To properly use the product, read this manual thoroughly and retain
for easy reference, inspection, and maintenance. Ensure the end user
receives this manual.
2 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
Table of Contents
i. PREFACE & GENERAL SAFETY............................................................................... 5
i.1 Preface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Applicable Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
i.2 General Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
General Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
1. RECEIVING ................................................................................................................. 9
1.1 Model Number and Nameplate Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
1.2 Component Names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Flange Type Enclosure (NEMA Type 12 Backside) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
2. MECHANICAL INSTALLATION................................................................................ 13
2.1 Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Installation Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Removing the Shipping Package Attachments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Panel Cut-Out Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 3
5.3 Installing Peripheral Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Dynamic Braking Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
A. SPECIFICATIONS ..................................................................................................... 51
A.1 Power Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
6-Phase/12 Pulse Input 400 V Class Drive Models CIMR-A4T0058 to 0208 . . . . . . . . 52
6-Phase/12 Pulse Input 400 V Class Drive Models CIMR-A4T0208 to 0675 . . . . . . . . 53
A.2 Drive Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
A.3 Drive Watt Loss Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
A.4 Drive Derating Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Temperature Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Altitude Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
B. PARAMETER LIST.................................................................................................... 59
B.1 L: Protection Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
L8: Drive Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
4 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
i
Preface & General Safety
This section provides safety messages pertinent to this product that, if not heeded, may result in
fatality, personal injury, or equipment damage. Yaskawa is not responsible for the consequences of
ignoring these instructions.
i.1 PREFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
i.2 GENERAL SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 5
i.1 Preface
i.1 Preface
Yaskawa manufactures products used as components in a wide variety of industrial systems and equipment. The selection
and application of Yaskawa products remain the responsibility of the equipment manufacturer or end user. Yaskawa
accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances
should any Yaskawa product be incorporated into any product or design as the exclusive or sole safety control. Without
exception, all controls should be designed to detect faults dynamically and fail safely under all circumstances. All systems
or equipment designed to incorporate a product manufactured by Yaskawa must be supplied to the end user with
appropriate warnings and instructions as to the safe use and operation of that part. Any warnings provided by Yaskawa
must be promptly provided to the end user. Yaskawa offers an express warranty only as to the quality of its products in
conforming to standards and specifications published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR
IMPLIED, IS OFFERED. Yaskawa assumes no liability for any personal injury, property damage, losses, or claims
arising from misapplication of its products.
This manual is designed to ensure correct and suitable application of A1000-Series Drives with 6-Phase/12-Pulse
rectification. Read this manual before attempting to install or operate a drive and keep it in a safe, convenient location for
future reference. Be sure you understand all precautions and safety information before attempting application.
Use this manual as the primary reference to install and wire A1000 drives with 6-Phase/12-Pulse rectification together
with the A1000 Quick Start Guide and Technical Manual.
Applicable Documentation
The following manuals are available for A1000 series drives:
A1000 Series AC Drive 6-Phase/12-Pulse Input Installation Guide (TOEP C710616 50) (this book)
This guide is packaged together with the product and contains additional information required to install
and wire the A1000 drive with 6-Phase/12-Pulse rectification. This manual is available for download at:
www.yaskawa.com.
A1000 Series AC Drive Quick Start Guide
Read this guide first. This guide is packaged together with the product and contains basic information
required to install and wire the A1000 drive. It also gives an overview of fault diagnostics, maintenance,
and parameter settings. The purpose of this guide is to prepare the drive for a trial run with an application
and for basic operation. This manual is available for download at:
www.yaskawa.com.
A1000 Series AC Drive Technical Manual
This manual provides detailed information on parameter settings, drive functions, and MEMOBUS/
Modbus specifications. Use this manual to expand drive functionality and to take advantage of higher
performance features. This manual is available for download at:
www.yaskawa.com.
6 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
i.2 General Safety
Power Supply
Capacity (kVA)
600
Reactor
unnecessary
0
60 400
Drive Capacity (kVA)
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 7
i.2 General Safety
8 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
1
Receiving
This chapter explains how to inspect the drive upon receipt, and gives an overview of the
components.
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 9
1.1 Model Number and Nameplate Check
Nameplate
Figure 1.1
10 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
1.1 Model Number and Nameplate Check
CIMR - A U 4 T 0675 U A A
Drive A1000 Series Design Revision
Order
<1> Provides method of mounting drive with backside (heatsink) external to enclosure, with NEMA 12 integrity.
<2> Drives with these specifications do not guarantee complete protection for the environmental conditions indicated.
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 11
1.2 Component Names
<1> Provides method of mounting drive with backside (heatsink) external to enclosure, with NEMA 12
integrity.
Figure 1.2 Flange Type Enclosure (CIMR-A4T0675)
12 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
2
Mechanical Installation
This chapter explains how to properly mount and install the drive.
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 13
2.1 Mechanical Installation
Installation Environment
Install the drive in an environment matching the specifications below to help prolong the optimum performance life of the
drive.
