You are on page 1of 22

इंटरनेट मानक

Disclosure to Promote the Right To Information


Whereas the Parliament of India has set out to provide a practical regime of right to
information for citizens to secure access to information under the control of public authorities,
in order to promote transparency and accountability in the working of every public authority,
and whereas the attached publication of the Bureau of Indian Standards is of particular interest
to the public, particularly disadvantaged communities and those engaged in the pursuit of
education and knowledge, the attached public safety standard is made available to promote the
timely dissemination of this information in an accurate manner to the public.

“जान1 का अ+धकार, जी1 का अ+धकार” “प0रा1 को छोड न' 5 तरफ”


Mazdoor Kisan Shakti Sangathan Jawaharlal Nehru
“The Right to Information, The Right to Live” “Step Out From the Old to the New”

IS 15908 (2011): Selection, Installation and Maintenance of


Control and Indicating Equipments for Fire Detection and
Alarm System--Code of Practice. ICS 13.220.10

“!ान $ एक न' भारत का +नम-ण”


Satyanarayan Gangaram Pitroda
“Invent a New India Using Knowledge”

“!ान एक ऐसा खजाना > जो कभी च0राया नहB जा सकता ह”


है”

Bhartṛhari—Nītiśatakam
“Knowledge is such a treasure which cannot be stolen”
1515908:2011

'JOf1'?rfJ2J J7/'iCf)

31fT;f x=r xi-q Cf) q xi -iJ C1 Cl? in ~ ~ ~ ?I 0 I 3fi~ xt-q Cf)


\3Q"!=¢'! in -g~lq, m~ q ffi-\!~Iq -~ "!i f%C1 I

Indian Standard
SELECTION, INSTALLATION AND MAINTENANCE
OF CONTROL AND INDICATING EQUIPMENTS
FOR FIRE DETECTION AND ALARM
SYSTEM - CODE OF PRACTICE

les 13.220.10

© BIS 2011

BUREAU OF INDIAN STANDARDS


MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG
NEW DELHI 110002

September 20 I I Price Group 8


Fire Fighting Sectional Committee, CED 22

FOREWORD

This Indian Standard "vas adopted by the Bureau of Indian Standards, after the draft finalized by the Fire Fighting
Sectional Committee had been approved by the Civil Engineering Division Council.

In fire alarm systems, control and indicating (C and 1) equipment are the backbone of the entire network and
performs three important functions, namely;

a) Continuous and automatic monitoring and control of circuits external to the equipment (such as fire
detection and lIre alarm device circuits) and also supply of power to these circuits.
b) Indication of fire signals, fault signals and their location.
c) Manual control to facilitate actions sLich as testing, disablement of devices, triggering of fire signals,
silencing of audible fire warning and resetting the system after a fire signal.

As these facilities are required by different people at different times all these facilities need not always be provided
at a single location. For example according to the premises, indication of faults might be required by an engineering
personnel, who might not require detailed infol111atio11 on fire signals whereas accurate infonnation on the location
of a tire is essential to the safety/security personnel, who might need in specific information about system fault(s).

In small and simple systems the control indicating and power supply equipment for the system normally is
hOllsed within a single enclosure. In large and complex premises, the main control equipment circuitry might be
installed at one location, power supplies might be distributed around the building, while main indicating equipment
incorporating certain basic controls is installed at another location, such as near a main entrance to the building
and lastly repeat indicating equipment (with or without control) may be installed at other locations (such as
security or control rooms).

Since premises vary in size, complexity and fire strategy, it is essential that the nature and location of manual
controls and all indicating equipment, in particular, is suitable for the fire and evacuation procedure that are to be
adopted and for the person that shall use lhe system, including security or safety staff and tire-fighter attending
a fire. Location of control circuitry and power supplies shall more likely to be determined by engineering
considerations and the preference of the personnel who are going to use the system.
For the purpose of deciding whether a pmticular requirement of this standard is complied \vith, the final value
observed or calculated, expressing the result of a test or analysis, shall be rounded off in accordance with IS 2 ; 1960
. Rules for rounding off numerical values (revised),. The number of significant places retained in the rounded off
value should be the same as that of specified value in this standard.
IS 15908 : 2011

Indian Standard
SELECTION, INSTALLATION AND -MAINTENANCE
OF CONTROL AND INDICATING EQUIPMENTS
FOR FIRE DETECTION AND ALARM
SYSTEM - CODE OF P.RACTICE

1 SCOPE d) Where there are multiple entrances to a


complex building, there shall also be
1.1 This standard covers planning, design, maintenance
consultation with the external fire brigade
and performance criteria for control and indicating
regarding the possible need for repeat control
equipments for tire detection and alarm systems.
and/or indicating equipment.
1.2 This standard covers minimum level of protection. e) In buildings which are not continuously
Nothing in this standard prevents to install systems occupied, location of indicating equipment in
designed for higher degree of protection, for special a location that shall be visible to the fire
risks, etc. brigade from outside the building can be of
benefit particularly if there is a facility for
2 REFERENCES
transrnission of alarms to an alarm receiving
The standards listed at Annex A contain provisions centre.
which through reference in this text, constitute
3.2 All control indicating and pOVv'er supply equipment
provisions of this standard. At the time of publication,
that is likely to need routine attention for maintenance
the editions indicated were valid. All standards are
shall be located in readily accessible locations that
subject to revision and parties to agreements based on
facilitate safe maintenance work.
this standard are encouraged to investigate the
possibility of applying the most recent editions of the 3.3 The surrounding ambient illumination level in the
standards indicated at Annex A. vicinity of all control and indicating equipment shall
be such that visual indications can be clearly seen,
3 LOCATIONS OF CONTROL AND INDICATING controls easily operated and any instructions or legends
EQUIPlVIENT (all be easily read. Whl~re this is impracticable, suitable
3.1 The following requirements shall be followed by illumination backed up by an emergency source shall
the user and installers before locating control and be made available.
indicating equipment: 3.4 The surrounding ambient noise level in the vicinity
a) Indicating equipment, in conjunction with of all control and indicating equipment shall not be
suitable manual control facilities, shall be such as to prevent audible indications (sllch as the fault
located at an appropriate location for bOlh warning sounder) from being heard.
safety staff and fire-fighters responding to a 3.5 The fire ;:llann control and indicating equipment,
fire signal. power supply equipment for the control and indicating
h) The location shall normally comprise an area equipment and other essential control facilities shall
on the ground floor close to the entrance to be located in safe areas. so that the equipment is
the building likely to be used by the fire unlikely to be involved in a fire before adequate
fighters, or a suitably located, continuously \varning has been given.
manned control room from which at least
3.6 It is preferable to provide detection system for the
initial control of any fire incident, by safety
enclosure where C and I equipment is installed though
staff and/or the fire fighters, shall be
it is compulsory if installed in a part of the protected
implemented.
building.
c) In complex premises, there shall be
consultation between the user, installer and 3.7 On or adjacent to indicating equipment there shall
the fire fighters, regarding the location of all be a diagrammatic representation of the building
control and indicating equipment and the showing at least the building entrance, the main
htcilities provided. circulation area and the division into zones. Where the
IS 15908 : 20U

