Kilsen Fire Systems - Product Catalogue


Kilsen

KILSEN FIRE SYSTEMS


Product catalogue

www.GE-Security.com
GE Security

GE Security reserves the right to change product specifications without notice.


For the latest product specifications, visit www.GE-Security.com or contact your Sales Representative. 03/2004
Fire Panels
Page 1

Conventional fire alarm panel with 2 zones NKB602

The NKB600 Series microprocessor controlled, conventional fire panels


incorporate state of the art technology, reliability, ease of installation and
maintenance in a basic package. They are compatible with conventional
detectors such as the Kilsen 200, 300, 500 and 700 series devices. The
NKB602 has 2 conventional zones.

Technical Data

Supply Voltage 125/230 VAC @ 50/60 Hz


Mains fuse (Type 5x20 mm) 0.5/0.25 A
Total consumption < 20 W
Nominal Output Voltage 24 VDC
Batteries
Recommended batteries 2 off 1.9 Ah, 12 V
Fuse Rating 1A
Maximum load current < 100 mA
Zone
Maximum Load 72 mA
Maximum number of detectors 20
Ouput voltage 22 to 28 VDC
End-of-line resitance 4k7 Ohm
Manual call point resistance 100 Ohm, 2 W
Outputs
Fire alarm 24 VDC ± 15%, 300 mA z Modern, elegant design
Fault alarm (Fail-to-safe) 24 VDC ± 15%, 100 mA
Environmental z Compact models for 2, 4 and 6 zones
Working temperature +5 to +40°C
Storage temperature -10 to +70°C
z Microprocessor controlled
Relative humidity 95 % (non-condencing) z Multilingual keyboard
Physical Characteristics
Size (w x h x d) 305 x 295 x 100 mm z 2 Access levels
Weight without batteries 3 kg z Differentiation between alarms from manual call points and
automatic detectors in the same zone
z Acoustic indications for fire and fault
Ordering Information z Optical indications for fire and fault by zone
NKB602 Conventional fire alarm panel with 2 zones z Low maintenance
z Compatible with all ranges of KILSEN conventional detectors
Fire Panels
Page 2

Conventional fire alarm panel with 4 zones NKB604

The NKB600 Series microprocessor controlled, conventional fire panels


incorporate state of the art technology, reliability, ease of installation and
maintenance in a basic package. They are compatible with conventional
detectors such as the Kilsen 200, 300, 500 and 700 series devices. The
NKB604 has 4 conventional zones.

Technical Data

Supply Voltage 125/230 VAC @ 50/60 Hz


Mains fuse (Type 5x20 mm) 0.5/0.25 A
Total consumption < 20 W
Nominal Output Voltage 24 VDC
Batteries
Recommended batteries 2 off 1.9 Ah, 12 V
Fuse Rating 1A
Maximum load current < 100 mA
Zone
Maximum Load 72 mA
Maximum number of detectors 20
Ouput voltage 22 to 28 VDC
End-of-line resitance 4k7 Ohm
Manual call point resistance 100 Ohm, 2 W
Outputs
Fire alarm 24 VDC ± 15%, 300 mA z Modern, elegant design
Fault alarm (Fail-to-safe) 24 VDC ± 15%, 100 mA
Environmental z Compact models for 2, 4 and 6 zones
Working temperature +5 to +40°C
Storage temperature -10 to +70°C
z Microprocessor controlled
Relative humidity 95 % (non-condencing) z Multilingual keyboard
Physical Characteristics
Size (w x h x d) 305 x 295 x 100 mm z 2 Access levels
Weight without batteries 3 kg z Differentiation between alarms from manual call points and
automatic detectors in the same zone
z Acoustic indications for fire and fault
Ordering Information z Optical indications for fire and fault by zone
NKB604 Conventional fire alarm panel with 4 zones z Low maintenance
z Compatible with all ranges of KILSEN conventional detectors
Fire Panels
Page 3

Conventional fire alarm panel with 6 zones NKB606

The NKB600 Series microprocessor controlled, conventional fire panels


incorporate state of the art technology, reliability, ease of installation and
maintenance in a basic package. They are compatible with conventional
detectors such as the Kilsen 200, 300, 500 and 700 series devices. The
NKB606 has 6 conventional zones.

Technical Data

Supply Voltage 125/230 VAC @ 50/60 Hz


Mains fuse (Type 5x20 mm) 0.5/0.25 A
Total consumption < 20 W
Nominal Output Voltage 24 VDC
Batteries
Recommended batteries 2 off 1.9 Ah, 12 V
Fuse Rating 1A
Maximum load current < 100 mA
Zone
Maximum Load 72 mA
Maximum number of detectors 20
Ouput voltage 22 to 28 VDC
End-of-line resitance 4k7 Ohm
Manual call point resistance 100 Ohm, 2 W
Outputs
Fire alarm 24 VDC ± 15%, 300 mA z Modern, elegant design
Fault alarm (Fail-to-safe) 24 VDC ± 15%, 100 mA
Environmental z Compact models for 2, 4 and 6 zones
Working temperature +5 to +40°C
Storage temperature -10 to +70°C
z Microprocessor controlled
Relative humidity 95 % (non-condencing) z Multilingual keyboard
Physical Characteristics
Size (w x h x d) 305 x 295 x 100 mm z 2 Access levels
Weight without batteries 3 kg z Differentiation between alarms from manual call points and
automatic detectors in the same zone
z Acoustic indications for fire and fault
Ordering Information z Optical indications for fire and fault by zone
NKB606 Conventional fire alarm panel with 6 zones z Low maintenance
z Compatible with all ranges of KILSEN conventional detectors
Fire Panels
Page 4

Conventional fire panel with 2 fire alarm zones NK702

The NK700 series of conventional fire alarm and extinguishing control panels
is the ideal solution for small to medium-sized installations. Very powerful
and cost-effective, they are extremely simple to install and use due to their
ergonomic, advanced design. The NK704 has 4 conventional zones.

Technical Data

Supply Voltage (+10% - 15%) 230 VAC @ 50 Hz / 110 VAC @ 60 Hz


Batteries
Capacity 2 x 2.3 Ah
Fuse rating 2A
Zone
Maximum load 94 mA
Max. number of detectors per zone 20
Maximum zone resistance 44 ohm
Sounders
Maximum load 250 mA
Delay Selectable 0 - 9 min
Relay Outputs (excluding sounders) 1 A @ 30 VDC
Extinguishing Relay Outputs
Maximum load NA
Fuse rating NA
Auxilliary Output 250 mA
24 VDC Resetable Output
Maximum Load 100 mA z Modern, attractive design
Reset time 3s z Microprocessor-controlled
Environment
Working temperature -5°C to +40°C z From 2 up to 16-zones
Relative humidity (non condencing) 95 %
IP rating IP30
z EN54 compliant with approvals pending
Physical Characteristics z 2 User access levels
Size (mm) 297 (w) x 307 (h) x 105 (d)
Weight (without batteries) 3.6 kg z 2 Monitored sounder outputs
z One-man test capability
z Open-collector output for every zone
Ordering Information z 24 Volt resetable output
NK702 Conventional fire panel with 2 fire alarm zones z External ‘Class Change’ facility
z Alarm output with potential free relay
z Common fault output with potential free relay
z External watchdog
z Active end-of-line support
Fire Panels
Page 5

Conventional fire panel with 4 fire alarm zones NK704

The NK700 series of conventional fire alarm and extinguishing control panels
is the ideal solution for small to medium-sized installations. Very powerful
and cost-effective, they are extremely simple to install and use due to their
ergonomic, advanced design. The NK704 has 4 conventional zones.

Technical Data

Supply Voltage 230 VAC @ 50 Hz (±10%)


Batteries
Capacity 2 x 7.5 Ah
Fuse Rating 1A
Zone
Maximum Load 72 mA
Max number of detectors 20
Sounders
Maximum Load 300 mA
Relay Outputs (excluding Sounders) 2 A @ 250 V
Extinguishing relay outputs
Maximum Load NA
Fuse Rating NA
Open Collector outputs 15 mA
Auxilliary Output
Maximum Load 300 mA
24 V resetable output
Maximum Load 150 mA z Modern, attractive design
Reset time 4 seconds z Microprocessor-controlled
Delays
Sounder Selectable 0.15 & 60 s z From 2 up to 16-zones
Relay module 3 to 180 s
Enviroment
z EN54 compliant with approvals pending
Working Temperature +5°C to +40 °C z 2 User access levels
Relative humidity 95 % (non-condensing)
z 2 Monitored sounder outputs
z One-man test capability
Ordering Information z Open-collector output for every zone

NK704 Conventional fire panel with 4 fire alarm zones


z 24 Volt resetable output
z External ‘Class Change’ facility
z Alarm output with potential free relay
z Common fault output with potential free relay
z External watchdog
z Active end-of-line support
Fire Panels
Page 6

Conventional fire panel with 8 fire alarm zones NK708

The NK700 series of conventional fire alarm and extinguishing control panels
is the ideal solution for small to medium-sized installations. Very powerful
and cost-effective, they are extremely simple to install and use due to their
ergonomic, advanced design. The NK708 has 8 conventional zones.