Table 2.1 Installation Environment
Environment Conditions
Installation Area Indoors
-10°C to +40°C (Flange Type Enclosure)
Drive reliability improves in environments without wide temperature fluctuations.
Ambient Temperature When using the drive in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air
temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the drive.
Humidity 95% RH or less and free of condensation
Storage Temperature -20°C to +60°C
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water, or other foreign materials
• radioactive materials
Surrounding Area • combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight.
Altitude Up to 1000 m without derating, up to 3000 m with output current and voltage derating.
10 Hz to 20 Hz at 9.8 m/s2
Vibration
20 Hz to 55 Hz at 5.9 m/s2 (Models CIMR-A4T0058 to 0165) or 2.0 m/s2 (Models CIMR-A4T0208 to 0675)
Orientation Install the drive vertically to maintain maximum cooling effects.
NOTICE: Avoid placing drive peripheral devices, transformers, or other electronics near the drive as the electrical interference created
can lead to erroneous operation. If such devices must be used in close proximity to the drive, take proper steps to shield the drive from
noise.
NOTICE: Damage to Equipment. Drive heatsink air outlet temperature may be over 80°C. Do not install components above the air
outlet that may be damaged by 80°C air temperature.
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the drive during installation. Failure to
comply could result in damage to the drive. Place a temporary cover over the top of the drive during installation. Remove the temporary
cover before drive start-up, as the cover will reduce ventilation and cause the drive to overheat.
14 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
2.1 Mechanical Installation
Shipping Package
Shipping Package
Attachmet
Attachmet
Screws Screws
Dimensions
Flange Type Enclosure
CIMR-A4T0058U
Figure 2.2
214 (8.43)
Eye Bolts
97.85 97.85 153.6 (6.05)
with M8 Screw
(3.85) (3.85)
88 (3.46)
362.2 (14.26)
422.2 (16.62)
414 (16.30)
220 (8.66)
88 (3.46)
25.9 (1.02)
9 (0.35)
255.2 (10.05) 3
(0.12) 258 (10.16)
308 (12.13)
97 (3.82)
unit: mm (inch)
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 15
2.1 Mechanical Installation
CIMR-A4T0072U
Figure 2.3
23.9 (0.94)
Eye Bolts 153.6 (6.05)
103 (4.06) 103 (4.06)
with M8 Screw
96.5 (3.80)
412.2 (16.23)
470.2 (18.51)
460 (18.11)
250 (9.84)
96.5 (3.80)
8.5 (0.33)
23.9 (0.94)
280.2 (11.03) 3
(0.12) 258 (10.16)
330 (12.99)
97 (3.82)
unit: mm (inch)
292 (11.50)
25.5 (1.00)
473.2 (18.63)
170 (6.69)
542 (21.34)
150 (5.91)
25.5 (1.00)
10.5 (0.41)
330.2 (13.00)
23.7 (0.93)
3
390 (15.35) (0.12) 258 (10.16)
101 (3.98)
unit: mm (inch)
16 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
2.1 Mechanical Installation
CIMR-A4T0139U, 0165U
Figure 2.5
24.9 (0.98)
130.5 (5.14) 130.5 (5.14) Eye Bolts
27 (1.06)
199.8 (7.87) with M8 Screw 132.6 (5.22)
165 (6.50)
512.7 (20.19)
161 (6.34)
568 (22.36)
562 (22.13)
165 (6.50)
27 (1.06)
24.5 (0.96)
8.5 (0.33)
130.5 130.5
(5.14) (5.14) 3
(0.12) 283 (11.14)
324 (12.76)
386 (15.20)
(4.21)
106.9
unit: mm (inch)
15 (0.59)
218 (8.58)
647.2 (25.48)
570 (22.44)
725 (28.54)
190 (7.48)
218 (8.58)
36 (1.42)
(1.52)
455.2 (17.92) 3
38.7
Eye Bolts
with M10 Screw
157.5 (6.20)
127 (5.00)
unit: mm (inch)
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 17
2.1 Mechanical Installation
CIMR-A4T0250U to 0362U
Figure 2.7
13-Mounting Holes
590 (23.22) for M10 Screw
270.6 (10.65) 270.6 (10.65)
160 (6.30) 175 (6.89)
132.5 (5.22)
44.9 (1.77)
37.4 (1.47)
15 (0.59)
225 (8.86)
730.7 (28.77)
555 (21.85)
820 (32.28)
241.4 (9.50)
225 (8.86)
(1.47)
(0.81)
37.4
20.6
(5.22)
(1.75)
132.5
44.4
3
125 (4.92) 175 (6.89) 175 (6.89) 125 (4.92) (0.12) 350 (13.78)
500 (19.69)
600 (23.62)
Eye Bolts
with M10 Screw
(6.70)
170.1
(4.99)
126.7
unit: mm (inch)
18 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
