You are on page 1of 7

64/4CPIG"&KIKVCN"/GVGT

22-811 OWNER’S MANUAL — Please read before using this equipment.

%106'065 a range when you measure voltage, current, power from the circuit you are measuring
resistance, capacitance, and frequency. You before you connect test leads to high-
Introduction ....................................................... 1 can also manually set the range when voltage points.
A Word About Safety ........................................ 1
measuring values you know are within a • Never connect the test leads to a source
Special Panel Markings .................................... 2
certain range. of voltage when you select the diode
Specifications .................................................... 2
A Quick Look at Your Meter ............................. 3 check, resistance measurement,
Diode Check Function — the meter safely
Preparation ........................................................ 3 capacitance measurement, continuity
checks semiconductor junctions for open,
Installing a Battery ............................................ 3 function, frequency function, and electric
Connecting the Test Leads ............................... 3 short, or normal.
field detection function, or any of the
Using the Meter ................................................. 3 current measurement functions.
Electric Field Detection — Lets you detect
Turning the Meter On/Off/Testing the Display .. 3
Before You Start ............................................... 3 the presence of AC voltage. • Always discharge any capacitors of the
Holding a Measurement ................................... 4 circuit under test before you attach test
Data Hold Function — the meter holds the leads.
Using Relative Measurement ........................... 4
Automatic Power Off ........................................ 4 displayed value, so you can see the reading
even after you disconnect the probes. • Always turn off power and disconnect
Using Power Lock ............................................ 4
the test leads from the circuit you are
Making Measurements ...................................... 4
Auto-Polarity Operation — protects your testing before you replace the meter’s
Measuring DC/AC Voltage ............................... 4
Measuring AC Voltage Riding On a DC Source meter and gives valid measurements when battery or fuse.
Bias 5 you connect the leads in reverse polarity. • Never operate the meter unless its back
Measuring Three-Phase AC Voltage 5 cover and battery cover are in place and
Measuring DC/AC Current ............................... 5 Auto Power Off — the meter turns itself off
fully closed.
Measuring Resistance ...................................... 5 after about 30 minutes if you do not change
Measuring Capacitance ................................... 6 any setting, helping conserve battery power. • This equipment is rated for installation
Checking Continuity ......................................... 6 category II (maximum 3600VA).
Checking Diodes .............................................. 6 UL Listed — your meter has passed the • Because many AC/DC sets have a
Checking Diode Polarity 6 stringent safety tests required by potentially hot chassis, be sure the top of
Measuring Frequency/Duty Cycle .................... 7 Underwriters Laboratories. your workbench and the floor
Measuring an Electric Field .............................. 7
underneath it are made of non-
Care .................................................................... 7 Note: The UL mark does not indicate that this
conductive materials.
Cleaning ........................................................... 7 product has been evaluated by Underwriters
Replacing the Fuse .......................................... 7 Laboratories for the accuracy of its readings. This meter is fully calibrated and tested,
Under normal use, no further adjustment
Latest IC and Display Technology — should be necessary except as noted in this
+0641&7%6+10 ensures reliability, accuracy, stability, and Owner’s Manual. If the meter requires repair,
Your RadioShack 42-Range Digital Meter is a ease of operation. do not try to adjust it yourself. Take it to your
portable, compact, auto-ranging, digital local RadioShack store.
Overload and Transient Protection —
multimeter. It is ideally suited for field, lab, helps protect the meter from accidental WARNINGS:
shop, and home applications. The multimeter overload in most ranges.
provides precise measurements and is built • Use extreme caution in the use of this
to provide the highest possible reliability. The Note: Your multimeter requires one 9V device, improper use of this device
meter measures DC and AC voltage up to battery (not supplied). can result in injury or death. Follow
600V, DC and AC current up to 10A, all safeguards suggested in this
resistance up to 40MΩ, capacitance from owner’s manual, in addition to normal
0.5nF to 40µF, and frequency from 10Hz to #"914&"#$176"5#('6; safety precautions, in dealing with
4MHz. Its 33/4-digit digital display can display We have taken every precaution in designing electrical circuits. Do not use this
up to 4,000 units. this meter to ensure that it is as safe as we device if you are unfamiliar with
can make it. But safe operation depends on electrical circuits and testing
Important:
you, the operator. We recommend that you procedures.
• Completely read this manual before you follow these simple safety rules: • Never try to probe with both test
use this meter. leads at the same time or hold both
• If you are not familiar with meters and • Never apply voltages to the meter that test leads in one hand.
testing procedures, we suggest you read exceed the limits given in the
specifications. Never apply more than • Use extreme care while using the
Using Your Meter (Cat. No. 62-2039, not meter to measure current and voltage
supplied) before you use this meter. 600V DC and AC between the input
jacks and ground. in commercial electrical panels.
Auto-Ranging with Manual-Ranging Unlike a home AC outlet, a
Override — the meter automatically selects • Use extreme caution when working with
commercial electrical panel has
voltages above 100V. Always disconnect

© 2001 RadioShack Corporation.