Technical Data

Supply Voltage (+10% - 15%) 230 / 110 VAC @ 50 / 60 Hz


Batteries
Capacity 2 x 7.5 Ah
Fuse rating 5A
Zone
Maximum load 94 mA
Max. number of detectors per zone 20
Maximum zone resistance 44 ohm
Sounders
Maximum load 250 mA
Delay Selectable 0 - 9 min
Relay Outputs (excluding sounders) 1 A @ 30 VDC
Extinguishing Relay Outputs
Maximum load NA
Fuse rating NA
Auxilliary Output 250 mA
24 VDC Resetable Output
Maximum load 100 mA z Modern, attractive design
Reset time 3s z Microprocessor-controlled
Environment
Working temperature -5°C to +40°C z From 2 up to 16-zones
Relative humidity (non condencing) 95 %
IP rating IP30
z EN54 compliant with approvals pending
Physical Characteristics z 2 User access levels
Size (mm) 420 (w) x 335 (h) x 110 (d)
Weight (without batteries) 6.2 kg z 2 Monitored sounder outputs
z One-man test capability
z Open-collector output for every zone
Ordering Information z 24 Volt resetable output
NK708 Conventional fire panel with 8 fire alarm zones z External ‘Class Change’ facility
z Alarm output with potential free relay
z Common fault output with potential free relay
z External watchdog
z Active end-of-line support
Fire Panels
Page 7

Conventional fire panel with 12 fire alarm zones NK712

The NK700 series of conventional fire alarm and extinguishing control panels
is the ideal solution for small to medium-sized installations. Very powerful
and cost-effective, they are extremely simple to install and use due to their
ergonomic, advanced design. The NK712 has 12 conventional zones.

Technical Data

Supply Voltage (+10% - 15%) 230 VAC @ 50 Hz / 110 VAC @ 60 Hz


Batteries
Capacity 2 x 7.5 Ah
Fuse rating 5A
Zone
Maximum load 94 mA
Max. number of detectors per zone 20
Maximum zone resistance 44 ohm
Sounders
Maximum load 250 mA
Delay Selectable 0 - 9 min
Relay Outputs (excluding sounders) 1 A @ 30 VDC
Extinguishing Relay Outputs
Maximum load NA
Fuse rating NA
Auxilliary Output 250 mA
24 VDC Resetable Output
Maximum Load 100 mA z Modern, attractive design
Reset time 3s z Microprocessor-controlled
Environment
Working temperature -5°C to +40°C z From 2 up to 16-zones
Relative humidity (non condencing) 95 %
IP rating IP30
z EN54 compliant with approvals pending
Physical Characteristics z 2 User access levels
Size (mm) 420 (w) x 335 (h) x 110 (d)
Weight (without batteries) 6.2 kg z 2 Monitored sounder outputs
z One-man test capability
z Open-collector output for every zone
Ordering Information z 24 Volt resetable output
NK712 Conventional fire panel with 12 fire alarm zones z External ‘Class Change’ facility
z Alarm output with potential free relay
z Common fault output with potential free relay
z External watchdog
z Active end-of-line support
Fire Panels
Page 8

Conventional fire panel with 16 fire alarm zones NK716

The NK700 series of conventional fire alarm and extinguishing control panels
is the ideal solution for small to medium-sized installations. Very powerful
and cost-effective, they are extremely simple to install and use due to their
ergonomic, advanced design. The NK716 has 16 conventional zones.

Technical Data

Supply Voltage (+10% - 15%) 230 VAC @ 50 Hz / 110 VAC @ 60 Hz


Batteries
Capacity 2 x 7.5 Ah
Fuse rating 5A
Zone
Maximum load 94 mA
Max. number of detectors per zone 20
Maximum zone resistance 44 ohm
Sounders
Maximum load 250 mA
Delay Selectable 0 - 9 min
Relay Outputs (excluding sounders) 1 A @ 30 VDC
Extinguishing Relay Outputs
Maximum load NA
Fuse rating NA
Auxilliary Output 250 mA
24 VDC Resetable Output
Maximum Load 100 mA z Modern, attractive design
Reset time 3s z Microprocessor-controlled
Environment
Working temperature -5°C to +40°C z From 2 up to 16-zones
Relative humidity (non condencing) 95 %
IP rating IP30
z EN54 compliant with approvals pending
Physical Characteristics z 2 User access levels
Size (mm) 420 (w) x 335 (h) x 110 (d)
Weight (without batteries) 6.2 kg z 2 Monitored sounder outputs
z One-man test capability
z Open-collector output for every zone
Ordering Information z 24 Volt resetable output
NK716 Conventional fire panel with 16 fire alarm zones z External ‘Class Change’ facility
z Alarm output with potential free relay
z Common fault output with potential free relay
z External watchdog
z Active end-of-line support
Extinguishing Panels
Page 9

Conventional extinguishing control panel with 3 zones NK703

The NK703 conventional fire alarm and extinguishing control panels is the
ideal solution for small to medium-sized installations. Very powerful and cost-
effective, they are extremely simple to install and use due to their ergonomic,
advanced design. It has 1 double-knock extinguising area consisting of two
fire zones, and 1 free fire detection zone.

Technical Data

Supply Voltage (+10% - 15%) 230 VAC @ 50 Hz / 110 VAC @ 60 Hz


Batteries
Capacity 2 x 7 Ah
Fuse rating 2A
Zone
Maximum load 94 mA
Max. number of detectors per zone 20
Maximum zone resistance 44 ohm
Sounders
Maximum load 250 mA
Delay Selectable 0 - 9 min
Relay Outputs (excluding sounders) 1 A @ 30 VDC
Extinguishing Relay Outputs
Maximum load 250 mA
Fuse rating 0.3 A
Auxilliary Output 250 mA z Modern, attractive design
24 VDC Resetable Output
Maximum Load 100 mA z Microprocessor controlled
Reset time 3s
Environment
z 3 zone (1 ext. area) and 6 zone (2 ext. areas) available
Working temperature -5°C to +40°C z Automatic extinguishing agent release control
Relative humidity (non condencing) 95 %
IP rating IP30 z EN54 compliant
Physical Characteristics z 2 Access levels
Size (mm) 420 (w) x 335 (h) x 110 (d)
Weight (without batteries) 6.2 kg z Supervised general sounder output
z Supervised extinguishing inputs and outputs
z One-man test capability
Ordering Information
z 24 Volt resetable output
NK703 Conventional extinguishing control panel with 3 zones z External ‘class change’ facility
z Alarm output with potential free relay
z General fault output with potential free relay
z External watchdog
Extinguishing Panels
Page 10

Conventional extinguishing control panel with 5 zones NK706

The NK706 conventional fire alarm and extinguishing control panels is the
ideal solution for small to medium-sized installations. Very powerful and cost-
effective, they are extremely simple to install and use due to their ergonomic,
advanced design. It has 2 double-knock extinguising areas consisting of two
fire zones each, and 2 free fire detection zones.

Technical Data

Supply Voltage (+10% - 15%) 230 VAC @ 50 Hz / 110 VAC @ 60 Hz


Batteries
Capacity 2 x 7 Ah
Fuse rating 2A
Zone
Maximum load 94 mA
Max. number of detectors per zone 20
Maximum zone resistance 44 ohm
Sounders
Maximum load 250 mA
Delay Selectable 0 - 9 min
Relay Outputs (excluding sounders) 1 A @ 30 VDC
Extinguishing Relay Outputs
Maximum load 250 mA
Fuse rating 0.3 A
Auxilliary Output 250 mA z Modern, attractive design
24 VDC Resetable Output
Maximum Load 100 mA z Microprocessor controlled
Reset time 3s
Environment
z 3 zone (1 ext. area) and 6 zone (2 ext. areas) available
Working temperature -5°C to +40°C z Automatic extinguishing agent release control
Relative humidity (non condencing) 95 %
IP rating IP30 z EN54 compliant
Physical Characteristics z 2 Access levels
Size (mm) 420 (w) x 335 (h) x 110 (d)
Weight (without batteries) 6.2 kg z Supervised general sounder output
z Supervised extinguishing inputs and outputs
z One-man test capability
Ordering Information
z 24 Volt resetable output
NK706 Conventional extinguishing control panel with 5 zones z External ‘class change’ facility
z Alarm output with potential free relay
z General fault output with potential free relay
z External watchdog
Expansion Modules
Page 11

Relay module, 4 potential free relays for NK700/Fx400 fire panels RB404

The RB404 relay expander module has voltage-free 4 relays. The unit allows
for a relay for each detection zone or for programming the activation of
different relays depending on the status of one or more zones. It is used on the
GE-Interlogix NK700/FP400 conventional fire panel range.

Technical Data

Relay Rating
Voltage 230 VDC
Current 2A
Delay setting 0 to 9 minutes

Ordering Information

RB404 Relay module, 4 potential free relays for NK700/Fx400 fire panels

z 4 Potential free relays


z Up to 4 modules may be housed inside the fire panel cabinet
z Programable with basic boolen functions
z Power supplied from fire panel bus
z Output delay setting per relay

Relay module, 4 supervised relays for NK700/Fx400 fire panels SB404

The SB404 module has 4 relays that provide 4 of 24 VDC supervised outputs.
These may be configured to power sounders or as standard 24 VDC supervised
outputs for other devices.

Technical Data

Aux. Supply 24 VDC


Delay Setting 0 to 9 minutes

Ordering Information

SB404 Relay module, 4 supervised relays for NK700/Fx400 fire panels

z 4 Supervised relays
z Up to 4 modules may be housed inside the fire panel cabinet
z Programable with basic boolen functions
z Output delay setting per relay
z Configurable for sounder control or as supervised outputs
Fire Panels
Page 12

Analogue addressable fire detection panel - 1 loop KSA701/1

The KSA701 analogue addressable fire alarm control panel is the ideal
solution for small to medium-sized installations. Very powerful and cost-
effective, it is extremely simple to install and use due to its ergonomic,
advanced design. The panel is supplied in an elegant, high-quality,
conveniently sized, heavy-duty enclosure. The cabinet allows for enough space
for the batteries for the system to be housed inside the cabinet. The KSA701 is
fully compatible with the Kilsen 700A series detectors and KAL400 series
accessories.