division into zones is not provided, a correctly mains supply needs to be reliable and capable
orientated plan of the premises shall be displayed. for supplying the largest load that can be
Nan:: - See also 6 for additional requirements. placed on it lInder normal, fire and fault
conditions.
4 GUIDELINES FOR NETWORKED FIRE b) The design of the main supply to the system
ALARM SYSTKlVIS needs to be slich that it is unlikely to be
a) The functions of the control and indicating affected by faults on other circuits or
equipment are not centralized in one location equipment, or by isolation of supplies in the
or paneL but distributed amongst a number building for maintenance or economy in
of sub-panels located remotely from each consumption of electricity.
other. These panels are than inter-connected c) The main supply shall need to be backed up
by a network which usually serves as a data by a standby supply that is able to support
highway. Snmc sub-panels may simply act as the system while the main supply is restored
'data gathering' panels and provide no or fault in the mains supply is corrected. The
indications. Others may be fully functional standby supply also needs to be reliable, and
control and indicating panels. Control and transfer between the two supplies shall not
indicating panels configured so as to 'stand affect the operation of the system.
alone' and continue to operate nonnally in the d) Failure of the main supply may occur when
event of a failure of the communications links the premises are unoccupied and the system
between sub-panels. might be inoperative on re-occupation. It is
b) Networked system is usually installed in the important that (he presence of a power supply
following circumstances to the system is indicated by a visual indicator
I) Where the fire alarm system is large and at the indicating equipment to enable total
beyond the capacity of single control and power failure to be identified by the personnel.
indicating equipment. and e) There shall be a need to set some practical
1) Where there is a need for centralized limit on the duration of standby batteries.
monitoring and/or control of a number However, when the premises are not occupied
of fire alarm systems in different for longer durations, the limit recommended
buildings in the same vicinity (for in this standard could be insufficient to cater
example 011 the same site). for the longest periods for which premises
might be unattended. TIle user shall need to
c) The effect of the communication link and the
consider this aspect and arrange frequent
implications for fire alarm operation shall
check on the batteries or consider the need
depend onlhe configuration or the networking
for standby batteries with a longer duration.
system, the lype of net\vork and whether or
not the network forms part of the critical f) If the premises are provided with emergency
signal path. supply through a diesel generator or a captive
power plant and if the process in the risk is
d) Ring or loop network are more resilient to
continuous, then the capacity of the standby
communities failures than redial type
batteries may be reduced provided the circuits
network, peer to peer netvv·ork with a central
served by the generator include that of the
processor controlling panel to panel
alarm system.
communications.
g) In some complex buildings, sllch as shopping
e) If all sub-panel can function as 'stand alone'
centre, additional indicating equipment, such
fire alarm system and do not depend on the
as color graphics terminals, not essentials for
network to facilities primary alarm functions
compliance with this standard, may be
(for example sounding lhe alarm initiating
provided to assist the lIser in the monitoring
other activities), a communications failure
and control of fire incidents. Stand-by supply
shall have no signi rican! effect and the
shall take care of this equipment also.
network can be considered as an ancillary
circuit. NOTE - Detailed requircments for the above arc listed
in various clauses.
5 POWER SUPPLIES
5.2 Power Requirements
5.1 General
The system shall derive its power from either,
a) Power supply for the fire alarm system shall
normally be uerived from the low voltage a) mains electricity supply single phase (normal
IS 15908 : 2011

supply), or the standby power supply that shall full load operation for at least 30 min. The
be immediately available in the event of full load would be defined as that caused by
failure of normal supply and shall be the operation of all the alarm sounders
automatically connected (automatic switch - operating simultaneously, operation of a
over) so as to maintain the equipment in ready detector in at least 25 percent of zones (with
condition of taking the maximum load. The a minimum of two zones) and the operation
standby shall be derived mostly from of the fault indicator. The operation of trigger
exclusive secondary batteries where captive devices in further zones shall not result in
power generation (like automatically started cancellation of fire alarms existing at that
generation, continuously running generation) time.
is readily and certainly available, such as in NOTE - Where failure of norll1<l1 mains supply is !lot
process plants, industrial complexes and other likely to be made good within 2·~ h due to long
occupancies, a standby can be derived from unattended/unoccupied periods, the system inspection
there. frequency lllC.lCd to be arranged at intervals such that in
the event of normal mains supply failure, at least 24 h
b) C and I equipment shall be connected to the standby capacity remains at the lime of next inspection.
mains via a switch-fuse or MCCB reserved
f) standby power supply derived from exclusive
solely for the purpose, its cover being painted
red and labeled 'FrRE ALARM - DO NOT back-up batteries shall have provision of
SWITCH OFF'. Switch-fuse shall be automatic charging and automatic load
contained in a securely closed box and the switch-over whenever normal mains supply
condition of 'Main-on' shall be indicated by rails. It shall be ensured that charging
a new lamp. The voltage and ampere ratings conditions are matched to the system. The rate
shall be compatible with the requirements of of battery charging shall be such that, having
various parts of the system and power capacity discharged to its final voltage, the battery can
of the power supplies shall meet the maximum comply with the recommendations of 5.2 (e)
load likely to be placed on the system. after a charging period of 24 h.

Where the user requires isolating the building g) external batteries shall be properly mounted.
during closed hours, a separate supply shall The best practice shall be to mount t.hem on a
be provided for the fire alarm system that shall metal stand at a well ventilated location.
not normally be isolating during closed hours. h) every isolator, switch and protective device
c) minimum capacity of the normal mains that is capable of disconnecting the mains
supply to the fire alarm system, shall be
supply shall be calculated so as to meet the
total power consumption of the entire system situated in a position inaccessible to
in quiescent condition plus that of all the antiauthority pers~)ns or be protected against
sounders and 25 percent zones in alarm unauthorized operations by persons without
condition. a speciaJ tool.

d) main connection to the system shaII be j) voltage of the batteries shall be monitored and
arranged such that the mains supply to the low voltage indicated 011 C and I equipment.
system (which is through exclusive s\vitch- k) capacity of the battery shall he as per
('use) is not interrupted as a result of switching calculations shown in Annex B.
off mains power to premises/other services. m) where distributed power supplies for fire
Prov isions made for normal and standby alarm system to power sounders, beam
power supply shall be such that the s\vitch- detectors, etc, are installed, It shall be
over from one supply to another is automatic mandatory that the entire system be povvered
and each is capable of supplying the largest from the C and I panel power/back up and
load to be placed on them under nonnal, fire the same shall be monitored.
and fault conditions. Further, the power
supply for the fire alarm system shall be 6 CABLES AND THEIR INSTALLATIONS AND
totally dedicated and shall not be connected CIRClllTS
to other loads.
6.1 General
e) standby power supply shall be capable of
maintaining the system in normal operation a) The components of most fire alaml systems
for a period of not less than 48 h after the are connected by cables and wiring and hence,
failure of normal mains supply after which cables are most important link between fire
sufficient capacity would remain to provide detection devices and the control centre. It is
IS 15908 : 20U

essential that the cables used for Loop shall be of Class A wiring. Class A
interconnection of devices and the control wiring shall be return loop. Tapping may be
centre remain operational and maintain circuit used from the loop as Class B wiring.
integrity for adequate c1urution with inherent
NOTE - See Fig. I for wiring details.
capability to resist direct exposure to fire.

