP 4.4
provided. Support is not available for multiple sources controller automatically adjusts the voltage and
connecting to the bus beyond the single generator set frequency of the generator set. When the generator
and single utility connection. output is synchronized with the second source, the
EMCP 4.4 controller closes the generator circuit
Baseload: TThe EMCP 4.4 generator set will breaker.
provide a programmed kW level at a programmed
power factor to the utility. Manual paralleling
o The EMCP 4.4 is also capable of operating In the manual paralleling mode, the operator will
as a single controller paralleling to the utility manually adjust the voltage and frequency of the
across a single intertie circuit breaker. generator set. When the generator set is synchronized
When operating in this mode, support for with the second source, the operator will initiate a
baseload of real power and Power Factor is generator circuit breaker close command. A 3-phase
provided. sync check function is also included to prevent out of
phase paralleling.
Import: The EMCP 4.4 will adjust provided kW to
meet a programmed kW and programmed power Sync check mode
factor as measured across the utility breaker being In the sync check mode, the EMCP 4.4 controller
imported into the system. automatically adjusts the voltage and frequency of the
generator set without closing the generator circuit
Export: The EMCP 4.4 will adjust provided kW to breaker. When the generator set is synchronized with
meet a programmed kW and programmed power the second source, the operator will initiate a
factor. as measured across the utility breaker being generator circuit breaker close command. A 3-phase
exported from the system. sync check function is also included to prevent out of
phase paralleling.
LEHE0135-04 4
Attachment
The EMCP 4.4 provides advanced overcurrent The programmable cycle timer (PCT) feature allows for
detection for protection of the generator set system. programming of seven independent times, when tasks
The Generator Inverse Definite Minimum Time (called PCT outputs), will be activated or deactivated
Curve type selection allows for additional configuration automatically during the week. This is useful for
of the overcurrent protective scheme. Selections exercising generator sets, or cases where two or more
include: Normally Inverse, Very Inverse and Extremely generators are required to automatically share the duty of
Inverse. Respectively, these curves have supplying a load throughout the week. Using the PCT,
progressively slower trip times for the same conditions each generator set can be programmed to start and stop
and configurations. at pre-set times. The PCT can handle a seven-day
A fourth selection entitled Thermal Damage Curve is sequence with seven independent starts happening one
available that is specific to the generator design, or more times each week. Each of the seven timers has
causing an overcurrent shutdown after a defined trip the following set points: activation day of the week,
time expires. activation start time, active time and includes three (3)
independent activation outputs.
Integrated programmable logic controller (PLC)
Real (kW) load histogram
This feature set of the EMCP 4.4 allows the user to
create custom logic functions in similar fashion to that The EMCP 4.4 is equipped with a real (kW) load
of the capability of a PLC controller. These logic histogram. This feature keeps track of the amount of
functions allow for increased capability of the EMCP time the generator percent kW is within certain
4.4 through interaction and control of internal signals predefined ranges. The four ranges include:
within the control software as well as the 1. Time spent below 30% load
programmable inputs/outputs of the device.
2. Time spent greater than or equal to 90% load
Programmable kW relay and less than 100% load
The EMCP 4.4 includes three programmable kW relay 3. Time spent greater than or equal to 100% load
outputs configured based on the % kW of the and less than 110% load
generator set. The configurable set points of the kW 4. Time spent greater than or equal to 110% load
relay include: trigger condition, percentage threshold,
hysteresis percentage and trip activation & Webserver
deactivation delay time. These output functions may The EMCP 4.4 controller includes an embedded web
also be used to trigger events, recordable within the server. The embedded web server allows the
event log and included in the remote monitoring of the operator to view basic event status, engine overview,
generator set. and generator overview over an Ethernet connection
to a local and/or remote viewing station.
LEHE0135-04
5
Attachment
Optional Modules
CAN annunciator Digital input/output module
The EMCP 4 CAN annunciator
serves to display generator set
system alarm conditions and status
indications.
The annunciator has been designed
for use on the accessory
communication network and may be
used in either local (package
mounted) or remote (up to 800 feet)
application. A maximum of four
annunciators may be used with a
single EMCP 4.4. The Digital input/output (DI/O) module serves to
provide expandable Input and Output event capability
RS-485 annunciator of the EMCP 4 and can read 12 digital inputs and
setting 8 relay outputs. The DI/O module has been
The EMCP 4 RS-485 Annunciator designed for use on the accessory communication
serves to display generator set network and may be used in either local (package
system alarm conditions and status mounted) or remote (up to 800 feet) application.
indications. The annunciator has
been designed for use on the long RTD module
distance annunciator datalink and is
used for remote (up to 4000 feet)
applications.
LEHE0135-04 6
Attachment
The thermocouple module serves to provide The EMCP 4.4 SCP is a wall-mountable control panel
expandable engine and generator temperature which adds 16-stage load add and load shed
monitoring capability of the EMCP 4 and can read functionality to an EMCP 4.4 island mode system
up to twenty type J or K thermocouple inputs. The (non-utility paralleling). Based on the proven
thermocouple module has been designed for use on reliability and serviceability of the EMCP 4, the SCP
the primary communication network for engine controller is fully integrated with each generator set
information and the accessory communication mounted EMCP 4.4 via the MGDL paralleling network.
Network for generator information. It may be used in
either local (package mounted) or remote (up to 800
feet) application. A maximum of one thermocouple EMCP 4.4 Master Control Panel (MCP)
modules may be used with a single EMCP 4.4 on
each datalink.