Technical Data

Supply Voltage 110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -


15%)
Current Consumption 175 mA Quiescent / 241 mA in alarm with no
devices connected
Batteries
Capacity 2 x 12 V - 7 AH (SLA type)
Fuse Rating 3A
Charger Rating 350 mA @ 27.6 VDC @ 20 °C (Temperature
compensated -3 V / °C)
Loop characteristics per loop
Capacity 125 addresses per loop
Maximum Load 400 mA / 26 VDC to 32 VDC z 4 x 40 characters LCD display
Maximum Electrical Characteristics 44 Ohm / 500 nF approximately 2 km of
1.5 mm2 diameter cable
z 20 Display zones
Sounders (reverse polarity supervision) z EN54 compliant with approvals pending
Maximum Load 250 mA each (2 Sounder outputs available) / 18
VDC to 24 VDC z 4 User access levels
Delays 10 seconds to 600 seconds, software adjustable in
z 2 Monitored sounder outputs
10 second intervals
Relay Outputs (potential free) 1 A @ 30 VDC z 2 Programmable voltage free relays
24 V Auxiliary Output
Maximum Load 250 mA @ 18 VDC to 28 VDC z 24 Volt auxiliary output
Environment z I/O programming capabilities with Boolean functions
Working Temperature -5°C to +40 °C
Relative Humidity 0-95% non-condensing z Day/night sensitivity settings
IP Rating IP30
z Coincidence within zones
Physical Characteristics
Size 420 mm (w) x 335 (h) x 110 (d) z Upload/download and graphic PC software
Weight 6.2 kg without batteries / 10.7 kg with 2 x 7 Ah
batteries z Panel networking
z Installation test capability

Ordering Information

KSA701
Fire Panels
Page 13

Analogue addressable fire detection panel - 2 loops KSA701/2

The KSA701 analogue addressable fire alarm control panel is the ideal
solution for small to medium-sized installations. Very powerful and cost-
effective, it is extremely simple to install and use due to its ergonomic,
advanced design. The panel is supplied in an elegant, high-quality,
conveniently sized, heavy-duty enclosure. The cabinet allows for enough space
for the batteries for the system to be housed inside the cabinet. The KSA701 is
fully compatible with the Kilsen 700A series detectors and KAL400 series
accessories.

Technical Data

Supply Voltage 110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -


15%)
Current Consumption 175 mA Quiescent / 241 mA in alarm with no
devices connected
Batteries
Capacity 2 x 12 V - 7 AH (SLA type)
Fuse Rating 3A
Charger Rating 350 mA @ 27.6 VDC @ 20 °C (Temperature
compensated -3 V / °C)
Loop characteristics per loop
Capacity 125 addresses per loop
Maximum Load 400 mA / 26 VDC to 32 VDC z 4 x 40 characters LCD display
Maximum Electrical Characteristics 44 Ohm / 500 nF approximately 2 km of
1.5 mm2 diameter cable
z 20 Display zones
Sounders (reverse polarity supervision) z EN54 compliant with approvals pending
Maximum Load 250 mA each (2 Sounder outputs available) / 18
VDC to 24 VDC z 4 User access levels
Delays 10 seconds to 600 seconds, software adjustable in
z 2 Monitored sounder outputs
10 second intervals
Relay Outputs (potential free) 1 A @ 30 VDC z 2 Programmable voltage free relays
24 V Auxiliary Output
Maximum Load 250 mA @ 18 VDC to 28 VDC z 24 Volt auxiliary output
Environment z I/O programming capabilities with Boolean functions
Working Temperature -5°C to +40 °C
Relative Humidity 0-95% non-condensing z Day/night sensitivity settings
IP Rating IP30
z Coincidence within zones
Physical Characteristics
Size 420 mm (w) x 335 (h) x 110 (d) z Upload/download and graphic PC software
Weight 6.2 kg without batteries / 10.7 kg with 2 x 7 Ah
batteries z Panel networking
z Installation test capability

Ordering Information

KSA702 Analogue addressable fire panel (expandable to 2 loops)


Fire Panels
Page 14

Analogue addressable fire panel (expandable to 5 loops) KSA705

The KSA700 Series analogue addressable fire panels offer leading-edge


technology for the control of analogue addressable fire detection devices.
Their unique user-friendly programming facilitate the ideal control
environment for either simple or complex fire systems.

Technical Data

Supply Voltage 230 VAC @ 50 Hz (+10% -15%)


Current Consumption
(no devices connected) 175 mA Quiest. / 241 mA Alarm
Batteries
Capacity 2 x 12 V - 6 AH (SLA type)
Fuse Rating 4A
Charger (Temp. comp. -3 V / °C) 350 mA @ 27.6 VDC @ 20 °C
Loop characteristics per loop
Capacity 250 addresses
Maximum Load 400 mA / 26 VDC to 32 VDC
Maximum Electrical Characteristics 44 Ohm / 500 nF
Sounders (reverse polarity supervision)
Maximum Load (2 Outputs) 250 mA each / 18 to 24 VDC
Delays (adjustable in 10 s intervals) 10 to 600 seconds
Relay Outputs (potential free) 1 A @ 30 VDC
24 V Auxiliary Output
Maximum Load 800 mA @ 18 to 28 VDC
Environment z 4-line, 40-character LCD display
Working Temperature -5°C to +40 °C z Panel networking capability
Relative Humidity (non-condensing) 0-95%
IP Rating IP41 z Graphic monitoring software
Physical Characteristics
Size 480 mm (w) x 455 (h) x 140 (d)
z Windows based up/download programming software
Weight (without batteries) 13.6 kg z Remote programming and maintenance via modem and TCP/IP
z Repeater facilities
z Powerful auto-configuration functions
Ordering Information
z Simple program options with on-screen menu selection
KSA705 Analogue addressable fire panel (expandable to 5 loops)
z EN54 approvals pending
Fire Panels
Page 15

Analogue addressable fire panel with printer (expandable to 5 loops) KSA705P

The KSA700 Series analogue addressable fire panels offer leading-edge


technology for the control of analogue addressable fire detection devices.
Their unique user-friendly programming facilitate the ideal control
environment for either simple or complex fire systems. The KSA705P offers an
additional internal printer facility.

Technical Data

Supply Voltage 230 VAC @ 50 Hz (+10% -15%)


Current Consumption (with no devices connected) 175 mA Quiescent / 241 mA in alarm
Batteries
Capacity 2 x 12 V - 6 AH (SLA type)
Fuse Rating 4A
Charger Rating (Temperature compensated -3 V / °C) 350 mA @ 27.6 VDC @ 20
°C
Loop characteristics per loop
Capacity 250 addresses
Maximum Load 400 mA / 26 VDC to 32 VDC
Maximum Electrical Characteristics 44 Ohm / 500 nF approximately 2 km of
1.5 mm2 diameter cable
Sounders (reverse polarity supervision)
Maximum Load 250 mA each (2 Sounder outputs available) / 18
VDC to 24 VDC
Delays (software adjustable in 10 second intervals) 10 to 600 seconds z 4-line, 40-character LCD display
Relay Outputs (potential free) 1 A @ 30 VDC
24 V Auxiliary Output z Panel networking capability
Maximum Load 800 mA @ 18 VDC to 28 VDC
Environment
z Graphic monitoring software
Working Temperature -5°C to +40 °C z Windows based up/download programming software
Relative Humidity (non-condensing) 0-95%
IP Rating IP41 z Remote programming and maintenance via modem and TCP/IP
Physical Characteristics z Repeater facilities
Size 480 mm (w) x 455 (h) x 140 (d)
Weight 13.6 kg without batteries / 21.6 kg with 2 x 7 Ah z Powerful auto-configuration functions
batteries
z Simple program options with on-screen menu selection
z EN54 approvals pending

Ordering Information

KSA705P Analogue addressable fire panel with printer (expandable to 5 loops)


Repeater Panels
Page 16

KSA700 Series LCD Repeater KSA701R

The KSA701R repeater allows the user to monitor and control panels
connected to the KSA700 fire panel network via and RS485 link. It displays 20
zones in alarm and fault on the face of the panel, whilst all systemn
messages are displayed on the easy to read, LCD display.

Technical Data

Supply Voltage
AC Version 110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -
15%)
DC Version 24 VDC
Current Consumption 175 mA Quiescent / 200 mA in alarm
Battery Charger (AC Version only)
Capacity 2 x 12 V - 7 AH (SLA type)
Fuse Rating 3A
Charger Rating 350 mA @ 27.6 VDC @ 20 °C (Temperature
compensated -3 V / °C)
Environment
Working Temperature -5°C to +40 °C
Relative Humidity 0-95% non-condensing
IP Rating IP30
Physical Characteristics
Size 420 mm (w) x 335 (h) x 110 (d)
Weight 6.2 kg without batteries / 10.7 kg with 2 x 7 Ah
batteries z Modern, attractive design
Communication Ports RS232 and RS485 standard z 4 x 40 characters LCD display
z 20 Display zones
z 3 User access levels
Ordering Information
z 24 VDC or 230 VAC models available
KSA701R KSA700 Series LCD Repeater
z Panel networking
z Full system control
z EN54 compliant with approvals pending
Expansion Modules
Page 17

GSM Modem for Kilsen Fire Panels MODGSM

The MODGSM modem may be used in KSA701/FP1500, KSA702 and KSA705


fire panel from GE-Interlogix. It is ideal for use as a standard modem for
making and receiving calls from and to the fire panel, but may also be used
for GSM messaging.