Conventional (Non - Addressable)


Detection System - Class B Wiring

DETECTOR BASE DETECTOR BASE END OF LINE


,.----...., RESISTOR
CONTROL
UNIT
INITIATING
DEVICE
CIRCUIT

1A Correct Wiring Method - Two Wire Detectors

Conventional (Non - Addressable)


Detection System - Class B Wiring

CIRCUIT WIRING CIRCUIT WIRING BENT


LOOPED UNDER BACK ON ITSELF AND
ONE TERMINAL SECURED IN ONE NOTCH
END OF LINE
0+----..,...----------,,..------.., RESISTOR
CONTROL
UNIT
INITIATING
DEVICE
CIRCUIT

1B Incorrect Wiring Method - Two Wire Detectors

FIG. I WIRING DETAILS FOR FIRE DETECTION AND ALARM SYSTEM (Continued)
IS 15908 : 2011

RELAY / CONTROL
MODULE
24V DC
/ HOOTER *
U I
...J
(fJ

ili +~~--~--~--~--~--,-~--~--~--~--~~
z
«
0..
...J
o
cr:
I-
25 + 1----'---1---'---""--.....
o
ADDRESSABLE
PULL STATION

* Loop Powered Hooter/Sounder


Or
* Separate Powered Hooter

1 C Addressable Fire Detection and Alarm System - Class A Wiring

ZONE ADDRESSABLE
RELAY! CONTROL
MODULE ~,AODLJLE
/----- *
./ HOOTER
U / -----
...J /
(fJ
...J
UJ + t----'----'----'----'---'
Z
«
0..
...J
o
n::
I-
6+ I----L.---I---"--""--.....
U

* Loop Powered Hooter/Sounder


Or
* Separate Powered Hooter

1 D Addressable Fire Detection and Alarm System - Class A Wiring With


Class B Tapping

FIG. I WIRING DETAILS FOR FIRE DETECTiON AND ALAR"'I SYSTEM


IS 15908 : 20U

b) It is essential that all interconnections operate I) breakdown of cable insulation of other


correctly at the time of a fire. This is circuit and/or fire alarm circuit:
particularly important in the case of cahles 2) a fire caused by a fault on another circuit:
that link control and indicating equipment to 3) electromagnetic interference to any fire
manual call points. automatic fire detectors alarm circuit as a result of the
and fire alarm devices. and that transmit proximately of another circuit: and
signals to an alarm receiving centre.
4) damage resulting from the need for other
c) It is not normally possible to predict, with any circuit to be installed in. or removed from,
accuracy. those areas of a building in which ducts or trucking containing a fire alarm
fire can or C<1nnot occur. At the design stage. circuit.
the exact rOllte that cables shall follow may
11) In order to facilitate identification of fire alarm
also be unknown. Therefore to ensure that
circuit, cable shall preferably be red in colour,
cables used remain operational for an
unless another form of colour coding is
adequate duration. cables, with an inherent
appropriate. By this means, the poss ible need
ability (0 resist attack by fire, need to be used
for appropriate segregation can be identified,
throughout.
and there shall be less likelihood of
d) The integrity of the mains supply to the system inadvertent manual interference with the
is also regarded as essential. even though the circuit of fire alarm systems.
system has a standby supply. Accordingly,
mains supply circuits need to be adequately 6.2 Cables
protected against the effects or fire. 6.2.1 The electrical characteristics of all cable, such as
e) The probability of disablement of any part of voltage drop, current carrying capacity, impedance and,
the lIre alarm system as a result of mechanical \vhere appropriate, ability to transmit data shall be
damage to cables can be reduced by the use suitable for the system.
of sutrlciently robust cables. careful selection
The cable specification for fire alarm system is as
of cable routes and by the provision of
follows:
protection against mechanical damage in
areas where cables are susceptible to a) Armoured or unarmollred FRLS cables of
mechanical damage. rvlonitoring of circuits minimum 2 x 1.5 rnm:~ ATe cables for
does not ensure that cable faults shall not conventional fire alarm and multistrand
occur, but is essential to minimize the time twisted pair shielded cables for addressable
between occurrence and identification (and fire alarm system.
hence repair) of the fault. Monitoring of b) PYC insulated copper conductor cables
circuilS and protection of cables against conforming to IS 694 having minimum
damage are, therefore. complementary 1.5 mm 2 cross-sectional area, i r stranded at
precautions, rather th~ll1 altematives. least 0.5 mm 2 cross-section shall be used.
f) It is the responsibility of the designer to ensure c) Rubber insulated braided cables conforming
that the dedrical characteristics of the cables, to IS 9968 (Part I).
including current carrying capacity and d) Armoured PYClrubber insulated cables
voltage drop are suitable for the system. The
conforming to IS 1554 (Part 1).
choice of cable and routes selected shall need
e) Mineral Insulated (MI) cables with overall
to take into account the need to avoid
LSF (Low Smoke and Fumes).
electrollla~netic interference from other
cables and SOllrce of electromagnetic NOTE -- It is strongly recornmended to use cahles
radiation. particularly in the case of the system mentioned under item 'e' above for certain specific
occupancies like Oil and Hydrocarbon Industries (high
in whil'h cables are used to be comhalive with hazard, high fire potential), Airports (high hazard and also
the characteristics of the data transmission for large public presence), Jetty (high hazard. high fire
example speed and waveform and remain so pOlential), P\)w\;~r Plants (crilic:ill{lf use), Metro Railways
far an adeqllate length of time during the (underground and large public presence, life safety), and
wht.'re huge public gathering is anticipated like Shopping
relevant ex posure to Ii re for category of cable. malls, Multiplex and large assembly halls (life safety)
g) The circuit of fire alarm systems shall need etc, where either the lire load is high or the intolerance of
to be segregated from the cable of the other d()wmime for the occupancy or life safety is foremost.

circuit to minirnize any potential for other 6.2.2 The cables used shall be exclusively for fire
circuit to cause rnalfunction of the fIre alarm detection system. The multi-core cables shall not be
system arising from. shared for other low voltage or high voltage circuits.

6
IS 15908 : 20ll

6.2.3 Cables/wiring shall be laid down in metal1iclrigid or at right angles to the walls of the building.
PVC conduits. PVC conduits shall be used only in Unseemly conduit bends and offsets shall be
concealed spaces. avoided by using fabricated galvanized steel
junction/pull through boxes for better
6.2.4 Cables connected to detectors shall be given'S'
appearances.
loop on both the sides of the detectors which shall be
f) No cross-over of conduits shall be allowed
properly clamped to the ceiling. Loop shall also be
left where cables connect sonnders, panels, dampers. unless it is necessary and entire conduit
ctc. Appropriate glands shall be provided \vhere the installation shall be clean and neat in
cable enters the junction box. appearance. Conduits embedded into the walls
shall be fixed by means of staples at not more
6.2.5 All the cables and wires shall be tagged ft1r proper than 500 mm intervals. Chases in the walls
identification. Wires shall be identified by ferrules at shall be neatly made and refilled after laying
junction and cables by colour bands at every 3 m the conduit.
distance. g) Conduits buried in concrete stmcture shall be
6.2.6 When connecting different buildings, etc, put in position and securely fastened to the
overhead lines for fire alarm system shall not be used. reinforcement before the concrete is poured.
They shall be laid underground according to IS 1255. Proper care shall be taken to ensure that the
conduits are neither dislocated nor choked at
6.2.7 There shall be no joint in the cable specially the time of pouring the concrete.
between the two detectors or detector to response
h) Suitable galvanized steel fish wires of not less
indicator and detector to manual call point. If any joint
than 0.63 mm diameter shall be drawn in all
is required because of the length of the cable which is
conduits before they are embedded. Where
connecting the detectorlresponse indicator/manual call
conduit passes through expansion joints in
point to the control panels, proper junction box shall
the building, adequate expansion fittings
be used and it shall be properly marked and easily
shall be lIsed to take care of any relative
accessible.
movement.
6.3 Conduit \:V;ring j) Inspection boxes shall be provided for
periodical inspection to facilitate withdrawal
The requirements given below shall be followed:
and removal of wires. Such inspection boxes
a) The conduits shall not be choked with cables. shall be tlush with the wall or ceiling in the
There shall be sufficient space inside the case or concealed conduits. Inspection boxes
conduit even after lhe cable is pulled. The shall be spaced at not more than 12 m apart
minimum size of the conduit shall be 25 mm. or two 90 solid bends or equal.
b) S-runs of conduits, vvhich shall be spaced at k) All junction and pull boxes shall be covered
not more than 4.25 m between draw boxes, by 6 mOl clear plate truly cut and fixed with
shall not det1ect from the straight by an angle cadmium phlted brass screws. Thesejunction
more than 15°. B-runs of conduits shall not boxes shall form part of point wiring or
deflect from the straight by more than IS'. conduit wiring as the case may be including
Conduits shall be kept at a minimum of the cost of removing the cover for painting
100 mm from the pipes of other non-electrical and refixing.
services. Ill) Conduits shall be free from sharp edges and
c) Wiring for short extensions to outlets in hung burs and the threading free from grease or oil.
ceiling or to vibrating equipments, motors, The entire system of conduits must be
etc, shall be installed in flexible conduits. No completely installed and rendered electrically
flexible extension shall exceed 1.2 m in continuous before the conductors are pulled
length. in.
d) CabJes and conduits run on surfaces shall be n) Conduits shall terminate in junction boxes of
supported on galvanized steel 6 mm thick not less than 32 mm deep and the termination
saddles and clamps which in turn are properly shall be rigid with check nuts and a smooth
screwed to the wall or ceiling. Saddles shall bushing. No wires shall be exposed in any part
be at intervals of not more than 500 mm. of the installation.
Fixing screws shall be with round or cheese p) Conduits and cables shall be laid by skilled
head and of cadmium plated brass. and experienced workmen. Care shall be taken
e) Exposed conduits shall be neatly run parallel while laying cables to avoid kinks. At all the