2.1 Mechanical Installation
CIMR-A4T0414U
Figure 2.8
22-Mounting Holes
for M10 Screw
151.25 151.25 151.25 151.25
122.3 (4.81)
74.6 (2.94)
(5.95) (5.95) (5.95) (5.95)
(6.30)
160
(6.59)
167.5
1105.4 (43.52)
(6.59)
861.4 (33.91)
167.5
956 (37.64)
(6.59)
167.5
(6.59)
167.5
(4.41)
112
(4.86)
123.4
54.8 (2.16)
121.7 (4.79)
74.8 (2.94)
500 (19.69) 3
(0.12) 370 (14.57)
645 (25.39)
Eye Bolts
with M12 Screw
(6.84)
174
(5.19)
131.8
unit: mm (inch)
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 19
2.1 Mechanical Installation
CIMR-A4T0515U, 0675U
Figure 2.9
22-Mounting Holes
for M10 Screw
781.2 (30.76)
132.5 (5.22)
193 (7.60) 193 (7.60) 193 (7.60) 193 (7.60)
58.7 (2.31)
17 (0.67)
(7.17)
182
(7.17)
182
(7.17)
182
1308 (51.50)
1044.6 (41.13)
1193.2 (46.98)
(7.17)
182
(7.17)
182
(7.17)
182
(7.17)
182
39.1 (1.54)
56.1 (2.21)
130.9 (5.15)
670 (26.38)
3.7
812 (31.97) (0.12) 370 (14.57)
Eye Bolts
with M12 Screw
(7.20)
183
(5.78)
146.8
unit: mm (inch)
20 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
2.1 Mechanical Installation
(0.75)
19
88 (3.46)
376 (14.80)
220 (8.66)
88 (3.46)
10 (0.39)
(0.75)
19
unit: mm (inch)
96.5 (3.80)
250 (9.84)
423 (16.65)
96.5 (3.80)
10 (0.39)
(0.73)
18.5
24.5 24.5
(0.96) 281 (11.06) (0.96)
unit: mm (inch)
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 21
2.1 Mechanical Installation
CIMR-A4T0088U, 0103U
Figure 2.12
(0.81)
(1.00)
20.5
25.5
150 (5.91)
170 (6.69)
501 (19.72)
150 (5.91)
10 (0.39)
25.5 (1.00)
(0.81)
31.5
20.5
unit: mm (inch)
(1.06)
18.5
27
165 (6.50)
525 (20.67)
161 (6.34)
165 (6.50)
27 (1.06)
10 (0.39)
(0.73)
26.8
18.5
unit: mm (inch)
22 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
2.1 Mechanical Installation
CIMR-A4T0208U
Figure 2.14
(1.10)
15 (0.59)
(1.42)
28
36
218 (8.58)
669 (26.34)
190 (7.48)
218 (8.58)
14.5 (0.57)
36 (1.42)
(1.10)
28
45
(1.77) 470 (18.50)
45
(1.77)
unit: mm (inch)
15 (0.59)
32
225 (8.86)
766.2 (30.17)
241.4 (9.50)
736 (28.98)
225 (8.86)
(1.47)
(1.26)
37.4
32
unit: mm (inch)
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 23
2.1 Mechanical Installation
CIMR-A4T0414U
Figure 2.16
(2.25)
(1.46)
57.2
37.2
(6.30)
160
(6.59)
167.5
(6.59)
167.5
991 (39.02)
(6.59)
167.5
(6.59)
167.5
(4.86) (4.41)
123.4 112
(2.25)
57.2
unit: mm (inch)
(0.67)
40.5
17
(7.17)
182
(7.17)
182
(7.17)
182
1227 (48.31)
1274 (50.16)
(7.17)
182
(7.17)
182
(7.17)
182
(7.17)
182
(1.59)
40.5
unit: mm (inch)
24 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
2.1 Mechanical Installation
Weight
Table 2.2 Drive Weight
CIMR-A4TU 0058 0072 0088 0103 0139 0165 0208 0250 0296 0362 0414 0515 0675
Drive Weight 21 24 35 35 39 40 78 90 95 97 127 210 215
kg (lb) (46.3) (52.9) (77.2) (77.2) (86.0) (88.2) (172.0) (198.4) (209.4) (213.8) (280.0) (463.0) (474.0)
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 25
2.1 Mechanical Installation
26 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
3
Electrical Installation
This chapter explains proper procedures for wiring the main circuit terminals and power supply.
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 27
3.1 Standard Connection Diagram
NOTICE: Equipment Hazard. Standard motors used with PWM drives may experience winding failures due to surge voltages, when
input line voltage is greater than 480 V or motor wire distance is greater than 100 meters. Select a motor design with insulation tolerant
of surge voltages, such as drive-rated motor for use with PWM drives. Failure to comply could lead to motor winding failure.
Note: The minimum load for the relay outputs M1-M2, M3-M4, M5-M6, and MA-MB-MC is 10 mA.
28 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
3.1 Standard Connection Diagram
Figure 3.1
<14>
Terminals -, +3, B1, and B2 are FU
for power option connections. Braking Resistor Unit
Never connect power supply lines (LKEB Type) FV M
Wiring sequence should shut off to these terminals (option) <1> <2> FW Cooling fan
power to the drive when a fault
output is triggered.