All Rights Reserved.
RadioShack and RadioShack.com are trademarks
used by RadioShack Corporation.
tremendous current surge potential. 52'%+(+%#6+105 Sensitivity
This is especially true for three-phase 400Hz–4k–40kHz ................................. 50 mVrms
industrial electrical panels. A small (Accuracies at 73.4°F (23°C) ±5°C, <75% RH) 400kHz ............................................... 100 mVrms
spark from one of these panels can
DC VOLTS (Maximum Measurement: 600V) 4MHz .................................................. 350 mVrms
cause a plasma explosion and fire
that can severely burn you. Do not 400mV ................................... ± 0.5% of Reading, DUTY CYCLE (10Hz to 100kHz)
hold the meter while using it. ± 4 in Last Digit 10% – 90% (Square wave at +5V/–0V)
4V to 40V ............................... ± 0.8% of Reading, ± 2 digits/kHz, ± 2 in last digit
• Always wear protective leather
gloves, a face shield, and fireproof ± 3 in Last Digit Note: Duty Cycle accuracy is dependent upon
400V ...................................... ± 0.8% of Reading, input signal frequency.
arm and upper body protection while
using the meter to measure current ± 3 in Last Digit DIODE MODE
and voltage in commercial electrical 600V ...................................... ± 1.0% of Reading, Open Circuit Voltage .............................. < 2.8Vdc
panels. ± 4 in Last Digit Test Current ..................................... 1 mA Typical
• If this equipment is used in a manner AC VOLTS (Maximum Measurement: 600V at 50/ CONTINUITY BEEPER
not specified by the manufacturer, 60 Hz, Average Responds, RMS Calibrated, DC
Coupled) Continuity (short) ......................... ≤ 50 ± 30 Ohms
the protection provided by the Open ........................................... > 50 ± 30 Ohms
equipment may be impaired. 400mV ................................... ± 0.8% of Reading,
± 4 in Last Digit Open Circuit ......................................... < 2.8 Volts
• To reduce the risk of fire or shock
4V .......................................... ± 0.5% of Reading, Short Circuit Current .............................. < 2.0 mA
hazard, do not expose this product to
± 3 in Last Digit Beeper Volume (at 5cm) ...................... 65dB Min.
rain or moisture.
40V to 400V ........................... ± 1.0% of Reading, ........................................................... (audio scale)
• For indoor use only. ± 3 in Last Digit
GENERAL
600V ...................................... ± 1.2% of Reading,
52'%+#."2#0'."/#4-+0)5 ± 4 in Last Digit
Maximum Common
Mode Voltage ....................... 500VDC or RMS AC
For your safety, we have added special DC CURRENT (Maximum Measurement: 10A)
Battery Life at 30 minutes
markings to the meter’s panel to remind you 400µA ........... ± 0.8% of Reading, ± 5 in Last Digit use per day ................... About 200 days, Alkaline
of the measurement limitations.
4mA .............. ± 0.8% of Reading, ± 3 in Last Digit Sleep Mode Timing ..................... 30 ± 10 Minutes
The maximum voltage that this 40mA ............ ± 1.0% of Reading, ± 5 in Last Digit Range Up Detect Value ......................... Overflow
600V • meter can measure is 600V DC and 400mA .......... ± 1.0% of Reading, ± 3 in Last Digit (>4000 Counts)
400mA AC. The maximum current that this 4A ................. ± 1.0% of Reading, ± 5 in Last Digit Range Down Detect Value ................. 380 Counts
MAX meter can measure at this jack is
10A ............... ± 1.2% of Reading, ± 5 in Last Digit Low Battery Indication ....................... 6.3V ± 0.3 V
400mA DC and AC.
AC CURRENT (Average Responds, RMS Cali- Sleep Mode Current ....................... 10 µA Normal,
Caution: Be extremely careful when
brated, 10A Maximum, DC Coupled) 20µA Max.
making high-voltage
measurements; DO NOT TOUCH 400µA ........... ± 1.0% of Reading, ± 5 in Last Digit Input Impedance ................... DCV/ACV: 10Mohm
TERMINALS OR PROBE ENDS. 4mA .............. ± 1.0% of Reading, ± 3 in Last Digit Power Source ........ One 9V battery (not supplied)
Caution: Risk of electric shock! 40mA ............ ± 1.2% of Reading, ± 5 in Last Digit Operating Temperature .................. 41°F to 104°F
Refer to the complete operating (+ 5°C to + 40°C)
! instructions.
400mA .......... ± 1.2% of Reading, ± 3 in Last Digit
Storage Temperature .................... – 4°F to 140°F
4A ................. ± 1.2% of Reading, ± 5 in Last Digit
The meter is protected by double (– 20°C to + 60°C)
10A ............... ± 1.5% of Reading, ± 5 in Last Digit
insulation. Humidity ........... Maximum Relative Humidity 80%
RESISTANCE for temperatures up to 87.8°F (31°C),
This equipment is rated for
CAT II INSTALLATION CATEGORY II 400Ω ...................................... ± 0.8% of Reading, decreasing linearity to
(3600VA max.). ± 5 in Last Digit 50% relative humidity at 104°F (40°C)