7
IS 15908 : 20ll

changes in directions (vertical and horizontal c) Electronic/electric circuit shall have relay
planes) the cables shall be bent smooth with a conforming to the relevant Indian Standard.
radius as recommended by the manufacturers. d) Each sectorlzone indicator, indicating fire
q) No joints shall be allowed between two points. shall consist of two LED/filament bulbs
The sleeve at joints shall be shaved off like a conforming to relevant Indian Standards
pencil and shall not be cut square to avoid connected in parallel. In case of fault
clltting of conductors. indicators, only one LED/filament bulb shall
be used - open and short circuit separately.
7 CONTROL CENTRE (FOR HOUS1NG C AND I Fire warning indicator shall be clearly labeled
EQUIPMENT) and coloured red while fault warning indicator
a) In high rise buildings and special buildings, a shall be clearly labeled and coloured amber.
control centre of an area of 15 m 2 to 20 m' e) The sector panels shall have the power
shall be provided where the control and capacity to be connected to all the zones in
indicating equipment, power supply units and the sector. In addition, it shall have facility
other fire protection ancillary panels could be for connections to external sounders.
installed. This shall preferably be on ground f) If required, the panel shall have additional
rIoor (floor one) and manned 24 h. capacity to operate auxiliary equipment like
b) The control centre room shall have attached fire dampers, fire closers, ventilation and/or
we bath, drinking water facilities and pressurizing fans, emergency light, smoke
approprbte tables, chairs. record racks, etc. exhausters, etc. Failure rate of power at the
c) The control centre room shall have emergency local sector panel shall be indicated in the
lighting system. main control room.
d) The control centre room shall have intercom 8.2 Fire Alarm/External Fire Alarm Sounders
and direct telephone facilities. Where
possible, a direct hotline or any other means a) A number of external fire alarm sounders are
of communication to local fire brigade shall generally required for protective premises.
be provided. The number and distribution of these alarms
e) The control centre room shall have mimic in the premises shall be slIch that the sound
panel or the premises protected and details of level/audibility requirements are met with a
all the lire protection systems. Fire orders shall view to alert the occupants and initiate fire
be prominently displayed. fighting actions with the least delay.

n Control centre in air conditioned premises b) The grouping of extemal fire alarm sounders
shall be segregated from the rest of the can be done in either of the following way.
buildings by fire walls and provided with an The grouping scheme shall be reflected in fire
independent ac system. If ducts are common, instructions issued for the use of the
the entry/exit points of ducts through the walls occupants.
shall be provided with aUlomatic damper c) Sounding of alarms can be so arranged that
units. Slatus of these dampers shall also be any a) arm operated all the sounders
displayed in the mimic panel. throughollt the premises. This grouping is
particularly suitable for smaller premises.
8 CONTROL AND INDICATING EQUIPIVIENT d) Sounding of alarms can be so arranged that
COMPONENTS the alarms sound initially in the sector of fire
origin or in this zone and on its adjoining
8.1 Sector/Zone Panels and C and I Equipmcnt
areas, or in this zone and in specially selected
a) The sector/zone panel shall be installed on areas of high flammability or ditficult egress.
individual sector/zone of the building and
shall confoml to the requirements given in 8.3 Silencing
Annex C. The operation of silencing switch either for general
b) The e and 1equipment and other control panel fire alarm sounders or for signal controlling internal
shall be wall mountinglfloor standing type and audio alarm ofC and I equipment shall cause an audible
shall be made of mild steel sheet conforming signal to be given in or near the e and I equipment.
to IS 513. The minimum thickness of sheet This audible signal which may be the same as that for
shall be 1.6 mm. The colour shall be fire red fault warning, is intended to act as a reminder that the
(Shade No. 536 of IS 5). silencing switch has been operated and shall give a

8
IS 15908 : 20U

distinctive sound different from that of any other alarm who are mobile within or in the vicinity of
sounder (extemal or internal to C and I equipment). the building.
NOTE - The requirement given here are not necessary in b) Depending on the choice of the system, C and
systems where automatic re-set is provided. I equipments shall have necessary controls.
Where two stage alarm is chosen, zonal!
8.4 Visual Alarm Signals sectors panels and C and 1 equipment are
In general, visual signals shall only be used to needed and in case of single stage zonal/sector
supplement audible alarms. A defect in visual alarm panel are not needed.
shall not cause a defect in audible alarm or vice-versa. c) The system may also adopt any oflhe cabling
Only in special cases where audible alarm is ineffective. scheme. that is connecting zones/sectors
slIch as even the occupants are deaf, immobile. etc, directly to the C and I equipment or through
visual alarms can be used in lieu of external alarm zone/sector control panels.
sounders. d) The audible and visual alarm state shall be
maintained by the sector/zonal control panels
8.5 Stages of General Fire Alarms
and control panel of C and 1 equipment
General fire alarm system though external sounders without a continued signal from fire detector.
can be provided in either of the following ways: The sound characteristics of the alarm shall
be similar throughollt the protected premises.
a) Single stage contillllOUS a/ann - In this
scheme, a continuous alarm (evacuation alarm 8.7 Fire Alarm Intimation
or signal) sounds in the ·sectorlzone of fire and
The operation of fire detector/manual call point shall
also on the C and I equipment with a provision initiate transmission of signal(s) resulting in,
on C and I equipment to sound continuous
general tire alarm throughout the protected a) an audible signal on the C and I equipment
premises. This is normally done, particularly (internal audio alarm C and 1 equipment):
in smaller premises, sparely populated b) a visual signal in the C and I equipment;
premises or storage premises. c) at least one external alarm sounder;
b) Two-stage general alarms -In this scheme, d) a visible indication for each sector/zone in
two-stage alarm is provided in which a which a detector/rvICP operations; and
continuous evacuation alarm is immediately e) audible signal (alert) on sector/zonal panel
given in sector/zone of fire or in a restricted concerned where sector/zonal panels have
area, together with intermittent alert signal in been provided.
other parts and on C and I equipment. The
In case of two stage alarm systems. if the alarm in the
provision shall be made at C and I equipment
first instance is not acknowledged on C and [
1'01' changing the alelt signal to evacuate signal
equipments. preferably within 60 s. a general evacuate
in any area. either manually or after a pre-
alarm shall sound on all the floors.
determined period, automatically. In deciding
the time delay between alert and general 8.8 Silendng of Fire Alarm
evacuation, consideration shall be given to the
communications that may be needed to a) The audible alarm(s) as specified in 8.7(a) and
control the evacuation. 8.7(b) shall continue to operate until silenced
c) The evacuation signal shall be continuous and manually. The alarm shall not be silenced
automatically. The operation of the silencing
intermittent alert signal shall have' ON' and
'OFF' periods of 1.0 ± 0.5 s each. switch shall automatically result in an audible/
visual signal being given at C and I equipment
d) In large installations, extensive and high rise
until the fire alarm is reset.
buildings, two-stage alarm scheme may be
more desirable to evacuate first the sector/ NOTE--··· Pmvi,i,)11 in this cbll~e ill\~ nol necessary in
case of automat ic resd ~y~tem.
zone where fire exists. other high risk areas
or restricted areas and simultaneollsly alert b) The equipment shall be so designed that
other areas. following the silencing of alarm sounders, in
8.6 Special System the event of subsequent operation of detector
MCP in any other zone. further tire alarm as
a) Here the alarm sounds only in the control specified in 8.7(a) and 8.7(b) shall be given.
centre of the C and I equipment and may also c) Any fault signal as specified in 8.9 which the
have public address facility to alert personnel C and I equipment may be giving shall not