B1 B2
Main U
Three-Phase Switch Fuse Fuse Main Circuit U/T1
U1
Power Supply R R/L1 V
V1
S/L2 V/T2 M
380 to 480 V S W1 W
50/60 Hz T
U2
V2
T/L3
R1/L11 Drive W/T3
W2
S1/L21
T1/L31 Control Circuit <3>
Ground
E (G)
Open Wire
jumper EDM (Safety Electronic Device Monitor)
Safety relay / DM+
controller <11>
HC
DM㧙
shielded line twisted-pair shielded line control circuit terminal main circuit terminal
<1> Set up a thermal relay sequence to disconnect drive main power in the event of an overheat condition on the dynamic braking option.
<2> Set L8-55 to 0 to disable the protection function of the built-in braking transistor of the drive when using an optional regenerative converter or
dynamic braking option. Leaving L8-55 enabled may cause a braking resistor fault (rF). Additionally, disable Stall Prevention (L3-04 = 0)
when using an optional regenerative converter, regenerative or braking units, or dynamic braking option. Leaving L3-04 enabled may prevent
the drive from stopping within the specified deceleration time.
<3> Supplying power to the control circuit separately from the main circuit requires a 24 V power supply (option).
<4> This figure illustrates an example of a sequence input to S1 through S8 using a non-powered relay or an NPN transistor. Install the wire jumper
between terminals SC-SP for Sink mode, between SC-SN for Source mode, or leave the jumper out for external power supply. Never short
terminals SP and SN, as it will damage the drive.
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 29
3.1 Standard Connection Diagram
<5> This voltage source supplies a maximum current of 150 mA when not using a digital input card DI-A3.
<6> The maximum output current capacity for the +V and -V terminals on the control circuit is 20 mA. Never short terminals +V, -V, and AC, as it
can cause erroneous operation or damage the drive.
<7> Set DIP switch S1 to select between a voltage or current input signal to terminal A2. The default setting is for current input.
<8> Set DIP switch S4 to select between analog or PTC input for terminal A3.
<9> Set DIP switch S2 to the ON position to enable the termination resistor in the last drive in a MEMOBUS/Modbus network.
<10> Use jumper S3 to select between Sink mode, Source mode, and external power supply for the Safe Disable inputs.
<11> Disconnect the wire jumper between H1 - HC and H2 - HC when utilizing the Safe Disable input.
<12> Monitor outputs work with devices such as analog frequency meters, ammeters, voltmeters, and wattmeters. They are not intended for use as a
feedback-type signal.
<13> Use jumper S5 to select between voltage or current output signals at terminals AM and FM. Set parameters H4-07 and H4-08 accordingly.
<14> Self-cooling motors do not require the same wiring necessary for motors with cooling fans.
WARNING! Sudden Movement Hazard. Do not close the wiring for the control circuit unless the multifunction input terminal parameters
are properly set. Improper sequencing of run/stop circuitry could result in death or serious injury from moving equipment.
WARNING! Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the correct state before
energizing the drive. Failure to comply could result in death or serious injury from moving equipment. When programmed for 3-Wire
control, a momentary closure on terminal S1 may cause the drive to start.
WARNING! Sudden Movement Hazard. When using a 3-Wire sequence, set the drive to 3-Wire sequence prior to wiring the control
terminals and set parameter b1-17 to 0 so the drive will not accept a Run command at power up (default). If the drive is wired for a 3-
Wire sequence but set up for a 2-Wire sequence (default), and parameter b1-17 is set to 1 so the drive accepts a Run command at
power up, the motor will rotate in reverse direction at drive power up and may cause injury.
WARNING! Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before executing the application preset
function. Executing the application preset function or setting A1-06 ≠ 0 will change the drive I/O terminal functions and may cause
unexpected equipment operation. Failure to comply may cause death or serious injury.
NOTICE: When using the automatic fault restart function with wiring designed to shut off the power supply upon drive fault, make sure
the drive does not trigger a fault output during fault restart (L5-02 = 0, default). Failure to comply will prevent the automatic fault restart
function from working properly.
NOTICE: Do not connect AC control circuit ground to drive enclosure. Improper drive grounding can cause control circuit malfunction.