To avoid electrical shock or 4kΩ – 40kΩ– 400kΩ .............. ± 0.8% of Reading, Dimensions (HWD) ........ 61/3 × 31/8 × 19/16 Inches
500V ± 3 in Last Digit (161 mm × 80 mm × 39.5 mm)
instrument damage, do not connect
MAX the common input terminal (– COM 4.0MΩ ..................................... ± 1.0% of Reading, Weight ................................ Approx 6.8 oz (195 g)
jack) to any source that exceeds ± 3 in Last Digit Accessories ............................. Fuse 500mA/250V
500 volts with respect to earth/ 40MΩ ..................................... ± 2.0% of Reading, 2 shrouded test leads red/black
ground. ± 5 in Last Digit
The maximum current you can CAPACITANCE Specifications are typical; individual units might
+10A MAX
measure at this jack is 10 amps DC/ vary. Specifications are subject to change and
UNFUSED 4nF ........................................ ± 4.0% of Reading,
AC. This jack is not fuse-protected. improvement without notice.
± 40 in Last Digits
40nF ...................................... ± 4.0% of Reading,
± 10 in Last Digits
400nF – 40µF – 400µF .......... ± 3.0% of Reading,
± 4 in Last Digit

Note: Accuracy with film capacitor or better,


specified from 9.5% of full scale to full scale except
4.0nF range from 0.5nF to full scale.

FREQUENCY (Frequency Range: 10Hz to 4MHz)


400Hz – 4k–40k–400kHz–4MHz ........... ± 0.1% of
Reading, ± 4 in Last Digit

2
#"37+%-".11-"#6" %100'%6+0)"6*'"6'56".'#&5 Warning: Always turn off power to the circuit
;174"/'6'4 The test leads (black and red) supplied with you are about to measure before you probe
the test leads into high-voltage points.
your meter are rated for 1000 volts. Use only
• — measures test leads of the same rating with the meter.
resistance and Caution: Be sure to select the correct
capacitance.
–/„ — measures You can order replacement leads from your
function before you touch the test leads to the
continuity and diodes. local RadioShack store.
circuit or component to be tested.
mA/A — Hz/Duty — WARNING: ALTHOUGH THE TEST LEADS
measures measures 1. Rotate the function selector to select one
ARE RATED FOR 1000 VOLTS. THE
amperage. frequency and of the following functions, then
MAXIMUM RATING OF THIS METER IS 600
duty cycle. repeatedly press SELECT to select the
VOLTS DC/600 VOLTS RMS AC. DO NOT
function you want.
µA/A — TRY TO MEASURE VOLTAGE GREATER
measures EF — THAN 600 VOLTS DC/600 VOLTS RMS AC.
amperage. measures 2QUKVKQP &GUETKRVKQP
electrical fields. Plug the black test lead’s right-angled end 1. Measures DC volts.
into –COM (common) on the front of the V
meter, then plug the red test lead’s right- 2. Measures AC volts.
angled end into + V.Ω.mA. If you want to 1. Measures amperage:
V — measures DC OFF — turns the
and AC voltages. measure current higher than 400mA, plug
meter off. the red test lead’s right-angled end into • DC 0.4/4 mA
+10A MAX instead of + V.Ω.mA.
• AC 0.4/4 mA
24'2#4#6+10 Note: The meter sounds a warning tone µA/A
when you set it to measure anything except 2. Measures amperage:
+056#..+0)"#"$#66'4; current and you connect a test lead to +10A
• DC 4/10 A
Your meter requires one 9-volt battery (not MAX. This reminds you not to touch the circuit
supplied) for power. For the best with the test leads. • AC 4/10 A
performance and longest life, we recommend 1. Measures amperage:
a RadioShack alkaline battery.
75+0)"6*'"/'6'4 • DC 40/400 mA
WARNINGS: Caution: When the meter is not in use,
always leave the function selector set to OFF. • AC 40/400 mA
• To avoid electrical shock, disconnect all mA/A
of the meter’s test leads from any For the most accurate reading, the 2. Measures amperage:
equipment before you install or replace temperature should be between 65°F and
the meter’s battery. • DC 4/10 A
83°F (18°C and 28°C), with a maximum of
• Do not use your meter until the battery is 75% relative humidity. • AC 4/10 A
properly installed and the battery cover 1. Measures resistance.
is in place and secured. 6740+0)"6*'"/'6'4"1011((1 •
Caution: Use only a fresh battery of the 6'56+0)"6*'"&+52.#; 2. Measures capacitance.
required size and recommended type. To turn on the meter, rotate the function 1. Checks continuity.
1. If the meter is on, rotate the function selector to any function except OFF. To turn –/„ 2. Checks diodes.
selector to OFF to turn it off. Then off the meter, rotate the function selector to
OFF. 1. Measures frequency.
disconnect the test leads if they are Hz/Duty
connected. Note: If the function selector is not set to OFF 2. Measures duty cycle.
2. Use a Phillips screwdriver to loosen the and nothing appears on the display, the EF Checks electrical fields.
battery cover’s screw, then lift off the meter might be in its auto power shut-off
battery cover. mode. Press any button to turn on the meter. For example, to measure a diode, rotate
If the meter remains off, set the function the function selector to –/„ then press
3. Snap a fresh 9V battery onto the selector to OFF and then set it to any function SELECT. „ appears.
terminals of the battery clip in the battery except OFF. If the meter still remains off, Your meter automatically enters the auto
compartment. replace the battery (see “Installing a Battery” range mode when you turn on the meter.
on Page 3). In the auto range mode, 7KJE appears
4. Replace the battery cover and secure it
To test the meter’s display, turn off the meter, and the meter automatically selects the
with the screw.
then hold down HOLD while turning on the next higher or lower range (if available)
When ~ appears on the left side of the meter. The meter turns on and all segments when the measurement causes the
display or the meter stops operating properly, on the display appear. Release HOLD to turn display to overflow (the meter tries to
replace the battery. off the test. display 4001 or more units) or underflow
(the meter tries to display 379 or fewer
Warning: Dispose of an old battery promptly units).
and properly. Do not burn or bury it. $'(14'";17"56#46 2. If. nothing appears on the display, press
Follow these steps to familiarize yourself with
Caution: If you do not plan to use the meter any button to turn on the meter.
the meter’s operation before you use it for the
for a month or more, remove the battery. first time.
Batteries can leak chemicals that can destroy
electronic parts.