Technical Data

GSM Band 900/1800 MHz


Services Data, SMS, Voice and Fax
AT Commands GSM 07.07 and 07.05
Output Power (max)
GSM900 2W
GSM1800 1W
Input Voltage 5 to 32 V
Current @ 5V
Avarage 330 mA
Peak 1.8 A
SIM Interface 3V / 5V
Dimensions (h x w x d) 98 x 54 x 25 mm
Weight 130 g
Environmental Temperature
Storage - 25 °C to + 70 °C
Operating - 20 °C to + 55 °C

z Dual-Band 90/1800 MHz


z Data and SMS services
Ordering Information
z Remote control by AT commands
MODGSM GSM Modem for Kilsen Fire Panels
z Wide input voltage range
Expansion Modules
Page 18

Loop driver module for KSA702/705 control panels KAL701

The KAL701 1 loop expander allows for an easy upgrade to the KSA702 and
KSA705 analalogue addressable fire panels. Each module consist of a simple
plug in card and requires no additional settings or connections for full
functionality. The KAL701 has loop isolators supplied on both drivers and
alows full class-A loop functionality with up to 250 device addresses.

Technical Data

Number of loops 1
Loop characteristics
Capacity 250 addresses
Maximum Load 400 mA / 26 VDC to 32 VDC
Maximum Electrical Characteristics 44 Ohm / 500 nF
Maximum Loop Length 2 km

Ordering Information

KAL701 Loop driver module for KSA702/705 control panels

z Expands the loop capabailities of the KSA702 and KSA705


z Allows for the connection of an additional 250 devices per unit
z Two isolated drivers support full class-A operation
z No hardware configuration required

RS232 communications module for KSA702/5 control panels KAL732

The KAL732 RS232 expander allows for an easy upgrade to the KSA702 and
KSA705 analalogue addressable fire panels. Each module adds an additional
industry standard RS232 communication port to the panel. This port could be
used for communications with a PC or for connections to a printer or modem.

Technical Data

Number of ports 1
Communications medium RS232
Technical specifications
Maximum cable length 15 m
Communication speed 9600 baud
Cable 3 core with screen

Ordering Information

KAL732 RS232 communications module for KSA702/5 control panels

z Industry standard RS232 communications


z No hardware configuration required
Expansion Modules
Page 19

RS485 communications module for KSA702/5 control panels KAL785

The KAL785 RS485 expander allows for an easy upgrade to the KSA702 and
KSA705 analalogue addressable fire panels. Each module adds an additional
industry standard RS485 communication port to the panel. This port could be
used for communications with other network nodes in the fire panel network.

Technical Data

Number of ports 1
Communications medium RS485
Technical specifications
Maximum cable length 1200 m
Communication speed 9600 baud
Cable CAT5 - twisted with screen
Termination resistance 150 Ohm

Ordering Information

KAL785 RS485 communications module for KSA702/5 control panels

z Industry standard RS485 communications


z No hardware configuration required

RS485 expansion kit for KSA701/FP1500 fire panels NC785

The NC785 RS485 expander allows for an easy upgrade to the KSA701/FP1500
series analalogue addressable fire panels. Each module adds an additional
industry standard RS485 communication port to the panel. This port could be
used for communications with other network nodes in the fire panel network.

Technical Data

Number of ports 1
Communications medium RS485
Technical specifications
Maximum cable length 1200 m
Communication speed 9600 baud
Cable CAT5 - twisted with screen
Termination resistance 150 Ohm

Ordering Information

NC785 RS485 expansion kit for KSA701/FP1500 fire panels


z Industry standard RS485 communications
z No hardware configuration required
CO Detection
Page 20

CO detection control panel - 1 Zone KM260/1-ING

CO detection control panel - 2 Zones KM260/2-ING

CO detection control panel - 3 Zones KM260/3-ING

CO detection control panel - 4 Zones KM260/4-ING

CO detection control panel - 5 Zones KM260/5-ING

The KM-Series CO detection system is designed for applications such as


vehicle parking areas where concentrations of CO may accumulate. The range
is compliant with the UNE23.300/84 standard. The KM260/1 is a 1 to 5 zones
control units, using KM170 detectors.

Technical Data

Power Supply
Mains Supply 230 VAC ±10% 50 Hz
Power Consumption 95 W (max)
Zone Configuration
Zone Input Voltage 10-20 VDC/VAC
Sensitiviy 0-300 ppm
Cable Requirement 3 core 1.5 mm²
Cable Length (max) 350 m
No. of Detectors (max) 15
No. of Zones (max) 5
Mechanical
Housing (w x h x d) 275 x 335 x 130 mm
Weight 6 kg

Ordering Information

KM260/1-ING CO detection control panel - 1 Zone


z Designed according to norm 23300/84
KM260/2-ING CO detection control panel - 2 Zones z Miner CDM8001 and CDM8002 standard password
KM260/3-ING CO detection control panel - 3 Zones z LGAI 154.909 and 96013132 standard certification
z Easy to use
KM260/4-ING CO detection control panel - 4 Zones
z Low current consumption
KM260/5-ING CO detection control panel - 5 Zones
z Direct reading of measured levels
z Easy installation
z Extraction relays and alarm outputs per area
z From 1 to 5 areas
z 3-wire system
z Modular design
z Up to 15 detectors per zone
z 10 seconds response time
z Elegant design
z Supervision of all zone lines
z Available in various languages
CO Detection
Page 21

CO detection expansion module KM260-ING

The KM260 is an expansion module for the KM260-Series CO panels from GE-
Interlogix. It allows for an additional monitoring zone to be added to the
control panel, each module allowing for an additional 15 sensors to be
connected.

Technical Data

Power Supply
Mains Supply 230 VAC ±10% 50 Hz
Power Consumption 95 W (max)
Zone Configuration
Zone Input Voltage 10-20 VDC/VAC
Sensitiviy 0-300 ppm
Cable Requirement 3 core 1.5 mm²
Cable Length (max) 350 m
No. of Detectors (max) 15
No. of Zones (max) 1

Ordering Information

KM260-ING CO detection expansion module

z Designed according to norm 23300/84


z Miner CDM8001 and CDM8002 standard password
z LGAI 154.909 and 96013132 standard certification
z Easy to use
z Low current consumption
z Direct reading of measured levels
z Easy installation
z Extraction relays and alarm outputs per area
z 3-wire system
z Up to 15 detectors per zone
z 10 seconds response time
z Supervision of zone line
z Available in various languages
CO Detectors
Page 22

CO detector with base and mounting supplement KM170

The KM170 detector is specifically designed to react to the presence of carbon


monoxide. The design complies with the requirements of the UNE 23-300
standard.

Technical Data

Sensor Type TGS Semicondictor


Useful Life 4 years
Electrical Characteristics
Supply Voltage 10 to 20 VDC
Quiescent Current 35 mA
Reaction Time 10 s
Environmental
Operating Temperature 0 to 40 °C
Protection Index IP205
Mechanical
Size (h x Ø) 81 x 109 mm
Weight 115 g
Material and Colour ABS White
Installation
Number of detectors per zone 15
Covarage 300 m²

z Complies with the requirements of the UNE23-300 standard


Ordering Information
z Microprocessor based
KM170 CO detector with base and mounting supplement z Resolution of up to 5 ppm
z Response time of 10 s
z Low current consumption
z Local status indication of:
z Normal operation
z 50 ppm detected
z Fault
z Useful life of up to 4 years
Detectors
Page 23

Aspiration Smoke Detector ASD20

General

The ASD20 Aspiration Smoke Detector consists of an analysis chamber with


one or two smoke detectors, which can be of conventional or analogue
technology, ionisation or optical. The smoke reaches the analysis chamber
through the installation pipes after having been sucked in by a turbine inside
the ASD20 system. An electronic circuit controls said turbine and the air flow,
giving off a fault signal if the pipes are broken or if the air intake is
obstructed. It has two voltagefree relays for local manoeuvres, one per
detector, and a third system fault relay. When analogical smoke detectors
from the 700A series are used, it is possible to adjust their sensitivity levels
from the fire control unit.

Technical Data

Power supply voltage 24 V


Consumption on standby 250 mA
Consumption 1st alarm 280 mA
Consumption 2nd alarm 320 mA
Fault consumption 220 mA
Working temperature -10 to +60°C z It can operate with conventional or analogue detectors
Storage temperature -10 to +70°C
Relative humidity <95% z Direct connection to the analogue loop
Size 314 x 254 x 115
Weight 4 kg
z Power supply at 24 VDC
Colour RAL9999 z Simple and robust architecture
Material Polycarbonate
Cable input 3 x PG11 z 30 m² coverage per sample intake per sample intake
Terminals Base fastening z 25 mm PVC piping system
Wire cross-section Max. 1.5 mm²
Coverage area per intake 30 m² z Installation of piping in I-shape and U-shape (symmetrical or
Maximum num. of intakes 12 assymmetrical)
DIN 8062-type PVC pipes Ø25 mm
Detectors Conventional/Analogue
z Continuous supervision of pipe flow volume
Aspiration motor type Radial z Local operation by NO NC relay inside the unit alarm 1, alarm 2
Useful lifetime of motor 65 000 hours at 40°C and fault

Ordering Information

ASD20 Aspiration Smoke Detector

59000034 Spare filter cartridge for the ASD20.


Power Supplies
Page 24

Power supply unit with battery charger 0.8A FC251

The FC250 Series is suitable for devices requiring an uninterrupted, regulated


24 VDC power supply. The units include a battery charger outlet and an
optional reset facility. The supply is mounted inside a metal casing which
includes space for two 12 V sealed lead acid batteries.