<)
IS 15908 : 2011

prevent a fire alarm being given, if the detector d) A facility shall be provided for deliberate
actuates at the same time or subsequently from isolation of zones/sectors. This facility shall
the other zone. be inside the panel not easily accessible to
people. Whenever isolation is lIsed, this shall
8.9 Fault Signals
be given visible indication.
An immediate rault 'vvarning shall be given by (a) e) Circuits and mechanical design of the panel
visible indicator (amber) on the sectorlzone control shall be such that the operation of one
panel (where provided), and (b) an audible alarm and indicator does not prevent the operation of the
visible indicator (amber) on the C and I equipment in other indicators and the alarm is not inhibited
the conlrol centre. The audible alarm shall be distinct by any defect/failure in the indicator.
from the fire alarm.
f) Each fire/fault indicator shall be clearly
a) The zonal arrangement in the panel shall be labelled with the zone address on a metal label
modular and mere replacement of fault from which the call originates.
module/rely plug in components shall put the g) 'System ON' and 'Standby ON' indicators
alarm system back in operation. shall be provided. Where system test key/
b) Fallit warning shall be given at C and I switch is lockable, indicator shall be provided.
equipment in the event of the following h) Test facilities, shall be provided to test alarm
occurrences: circuit sounder, indicator etc.

I) Failure or disconnection of normal j) The follmving shall be provided:


pO\ver supply. 1) Acknowledge button;
2) Failure or disconnection of standby 2) Where required, alarm cancel indicator,
power supply.
3) Isolationlreset facility; and
3) Failure or disconnecfion of battery
4) Related fuses/protective devices.
charging equipment.
4) Short-circuit or disconnection of the k) Sector/Zonal control panel shall be provided
leads to trigger devices unless the fault with voltages appropriate to the rating of the
conditions reproduces the effect of the interconnected detectors. The voltage drop in
operation of a triggered device. the cable risers shall be taken into account.
S) Removal of any triggered device of the 8.10 Fire Alarm (Sounder)
plug in type or disconnection from its
transmitter or power supply. a) Depending on the floor area and its layout,
external audible fire al<11111 sounders shall be
6) Short-circuit or disconnection of any of
the leads to alarm sounders external to provided to give the required sOllnd level with
a minimum of a pair of sounders in parallel.
the control and indicating equipment but
The number of fire sounders shall be sufficient
if the alarm sounders are connected by
to produce the sOllnd levels as specified in
a ring circuit. disconnection need not be
immediately indicated but shal1 be Annex D and measllred as per IS 9779.
capable of being detected by the routine b) The circuit feeding power from control panel
lest procedure. to these fire alarm devices shall be a ring
circuit. If a ring circuit is not provided, design
7) Rupture or disconnection of any fuse on
provision to give a faull signal on C and I
the operation of any protective devices
equipment in the event of short circuit or
that would prevent a fire alarm being
disconnection shall be made.
given.
8) Failure of a scanning device to 8.U Accessories and Controls
interrogate the detector or zones at the
a) Control and indicating equipment shall be
correct time intervals or failure of any
installed in the control room on ground floor.
monitoring or interrogating system
In the case of industrial premises, separate
within the control equipment, such as to
process control rooms are provided and shall
prevent an alarm being given.
be of the wall mounting/deskliloor standing
9) A faci lity may also be provided for type.
sending fault signal to remote centre. b) The manual controls for switching off/on,
c) It is desirable to have distinct earth fault main/standby power shall not be accessible
indication of the zone wiring. to outsiders.

10
IS J 5908 : 2011

c) All manual controls shall be clearly labelled on completion of the installation. Drawi ngs
to indicate the mode of operation and their shall clearly indicate the position of various
functions (metal label to be used). items of the equipment, junction boxes, sizes
d) The C and I equipment shall have electronic! and routes of all cables and wires and such
electrical relays conforming to relevant Indian other relevant details for maintenance and
Standards and shall have the follo\ving record purposes. If so desired by the user,
facilities: circuit diagrams of the fire alarm system and
its components shall also be supplied. 'nlese
I) A pair of red LED/bulb to indicate origin drawings and operating instructions shaH be
of fire and an amber LED/bulb to kept up-to-date and be available for
indicate the origin of fault; convenient reference and shall be located in
2) A sounder with distinct audible sounds the control room.
for lire and fault alarm; b) The installer shall supply the user with a log
3) Audible signal acknowledge/silence book. The log book shall be maintained for
button and lamp/LED to indicate its recording details. inL'luding causes of all the
operation, whenever necessary; alarms (genuine. practice, test or false), faulls,
4) Voltmeter and ammeter shall be service tests and routine inspections,
provided on main de power circuit; servicing/repairs, etc. as and when done.
5) 'Systems on' standby on indicators, test Periods of disconnection/in-operation shal1
key/button operation indicator and also be shown.
facility to isolate zonal/sector/main
control panel from the rest of the system:
10 INSPECTION. TESTING AND MAINTENANCE
6) Where sector panel is isolated, its signal 10.1 General
shall come on the main control panel and
where zonal panel is isolated the signal Even a well designed and properly installed automatic
shall come on the sector panel; rire alarm system may not be able to render reliable
and trouble-free service unless high standard of
7) Failure of any indicator circuit shall not
maintenance and supervision are ensured during the
prevent the fire alarm from sounding, nor
entire service period of the system. Regular
acknowledgement/silencing ofthe alarm
inspections and scheduled preventive maintenance are
from one zone shall prevent another
critical and shall include all the components of the
almm coming from the other zone on the
system.
same sector:
8) Switch to actuate alarms from C and [ to.2 Initial InstalJation Inspection Tests
equipment to one or more sectorslzones;
10.2.1 After installation, a visual inspection of all the
9) Test facility to check fire alarm/fault
detectors shall be made to make sLlre that they are
circuit, indicators; and
properly sited. Each detector shall be inspected to
10) The facility for indicators to ensure that it is properly mounted and connected.
acknowledge the operation of the
ancillary system (One colour code shall 10.2.2 Restorable heat detectors and restorable
be associated with one ancillary service elements of combination detectors shall be tested by a
and one or more indicator per zone). heat source, Stich as a hair dryer. or a shielded heat
lamp until it responds. making sllre that the sensing
NOT'E -- In high rise/special building like educationaL
inslitutional. assembly, bllsin(~ss, mercantile and hOlels,
element is not damaged. Arter each heat test. the
a handset/two-way speaker with relevant indicatioll detector shall be reset. Precautions shall be taken to
switches shall he provided for voice COllltnllllicuioIl avoid damage of the non-restorable fixed temperature
with difl(~rel1t floors when the circuit is actuated by element of a combination rate or risclfixed temperature
inserting the handset in manual call point sockets (This
detector.
is not a pan of the fire alarm syslem).

e) All zonal/sector control panels and control to.2.3 Non-reseuable fixed temperature heat detectors
and indicating equipment shall be provided which are not to be heat-tested shall be tested
with proper earthing. mechanically or electrically for fire alarm function.