3
3. To select manual range mode, press *1.&+0)"#"/'#574'/'06 –3.500 volts as a reference, then
RANGE while the meter is in auto-range Press HOLD to hold all indications on the measure +3.500 volts, the meter might
mode. 7KJE disappears. display. Hold appears and the meter holds display 7.000 volts.
the measured value on the display even if • You can not set E$< as a reference value.
4. Repeatedly press RANGE to select
you remove the probes from the circuit. To reset a relative measurement, press
different ranges. The decimal point shifts
each time you press RANGE. REL€ again or set the function selector to
To cancel hold, press HOLD again or set the
another setting.
selector to another setting or press SELECT.
5. Hold down RANGE for about 2 seconds,
Hold disappears.
the meter exits manual range mode and
#761/#6+%"219'4"1((
returns to its auto range mode.
75+0)"4'.#6+8'"/'#574'/'06 Your meter conserves power by
6. Set the meter to the different automatically turning off about 30 minutes
You can set the meter to have it not show an
measurement ranges. The unit of after the last time you changed a setting
unwanted value that might appear as a result
measure that appears on the display (even if you are making measurements).
of internal or other factors. For example, the
shows you the range that the meter is meter always shows a small value when you To turn the meter back on after it
currently set to. For example, cL set the selector to • to measure automatically turns off, press any button.
appears in the 400 mV range. Also, note capacitance, even when you have not
the position of the decimal. For example, connected the test leads to a component.
if &$&&&ýL appears, the meter is set to (This happens because the meter measures 75+0)"219'4".1%-
measure less than 4 volts. If &&&L its own internal capacitance, which is To set the meter so it does not turn off
appears, the meter is set to measure up normal). If you set the meter in relative mode automatically, set the function selector to
to 600 volts. with the small value as reference, it does not OFF to turn it off. Hold down HOLD and
display this value when you measure a SELECT at the same time, then turn on the
Read the range in volts, ohms,
component. meter. FBeY appears until you release HOLD
capacitance, or amps as indicated by and SELECT. The meter sets itself to its
the position of the decimal point. You can also set the meter to a baseline normal test mode and does not automatically
reference value. For example, if you are turn itself off.
4CPIG &KURNC[ 4CPIG &KURNC[ measuring resistors with a 100 ohm rating
and you want to see the resistor’s tolerance To reset the meter so it automatically turns
400 mV ZZZ$ZýcL 400 Ω ZZZ$ZýΩ itself off, turn off the meter then turn it back
(the actual value in ohms above or below the
4V Z$ZZZýL 4 kΩ Z$ZZZýaΩ resistor’s rating), you can set the meter to a on. The meter automatically turns itself off
40 kΩ ZZ$ZZýaΩ after about 30 minutes.
40 V ZZ$ZZýL baseline reference value of 100 ohms so it
displays only the resistor’s tolerance.
400 V ZZZ$ZýL 400 kΩ ZZZ$ZýaΩ
600 V 1. Set the function selector to any setting /#-+0)"
ZZZýL 4 MΩ Z$ZZZýCΩ
DC/AC except –/„, Duty function, or EF. /'#574'/'065
400 µA ZZZ$Zýµ7 40 MΩ ZZ$ZZýCΩ
2. Measure the zero offset (disconnect test
4 mA Z$ZZZýc7 4 nF Z$ZZZýd< leads for capacitance function, or touch /'#574+0)"&%1#%"81.6#)'
40 mA ZZ$ZZýc7 40 nF ZZ$ZZýd< the test leads together for other function) WARNINGS:
if you want to remove the zero offset
400 mA ZZZ$Zýc7 400 nF ZZZ$Zýd< • Never clamp a test lead to a hot wire
from reading, or connect the test leads
4A Z$ZZZý7 4 µF Z$ZZZýµ< to the component whose measurement
(usually red, black, or blue in AC wiring
circuits). If one lead is clamped to a hot
10 A ZZ$ZZý7 40 µF ZZ$ZZýµ< you want to use as a reference value.
wire and you touch the meter’s other
3. While measuring the zero offset or with probe, you could receive an electric
Note: The display might show a shock.
the test leads connected to a
phantom reading in some DC and AC
component, hold down REL€. Rel € • The maximum input limit for voltage
voltage ranges when the test leads are
appears. The meter is set to manual measurement is 600 V DC/AC (RMS).
not connected to a circuit. This is
range mode. To avoid electrical shock and damage to
normal. The high input sensitivity
the meter, never try to measure a DC
produces a “wandering” effect. When 4. Use the meter to make a measurement. voltage above 600 volts or an AC
you connect the test leads to a circuit, a
voltage above 600 volts RMS.
real measurement appears. Notes:
1. Rotate the function selector to V .
7. Connect the test leads to the circuit you • If the reference value you measured in
want to measure, To measure different Step 2 is greater than the value of the 2. Repeatedly press SELECT to select the
circuits, see “Making Measurements” on measurement you made in Step 4, the function between DC voltage and AC
Page 4. meter shows a negative value. This is voltage (~ appears on the left side of the
not a malfunction. display for AC voltage measurement).
Caution: If E$< (overflow) appears, the value
you are measuring exceeds the range for the • E$< appears if you measure values
outside of the meter’s currently set 3. If the meter is set to automatic range
setting you selected. This is normal when control, the meter automatically moves
you measure resistance or a diode, or do not range.
to the range that gives the best reading.
have the leads connected to a component. If • The meter displays values greater than
you are measuring voltage or current when 4000 counts as long as the range used 4. To set manual range control, press
E$< appears, however, immediately is not an overflow range. (A count is the RANGE then change the range (if
disconnect the probes from the circuit. smallest unit of measure that the meter necessary) by repeatedly pressing
can measure). For example, if you store RANGE.