Technical Data

Mechanical
Dimensions (w x h x d) 215 x 260 x 75 mm
Weight (without batteries) 2.5 kg
Electrical
Operating Voltage 230 VAC 50Hz ±10%
Output Voltage 24 VDC
Batteries 2 x 12 V 2.1 Ah
Environmental
Operating Temperature -10 °C to 40 °C
Storage Temperature -10 °C to 40 °C
Relative Humidity (Non Condencing) 95% max

Ordering Information

FC251 Power supply unit with battery charger 0.8A


z Fuse protection on both the input and the outputs
z Low maintenance
z Batteries may be housed internally
z Various supply ratings available

Power supply unit with battery charger FC252

The FC250 Series is suitable for devices requiring an uninterrupted, regulated


24 VDC power supply. The units include a battery charger outlet and an
optional reset facility. The supply is mounted inside a metal casing which
includes space for two 12 V sealed lead acid batteries.

Technical Data

Mechanical
Dimensions (w x h x d) 290 x 360 x 110 mm
Weight (without batteries) 6.26 kg
Electrical
Operating Voltage 230 VAC 50Hz ±10%
Output Voltage 27.6 VDC
Batteries 2 x 12 V 6 Ah
Environmental
Operating Temperature -10 °C to 40 °C
StorageTemperature -10 °C to 40 °C
Relative Humidity (Non Condencing) 95% max

Ordering Information
z Fuse protection on both the input and the outputs
FC252 Power supply unit with battery charger 1.5A
z Low maintenance
FC253 Power supply unit with battery charger 3A z Batteries may be housed internally
z Various supply ratings available
Fire indicators
Page 25

Illuminated warning sign (No text) 24VDC KR24B

The KR24 is specifically designed as an evacuation warning sign for gas


extinguising areas. The KR24B has no text on the backlit display, and text may
therefor be added as required for the application. Units supplied with text in
various languages are also availble.

Technical Data

Electrical Specifications
Supply Voltage 18 to 27 VDC
Activation Voltage 18 to 27 VDC
Current Consumption 600 mA
Switching Polarity NA
Indicators 24 V 3 W
Environmental Specifications
Working Temperature -10 to 75 °C
Physical Specifications
Number of zones NA
Buzzer output 80 dB
Housing Colour Grey
Display Colour Red
Weight 700 g

Ordering Information
z - Low current consumption
z - Large angle of view
KR24B Illuminated warning sign (No text) 24VDC
z - Optical and acoustic indications selectable
z - Modern and elegant design
Fire Detectors
Page 26

Ionisation detector, conventional KL700

Of outstanding performance, efficiency and durability, the 700 series fire


detectors are the ideal solution for conventional installations. They are
designed specifically for use with the Kilsen NKB600, NK600 and NK700 series
conventional fire panels, but are also compatible with most 3rd party industry
standard conventional control panels.

Technical Data

Operating voltage 18 to 28 VDC


Current consumption
Quiescent at 24 VDC 30 µA
Alarm at 24 VDC < 100 mA
Radio-active source Americium 241
Average activity 0.33 +/-0.04µCi (12.1 +/- 1.5 kBq)
Remote alarm output < 100 mA
Heat specification
Operating temperature -10 to +60 °C
Storage temperature -10 to +70 °C
Humidity (non-condensing) 0 - 95%
IP rating IP205
Number of detectors per zone 20
Recommended protection resistor 300 ohm
Dimensions (h x Ø)
Head 45 mm x 99 mm z Full line consisting of Optical, Ionisation and Heat detectors
Base 24 mm x 103 mm
Approvals* VdS z An ultra-fine grid prevents the ingress of dust and insects in
LPCB smoke detectors
* Check current status with local office
z Attractive, low-profile design
z EN54, LPCB and VdS certification marks (*)

Ordering Information
z Innovative base compensates for uneven surfaces
z Field exchangable optical chamber for ease of maintenance
KL700 Ionisation detector, conventional
Fire Detectors
Page 27

Temperature detector (fixed and rate-of-rise), conventional KL710

Of outstanding performance, efficiency and durability, the 700 series fire


detectors are the ideal solution for conventional installations. They are
designed specifically for use with the Kilsen NKB600, NK600 and NK700 series
conventional fire panels, but are also compatible with most 3rd party industry
standard conventional control panels.

Technical Data

Operating voltage 18 to 28 VDC


Current consumption
Quiescent at 24 VDC 70 µA
Alarm at 24 VDC < 100 mA
Radio-active source
Average activity
Remote alarm output < 100 mA
Heat specification Max. & ROR to EN54p5
Operating temperature -10 to +70 °C
Storage temperature -10 to +80 °C
Humidity (non-condensing) 0 - 95%
IP rating IP205
Number of detectors per zone 20
Recommended protection resistor 300 ohm
Dimensions (h x Ø)
Head 45 mm x 99 mm z Full line consisting of Optical, Ionisation and Heat detectors
Base 24 mm x 103 mm
Approvals* VdS z An ultra-fine grid prevents the ingress of dust and insects in
LPCB smoke detectors
* Check current status with local office
z Attractive, low-profile design
z EN54, LPCB and VdS certification marks (*)

Ordering Information
z Innovative base compensates for uneven surfaces
z Field exchangable optical chamber for ease of maintenance
KL710 Temperature detector (fixed and rate-of-rise), conventional
Fire Detectors
Page 28

Optical detector, conventional (with field exchangeable optical block) KL731

Of outstanding performance, efficiency and durability, the 700 series fire


detectors are the ideal solution for conventional installations. They are
designed specifically for use with the Kilsen NKB600, NK600 and NK700 series
conventional fire panels, but are also compatible with most 3rd party industry
standard conventional control panels.

Technical Data

Operating voltage 9 to 28 VDC


Current consumption
Quiescent at 24 VDC 85 µA
Alarm at 24 VDC < 100 mA
Radio-active source
Average activity
Remote alarm output < 100 mA
Heat specification
Operating temperature -10 to +70 °C
Storage temperature -10 to +70 °C
Humidity (non-condensing) 0 - 95%
IP rating IP42
Number of detectors per zone 20
Recommended protection resistor 300 ohm
Dimensions (h x Ø)
Head 45 mm x 99 mm z Full line consisting of Optical, Ionisation and Heat detectors
Base 24 mm x 103 mm
Approvals* EN54 z An ultra-fine grid prevents the ingress of dust and insects in
* smoke detectors
* Check current status with local office
z Attractive, low-profile design
z EN54, LPCB and VdS certification marks (*)

Ordering Information
z Innovative base compensates for uneven surfaces
z Field exchangable optical chamber for ease of maintenance
KL731 Optical detector, conventional (with field exchangeable optical block)
Test and Service Equipment
Page 29

KL731/DP331I Calibration Tool KCT731

The KCT731 is a calibration tool to recalibrate the KL731/DP331I conventional


detectors after replacement of the field exchangeable optical block.

Technical Data

Supply 2 x 9 V batteries

Ordering Information

KCT731 KL731/DP331I Calibration Tool

z Easy to use
z Simple “go/no-go” function
z Battery operated
Fire Detectors
Page 30

Analogue addressable ionisation sensor KL700A

The KL700A Series uses a microprocessor for measurement and


communication. An enhanced protocol ensures the overall integrity and error
free operation of the fire system, without compromising speed. All sensors are
compatible with a standard base that makes them easily interchangeable and
that supports the connection of a remote indicator.

Technical Data

Operating voltage 22 - 38 VDC


Current consumption
Quiescent @ 38 VDC 200 µA
In Alarm less than 11 mA
Alarm indication (Dual LED) White OFF - Red ON
Remote Alarm Output Available
Environment
Storage Temperature -10 °C to +70 °C
Operating Temperature -10 °C to +60 °C
Humidity (non-condensing) 0-95%
IP rating IP205
Radioactive Source 0.33 ± 0.04 µCi Am 241
Dimensions (h x Ø) 45 mm x 99 mm

z Remote signalling capabilities


Ordering Information
z Easy soft addressing (1-125)
KL700A Analogue addressable ionisation sensor
z SMD technology
z Reliable communication protocol
z Full diagnostic self testing
z Full range: Ionisation, Optical and Heat and Duel sensors
(optical/heat)
z Full range of supporting I/O units and accessories
z EN54 Approved
Fire Detectors
Page 31

Analogue addressable temperature sensor KL710A

The KL700A Series uses a microprocessor for measurement and


communication. An enhanced protocol ensures the overall integrity and error
free operation of the fire system, without compromising speed. All sensors are
compatible with a standard base that makes them easily interchangeable and
that supports the connection of a remote indicator.