10.2.4 Heat detectors with replaceable fusible alloy


9 INSTRUCTION MANUAL
element shall be tested first by removing the element
a) The record drawings and operating to see whether contact operate properly and then re-
instructions shall be supplied by the installers inserting them in proper position.

II
IS 15908 : 2011

10.2.5 In periodic testing. heat detectors shall be on completion of the installation whether the premises
visually examined for damage or other conditions (such are occupied or not. If the premises are not occupied,
as heavy coats of paints. etc) likely to interface with special precautions shall be taken, if necessary, to
the correct operation. protect the system against damage by dampness or
other causes.
10.2.6 Each smoke detector shall be tested to initiate
an alarm at its installed location with smoke or other 10.4 Maintenance Schedule
approved aerosol which demonstrates that the smoke
can enter the chamber and initiate an alarm. 10.4.1 It is the responsibility of the user of the
equipment to ensure that proper instructions are
to.2.7 In order to ensure that each smoke detector is obtained from the manufacturer/supplier or installer
within its sensitivity range, it shall be tested using regarding the routine attention and test procedures.
either,
10.4.2 The routine t( adopted in individual premises
a) A cal ibrated Lest method; or may vary with the u:-;e of the premises: equipment
b) A manufactllrer's/supplier's approved installed in corrosive or dirty environmental conditions
calibrated sensitivity test instrument; or shall need to be checked more thoroughly and at more
c) Approved control equipment arranged for the frequent intervals than that in clear and dry situations.
purpose: or Care shall be taken that all equipments are properly
d) Other approved calibrated sensitivity rest reinstated after testing. The occupants of the premises
method. shall be notified of any test of the system that may
result in the sounders being operated.
10.2.7.1 Detectors found to have sensitivity outside the
approved range shall be replaced. 10.4.3 Daily Attentioll by User

NOTE - Delt:ctor sensitivity cannot bt:' tested or measured A check shall be made every day to ascertain that,
using any spray/smoke producing device that administers an
unmeasured concentration nf al:rosol/smoke into the detector. a) panel indicates nonnal operation; if not, that
any fault indicated is recorded in the log book
10.2.8 Other types of detectors like !lame detectors, and is receiving urgent attention; and
spark/ember detectors. aspirating type smoke detectors.
b) any fault warning recorded the previolls day
etc, shall be tested for sensitivity in accordance with
has received attention.
the recommendations of the manufacturers and/or the
Indian Standards according to which they are made. 10.4.4 Weekly Attention b.v the User

10.3 Scnicing/PcriodicailVIaintenance The following tests shall be made every week to ensure
that the system is capable of operating under alarm
10.3.1 To ensure that regular and reliable servicing/ conditions:
maintenance of the systems and its components is
carried out: any of the followillg methods shall be a) Once a week, at least one trigger device or
adopted: end of line switch on one zone circuit shall
be operated to test the ability of the control
a) Through an agreement/contract with the and indicating equipment to receive a signal
actual supplier or his authorized dealer who and to sound the alarm and operate other
shall attend to the maintenance/repair, when warning devices. If there is more than one
necessary, promptly. zone on a system having unmonitorecl wiring,
b) Where no such service contract can be entered each unmonitored zone shall be tested each
into for any reason, atleast one qualified week, but without sounding the alarm more
employee or the user with suitable experience then once. For systems having monitored
of electrical equipment shall undergo special wiring and lip to 13 zones, each zone shall be
training to deal with all aspects or basic tested in turn but if there are more than 13
servicing and maintenance. including routine zones, more than one zone may need to be
sensitivity tesls!checks of the detectors. as and tested in any week so that the interval between
when required. tests on one zone does not exceed 13 weeks.
It is preferable that each time a particular zone
10.3.2 For institutional occupancies, such as hospitals,
is tested, a different trigger device is used. An
hotels, old people's homes. etc. the provision shall
entry shall be made in the log book quoting
include a requirement that an engineer shall be on call
the particular trigger device that has been used
at all times and that request over the telephone for
to initiate the test. Ifthe operation of the alarm
emergency service shall be executed promptly. \vithin
sounders and/or the transmission of the alarm
24 h. Serving arrangement shall be made immediately

12
IS 15908 : 2011

signal has been prevented by disconnection, inspection shall also con firm that a clear space
then a further test shall be carried out to prove of at least 750 rnm radius is preserved in all
the final reinstatement to the sounders, and if directions belo"v every detector, that the
permissible, the alarm transmission circuits: detectors are preferably sited and that all
and manual call points remain unobstructed and
b) A visual examination of the battery and conspicuous.
connection shall be made to ensure that they Any defect shall be recorded in the log book and
are in good condition. Action shall be taken reported to the responsible person, and action shall be
to remove any defect, including low taken to correct it.
electrolyte level.
10.4.6 Annual Inspection Tests
Any defect noticed shaH be recorded in the log book
The following checks and test sequence shall be calTieci
cmd reported to the responsible person, and action shall
o LIt:
be taken to correct it.
a) The instruction and test routines detailed in
10.4.5 Quarterlv Inspection and Test hy the User
10.4.5 (a) to 10.4.5 (l}
The following check-list and test sequence shall be b) Operation of at least 20 percent of the
carried out: detectors in an installation shall be checked
a) Entries in the log book since the previous each year and the selection shall be done in
such a way that all the detectors in an
inspection shall be checked and any necessary
action taken. installation shall have been checked once in
every 5 years.
b) Batteries and their connections shall be
examined and tested to ensure that they are c) Each detector shall be checked for correct
in good serviceable condition. operation using specitied test equipment and
method, except non-resettable detectors. The
c) Where applicable, secondary batteries shall
checks to be carried out are specitied in 10.2.2
be examined to ensure that the specific gravity
to 10.2.5 in respect of heat detectors and,
of electrolyte in each cell is correct. Necessary
10.2.6 and 10.2.7 in res pect of smoke
remedial action shall be taken and an
detectors.
appropriate entry made in the log book. Care
shall be taken to ensure that hydrometers, d) Visual inspection shall he made to confirm
vessels, etc, used in the servicing of alkaline that all cable fittings and equipment are
secondary cells are not contaminated by acid secure. undamaged and adequately protected.
and vice-versa. Contamination of electrolyte e) At least once in every three years at the annual
can ruin a cell. inspection, the electrical installation shall be
d) Primary batteries, including reserves, shall be tested. Any deJect shall be recorded in log book
tested to verify that they are satisfactory for a and suitable remedial action shall be taken.
flllther period. /) On completion of the annual inspection. the
e) The alarm function of control and indicating entry shall be made in register in respect of
equipment shall be checked by the operation defects found. After the defects are rectified,
of a trigger device in each zone as described. the entries shall then again be made. And if
The operation of alarm sounders and any link required. detectors shall be replaced by the
to a remote manned centre shall be tested. new one.
Ancillary functions of the control panel shall
10.5 Genual Points About Detectors
also be tested where practicable. All fault
indicators and their circuits shan be checked It is essential (particularly for installations involving
preferable by simulation of fault conditions. life hazard) [0 ensure speci lied range of sensitivity of
The Control and Indicating equipment shall the detec£Ors being installed and Ihal the correct degree
be visually inspected for signs of moisture of sensitivity is maintained. Users shall satisfy
ingress and other deterioration. themselves on this point. Sensitivity range shall be
f) A visual inspection shall be made that checked on equipment as already specified. It is
structural or occupancy changes have not essential to apply frequent sensitivit.y checks and
affected the requirements for the sting of routine tests as prescribed in the code so that the correct
trigger devices (manllal call points, smoke sensitivity levels/degree is maintained during the entire
detectors and heat detectors). The visual service span of the installation (see 10.2.7).

