Professional Documents
Culture Documents
Calculation of Harmonic Current Content in PV Power Plants Based On Single Inverter Data
Calculation of Harmonic Current Content in PV Power Plants Based On Single Inverter Data
net/publication/236119496
CITATIONS READS
0 566
5 authors, including:
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Joerg Dannehl on 04 June 2014.
Abstract-- PV power plants connected in parallel with the II. REQUIREMENTS
medium voltage (MV) network have to fulfil certain
The maximum amount of harmonic currents, which a
requirements for the amount of harmonic current which they
generate. Normally, one reference measurement on a single plant connected to the same point of common coupling
inverter is extrapolated to estimate the amount of harmonics (PCC) as other plants, is given as (eq. 2.4.3-2 in [1]):
from an entire power plant with several inverters. We show in SA
this paper that the normal method of extrapolating is not I vAzul ivzul S kv (1)
always valid for both weak and strong networks. The SGesamt
underlying reasons why the established method fails could be where iνzul is the relative limit given in table 1 below, Skv is
that they are made for PWM inverters with low switching the short circuit power at the PCC, SA is the apparent power
frequency and control bandwidth, whereas PV inverters tends
to operate at high switching frequencies (> 10 kHz). of the plant under investigation and SGesamt is the total
apparent power for all plants. Note that if only one plant is
Index Terms-- Harmonic current, Low voltage network, connected at the PCC, then SA = SGesamt. If the MV network
Medium voltage network, Photovoltaic. contains more PCC’s, the limit for each PCC is given as (eq.
2.4.3-4 in [1]):
I. INTRODUCTION
SGesamt (2)
I vAzul ivzul Skv
P hotovoltaic power plants connected in parallel with the
medium voltage (MV) network have to fulfil certain
requirements for the amount of harmonic current which they
S Nezt
where SNetz is the size of the transformer connecting the MV
inject into the network [1], [2], [3], [4]. Since PV power network with the HV network, assuming the generators to
plants are only recently being connected with the MV include a voltage source inverter controlled by means of
network, there is not much known knowledge about their pulse width modulation (PWM) and switching at minimum 1
harmonic current injection [5]. So far, results from the wind kHz.
turbine industry has been adopted for calculating the amount TABLE 1: ALLOWED HARMONIC CURRENT, WHICH MAY BE FED IN TOTAL
of harmonics the PV power plants injects into the MV INTO THE MV NETWORK [1].
network [1], [2]. The present state of the art calculation-
principles lead to a situation where most of the power plants
exceed their limits, and hereby have to lower the amount of
installed power. Reason for that could be the calculation
principles instead of real life measurements. The background
for this paper is the method still applied for wind turbines,
but with focus on the validity of the method. The method is
investigated by measuring the harmonics content of multiple
inverters (up to nine) and the sum at the point of common
coupling on the low and medium voltage side of the mains
transformer.
The content of this paper is as follows. An introduction to
the problem is given in section 2. Measurements are
presented in section 3 and finally a conclusion is given in Equation (1) assumes that the harmonic currents add
section 4. together in a constructive approach, i.e. positive
interference, whereas (2) assumes that the sum of the
harmonic currents are attenuated due to negative
interference, i.e. harmonic phase-displacement between the
1 Søren Bækhøj Kjær (sbk@danfoss.com), Adrian Constantin generators.
(adrian@danfoss.com), Radu Dan Lazar (radu@danfoss.com) and Jörg
Dannehl (dannehl@danfoss.com) are with Danfoss Solar Inverters, DK-
In PV power plants, especially in string inverter plants
6400 Sønderborg with high number of inverters, the important question is how
2 Marko Ibsch (Marko.Ibsch@gl-group.com) is with GL Garrad Hassan these harmonics sum up on the secondary side (LV network)
America, Inc
of the connecting transformer, in order to estimate the
amount of harmonics at the PCC based on one inverter data.
The method used in [1] (eq. B.2.4-3) for PWM controlled
inverters with a switching frequency above 1 kHz, is:
I
n (3)
I
2
i 1 ,i
I
n (5)
I i 1 ,i
III. MEASUREMENTS
The PV test power plant is composed by nine Danfoss
TLX 15 kVA inverters coupled to a relatively weak grid
using the star topology as shown in Figure 1. Each inverter is
connected to the feeding transformer through a cable not
longer than 100 meters and with approximate 1% loss at
nominal power. The transformer is ΔΥ type, thus harmonics
of orders odd multiple of three do not pass to the MV
network (they are circulating in the Δ windings on the
primary side). The currents are measured simultaneously Figure 2: Busenwurth 12 MW PV power plant from the air, courtesy of
with a data acquisition solution from Dewetron. Using the Möhring Energie GmbH [6].
nominal data for the test plant (see Figure 1) the results in
Additional 8 MW
(1) and (2) are IνAzul / iνzul = 1.55 and 1.27, respectively. Uk = 20 kV power plant
Sa = 154 MVA
The first results (figures 4 to 7) are obtained with a R = 0.19 Ω
XL = 2.59 Ω
3 2
2 1
1 0
0 5 10 15 20 25
Harmonic order
st th
Figure 6: LV busbar vs. MV PPC harmonics in the range 1 - 25 with
non-optimized control algorithm.