Technical Data

Operating voltage 22 - 38 VDC


Current consumption
Quiescent @ 38 VDC 250 µA
In Alarm less than 11 mA
Alarm indication (Dual LED) White OFF - Red ON
Remote Alarm Output Available
Environment
Storage Temperature -10 °C to +80 °C
Operating Temperature -10 °C to +70 °C
Humidity (non-condensing) 0-95%
IP rating IP205
Radioactive Source NA
Dimensions (h x Ø) 45 mm x 99 mm

z Remote signalling capabilities


Ordering Information
z Fixed and Rate-of-Rise heat detectors
KL710A Analogue addressable temperature sensor
z Easy soft addressing (1-125)
z SMD technology
z Reliable communication protocol
z Full diagnostic self testing
z Full range: Ionisation, Optical and Heat and Duel sensors
(optical/heat)
z Full range of supporting I/O units and accessories
z EN54 Approved
Fire Detectors
Page 32

Analogue addressable optical sensor (with field exchangeable chamber) KL731A

The KL700A Series uses a microprocessor for measurement and


communication. An enhanced protocol ensures the overall integrity and error
free operation of the fire system, without compromising speed. All sensors are
compatible with a standard base that makes them easily interchangeable and
that supports the connection of a remote indicator.

Technical Data

Operating voltage 22 - 38 VDC


Current consumption
Quiescent @ 38 VDC 350 µA
In Alarm less than 11 mA
Alarm indication (Dual LED) Red
Remote Alarm Output Available
Environment
Storage Temperature -10 °C to +70 °C
Operating Temperature -10 °C to +60 °C
Humidity (non-condensing) 0-95%
IP rating IP205
Radioactive Source NA
Dimensions (h x Ø) 45 mm x 99 mm

z Remote signalling capabilities


Ordering Information
z Field exchangeable optical chamber
KL731A Analogue addressable optical sensor (with field exchangeable chamber)
z Easy soft addressing (1-125)
z SMD technology
z Reliable communication protocol
z Full diagnostic self testing
z Full range: Ionisation, Optical and Heat and Duel sensors
(optical/heat)
z Full range of supporting I/O units and accessories
z EN54 Approved
z Black Colour
Fire Detectors
Page 33

Analogue addressable dual (optical and thermal) sensor KL735A

The KL700A Series uses a microprocessor for measurement and


communication. An enhanced protocol ensures the overall integrity and error
free operation of the fire system, without compromising speed. All sensors are
compatible with a standard base that makes them easily interchangeable and
that supports the connection of a remote indicator.

Technical Data

Operating voltage 22 - 38 VDC


Current consumption
Quiescent @ 38 VDC 350 µA
In Alarm less than 5 mA
Alarm indication (Dual LED) Red
Remote Alarm Output Available
Environment
Storage Temperature -10 °C to +70 °C
Operating Temperature -10 °C to +70 °C
Humidity (non-condensing) 0-95%
IP rating IP42
Radioactive Source NA
Dimensions (h x Ø) 51 mm x 99 mm

z Remote signalling capabilities


Ordering Information
z Fixed and Rate-of-Rise heat detectors
KL735A Analogue addressable dual (optical and thermal) sensor
z Easy soft addressing (1-125)
z SMD technology
z Reliable communication protocol
z Full diagnostic self testing
z Full range: Ionisation, Optical and Heat and Duel sensors
(optical/heat)
z Full range of supporting I/O units and accessories
z EN54 Approved
Accessories
Page 34

Fire sensor programmer PG700

The PG700 is a handheld device programmer and tester for the


KL700A/Dx1500 series detectors. It is battery operated and allows the installer
to perform installation tasks (such as device addressing) and maintenance
tasks (such as device clibration) in the field without external assistance.

Technical Data

Supply 2 x 9 V batteries

Ordering Information

PG700 Fire sensor programmer

z Easy to use
z Battery operated
z 4 User selectable programs
z - Device analogue value
z - Change Device Address
z - Sequential device addressing
z - KL731A Calibration
Bases
Page 35

Fire Detector base for KL300 series devices KZ300

The KZ300 base is designed to be used with the KL300 series detectors from
Kilsen.

Technical Data

Dimensions
Diameter 107 mm
Height 22 mm

Ordering Information

KZ300 Fire Detector base for KL300 series devices

z Polarity sensitive
z Remote indicator contact available.

Surface mount supplement for KL300 detectors S300

The S300 is a base accessory designed for use with the KZ300 detector base.
It allows for a surface mount conduit and cable to enter the base from the
side. The KZ300 base fits on top of this accessory.

Technical Data

Dimensions
Diameter 107 mm
Height 25 mm

Ordering Information

S300 Surface mount supplement for KL300 detectors

z Surface mount accessory for KZ300


Bases
Page 36

Surface mount accessory for KZ700/DB304 and KZ700 series bases S700

The S700 is a base accessory designed for use with the KZ700 series detector
bases. It allows for a surface mount conduit and cable to enter the base from
the side. The KZ700 series base fits on top of this accessory.

Technical Data

Dimensions
Diameter 95 mm
Height 30 mm

Ordering Information

S700 Surface mount accessory for KZ700/DB304 and KZ700 series bases

z Surface mount accessory for KZ700 series bases

Conventional fire detector base with diode KZ705D

The KZ705D is a 5 contact universal detector base for use with the
KL700/Dx300 series detectors from GE-Interlogix. In addition to the normal
base and remote indication connectors, the KZ705D also has an additional
earth terminal connector to allow for easy terminations of a possible cable
screen. The built in diode is specifically targeted at systems using active end-
of-line devices.

Technical Data

Dimensions (Ø x h) 100 x 29 mm
Operating Voltage
Current Consumption
Isolation Current
Isolation Resistance
Sounder Frequency
Sound Output
@ 3 mA
@ 5 mA
Environmental Characteristics
Operating Temperature -10 to 70 °C
Storage Temperature -10 to 70 °C
Relative Humidity (max) 95 % (non-cond.)

z Polarity sensitive
z Universal base for conventional detectors
Ordering Information
z Additional earth terminal available
KZ705D Conventional fire detector base with diode
z Remote indicator contact available
z Built in diode for active end-of-line systems
Bases
Page 37

Universal fire detector base (for KL700 and KL700A series detectors) KZ700

The KZ700 is a 4 contact universal detecor base for use with the KL700 and
KL700A series detectors from Kilsen. It has the ability to compensate for
uneven mounting surfaces.

Technical Data

Dimensions
Diameter 104 mm
Height 24 mm

Ordering Information

KZ700 Universal fire detector base (for KL700 and KL700A series detectors)

z Polarity sensitive
z Universal base fits conventional and analogue detectors
z Compensates for uneven surfaces
z Remote indicator contact available
z EN54 approved
z Black Colour

Universal fire detector base with earth connection KZ705

The KZ705 is a 5 contact universal detector base for use with the
KL700/Dx300 and KL700A/Dx1500 series detectors from GE-Interlogix. In
addition to the normal base and remote indication connectors, the KZ705 also
has an additional earth terminal connector to allow for easy terminations of a
possible cable screen.

Technical Data

Dimensions (Ø x h) 100 x 29 mm
Operating Voltage
Current Consumption
Isolation Current
Isolation Resistance
Sounder Frequency
Sound Output
@ 3 mA
@ 5 mA
Environmental Characteristics
Operating Temperature -10 to 70 °C
Storage Temperature -10 to 70 °C
Relative Humidity (max) 95 % (non-cond.)

z Polarity sensitive
Ordering Information
z Universal base fits conventional and analogue detectors
KZ705 Universal fire detector base with earth connection
z Additional earth terminal available
z Remote indicator contact available
Bases
Page 38

Active end-of-line device for use with FP400/KL700 fire panels EOL-ACT

The EOL-ACT is designed for use with the NK700/FP400 fire panels from GE-
Interlogix. It is an active end-of-line device to allow the monitoring of a
conventional zone through a diode base (such as the KZ705D).

Ordering Information

EOL-ACT Active end-of-line device for use with FP400/KL700 fire panels

z Small
z Easy to install
Bases
Page 39

Conventional fire detector base with relay KZ705R

The KZ705R is a 5 contact detector base for use with the KL731/DP331I
detectors from GE-Interlogix. In addition to the normal base and remote
indication connectors, the KZ705R also has an additional earth terminal
connector to allow for easy terminations of a possible cable screen. A built in
12 V relay makes it ideal for use on low voltage intrusion systems.

Technical Data

Dimensions (Ø x h) 100 x 29 mm
Operating Voltage 12 V ± 10%
Current Consumption 12 µA
Isolation Current
Isolation Resistance
Sounder Frequency
Sound Output
@ 3 mA
@ 5 mA
Environmental Characteristics
Operating Temperature -10 to 70 °C
Storage Temperature -10 to 70 °C
Relative Humidity (max) 95 % (non-cond.)

z Polarity sensitive
Ordering Information
z 12 V relay for 4 wire systems
KZ705R Conventional fire detector base with relay
z Additional earth terminal available
z Remote indicator contact available

Analogue fire detector base with isolator KZ705I

The KZ705I is a detector base with built in isolator for use with the
KL700A/Dx1500 series detectors from GE-Interlogix. The isolator protects the
loop from short circuit conditions. A LED on the side of the base indicates the
status of the isolator.

Technical Data

Dimensions (Ø x h) 100 x 29 mm
Operating Voltage 17 - 34 V
Current Consumption 50 µA
Isolation Current 6 mA
Isolation Resistance 140 MOhm
Sounder Frequency
Sound Output
@ 3 mA
@ 5 mA
Environmental Characteristics
Operating Temperature -10 to 70 °C
Storage Temperature -10 to 70 °C
Relative Humidity (max) 95 % (non-cond.)

Ordering Information
z Polarity sensitive
KZ705I Analogue fire detector base with isolator z Universal base for analogue detectors
z Additional earth terminal available
z Remote indicator contact available
z Built in isolator
Bases
Page 40

Analogue fire detector base with sounder KZ705AS

The KZ705AS is a detector base with built in analogue addressable sounder


for use with the KL700A/Dx1500 series detectors from GE-Interlogix. The
sounder has its own address on the fire panel loop and works independent of
the detector. It is fully controlled from the fire panel.