4
5. Touch the probes to the circuit you want /GCUWTKPI"6JTGG/2JCUG"#%" 5. Connect the meter’s test leads in series
to test. 8QNVCIG with the circuit.
Your multimeter is designed primarily to
When you measure DC voltage, – appears measure household AC voltages. If you want 6. Apply power and read the current.
on the left side of the display if you touched to measure 3-phase, line-to-line voltage,
the black probe to a point in the circuit that If the measurement is less than 400mA,
please note the following:
has a higher voltage potential than the point connect the red test lead to + 10A MAX,
where you connect the red probe. • Because of the dangers inherent in and proceed to Step 7.
measuring three-phase circuit, we If the measurement is greater than
Notes: strongly recommend you do not use this 400mA, connect the red test lead to +
meter for such applications. 10A MAX, take the reading now, and do
• In the 400 V and 400mV ranges, the
• The actual voltage can be greater than not follow the remaining steps.
decimal point appears in the same
position (one place to the left). To the circuit’s rated line-to-ground voltage. 7. Remove power from the circuit.
distinguish between the two ranges, mV Most 3-phase power circuits are rated by
8. Move the red test lead to + V.Ω.mA.
appears in the 400mV range and V their line-to-line voltage. This voltage is
appears in the 400 V range. higher than the line (or phase) to ground 9. Rotate the function selector to µA/
• If the meter is set to the 400mV DC voltage. To determine if a line-to-line 3-phase A for 0.4/4mA or mA/A for 40/400mA.
manual range and you measure an over- voltage exceeds the rating of this meter,
range input, E$< continues to appear multiply the rated line-to-ground voltage by 10. Reapply power to the circuit.
even after you remove the input. This is 1.732 (the square root of 3). For example, if
the rated line-to-ground voltage is 400 volts, If the measured current’s polarity is negative,
not a malfunction. If this happens, touch
– appears before the value.
the test leads together or change the the line-to-line voltage is 400 × 1.732 = 692.8
meter’s setting to clear it. V AC. Notes:
WARNING: This voltage exceeds the meter’s
/GCUWTKPI"#%"8QNVCIG"4KFKPI"1P" rating. Therefore, you should not connect the
• If your measurement exceeds the
C"&%"5QWTEG"$KCU currently selected range, E$< appears
meter to this circuit or to any equipment until the measured voltage or current is
WARNING: To avoid injury or damage to
connected to the circuit. Doing so could reduced to a value below the currently
your meter, never try to measure an AC
present a dangerous shock hazard to you, selected range.
voltage that is riding on a DC source bias
and could also damage the meter.
where the peak AC voltage exceeds 100 V • + V.Ω.mA is fuse-protected. If the meter
with respect to earth ground. does not show a reading in the 0.4/4mA
/'#574+0)"&%1#%"%744'06 range or 40/400mA ranges, check the
1. Rotate the function selector to V . The To measure AC or DC current, you must fuse (see “Replacing the Fuse” on
meter automatically selects auto range break the circuit and connect the test leads to Page 7).
and the DC measurement mode. two circuit connection points. The connection
must be in series with the circuit under test.
2. Measure the DC voltage to ensure that it /'#574+0)"4'5+56#0%'
does not exceed 100V. WARNING: Do not apply voltage directly The resistance measuring circuit in your
across terminals. You must connect the meter compares the voltage gained through a
3. Press SELECT to select the AC mode. ~ known resistance (internal) with the voltage
meter in series with the circuit.
appears. developed across an unknown resistance.
Cautions:
4. Turn off the power of the circuit under WARNING: Be sure the circuit under test has
test. • Never connect the test leads across a all power removed and any associated
voltage source. Doing so can damage capacitors are fully discharged before you
5. Connect the black test lead to the
the meter or the circuit under test. The make a resistance measurement.
circuit’s neutral or ground lead.
maximum input limit for AC/DC current
6. Connect a 0.1 microfarad/100V mylar measurement is 10A. Caution: Your meter has a circuit to protect
capacitor in series with the positive • If you do not know the amount of current the resistance range from over-voltage.
terminal of the voltage source and the in the circuit you are measuring, always However, to avoid accidentally exceeding the
red probe. connect the red test lead to +10A MAX. protection circuit’s rating and to ensure a
correct measurement, never connect the test
1. Rotate the function selector to µA/ leads to a source of voltage while the function
7. Apply the power to the circuit. The
display shows the AC voltage.
A for 0.4/4mA and 4/10A ranges or mA/
selector is set to •.
A for 40/400mA and 4/10A ranges.
Warning: To avoid electrical shock, do 1. Remove all power from the circuit under
2. Repeatedly press SELECT to set the test and discharge all capacitors.
not touch the test probes, capacitor, or
meter to measure AC current
the circuit under test while applying
power.
(∼ appears) or DC current 2. Rotate the function selector to •.
(∼ disappears).
8. When you finish measuring the AC Caution: Never connect the test leads to
voltage, turn off the power of the circuit 3. Remove the power from the circuit under a source of voltage while the rotary
under test, then disconnect the capacitor test and discharge all capacitors. function selector is set to •.
you connected in Step 6. 3. Repeatedly press SELECT until Ω, KΩ, or
4. Plug the black test lead into –COM and
M Ω appears to set the meter to measure
the red test lead into the appropriate
jack. resistance.

