Professional Documents
Culture Documents
com/training/online/refrigeration-compressor-failure-cause-
cure-%E2%80%93-part-
1#targetText=Slugging%20is%20a%20short%2Dterm,conditions%20can%20also%20cause%20sluggin
g.
Refrigeration Compressor Failure: Cause & Cure – Part 1
Compressor failure is a big, expensive problem in the refrigeration industry. Compressor
manufacturers are concerned about failure of their product, since it can reflect negatively on them.
Slugging
“Slugging” usually results in a broken component. Slugging is a short-term return of a mass of
liquid, consisting of refrigerant or oil, or as a mixture of both. The slug enters the cylinders of the
compressor instead of super-heated vapor. Slugging almost always occurs on startup, but a very
rapid change in system operating conditions can also cause slugging. A loud knocking noise heard at
the compressor is evidence of slugging. The noise is produced by hydraulic compression – the
compressor is trying to do something it wasn’t designed to do – compress a liquid. Extremely high
pressure will be reached in a cylinder. A hole may be punched in the top of a piston. More often, the
suction, discharge, or both valves will be bent or broken. Cylinder head or valve plate gaskets will
blow out at the internal partition between the high and low side.
If a compressor continues to run with this damage, that head where the failure occurred will run
very hot compared to any other cylinders. Slugs can break connecting rods, even crankshafts. If a
technician finds a compressor with broken or severely damaged internal parts, he or she
should suspect slugging.
Refrigerant will condense in any cold part of a system during the off cycle. The coldest parts of
the system are the evaporator and suction line. If allowed, they will collect the refrigerant and oil
mixture. On the next start-up, this liquid mixture will return to the compressor as a slug. Using a
“pump down” system of control can prevent this condition. Pump down control stops off cycle
migration of refrigerant to any part of the system, including the compressor’s crankcase, which, we
will see later, can cause lack of proper lubrication.
An oversized TXV will hunt under a light load and can cause a slug. It is best to slightly
undersize rather than oversize a TXV.
Poor suction line sizing or poor installation of the suction line also causes slugging. The design
and installation of a suction line is one of the most critical parts of a whole refrigeration system (see
Info-Tec 12).
Floodback/Flooded Starts
Flooding is the continuous return of liquid refrigerant as droplets in the suction vapor instead of
all super-heated vapor. This floodback washes oil off of bearing surfaces. Refrigerant is a lousy
lubricator. All bearing surfaces will prematurely wear. Overheating will result. On a compressor
with a crankcase sight glass, flooding can be observed as constant foaming of the oil during
run. Floodback is always due to a problem with the expansion device.
If the expansion device is a TXV, check its installation. Is the bulb properly located and
insulated? Is it the correct tonnage? Poor installation of the wrong TXV cannot be compensated for
by valve adjustment.
Check super-heat. Too low a super-heat allows more refrigerant to the low side of the system
than the load will require. Saturated, not super-heated refrigerant will have liquid droplets in the
vapor, gradually washing the oil off lubricated surfaces.
If a cap tube or other fixed orifice expansion device is used, the system is critically
charged. Those devices do not react much to load changes. Overcharging will increase the head
pressure, which increases the flow rate through the expansion device until there is too much flow
available for the heat transfer in the evaporator to boil the entire refrigerant off. Result – floodback.
Low load is a major problem of most refrigeration systems. The most carefully designed and
installed system will, at some time, suffer from low load running conditions.
The single best device to protect the compressor from slugging and floodback is the
suction line accumulator.
Accumulators are most often found on low temperature systems, but all refrigeration systems
can benefit from this relatively low-cost protective device.
Flooded starts are the result of the oil in the crankcase-absorbing refrigerant during the off
cycle. The amount absorbed will vary according to the temperature and pressure in the
crankcase. The refrigerant and oil mixture will stratify, with the refrigerant at the bottom of the
crankcase, where a bearing and/or oil pump intake is located.
On startup, bearing lubrication will be marginal at best, and as the crankcase pressure drops, the
refrigerant will boil, flashing to a gas, causing “foaming.” This foam clogs oil passages and may even
enter the cylinders, resulting in slugging.
All semi-hermetics use an oil pump to force oil to bearing surfaces. These oil pumps will not
pump foam. Full hermetic compressors rely on splash lubrication and semi-hermetics also utilize
some splash lubrication. Foam will not “splash.”
As previously noted, pump down helps keep excess refrigerant out of the crankcase. Crankcase
heaters should be used, and if present, should be checked that they are not burned-out and “on” at
the proper time. Flooded starts can be minimized on cap tube systems by having the proper charge
in the system.
Contamination
Contamination was found to be the major cause of replacement compressor failure. It
bears repeating that only two things should be inside any refrigeration system: refrigerant and
oil. Anything else is a contaminant! Air, moisture, non-condensables, chips, oxides, scale, brazing, or
soldering flux, any “dirt” that gets into a system accidentally or through poor service techniques is a
contaminant that will lead to sure and swift failure!
Air in a system will displace refrigerant in a condenser resulting in high head pressure and higher
than normal temperatures. The temperature at the valves of a compressor is about 50F hotter than
the discharge line temperature. This high temperature will cause carbonization of oil on the discharge
valves. A build up will occur, and in a short time, the valves will leak. Leaking valves cause higher
temperatures, causing more build up – finally, total failure.
Moisture in a system will react with refrigerant to form acids. Acids can cause electrical failures
by eating at the wires on electrical terminals, can etch parts, and can travel throughout the system
eroding other components.
All contaminants must be eliminated. A thorough evacuation will eliminate air and
moisture. Solid contaminants, chips and dirt, can be trapped in strainers, filters, or filter driers.
Most modern day filter driers have acid removal capability. Replace the filter drier, and if the
compressor is semi-hermetic, change the oil, until an acid test proves the system is free from acid.
Make good installation and service practices a habit. Keeping contaminants out of a system in
the first place is better than any procedure to remove them.
Replacing a “burned-out” compressor presents the ultimate challenge in eliminating
contaminants.
It is best to assume that all burnouts are bad burnouts and proceed accordingly. The chemical
reactions that take place when a compressor burns out will create a lot of acid, moisture, and solids in
the form of carbonized oil and “soot.” The soot will coat the inside of the discharge line at least to the
first elbow, and depending on the size of the system, some distance beyond the elbow. The suction
line may even be coated six inches to a few feet from the compressor. It is best to cutout, remove,
and replace these coated sections of line with clean, new tubing (Government regulations no longer
allow cleaning up by pumping R-11 through systems). An oversized liquid line filter drier should be
installed along with a suction line filter designed for high acid removal and having access fittings for
checking pressure drop through the suction line filter. They should be installed to facilitate easy
replacement.
Deep or triple evacuation of the system is an absolute necessity to remove air and moisture
before putting the system back into operation.
Of course, the technician has found the reason for the burnout, repaired the malfunction, and
can now operate the system. After 48 to 72 hours of operation, the technician should return to check
the pressure drop across the suction line filter and take an acid test. Depending on what is found,
replace the suction line and liquid line filter driers until an acid test and pressure drop test shows no
more contamination. The extra expense of proper clean up of a system will be more than paid for by
the long life of the much more expensive compressor.
SAE – Society of Automotive Engineers
ODF = Outside Diameter Flared (flare fitting)
ODS = Outside Diameter Soldered