Technical Data

Dimensions (Ø x h) 120 x 58 mm
Operating Voltage 22 - 38 V
Current Consumption 300 µA Quiescent
Isolation Current
Isolation Resistance
Sounder Frequency 1 KHz
Sound Output
@ 3 mA 85 dBA
@ 5 mA 95 dBA
Environmental Characteristics
Operating Temperature -10 to 70 °C
Storage Temperature -10 to 70 °C
Relative Humidity (max) 95 % (non-cond.)
IP Rating IP21c

Ordering Information
z Polarity sensitive
z Universal base for analogue detectors
KZ705AS Analogue fire detector base with sounder
z Additional earth terminal available
z Remote indicator contact available
z Built in sounder
z Up to 90 dBA sound output
z Low current consumption
Bases
Page 41

Analogue fire detector base with isolator and sounder KZ705IAS

The KZ705IAS is a detector base with built in analogue addressable sounder


and isolator for use with the KL700A/Dx1500 series detectors from GE-
Interlogix. The sounder has its own address on the fire panel loop and works
independent of the detector. It is fully controlled from the fire panel. The
isolator protects the loop from short circuit conditions.

Technical Data

Dimensions (Ø x h) 120 x 58 mm
Operating Voltage 22 - 38 V
Current Consumption 350 µA Quiescent
Isolation Current 6 mA
Isolation Resistance 140 MOhm
Sounder Frequency 1 KHz
Sound Output
@ 3 mA 85 dBA
@ 5 mA 95 dBA
Environmental Characteristics
Operating Temperature -10 to 70 °C
Storage Temperature -10 to 70 °C
Relative Humidity (max) 95 % (non-cond.)
IP Rating IP21c

z Polarity sensitive
Ordering Information z Universal base for analogue detectors
z Additional earth terminal available
KZ705IAS Analogue fire detector base with isolator and sounder
z Remote indicator contact available
z Built in sounder
z Up to 90 dBA sound output
z Low current consumption
z Built in isolator
I/O Modules
Page 42

Conventional Zone Monitor Unit - 1 Zone KAL410

Allows the connection of one conventional zone to the analogue fire system
loop. This zone is constantly monitored. Up to 20 conventional devices may be
connected to this zone.

Technical Data

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 90 µA
Quiescent @ 35 V 105 µA
Alarm < 3 mA
Aux. Supply (24V DC) Quiescent 200 µA + equip
Aux. Supply (24V DC) Alarm < 85 mA
End-of-line resistor 4.7 kOhm
Relay contact rating NA
Environmental
Storage temperature -10 to +50°C
Operating temperature -10 to +70°C
Relative humidity (non-condensing) 0-95 %
Dimensions (l x w x h) 117 x 80 x 44 mm

Ordering Information
z Easy numeric addressing
KAL410 Conventional Zone Monitor Unit - 1 Zone
z Continuous supervision of the conventional zones
z Surface mount
z Local alarm indication
z Externally powered
z Aesthetically pleasing
z Part of a family of I/O modules consisting of:
z - Conventional Zone Monitors
z - Digital Input Modules
z - Extinguishing Control Modules
z - Isolator Modules
z - Manual Call Points
z - Output Units
z - Retention Units
z - Supervised Output Units for sounder control
I/O Modules
Page 43

Conventional Zone Monitor Unit - 4 Zones KAL414/4

Allows the connection of four conventional zones to the analogue fire system
loop. These zones are constantly monitored. Up to 20 conventional devices
may be connected to any zone.

Technical Data

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 110 µA
Quiescent @ 35 V 135 µA
Alarm < 5 mA
Aux. Supply (24V DC) Quiescent 200 µA + equip
Aux. Supply (24V DC) Alarm < 360 mA
End-of-line resistor 4.7 kOhm
Relay contact rating NA
Environmental
Storage temperature -10 to +50°C
Operating temperature -10 to +70°C
Relative humidity (non-condensing) 0-95 %
Dimensions (l x w x h) 163 x 107 x 36 mm

Ordering Information
z Easy numeric addressing
KAL414/4 Conventional Zone Monitor Unit - 4 Zones
z Continuous supervision of the conventional zones
z Surface mount
z Local alarm indication
z Externally powered
z Aesthetically pleasing
z Part of a family of I/O modules consisting of:
z - Conventional Zone Monitors
z - Digital Input Modules
z - Extinguishing Control Modules
z - Isolator Modules
z - Manual Call Points
z - Output Units
z - Retention Units
z - Supervised Output Units for sounder control
I/O Modules
Page 44

Extinguishing Control Module KAL426

The 400 Series modules consists of a complete range of interfaces developed


for input/output control in the KSA700/FP1500 analogue fire systems from GE
Interlogix. The KAL426 allows for the connection and control of one
extinguishing area to the addressable fire panel loop.

Technical Data

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 110 µA
Quiescent @ 35 V 210 µA
Alarm < 10 mA
Aux. Supply (24V DC) Quiescent 120 mA
Aux. Supply (24V DC) Alarm <1A
End-of-line resistor 4.7 kOhm
Relay contact rating 2½ A
Environmental
Storage temperature -10 to +50°C
Operating temperature -10 to +70°C
Relative humidity (non-condensing) 0-95 %
Dimensions (l x w x h) 163 x 107 x 36 mm

Ordering Information
z Aesthetically pleasing
z Easy numeric addressing
KAL426 Extinguishing Control Module
z Externally powered
PK10TD Extinguishing RELEASE MCP with protective cover (Spanish Version)
z Normally Open / Normally Closed operation for I/O
PK10TP Extinguishing INHIBIT MCP with protective cover (Spanish Version)
z Surface mount
KR24 Illuminated extinguishing waring sign (Spanish version) 24VDC
z Wide range of I/O modules consiting of:
SK07 Low consumption multi-tone alarm siren z - Conventional Zone Monitors
z - Digital Input Modules
z - Extinguishing Control Modules
z - Isolator Modules
z - Manual Call Points
z - Output Units
z - Retention Units
z - Supervised Output Units for sounder control
I/O Modules
Page 45

Relay Module - 1 Relay KAL430

Provides for one potential free relay output for the fire system loop. Each relay
allows for COMMON, NORMALLY OPEN and NORMALLY CLOSED contacts. The
output may be used to activate ventilation controls, warning signs, activation
of other alarm devices etc. during fire situations.

Technical Data

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 70 µA
Quiescent @ 35 V 100 µA
Alarm < 3.5 mA
Aux. Supply (24V DC) Quiescent 22 mA
Aux. Supply (24V DC) Alarm < 50 mA
End-of-line resistor NA
Relay contact rating 2½A @ 250 VAC
Environmental
Storage temperature -10 to +50°C
Operating temperature -10 to +70°C
Relative humidity (non-condensing) 0-95 %
Dimensions (l x w x h) 117 x 80 x 44 mm

Ordering Information
z Easy numeric addressing
z Externally powered
KAL430 Relay Module - 1 Relay
z Normally open / normally closed operation for I/O
z Surface mount
z Aesthetically pleasing
z Local status indication
z Part of a family of I/O modules consiting of:
z - Conventional Zone Monitors
z - Digital Input Modules
z - Extinguishing Control Modules
z - Isolator Modules
z - Manual Call Points
z - Output Units
z - Retention Units
z - Supervised Output Units for sounder control
I/O Modules
Page 46

Supervised Relay Module KAL440

Allows for the supervision of a single, 24 Volt powered output contact on the
fire system loop. This unit may be used to control for e.g. sounders in case of
fire conditions, but may also be used to switch any output considered crucial
enough to have the cable integrity between the unit and the switch point
monitored.

Technical Data

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 110 µA
Quiescent @ 35 V 135 µA
Alarm < 3.6 mA
Aux. Supply (24V DC) Quiescent 23 mA
Aux. Supply (24V DC) Alarm 23 mA + equip
End-of-line resistor 4.7 kOhm
Relay contact rating 1¼ A @ 250 VAC
Environmental
Storage temperature -10 to +50°C
Operating temperature -10 to +70°C
Relative humidity (non-condensing) 0-95 %
Dimensions (l x w x h) 117 x 80 x 44 mm

z Easy numeric addressing


Ordering Information z Externally powered
z Normally open / normally closed operation for I/O
KAL440 Supervised Relay Module
z Surface mount
z Aesthetically pleasing
z Local status indication
z Part of a family of I/O modules consiting of:
z - Conventional Zone Monitors
z - Digital Input Modules
z - Extinguishing Control Modules
z - Isolator Modules
z - Manual Call Points
z - Output Units
z - Retention Units
z - Supervised Output Units for sounder control
I/O Modules
Page 47

Relay Module - 4 Relays KAL434/4

Provides for four potential free relay outputs for the fire system loop. Each
relay allows for COMMON, NORMALLY OPEN and NORMALLY CLOSED contacts.
The outputs may be used to activate ventilation controls, warning signs,
activation of other alarm devices etc. during fire situations.