5
Note: With no resistance connected 4. Attach the red test lead to the positive ohms (meaning the circuit is not
across the test leads (meaning side of the capacitor and attach the continuous).
resistance is infinite), E$< appears when black test lead to the negative side of the
you set the meter to measure capacitor. Or remove one of the leads of %*'%-+0)"&+1&'5
resistance. This is normal. the capacitor you want to measure from
This procedure lets you check diodes,
4. Touch the test leads across the circuit its circuit and connect the test leads to
transistors, and other semiconductors for
you want to measure, or remove one of the capacitor.
opens, shorts, and normal operation. It also
the leads of the component you want to lets you determine the forward voltage and
Note: Electrolytic capacitors have
measure from its circuit and touch the polarity for diodes. (This is handy when you
positive and negative terminals. Be sure
test leads across the component. If the need to match a diode). You can also check
to connect each test lead to the correct
meter is set to automatic range control, it LEDs using this procedure.
terminal to match the polarity of these
automatically moves to the proper
capacitors.
range. Caution: Do not connect the test leads to a
5. Read the measured value on the display. source of voltage with the function selector
If you set the meter to use manual range, set to –/„. This could damage the meter
repeatedly press RANGE to set manual-range Notes:
or the circuit being tested.
control and change the range (if necessary). • The voltage applied across electrolytic
capacitors will affect their measured 1. Remove all power from the circuit under
Notes: values. That is, a meas-urement taken test and discharge all capacitors.
• If you are measuring resistance of about with a low voltage will be different and
2. Rotate the function selector to –/„.
1MΩ or more, the display might take a lower than that taken with a voltage that
few seconds to stabilize. This is normal. approaches the capacitor’s voltage 3. To select the diode function, repeatedly
• As with the voltage range, use the rating. Since this meter cannot use high press SELECT until „ appears on the
measuring units that appear on the voltage to set the electrolyte. It cannot top of the display.
display to determine the current measure the absolute value of
resistance range. If only Ω appears, the capacitance. 4. Connect the test leads to the device you
values of the measurements are in • Low-value capacitors might match or be want to check, or remove one of the
ohms. If A and Ω appear, the meter is close to the actual input capacitance of leads of the component you want to
measuring kilohms (1 kilohm = 1000Ω). your meter. To measure low capacitance measure from its circuit and connect the
If C and Ω appear, the meter is values, use the meter’s relative feature test leads to the component. Note the
measuring megohms (1 megohm = to adjust the meter for the meter’s own first reading.
1,000,000 Ω). capacitance (see “Using Relative
5. Reverse the test leads and note the
Hint: If you want to accurately measure a Measurement” on Page 4).
second reading.
very small resistance, you can view the • The accuracy of capacitance
resistance of the meter’s test leads, then measurement depends on the If one reading shows a value and the other is
subtract that resistance from the measured measurement method and also differs overrange (E$< appears) the device is good. If
value. To measure the meter’s internal with different types of capacitors. The E$< appears during both readings, the device
resistance, simply touch the end of the test meter’s measurement is for reference is open. If both values are very small or zero,
leads together. The meter selects the 400Ω only. the device is shorted.
scale and displays its internal resistance.
Notes:
You can also use the meter’s relative %*'%-+0)"%106+07+6;
function to do this (see “Using Relative • When you test a silicon-type
Caution: Do not connect the test leads to a
Measurement” on Page 4).
source of voltage with the selector set to –/
semiconductor, the values might vary
„. This could damage the meter or the depending on the temperature.
/'#574+0)"%#2#%+6#0%' circuit being tested. • The values that appear during a diode
The capacitance measuring circuit in your check show the actual forward voltage
meter charges a connected capacitor to a You can use the meter to check for shorted (2.0V max). If the voltage exceeds 2.0V,
specific voltage level, then discharges the or open electrical circuits. E$< appears. This means the diode
capacitor to a lower voltage. The meter check cannot be made using this meter.
1. Remove all power from the circuit under
measures the amount of time takes to
test and discharge all capacitors.
discharge the capacitor. %JGEMKPI"&KQFG"2QNCTKV[
2. Rotate the function selector to –/„. Many diodes have a stripe or mark on one
Caution: Do not connect the test leads to a side. The marked side of the diode indicates
source of voltage with the function selector 3. To select the continuity function, the diode’s cathode or negative (–) side. The
set to •. This could damage the meter or repeatedly press SELECT until – other side is the anode or positive (+) side.
the circuit being tested. appears at the top of the display.
If a diode is not marked, you can use your
1. Remove all power from the circuit under 4. Touch the test leads across the circuit meter to check the diode’s polarity. As you
test and discharge all capacitors. you want to measure. Shrt appears and follow the steps under “Checking Diodes” on
2. Rotate the function selector to •.
the buzzer sounds if the circuit Page 6, connect the red test lead to one side,
resistance is less than about 50 ohms connect the black test lead to the other side,
3. Set the meter to measure capacitance (meaning the circuit is continuous or then measure and note the voltage. Then
by repeatedly pressing SELECT until nF shorted). Open appears and the meter’s reverse the test leads and measure and note
or µF appears. buzzer does not sound if the circuit the second reading. The side of the diode
resistance is greater than about 50 where the meter shows a higher voltage
using the red test lead is the anode (+) side.