0
0 5 10 15 20 25
Harmonic order
st
Figure 4: Harmonics in the range 1 – 25 with non-optimized control th If one compares the LV busbar harmonics with the
algorithm, measured at the LV busbar. harmonics measured in MV at the PCC (see Figure 7) it is
obvious that the harmonics multiple of three are almost
Figure 4 shows a poor match between the estimated and disappearing from the picture (they are circulating in the Δ
measured data for most of the harmonics. For the 3rd, 5th and windings on the primary side of the transformer, generating
7th harmonic, the sum of harmonic currents from all nine losses). This is due to the ΔΥ connection of the transformer
inverters (yellow bars) is higher than the one predicted when which will suppress these harmonics. In most cases, the
only one inverter is running (blue bars). This indicates that currents on the primary side of the transformer are slightly
the inverters are disturbing each other to generate a higher attenuated, but this could also be a case of errors in the
level of harmonics. The reason for this could be the weak measurements / calibration of current probes. The higher
network. For higher order harmonics the estimation is order harmonics are more or less showing the same picture
getting closer to the measured results, but both over and in Figure 7.
under estimating the levels. However, in all cases the results
from one inverter is always higher then the sum, indicating Limit for one PCC in MV
Nine inverters injecting power (measured in LV busbar)
destructive interference. Nine inverters injecting power (measured at MV PCC)
0.2
Harmonic level [%]
0.2
0.15
Harmonic level [%]
0.15
0.1
0.1
0.05
0.05
0
25 30 35 40 45 50
Harmonic order
2
Harmonic level [%]
1.5
1
1
0.5
0.5
0
0 5 10 15 20 25
Harmonic order 0
0 5 10 15 20 25
Figure 8: Harmonics in the range 1st – 25th with default control Harmonic order
algorithm, measured at the LV busbar. Figure 10: Harmonics in the range 1st – 25th measured in Busenwurth
plant at the LV busbar for block 1.
In this case (Figure 8) the estimation is better than the
previous case showing that poor control can seriously affect 0.4
the expected harmonic levels. Still the 2nd, 5th, 6th, 7th and 9th Reference inverter - Wind test measurement
LV bus bar estimation eq.4
0.15
0.2
Harmonic level [%]
0.1
0.15
0.05
0.1
0
25 30 35 40 45 50
Harmonic order
IV. CONCLUSION
At this moment there is no feasible general method which
can estimate the current harmonics in MV based on data
from one LV generating unit, in case of LV plants with
identical generating units coupled to MV through a
transformer.
Nevertheless such a method cannot be pure theoretical
due to complexity of the necessary calculations and
multitude of parameters. In case of a more practical
approach (experience based) there is a sum of situations
which might not be covered.
For this reason the best method until now is still the direct
measurement in MV using the before and after approach in
order to be able to subtract the background harmonics [4].
A good current control will always ensure that the
harmonic level is low, easing the compatibility with
harmonic standards not only for LV but also for MV.
V. REFERENCES
[1] Technical guideline: Generating Plants Connected to the Medium-
Voltage Network. Guideline for generating plants’ connection to and
parallel operation with the medium-voltage network. BDEW June
2008.
[2] IEC 61400-21 ed. 2. Wind turbine generator systems – Part 21:
Measurements and assessment of power quality characteristics of grid
connected wind turbines.
[3] FGW TR3 Rev. 21, Bestimmung der Elektrischen Eigenschaften von
Erzeugungseinheiten am Mittel-, Hoch- und Höchstspannungsnetz,
http://www.wind-fgw.de/
[4] N. Goldenbaum, P. Brogan, B. Andresen, “HARMONIC
DISTORTIONS FROM LARGE WIND FARMS EQUIPPED WITH
MODERN WIND,” EWEA 2011, Brussels, Belgium.
[5] S. B. Kjær, J. Dannehl, F. Mecking and J. Godbersen, “A 12
megawatt power plant with full implemented ancillary services
according to the German grid codes the first results,” in Proc. of 26th
European Photovoltaic Solar Energy Conference and Exhibition
(EUPVSEC) / 6th World Conference on Photovoltaic Energy
Conversion, Hamburg, Germany, 2011.
[6] http://www.moehring-energie.de/