13
IS 15908: 2011

10.6 Cleaning and Maintenance provisions contained in this Code pertaining to annllal
inspection tests. In addition, a visual check of the
Detectors require periodic cleaning to remove dust or
battery charger shall be carried out to ensure perfect
dirt that has accumulated. The frequency of cleaning
serviceability. However, a check shall be made to the
depends upon the type of detector and local ambient
extent of damage. if any, to the cables and other
conditions. In any case. the interval shall not exceed a
components and also the operation of the systems as
period of 3 months. For each detector. the cleaning.
a whole.
checking, operating and sensitivity adjustment shan
be attempted only after consulting manufacturer's 10.8 System Disconnection During Testing
instructions. TIlese instructions shall detail methods
sllch as creating vacuum to remove loose dust and Care shall be taken to minimize the disruption of the
insects, and cleaning heavy greasy deposits, following normal lise of the building by alarm sounding during
partial disassembly or the cleaning or lhe washing of detector testing. If detectors are removed for testing or
detectors to remove contamination. the sensitivity test servicing, replacement detectors shall be provided.
requirements in accordance with the relevant clauses
10.9 Spares
shall be performed.
It may not be necessary to keep spares in premises other
10.7 Tests Following an Alarm or Fire lhan covers for manual call point and fuses and other
All detectors suspected of exposure to a fire essential spares which shall be worked out based on
conditions shall be tested in accordance \vith the installation.

ANNEXA
(Clause 2.1)
LIST OF REFERRED INDIAN STANDARDS

IS No. Title IS No. Title


5 : 2004 Colours for ready mixed paints and up to and including I 100 V (third
enamels UUrh revision) revision)
513: 1994 Cold-rolled low carbon steel sheets 2175 : 1988 Specification for heat sensitive fire
and strips (lourth rerision) detectors for use in automatic fire
694; 1990 PVC insulated cables for working alarm system (second revision)
voltages up to and including I 100 V 9779 : 1981 Sound level meters
(third revisioll) 9968 (Part 1) : Elastomer insulated cables: Part
1255 : 1983 Code of practice for installation and 1988 For working voltages lip to and
maintenance of power cables up to including 1 100 V (first revision)
and including 33 k V rating (second 11360 : 1985 Specification for smoke detectors for
revision) lise in automatic electrical fire alarm
1554 (Part I): PVC insulated (heavy duty) electric system
1988 cables: Part I For working voltages

14
IS 15908 : 2011

ANNEXB
[Clause S.2(k)]
METHOD OF CALCULATION OF STANDBY BATTERY CAPACITY FOR FIRE ALAHM PANEL

H-l VALVE REGULATED LEAD ACID NOTES


I~ATTERIES 1 If C",."I20 shall be 2 '2'
then take D = I. If C"",/20 shall be is
less than /2' then the value (\f D sh(luld be taken as 1.75 or
Apply the following formula: manufacturer's recommenckJ value.
2 In actual practice, C""" is unlikely to ,:orrespond exactly to
Cillill = 1.25 (TI '1+ Dli2) an available hattery capacity and hence the next availahle
capacity size should be lIsed.
where

emill = minimum capacity of the battery when new B-2 OTHER TYPES OF BATTERIES
at the 20 h discharge rate and at 20 D e in
The minimum capacities should be determined in
ampere-hour;
consultation with the manufacturer and should take into
TI total battery standby period, in hour; account (a) standby load. (b) alarm load, (c) any
'I total battery standby load, in ampere; required de-rating to take into account of the higher
current drawn in the alarm condition, and (d) a de-
D de-rating factor j and
rating factor to take into account of battery ageing
T, total battery alarm load, in ampere.
during the anticipated life of the battery.

ANNEXC
[Clause 8.1 (a)]
PERFORMANCE TESTS/REQUIREMENTS FOR CONTROL AND INDICATING EQUIPl\-IENT

C-l GENERAL The test specified under C-2 are type tests only that
neither ensure uniformity of quality in production or
C-1.1 Control and Indicating C and I equipment and
rernove the essentiality of regular inspection and
sector/zonal panels shall be subjected to performance
rnaintenance which are essential for reliable operation.
tests. For the purpose of these tests, standard production
sample or equipment panel shall be taken and tested in C and I equipment shall be appropriately labeled to
minimum configuration arrangement. When the size include model number or code. number of zone, fixed
is large, the tests are to be applied to damage prone or mociular design and address of manufacturer/supplier.
electronic/electric parts of the unit.
C-2 PERFOR1\lANCE
C-1.2 Proper operation of the fire alarm sounder being
critical and essential, tests/performance criteria C-2.1 Control and Indkating Equipment
specified in C-3 shall apply to these devices.
Prior to conducting each of environmental tests given
0l(JI'E - It is the primary funclion of C and I equipment to in C-Z.3, the equipment is preconditioned (see C-2.1.1)
raise an effective alarm in response to the operation of a trigger
and checked for functional lcsts (sec (>2.2) and after
device by automatically switching on alarm sounder ill the
protected premises. by indicating where the trigger device is undergoing each or
the environml~ntal tests given
situated and ill certain cases, by transmitting a fire alarm signal in C-2.3 (after being stabilized). the equipment is tested
to remote locations. Automatic indication of those faults for functional tests (see C-2.2).
directly affecting the primary function of the equipment is
required. It is necessary to specify routine testing scheme and C-2.l.l Pre-conditioning lind Recm'elY
routine test fr,~qllency (time interval hetween tests). It is
understood, however. that testing rOlltine shall vary widdy wilh Before and after each environmental test, the
the type of equipment or system. All technical informatioll temperature of the equipment shall be allowed to
(instruction manual, operational data. wiring and connection
stabilize for at leasl3 h to room ambient between 15 D C
diagrams. provision of special and standard faci lilies and other
relevant information) shall be provided with the C and I and 37°C and relative humidity lying between 45 to
equipment. Compatihility with other components/parts of fire 85 percent. The ambient temperature and humidity
alarm system shall be ensured. shall be substantially constant during precondition,