6
/'#574+0)"(4'37'0%;1&76;" %#4' 6. If the fuse is blown, discard it and save
%;%.' Keep the meter dry; if it gets wet, wipe it dry
the ribbon. Then remove the spare fuse
from the plastic holder and insert it into
The meter can measure frequency from 10 immediately. Use and store the meter only in the fuse holder through the loop of the
Hz to 4 MHz and a duty cycle with a signal normal temperature environments. Handle attached ribbon.
frequency from 10 Hz to 100 kHz. The the meter carefully; do not drop it. Keep the
amplitude of a signal is not larger than 10V meter away from dust and dirt. 7. Replace the back cover and secure it
peak. with the screws.
Modifying or tampering with the meter’s
1. Rotate the function selector to Hz/Duty. internal components can cause a malfunction 8. Install the battery (see “Installing a
and might invalidate its warranty. If your Battery” on Page 3).
2. To select the frequency function,
meter is not performing as it should, take it to
repeatedly press SELECT until Hz, kHz, 9. Replace the battery cover and secure it
your local RadioShack store for assistance.
or MHz appears. with the screw.
3. Press RANGE to manually select the %.'#0+0) WARNING: Do not operate your meter until
range, then repeatedly press RANGE To keep the meter looking new, occasionally the back cover is in place and secured.
until the desired range appears. wipe it with a cloth lightly dampened with
water. Do not use harsh chemicals, cleaning
4. To select the duty cycle function,
solvents, or strong detergents to clean the
repeatedly press SELECT until %
meter.
appears.
WARNINGS:
5. Connect the black test probe to a ground
reference for the signal, and connect the • Do not let any water drip inside the
red test probe to the signal source. meter while cleaning it.
• Make sure that the meter is completely Limited Ninety-Day Warranty
/'#574+0)"#0"'.'%64+%"(+'.& dry before using it. This product is warranted by RadioShack against manufacturing
defects in material and workmanship under normal use for
You can use this feature to detect the ninety (90) days from the date of purchase from RadioShack
presence of AC voltage in places such as an 4'2.#%+0)"6*'"(75' company-owned stores and authorized RadioShack franchisees
and dealers. EXCEPT AS PROVIDED HEREIN, RadioShack
AC power cord. This lets you easily detect a If the meter does not work, you might need to MAKES NO EXPRESS WARRANTIES AND ANY IMPLIED
WARRANTIES, INCLUDING THOSE OF MERCHANTABILITY
break in an electric circuit or locate the replace the fuse with the spare fuse we have AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED
source of an electric field. included with your meter. The spare fuse is IN DURATION TO THE DURATION OF THE WRITTEN LIM-
ITED WARRANTIES CONTAINED HEREIN. EXCEPT AS PRO-
inserted into plastic holder on the top cabinet VIDED HEREIN, RadioShack SHALL HAVE NO LIABILITY OR
Note: Varying construction materials and near the terminals. RESPONSIBILITY TO CUSTOMER OR ANY OTHER PERSON
OR ENTITY WITH RESPECT TO ANY LIABILITY, LOSS OR
methods give unreliable results for DAMAGE CAUSED DIRECTLY OR INDIRECTLY BY USE OR
measuring an electric field behind a wall. Do The fuse is a 500mA, 250V ceramic fuse PERFORMANCE OF THE PRODUCT OR ARISING OUT OF
ANY BREACH OF THIS WARRANTY, INCLUDING, BUT NOT
not attempt to measure voltage on in-wall or (Cat. No. 27-1070). LIMITED TO, ANY DAMAGES RESULTING FROM INCONVE-