30 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
3.2 Main Circuit Connection Diagram
B1 B2
Relay
R/L1 Current
S/L2 Sensor
T/L3 U/T1
V/T2
R1/L11 W/T3
S1/L21
T1/L31
Gate
Board
Control
Operator
Board
Figure 3.2 A1000 6-Phase/12-Pulse Drive Internal Main Circuit Diagram (CIMR-A4T0058, 0072)
+3
Relay
R/L1 Current
S/L2 Sensor
T/L3 U/T1
V/T2
R1/L11 W/T3
S1/L21
T1/L31
Gate
Board
Control
Operator
Board
Figure 3.3 A1000 6-Phase/12-Pulse Drive Internal Main Circuit Diagram (CIMR-A4T0088 to 0139)
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 31
3.2 Main Circuit Connection Diagram
+3
Relay
R/L1 Current
+
S/L2 Sensor
T/L3 U/T1
V/T2
R1/L11 W/T3
S1/L21
T1/L31
24 V Gate
Power Board Control
Supply Operator
Board
Figure 3.4 A1000 6-Phase/12-Pulse Drive Internal Main Circuit Diagram (CIMR-A4T0165 to 0675)
32 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
3.2 Main Circuit Connection Diagram
6-Phase/12-Pulse Rectification
Installing a Transformer
Install a 6-Phase/12-Pulse isolation transformer with output windings phase shifted by 30 electrical degrees or install a
Hybrid 6-Phase topology on the power supply.
Installing a 3-Phase Line Monitor
Yaskawa requires installation of a 3-Phase line monitor to protect the drive in the event of an input line phase loss.
The 3-Phase line monitor must be installed on the primary circuit of the 6-Phase/12-Pulse transformer and connected to
the A1000 drive to remove the RUN command when a phase loss condition occurs.
The A1000 power circuit may be damaged during a phase-loss condition if a 3-Phase line monitor is not properly
installed.
Connection Diagram
Braking Resistor Unit (LKEB Type)
3-Phase Line Monitor (option) <1>
+3 㧙
Fuse
6-Phase/12-Pulse
Main Circuit Isolation Transformer
Power Supply Fuse Fuse U/T1
R/L1
V/T2 Motor
S/L2
W/T3
T/L3
R1/L11
S1/L21
T1/L31
<1> A braking resistor can be connected to the B1 and B2 terminals on the CIMR-A4T0058 and 0072 drives.
<2> A braking unit cannot be connected to the CIMR-A4T0058 and 0072 drives.
Figure 3.5 Main Circuit Terminal Connections
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 33
3.3 Main Circuit Terminal Configuration
B1 B2
34 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
3.3 Main Circuit Terminal Configuration
Figure 3.8
㧙 +3
㧙 +3
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 35
3.3 Main Circuit Terminal Configuration
Figure 3.11
㧙 +3
36 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
3.4 Main Circuit Wiring
NOTICE: Do not switch the drive input to start or stop the motor. Frequently switching the drive on and off shortens the life of the DC
bus charge circuit and the DC bus capacitors, and can cause premature drive failures. For the full performance life, refrain from
switching the drive on and off more than once every 30 minutes.
Note: DC power supply input is not available for 6-Phase/12-Pulse Input models.
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 37
3.4 Main Circuit Wiring
38 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
3.4 Main Circuit Wiring
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 39
3.4 Main Circuit Wiring
40 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
3.5 Wiring Checklist
15 MC2 OL2
MC1 - MCn ... magnetic contactor –
M2 OL 1 - OL n ... thermal relay
MCn OLn
Mn
Note: Close MC1 - MCn before operating the drive. MC1 - MCn cannot be switched off during run.
Install a magnetic contactor when using a dynamic braking option. Properly install the resistor and ensure that
16 –
overload protection shuts off the main power supply using the magnetic contactor.
Verify phase advancing capacitors, input noise filters, or GFCIs are NOT installed on the output side of the
17 –
drive.
Control Circuit Wiring
18 Use twisted-pair line for all drive control circuit wiring. –
19 Ground the shields of shielded wiring to the GND terminal. –
For 3-Wire sequence, set parameters for multi-function contact input terminals S1 - S8, and wire control
20 –
circuits.
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 41
3.5 Wiring Checklist
42 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
4
Start-Up Programming & Operation
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 43
4.1 Powering Up the Drive
<1> Install a 6-Phase/12-Pulse isolation transformer with each of the output windings phase shifted by 30 electrical degrees or use a Hybrid 6-
Phase topology.
44 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
5
Peripheral Devices & Options
This chapter explains the installation of peripheral devices and options available for the drive.
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 45
5.1 Drive Options and Peripheral Devices
46 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
5.1 Drive Options and Peripheral Devices
<1> Limited support. Contact a Yaskawa representative or the nearest Yaskawa sales office for assistance.
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 47
5.2 Connecting Peripheral Devices
YASKAWA
USB Copy Unit
ERR
COM
Power
JVOP-181
LOCK
py rify ad
Co Ve Re
Line PC
Breaker USB Type-AB Cable
(MCCB) (sold separately)
or Surge
Leakage Absorber Drive
+3 -
Breaker
Braking Unit
(CDBR Type)
6-Phase/12-Pulse
Isolation Transformer <1>
or
Hybrid 6-Phase
Topology
Input Side
Noise Filter
24 V Control Ground
Power Supply
Unit
R/L1 S/L2 T/L3 R1/L11 S1/L21 T1/L31 U/T1 V/T2 W/T3
Ground
<1> With each of the output windings phase shifted by 30 electrical degrees.
48 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
5.3 Installing Peripheral Devices
Note: 1. Properly size the braking circuit to dissipate the power required to decelerate the load in the desired time. Ensure that the braking
circuit can dissipate the energy for the set deceleration time prior to running the drive.
2. Set L8-55 to 0 to disable the internal braking transistor of the drive protection when using braking resistor options.
WARNING! Fire Hazard. The braking unit connection terminals are +3 and –. Do not connect a braking resistor directly to any other
terminals. Improper wiring connections could result in death or serious injury by fire. Failure to comply may result in damage to the
braking circuit or drive.
NOTICE: Connect a braking unit to the drive as shown in the I/O wiring examples. Improperly wiring braking circuits could result in
damage to the drive or equipment.
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 49
5.3 Installing Peripheral Devices
1 2
MC R/L1
Y S/L2 +3 -
R T/L3
S 㰱
T R1/L11
㰱 S1/L21
T1/L31
400 V
MC MB 2MCCB THRX OFF ON MC
SA Drive
MC
Braking Resistor Unit
Thermal Relay Trip Contact THRX
1 2
SA
TRX
MC MA SA
TRX
Fault Relay
Contact
<1> A braking unit cannot be connected to the CIMR-A4T0058 and 0072 drives.
<2> A braking resistor can be connected to the B1 and B2 terminals on the CIMR-A4T0058 and 0072 drives.
Figure 5.2 Power Supply Interrupt for Braking Resistor Overheat Protection (Example)
50 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
Appendix: A
Specifications
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 51
A.1 Power Ratings
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater
than the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
conditions, and power supply impedance. This input current rating is the 3-Phase total input current rating. For the 6-Phase input current rating
see Table C.1.
<3> Rated motor capacity is calculated with a rated output voltage of 440 V.
<4> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<5> Carrier frequency can be increased to 8 kHz while keeping this current derating. Higher carrier frequency settings require derating.
<6> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
52 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
A.1 Power Ratings
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater
than the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
conditions, and power supply impedance. This input current rating is the 3-Phase total input current rating. For the 6-Phase input current rating
see Table C.1.
<3> Rated motor capacity is calculated with a rated output voltage of 440 V.
<4> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<5> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 53
A.2 Drive Specifications
Item Specification
The following control methods can be set using drive parameters:
• V/f Control (V/f)
• V/f Control with PG (V/f w/PG)
• Open Loop Vector Control (OLV)
Control Method
• Closed Loop Vector Control (CLV)
• Open Loop Vector Control for PM (OLV/PM)
• Advanced Open Loop Vector Control for PM (AOLV/PM)
• Closed Loop Vector Control for PM (CLV/PM)
Frequency Control Range 0.01 Hz to 400 Hz
Frequency Accuracy Digital input: within ±0.01% of the max output frequency (-10°C to +40°C)
(Temperature Fluctuation) Analog input: within ±0.1% of the max output frequency (25°C ±10°C)
Frequency Setting Digital inputs: 0.01 Hz
Resolution Analog inputs: 1/2048 of the maximum output frequency setting (11 bit plus sign)
Output Frequency 0.001 Hz
Resolution
Frequency Setting Signal -10 V to 10 V, 0 V to 10 V, 0 mA to 20 mA, 4 mA to 20 mA, Pulse Train Input
V/f, V/f w/PG: 150% at 3 Hz
OLV: 200% at 0.3 Hz <1>
Starting Torque <2>
CLV, AOLV/PM, CLV/PM: 200% at 0.0 r/min <1>
OLV/PM: 100% at 3 Hz
V/f, V/f w/PG: 1:40
OLV: 1:200
Speed Control Range <2> CLV, CLV/PM: 1:1500
OLV/PM: 1:20
AOLV/PM: 1:100
Control
Characteristics Speed Control Accuracy OLV: ±0.2% (25°C ±10°C)
<2> CLV: ±0.02% (25°C ±10°C)
OLV, OLV/PM, AOLV/PM: 10 Hz
Speed Response <2>
CLV, CLV/PM: 50 Hz
Parameters setting allow separate limits in four quadrants
Torque Limit
(available in OLV, CLV, AOLV/PM, CLV/PM)
0.0 s to 6000.0 s (4 selectable combinations of independent acceleration and deceleration
Accel/Decel Time
settings)
Approx. 20% (approx. 125% when using braking resistor) <3>
• Short-time decel torque <4> : over 100% for 0.4/ 0.75 kW motors, over 50% for 1.5 kW
motors, and over 20% for 2.2 kW and above motors <5> (overexcitation braking/High Slip
Braking Torque
Braking: approx. 40%)
• Continuous regenerative torque: approx. 20% <5> (approx. 125% with dynamic braking
resistor option <3> : 10% ED, 10 s)
V/f Characteristics User-selected programs and V/f preset patterns possible
Torque Control, Droop Control, Speed/torque Control Switching, Feed Forward Control, Zero
Servo Function, Momentary Power Loss Ride-Thru, Speed Search, Overtorque/Undertorque
Detection, Torque Limit, 17 Step Speed (max), Accel/decel Switch, S-curve Accel/decel, 3-wire
Sequence, Autotuning (rotational, stationary tuning), Dwell, Cooling Fan on/off Switch, Slip
Compensation, Torque Compensation, Frequency Jump, Upper/lower Limits for Frequency
Main Control Functions Reference, DC Injection Braking at Start and Stop, Overexcitation Braking, High Slip Braking,
PID Control (with sleep function), Energy Saving Control, MEMOBUS/Modbus Comm. (RS-
422/RS-485 max, 115.2 kbps), Fault Restart, Application Presets, DriveWorksEZ (customized
function), Removable Terminal Block with Parameter Backup Function, Online Tuning, KEB,
Overexcitation Deceleration, Inertia (ASR) Tuning, Overvoltage Suppression, High Frequency
Injection.