15
IS 15908 : 2011

during recovery and while a functional test is carried stability has been reached. The equipment shall remain
out. in the chamber during the recovery period (of 3 h) with
cooling off.
C"2.2 Functional Test
C-2.3.4 Vibrations
These tests shall consist of the following operation in
sequence: The equipment mounted on vibrating table in its norma)
operating position and by its normal fastenings shall
a) Operate momentarily a trigger device be subjected to vibrations as given in IS 2175.
(automatic detector/MCP) from any zone to
ensure correct functioning; C-2.4 Inspection and Performance Requirements
NOTE - Mel' = j\!!anual Call Point
After each environmental test, the equipment shall be
b) Operate alarm silencing switch to ensure opened and inspected for faults consequential to that
correct functioning; test. The equipment/panels shall be considered
c) Operate another trigger device (detector/ satisfactory if,
MCP) from another zone to ensure correct a) no damage is revealed during inspection
functioning of C and [ equipment and sector/ which is a result of the faulty design or
zonal panel. in case of big/sectored workmanship; and
equipment;
b) each operation made during the functional
d) Operate reset control to ensure correct tests specified above cause the equipment/
functioning; panel to operate normally.
e) Check the audible and visible warnings given
on disconnection of nonnal lmains) power; C"2.5 Operational Test
and
With C and I equipment in its quiescent condition for
f) Restore the equipment to quiescent condition. 20 h, the cumulative effect of the operation of trigger
C-2.3 Test Environments device shall be applied to each zone in succession, the
audible alarm being silenced between each operation
'rhe equipment shall subjected to the following test where this facility is provided. The equipment shall be
environments. considered satisfactory, if all fire alarms supposed to
C-2.3.1 Dry Hear Environment be initiated by the operation of a trigger device
functions normally and no fault warning is given as a
The equipment/electronic panels shall be introduced result of this test. In successive zone activation process
into the chamber/oven which shall be at the ambient for a control panels having three zones, heat detectors,
temperature of the laboratory (see C"2.1.1) The smoke detectors and MCPs shall be used unless
chamber shall then be adjusted to temperature of 45° otherwise specified. The following two conditions shall
to 50 and 40 to 45 percent relative humidity. The rate
0

be observed:
of temperature rise shall not exceed t °C/min. After
the temperature equilibrium in the chamber has been a) At least one zone shall be activated by type
reached, the equipment shall be exposed to these of trigger device, and
conditions for J 6 h continuously. b) 1'lCP shall be mounted and operated as
intended while heat and smoke detectors shan
C-2.3.2 Damp Heat Em'iro/lment
be mounted (at least once) in hot air tunnel
'The equipment/electronic panels shall be introduced (as per IS 2175) and smoke tunnel (as per
into a chamber which shall be maintained at a IS 113(0) respectively and brought into
temperature of 45 ± 3' C and relative humidity of 90 to
l
operation by essentially slow build up of
95 percent. The equipment shall be exposed to these temperature and smoke concentration. Rate
conditions for! 611 continuously. of rise of temperature shall be 3°e/min and
rate of smoke build up shall be less than
(>2.3.3 Cold Environmcnt
0.2 dB/m as specified in the standard for
The equipment/electronic panel while being at the measuring the response of smoke detectors.
ambient temperature of the laboratory shall be
introduced into the chamber, which shall also be at C-3 FIRE ALARM SOUNDER
that temperature at the start. The temperature shall then
C·3.1 Continuous Normal Operation
be lowered to 0 ± 5°C at the rate not exceeding
I "C/min. The equipment shal1 be exposed to cold The fire ~larm sounder shall be able to operate
environment for a period of 16 h after the temperature continllollsly for a period of at least 50 min without

16
IS 15908 : 2011

damage or malfunction. The sound output (peak value) b) Corrosion - One device shall be sllspended
shall not vary by more than ± 5 dB(A) during this in corrosive atmosphere of S02 as described
operation. in IS 2175.
c) Vihratiof1.), - One device shall be mounted
C-3.2 Sound Level/Characteristics on vibrating lable and shall be subjected to
The sound level (peak vullle) shall be not less than vibrations as per IS 217).
65 dB(A) and not more than 120 dB(A) when measured d) Climaric cOllditions -- One device shall be
at a distance of 1.5 m (measured in audiometric chamber). exposed to dry heat, damp heat and cold
environment as per C-2.3.1 to C-2.3.3.
C-3.3 Environmental Stresses
After each environment stress test, device shall be
Construction and housing of sounder shall be such as inspected for faults consequential to that test and its
to afford protection against fouling by dust and damage sound output measured. Device shall be considered
by other environmental stresses. satisfactory, if no damage is revealed and operates
a) Dust - One device shall be exposed to dust normally withollt output variation greater than
test as described in IS 11360. ± 5dB(A).

ANNEXD
[Clause 8.10 (a)]
TYPICAL OCCUPATIONAL NOISE LEVELS

SI No. Location Decibel LeveL Sl No. Lo('({ ti () fl Decibel Level


(1) (2) (3) 0) (2) (3 )
i) Business occupancies 55 xiv) Tower occupancies 35
ii) Educational occupancies 45 xv) Underground structures and
iii) lndustrialoccupancies 80 windowless buildings 40
iv) Institutional occupancies SO xvi) Vehicles and vessels 50
v) IVIercantile occupancies 40 xvii) Conferences and meeting rooms 40-45
vi) Mechanical rooms 85 xviii) Exhibition halls 63-73
vii) Piers and \vater surrounded structures 40 xix) Commercial kitchens 65-75
viii) Places of assembly 55 xx) Boiler areas 75-85
ix) Residential occupancies 35 xxi} Air conditioning plant 85-90
x) Storage occupancies 30 xxii) Cafeterias 68-78
xi) Thoroughfare and high density urban 7 xxiii) Railway stations 75-85
xii) Thoroughfare and medium density urban 55 xxiv) Shopping malls 70-75
xiii) Thoroughfare and rural and suburban 40 xxv) Sports halls 70-80
._--

17
Bureau of Indian Standards

BIS is a statutory institution established under the Bllreau (~llfldi(ln Standards Act, 1986 to promote
harmonious development of the activities of standardization, marking and quality certification of goods
and attending to connected matters in the country.

Copyright

BIS has the copyright of all its publications. No part of these publications may be reproduced in any form
without the prior permission in \vriting of BIS. This does not preclude the free use, in the course of
implementing the standard, of necessary details, such as symbols and sizes, type or grade designations.
Enquiries relating to copyright be addressed to the Director (Publications), BIS.

Review of Indian Standards

Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed
periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are
needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards
should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue or
"HIS Catalogue' and 'Standards: Nlonthly Additions'.

This Indian Standard has been developed from Doc No.: CED 22 (7587).

Amendments Issued Since Publication

Amend No. Date of Issue Text Affected

BUREAU OF INDIAN STANDARDS


Headquartcl's:
Manak Bhav<ln, 9 Bahadur Shah Zafar Marg, New Delhi 110002
Telephones: 2323 0 U I, 2323 3375,2323 9402 lVebsite: www.bis.org.in

Regional Offices: TelephonE's


Central Manak Bhavan, 9 Bahadur Shah Zafar lVlarg 232,,37617
NEW DELHI 110002 { 2323 3841

Eastern 1114 e.LT. Scheme VIlM, V. 1. P. Road, Kankurgachi 2337 8499" 2337 8561
KOLKATA 700054 { 2337 8626. 23379120

Northern SCO 335-336, Sector 34-A, CH.ANDIGARH 160022 603843


{ 609285

SOllthern C.I.T. Campus, IV Cross Road, CHENNA1600113 2254 1216,2254 1442


{ 22542519, 2254 2315

Western ManakaJaya, 89 MIDe. Maro1, Andheri (East) 2832 9295, 2832 7858
MUivIBAl400093 { 2832 7891, 2832 7892

Branches: AHMEDABAD. BANGALORE. BHOPAL. BHUBANESHWAR. COIMBATORE. DEHRADUN.


FARIDABAD. GHAZlABAD. GUWAHATI. HYDERABAD. JAIPUR. KANPUR. LUCKNOW.
NAGPUR. PARWANOO. PATNA. PUNE. RAJKOT. THIRUVANANTHAPURAM.
VISAKHAPATNAM.
Published by BIS, New Delhi

You might also like