other premises wiring. NIENCE, LOSS OF TIME, DATA, PROPERTY, REVENUE, OR
PROFIT OR ANY INDIRECT, SPECIAL, INCIDENTAL, OR
Caution: Do not use a fuse with ratings CONSEQUENTIAL DAMAGES, EVEN IF RadioShack HAS
1. Rotate the function selector to EF. other than those specified here. Doing so BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES.
Some states do not allow limitations on how long an implied war-
might damage your meter. ranty lasts or the exclusion or limitation of incidental or conse-
2. Remove the test leads. quential damages, so the above limitations or exclusions may
not apply to you.
1. If the meter is on, rotate the function In the event of a product defect during the warranty period, take
3. Hold the meter so the built-in antenna selector to OFF to turn it off. Then the product and the RadioShack sales receipt as proof of pur-
(inside the top of the meter) is near the disconnect the test leads if they are chase date to any RadioShack store. RadioShack will, at its op-
tion, unless otherwise provided by law: (a) correct the defect by
object you wish to examine. Do not connected. product repair without charge for parts and labor; (b) replace the
touch the meter to the object being product with one of the same or similar design; or (c) refund the
purchase price. All replaced parts and products, and products
tested. WARNING: To avoid electric shock, you on which a refund is made, become the property of RadioShack.
New or reconditioned parts and products may be used in the
must disconnect the test leads before performance of warranty service. Repaired or replaced parts
Note: For the best sensitivity, hold the you remove the battery cover and back and products are warranted for the remainder of the original
meter behind the function selector. cover. warranty period. You will be charged for repair or replacement of
the product made after the expiration of the warranty period.
If the meter detects an electrical field, 1 to 5 2. Use a Phillips screwdriver to loosen the This warranty does not cover: (a) damage or failure caused by
or attributable to acts of God, abuse, accident, misuse, improper
bars appear on the display (corresponding to battery cover’s screw, then lift off the or abnormal usage, failure to follow instructions, improper instal-
the strength of the field), and the meter battery cover.
lation or maintenance, alteration, lightning or other incidence of
excess voltage or current; (b) any repairs other than those pro-
buzzes. EF appears but no bars appear if the vided by a RadioShack Authorized Service Facility; (c) consum-
electrical field is weak. 3. Remove the battery. ables such as fuses or batteries; (d) cosmetic damage; (e)
transportation, shipping or insurance costs; or (f) costs of prod-
uct removal, installation, set-up service adjustment or reinstalla-
4. Use a Phillips screwdriver to loosen the tion.
This warranty gives you specific legal rights, and you may also
screws in the back cover and lift off the have other rights which vary from state to state.
cover. RadioShack Customer Relations, 200 Taylor Street, 6th Floor,
Fort Worth, TX 76102
12/99
Caution: The battery line connects the
back cover and the top cabinet together.
Do not try to remove the back cover.
5. To remove the fuse, gently pull the red
ribbon holding it. The fuse pops out.

22-811
AO0070AAA1
RadioShack Corporation 12A01
Fort Worth, Texas 76102 Printed in China

You might also like