54 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
A.2 Drive Specifications
Item Specification
Motor Protection Electronic thermal overload relay
Momentary Overcurrent Drive stops when output current exceeds 200% of Heavy Duty Rating
Protection
Overload Protection Drive stops after 60 s at 150% of rated Heavy Duty output current <6>
Overvoltage Protection Stops when DC bus voltage exceeds approx. 820 V
Undervoltage Protection Stops when DC bus voltage falls below approx. 380 V
Momentary Power Loss Immediately stop after 15 ms or longer power loss <7> .
Protection Ride-Thru Continuous operation during power loss than 2 s (standard)
Functions
Heatsink Overheat Thermistor
Protection
Braking Resistor Overheat input signal for braking resistor (Optional ERF-type, 3% ED)
Overheat Protection
Stall Prevention Stall Prevention is available during acceleration, deceleration, and during run.
Ground Protection Electronic circuit protection <8>
DC Bus Charge LED Remains lit until DC bus voltage falls below 50 V
Area of Use Indoors
Ambient Temperature -10°C to +40°C (Flange Type Enclosure)
Humidity 95 RH% or less (no condensation)
Environment Storage Temperature -20°C to +60°C (short-term temperature during transportation)
Altitude Up to 1000 m without derating, up to 3000 m with output current and voltage derating.
10 Hz to 20 Hz: 9.8 m/s2
Vibration/Shock
20 Hz to 55 Hz: 5.9 m/s2 (CIMR-A4T0058 to 0165) or 2.0 m/s2 (CIMR-A4T0208 to 0675)
Standard UL 508C
Protection Design Flange Type Enclosure (NEMA Type 12 Backside)
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 55
A.3 Drive Watt Loss Data
56 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
A.4 Drive Derating Data
IP00/Open-Chassis Enclosure
Drive operation between -10°C and 50°C allows 100% continuous current without derating.
Side-by-Side Mounting
Drive operation between -10°C and 30°C allows 100% continuous current without derating. Operation between 30°C and
50°C requires output current derating.
IP20/NEMA Type 1 Enclosure
Drive operation between -10°C and 40°C allows 100% continuous current without derating. Operation between 40°C and
50°C requires output current derating.
External Heatsink Installation, Finless Drive
Drive operation between -10°C and 40°C allows 100% continuous current without derating. Operation between 40°C and
50°C requires output current derating.
Figure A.1
70
55
L8-35=1: Side-by-Side Mounting
0 L8-12
-10 30 40 50 (Ambient temp: °C)
Altitude Derating
The drive standard ratings are valid for an installation altitude up to 1000 m. If the altitude exceeds 1000 m both the drive
rated voltage and the rated output current must be derated for 1% per 100 m. The maximum altitude is 3000 m.
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 57
A.4 Drive Derating Data
58 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
Appendix: B
Parameter List
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 59
B.1 L: Protection Function
60 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
B.1 L: Protection Function
No.
(Addr. Name Description Values
Hex)
0: IP00/Open-Chassis enclosure
L8-35 1: Side-by-Side mounting Default: 3 <1> <2>
Installation Method Selection
(4EC) 2: IP20/NEMA Type 1 enclosure Range: 0 to 3
3: Finless model drive or external heatsink installation
0: Disabled
L8-38 Default: <3>
Carrier Frequency Reduction 1: Enabled below 6 Hz
(4EF) Range: 0 to 2
2: Enabled for the entire speed range
Sets the time that the drive continues running with reduced carrier Default: <4>
L8-40 Carrier Frequency Reduction
frequency after the carrier reduction condition is gone. Setting 0.00 s Min.: 0.00 s
(4F1) Off Delay Time
disables the carrier frequency reduction time. Max.: 2.00 s
0: Disabled
L8-41 Default: 0
High Current Alarm Selection 1: Enabled. An alarm is triggered at output currents above 150% of drive
(4F2) Range: 0, 1
rated current.
L8-55 Internal Braking Transistor 0: Disabled. Disable when using an optional braking unit. Default: 1
(45F) Protection 1: Protection enabled. Range: 0, 1
Enables motor protection in the event of output phase loss.
