If the Power Module, Basic Line Module, Active Line Module, and Motor Module have not been used
for more than two years, the DC link capacitors must be reformed. If this is not carried out, the units
could be damaged when the DC link voltage is connected under load.
If the cabinet is commissioned within two years of its date of manufacture, the DC link capacitors do
not need to be reformed. The date of manufacture can be taken from the serial number on the rating plate.
Note
Storage period
It is important that the storage period is calculated from the date of manufacture and not from the date
that the equipment was shipped.
Rating plate
Date of manufacture
The date of manufacture can be determined as follows:
This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims all liability for the
completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties.
2/1/2021
B 2011 O October
C 2012 N November
D 2013 D December
E 2014
F 2015
H 2016
J 2017
K 2018
L 2019
M 2020
• 3 incandescent lamps 230 V / 100 W for a line voltage of 380 to 480 V 3 AC.
Alternatively, use 3 resistors of 1 kΩ / 100 W each (e.g. GWK150J1001KLX000 from Vishay) instead of the
incandescent lamps.
• 6 incandescent lamps 230 V / 100 W for a line voltage of 500 to 690 V 3 AC, where 2 incandescent lamps
must be connected in series in each supply phase.
Alternatively, use 3 resistors of 1 kΩ / 160 W each (e.g. GWK200J1001KLX000 from Vishay) instead of the
incandescent lamps.
• Various small components, such as lamp sockets, cable 1.5 mm2, etc.
This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims all liability for the
completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties.
2/1/2021
Warning
Risk of death from electric shock when installation of lamp sockets is non-insulated
If two incandescent lamps connected in series are used, the insulation of the lamp sockets is not
rated for the high voltage of 500 to 690 V 3 ph AC.
― For a line voltage of 500 to 690 V 3 ph AC, install the two lamp sockets connected in series with insulation
and protect them from being touched.
Note
Forming the Line Modules
Voltage must be supplied to Line Modules via a connected Motor Module and the associated DC link.
This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims all liability for the
completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties.
2/1/2021
Procedure
• The unit being formed must not receive a power-on command (e.g. from the keyboard, BOP20 or terminal
block).
• During the forming process, the incandescent lamps must become less bright or go completely dark. If the
incandescent lamps continue to be brightly lit, a fault has occurred in the drive unit or in the wiring.
This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims all liability for the
completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties.