Professional Documents
Culture Documents
3-3/8”
3-1/8”
5-7/8”
2-21/32”
4-3/32”
.D.
2” Oapillary
p.C Bulb
Ty
Dia.
Length
Specifications — Table A
Sensing Bulb
with 7’
Temperature Standard Capillary Maximum
Range A.C. Rating
(˚F) Dia. Length (Amps)
Model Style (In.) ±1/2”
ARC-215 60-250˚ 5 3/8 4 30 Amp
120-277 Vac
ARC-219 60-250˚ 9 3/16 16-1/8 Resistive Loads
ARC-515 200-550˚ 5 3/8 3-1/4 Single Phase
ARC-519 200-550˚ 9 3/16 11-1/4 250 VA
ARC-715 300-700˚ 5 3/8 3-11/16 120-277 Vac 2-21/32”
ARC-715D* 300-700˚ 5 3/8 3-11/16 (Pilot Duty)
Figure 1
* This model has 15’ capillary
MOUNTING
Note: Do not mount control where it will be subject to vibration, B. Do not kink capillary tube. The resulting constrictions in
shock, grease, dust, lint or corrosive vapors. Do not mount adja- fluid flow can destroy control function or broaden tempera-
cent to a large magnetic contactor, as vibration and shock will ture differential. Minimum capillary tube bending diameter
cause thermal cutout to interact erratically — resulting in chatter- is 1/2” I.D. (See Figure 4.)
ing of the contactor. C. Any deformations of bulb or capillary that result in leakage
The air temperature in and around the control enclosure should of fluid from control renders control inoperative.
be kept as near to normal room temperature as possible … never
above 150˚F. 1”
1. Thermal cutout must be mounted 2-7/16”
in a vertical position only.
2. Use sheet metal or wood screws Figure 3
through the four 7/32” diameter (Sensing Bulb)
mounting holes in baseplate to
mount control. (See Figure 2.) Do Not
3. For controlling platen or die tem- Bend or Kink
Crimped End
perature, insert entire sensing bulb 3-7/8”
into drilled holes selected for snug
slip fit.
1/2”
The longer, more sensitive Style 9 Rod
bulbs should be used for controlling
air temperatures or pipe line heating. Figure 4
(Capillary Tube)
Note: If material in contact with bulb or
capillary is corrosive, a protective well Mounting Holes
should be used. Protective wells are Figure 2
available at extra cost. Check factory.
;
Reset Button
Load Control
Circuit
Pilot Light
Pilot Light
Line
Figure 8 — When load does not exceed Figure 9 — Three phase and single phase when load
rating of thermostat. exceeds rating of thermostat.
CALIBRATION
Thermometer C
Screwdriver
B
Adjusting
Shaft
A
Load (Tank, Vat, Die or Platen) Adjusting
Set Screw
Figure 10 Figure 12
Figure 11
1. Remove knob cover, knob and thermostat housing as per
instructions 3, 4, 5 under WIRING.
HAZARD OF SHOCK. Extreme care should be exer- 2. Replace knob and turn to highest temperature setting.
cised during calibration adjustments because of 3. Slowly turn knob when controls click “off”, compare the dial
shock hazard due to exposed electrical terminals. reading against the thermometer reading.
Disconnect all power before attempting to cali- 4. If they do not agree —
brate cutout. A. Set dial knob to thermometer temperature reading and pull
off knob.
These controls are factory calibrated to the range indicated on B. While holding the adjusting shaft (B) tightly, turn small
the control adjustment knob. center adjusting screw (A) with small screwdriver (C) until
If calibration is required, either one of two methods may be fol- thermostat clicks “off”. (See Figure 12.)
lowed.
A. If accurate measurement standards are not available, the Note: Always use extreme care not to damage the slot in the
thermostat can readily be adjusted to a known temperature center adjusting screw.
standard such as boiling water (212˚F). (See Figure 10.) C. Each quarter turn of the screw will change the calibration
B. With the aid of an accurate thermometer or other tempera- approximately 30˚F:
ture measuring device, recalibration may be performed — Clockwise to decrease temperature.
within the process as in Figure 11. — Counterclockwise to increase temperature.
For either method, the following general calibration procedures D. Recheck calibration and repeat process if closer calibration
should be followed. is required.
RENEWAL PARTS IDENTIFICATION
1 2
6
5 2 3 4 6 1
Thermostat Thermostat Pilot Light Thermostat
Dial Knob Base
Model Sub-Assembly Cover 120/240 Volt Knob
ARC-215 300-019801-001 169-019604-001 080-026032-006 213-018509-002 015-510457-001 080-510512-001
ARC-219 300-019801-002 169-019604-001 080-026032-006 213-018509-002 015-510457-001 080-510512-001
ARC-515 300-019801-003 169-019604-002 080-026032-006 213-018509-002 015-510457-001 080-510512-001
ARC-519 300-019801-004 169-019604-002 080-026032-006 213-018509-002 015-510457-001 080-510512-001
ARC-715 300-019801-014 169-019605-001 080-026032-006 213-018509-002 015-510457-001 080-510512-001
ARC-715D 300-019801-013 169-019605-001 080-026032-006 213-018509-002 015-510457-001 080-510512-001
Limited Warranty:
Please refer to the Chromalox limited warranty applicable to this product at
http://www.chromalox.com/customer-service/policies/termsofsale.aspx.