L8-78 Power Unit Output Phase Default: 1
0: Disabled
(2CC) Loss Protection Range: 0, 1
1: Enabled
<1> Default setting is dependent on parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
<2> Parameter setting value is not reset to the default value when the drive is initialized.
<3> Default setting is dependent on parameters A1-02, Control Method Selection, and o2-04, Drive Model Selection.
<4> Default setting is determined by parameter A1-02, Control Method Selection.
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 61
B.1 L: Protection Function
62 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
Appendix: C
Standards Compliance
This appendix explains the guidelines and criteria for maintaining UL standards.
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 63
C.1 UL Standards
C.1 UL Standards
UL Standards Compliance
The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product testing
and evaluation, and determined that their stringent standards for product safety have been met. For a product to receive
UL certification, all components inside that product must also receive UL certification.
Figure C.1
<1> This amp rating is 1/2 rated current because the 3-Phase current is split between 6 input phases for the 6-Phase/12-Pulse A1000 drive. Use this
amp rating to select input wiring size as recommended in Table 3.2.
64 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
C.1 UL Standards
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 65
C.1 UL Standards
Tool Insulation
Terminal Crimp Terminal
Wire Gauge Cap Code <1>
Screws Model Number Machine No. Die Jaw Model No.
YF-1, YET-150-1 TD-228, TD-214
M8 100-8 TP-100 100-068-032
YF-1, YET-300-1 TD-324, TD-312
4/0 AWG
YF-1, YET-150-1 TD-228, TD-214
M10 R100-10 TP-100 100-051-269
YF-1, YET-300-1 TD-324, TD-312
YF-1, YET-150-1 TD-228, TD-214
M10 100-L10 TP-100 100-051-559
4/0 AWG × 2P YF-1, YET-300-1 TD-324, TD-312
4/0 AWG × 4P YF-1, YET-150-1 TD-228, TD-214
M12 100-L12 TP-100 100-051-560
YF-1, YET-300-1 TD-324, TD-312
YF-1, YET-150-1 TD-229, TD-215
M10 R150-10 TP-150 100-051-272
YF-1, YET-300-1 TD-325, TD-313
250 / 300 kcmil
YF-1, YET-150-1 TD-229, TD-215
M12 R150-12 TP-150 100-051-273
YF-1, YET-300-1 TD-325, TD-313
250 kcmil × 2P YF-1, YET-150-1 TD-229, TD-215
M10 150-L10 TP-150 100-051-561
250 kcmil × 4P YF-1, YET-300-1 TD-325, TD-313
300 kcmil × 2P YF-1, YET-150-1 TD-229, TD-215
300 kcmil × 4P M12 150-L12 TP-150 100-051-562
YF-1, YET-300-1 TD-325, TD-313
M10 180-10 YF-1, YET-300-1 TD-326, TD-313 TP-200 100-066-687
350 kcmil
M12 180-12 YF-1, YET-300-1 TD-326, TD-313 TP-200 100-066-689
M10 200-10 YF-1, YET-300-1 TD-327, TD-314 TP-200 100-051-563
400 kcmil
M12 R200-12 YF-1, YET-300-1 TD-327, TD-314 TP-200 100-051-275
350 kcmil × 2P M12 180-L12 YF-1, YET-300-1 TD-326, TD-313 TP-200 100-066-688
400 kcmil × 2P M12 200-L12 YF-1, YET-300-1 TD-327, TD-314 TP-200 100-051-564
500 kcmil M10 325-10 YF-1, YET-300-1 TD-328, TD-315 TP-325 100-051-565
600 / 650 kcmil
500 kcmil × 2P
600 kcmil × 2P M12 325-12 YF-1, YET-300-1 TD-328, TD-315 TP-325 100-051-277
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the user
should order two sets of [100-051-272].
Example 2: Models with 4/0 AWG × 2P for both input and output require two sets for input terminals and two sets for output terminals, so the
user should order four sets of [100-051-560].
Note: Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum
allowable temperature of 75°C 600 Vac UL-approved vinyl-sheathed insulation.
66 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
C.1 UL Standards
When connecting the drive to more than one motor for simultaneous operation, disable the electronic overload protection
(L1-01 = 0) and wire each motor with its own motor thermal overload relay.
Enable motor overload protection (L1-01 = 1 to 6) when connecting the drive to a single motor, unless another motor
overload preventing device is installed. The drive electronic thermal overload function causes an oL1 fault, which shuts
off the output of the drive and prevents additional overheating of the motor. The motor temperature is continually
calculated while the drive is powered up.
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 67
C.1 UL Standards
Time (min)
10
7
3
Cold Start
1
0.4
Hot Start
68 YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
Revision History
The revision dates and the numbers of the revised manuals appear on the bottom of the back cover.
MANUAL NO. TOEP C710616 50Bޓ
Published in Japan January 2012 11-11 1
Revision number
Date of original publication
Date of publication
Place of publication
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide 69
YASKAWA AC Drive-A1000
High Performance Vector Control Drive
6-Phase/12-Pulse Input Installation Guide
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture
thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be sure
to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.