CAUTION If a unit has been non-operational for more than two years, the DC link
capacitors have to be newly formed. If this is not carried out, the unit
can be damaged when the line voltage is powered up.
If the unit was started-up within one year after having been
manufactured, the DC link capacitors do not have to be re-formed. The
date of manufacture of the unit can be read from the serial number.
How the serial (Example: A-N60147512345)
number is made up
Digit Example Meaning
1 and 2 A- Place of manufacture
3 N 2001
P 2002
R 2003
S 2004
T 2005
U 2006
V 2007
W 2008
4 1 to 9 January to September
O October
N November
D December
5 to 14 Not relevant for forming
Siemens AG 6SE7087-6KD60
SIMOVERT MASTERDRIVES Operating Instructions 12-1
Forming 04.2006
Motor-
connection
3AC R
U2/T1
C / L+ V2/T2
A C
D / L- W2/T3
Forming
DC link Inverter
PE1 PE2
DANGER The unit has hazardous voltage levels up to 5 minutes after it has been
powered down due to the DC link capacitors. The unit or the DC link
terminals must not be worked on until at least after this delay time.
Procedure Before you form the DC link capacitors, all DC link connections must
be disconnected.
The converter incoming power supply must be switched off.
The unit is not permitted to receive a switch-on command (e.g. via
the keyboard of the PMU or the terminal strip).
Connect the required components in accordance with the circuit
example.
Energize the forming circuit. The duration of forming is approx. 1
hour.