Technical Data

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 110 µA
Quiescent @ 35 V 135 µA
Alarm 10 mA
Aux. Supply (24V DC) Quiescent 100 µA
Aux. Supply (24V DC) Alarm 10 mA
End-of-line resistor NA
Relay contact rating 2½A @ 250 VAC
Environmental
Storage temperature -10 to +50°C
Operating temperature -10 to +70°C
Relative humidity (non-condensing) 0-95 %
Dimensions (l x w x h) 163 x 107 x 36 mm

Ordering Information
z Easy numeric addressing
z Externally powered
KAL434/4 Relay Module - 4 Relays
z Normally open / normally closed operation for I/O
z Surface mount
z Aesthetically pleasing
z Local status indication
z Part of a family of I/O modules consiting of:
z - Conventional Zone Monitors
z - Digital Input Modules
z - Extinguishing Control Modules
z - Isolator Modules
z - Manual Call Points
z - Output Units
z - Retention Units
z - Supervised Output Units for sounder control
I/O Modules
Page 48

Addressable Manual Call Point KAL450

The 400 Series modules consists of a complete range of interfaces developed


for input/output control in the KSA700/FP1500 analogue fire systems from GE
Interlogix. The KAL450 is an addressable manual call point for manual fire
activation.

Technical Data

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 90 µA
Quiescent @ 35 V 120 µA
Alarm < 3.5 mA
Aux. Supply (24V DC) Quiescent NA
Aux. Supply (24V DC) Alarm NA
End-of-line resistor NA
Relay contact rating NA
Environmental
Storage temperature -10 to +50°C
Operating temperature -10 to +70°C
Relative humidity (non-condensing) 0-95 %
Dimensions (l x w x h) 87 x 87 x 20

Ordering Information
z Easy numeric addressing
z Loop powered
KAL450 Addressable Manual Call Point
z Local test facility
KAL450C KAL450 spare glasses (10-pack) (DM711)
z Surface or flush mount
KAL450E KAL450 accessory for flush mounting
KAL450S KAL450 Surface mount back box (DM787) z Aesthetically pleasing
KAL450T KAL450 Anti-tamper plastic cover (DM782)
z Local status indication
DM800 Resettable element for MCP DM700/KAL450 z Part of a family of I/O modules consiting of:
z - Conventional Zone Monitors
z - Digital Input Modules
z - Extinguishing Control Modules
z - Isolator Modules
z - Manual Call Points
z - Output Units
z - Retention Units
z - Supervised Output Units for sounder control
Accessories
Page 49

Spare glasses (10-pack) DM715

DM715 spare glasses (10-pack) - replacement glass for manual call point

Ordering Information

DM715 Spare glasses (10-pack)

z prEN54 pt11 standard glass

KAL450 accessory for flush mounting KAL450E

The KAL450E accessory for flush mounting allows for the KAL450 and PK10
manual call points to be flush mounted.
z Allows for the KAL450 and PK10 to be flush mounted

Ordering Information

KAL450E KAL450 accessory for flush mounting


Accessories
Page 50

Surface mount back box DM787

The DM787 is an accessory for surface mounting / surface mout back box for
the KAL450 and PK10C manual callpoints. The KAL450C is availble in RED.

Ordering Information

DM787 Surface mount back box

z Surface mount back box for MCP - RED

Anti-tamper plastic cover DM782

The DM782 anti-tamper plastic cover is a protection cover for the KAL450 and
PK10 manual call points. It prevents accidental activation of the alarm by
enforcing a two step action i.e. lifting the cover, then activating the alarm.

Ordering Information

DM782 Anti-tamper plastic cover

z Unobtrusive
z Transparent
z Protects from accidental alarm activation
I/O Modules
Page 51

Digital Input Module KAL460

Provides a remote input to the fire system loop. The input is constantly
monitored and its status communicated to the fire control panel. The input
may be activated by closing or opening a potential free contact, depending on
the module configuration.

This module may be used to monitor any contact by showing its status
through the fire control panel e.g. the monitoring of pressure equipment and
closure fire break doors.

Technical Data

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 110 µA
Quiescent @ 35 V 135 µA
Alarm < 10 mA
Aux. Supply (24V DC) Quiescent 200 µA
Aux. Supply (24V DC) Alarm < 50 mA
End-of-line resistor NA
Relay contact rating NA
Environmental
Storage temperature -10 to +50°C
Operating temperature -10 to +70°C z Easy numeric addressing
Relative humidity (non-condensing) 0-95 %
Dimensions (l x w x h) 117 x 80 x 44 mm
z Externally powered
z Normally open / normally closed operation for I/O
z Surface mount
Ordering Information z Aesthetically pleasing
KAL460 Digital Input Module z Local status indication
z Part of a family of I/O modules consiting of:
z - Conventional Zone Monitors
z - Digital Input Modules
z - Extinguishing Control Modules
z - Isolator Modules
z - Manual Call Points
z - Output Units
z - Retention Units
z - Supervised Output Units for sounder control
I/O Modules
Page 52

Isolator Module KAL470

The 400 series modules consist of a complete range of interfaces developed


for input/output control in the KSA700/FP1500 analogue fire systems from GE
Interlogix. The KAL470 is an isolator module in this series that isolates the
faulty zone on a fire panel loop during short circuit conditions. The KAL470
does not use an address on the loop.

Technical Data

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 110 µA
Quiescent @ 35 V 135 µA
Alarm 10 mA
Aux. Supply (24V DC) Quiescent NA
Aux. Supply (24V DC) Alarm NA
End-of-line resistor NA
Relay contact rating NA
Environmental
Storage temperature -10 to +50°C
Operating temperature -10 to +50°C
Relative humidity (non-condensing) 0-95 %
Dimensions (l x w x h) 75 x 45 x 28 mm

z Requires no device address


Ordering Information z Automatic reset
z Local status indication
KAL470 Isolator Module
z Surface mount
z Part of a family of I/O modules consiting of:
z - Conventional Zone Monitors
z - Digital Input Modules
z - Extinguishing Control Modules
z - Manual Call Points
z - Output Units
z - Retention Units
z - Supervised Output Units for sounder control
I/O Modules
Page 53

Retention Module - 1 Input / 1 Output KAL490

Provides a remote input and a potential free voltage relay output to the fire
system loop. The input signal is constantly monitored and its status displayed
on the control panel, whilst the output is fail-to-safe. Auxiliary supply
monitoring is also included.

The module is used to for e.g. control and monitor doors such as fire break
doors. The relay provides the door activation and the input monitors the door
status.

Technical Data

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 110 µA
Quiescent @ 35 V 135 µA
Alarm 10 mA
Aux. Supply (24V DC) Quiescent 200 µA
Aux. Supply (24V DC) Alarm < 50 mA
End-of-line resistor NA
Relay contact rating 1A @ 30 VAC/VDC
Environmental
Storage temperature -10 to +50°C
Operating temperature -10 to +70°C z Easy numeric addressing
Relative humidity (non-condensing) 0-95 %
Dimensions (l x w x h) 117 x 80 x 44 mm
z Externally powered
z Normally open / normally closed operation for I/O
z Surface mount
Ordering Information z Aesthetically pleasing
KAL490 Retention Module - 1 Input / 1 Output z Local status indication
z Part of a family of I/O modules consiting of:
z - Conventional Zone Monitors
z - Digital Input Modules
z - Extinguishing Control Modules
z - Isolator Modules
z - Manual Call Points
z - Output Units
z - Retention Units
z - Supervised Output Units for sounder control
I/O Modules
Page 54

Addressable loop powered siren SK07A

The SK07A loop powered siren is designed for connection to and control by the
KSA700/FP1500 analogue fire detection systems from GE-Interlogix.
Communication is done digitally between the fire panel and the sounder.

Technical Data

Electrical
Supply Voltage 22 - 38 VDC
Quiescent current 300 µA
Alarm current 3 mA @ 85 dBA or less than 20 mA @ 95 dBA
Maximum sound level 95 dBA
Mechanical
Dimensions 63 mm (h) x 93 mm Ø
Maximum cable size 2.5 mm²
Fastening Screws 2 x 30 mm
Environmental
Working temperature -20 °C to +50 °C
Storage temperature -20 °C to +70 °C
Relative humidity (maximum) 95 %
Protection Index IP445

Ordering Information
z EN54 part 3 compliant
SK07A Addressable loop powered siren
z Up to 95 dBA sound output
z Different alarm tones and sound levels
z Low current consumption
z Low profile
z IP445 protection level
z Easy installation
z Polarity sensitive
z Rear and side cable entry possible
z Low and easy maintenance
Software
Page 55

KSA700 Configuration software kit PCC-Config

PCC-Config allows easy, menu driven, programming of all the features and
settings of the panel. Common texts can be easily copied to sensors and
zones. Programming becomes simple as all settings are displayed for the
programmers convenience.

Technical Data

Hardware Requirements
Communication RS232, Modem and/or TCP/IP
Display VGA or higher resolution
Hard Disk 2 GB with 650 MB free space
Keyboard Required
Pointing Device Required
Printer System printer required for printing
Processor 133 MHz or higher Pentium-compatible CPU
RAM 64 Mb or more
Removable Media 1.44 Mb stiffy and CD-ROM or DVD drive
Software Requirements
Operating System Windows ‘98 or Windows 2000

Ordering Information

KSP700 PC Interface & Software for up/download configuration for KSA702/5 z Windows based
PCC-Config KSA700/FP1500 Configuration software kit z Complete external configuration of the installation
z Configuration possibilities for single and networked fire
systems
z Local or remote operation via modem or TCP/IP
z Standard RS232 communication

Graphic Software for KSA700 Fire Systems (1 panel-2 loops) PCG-Graphic102

The PCG-Config series consists of 3 software applications. The individual


software formats allows the graphic package to grow with the installation.
PCG-Config102 operates with a single panel and allows for the configuration z Bi-directional communication with single panels and networked
of all devices up to a maximum of two loops. fire systems
z Local or remote connection via modem or TCP/IP
Technical Data z Large selection of user configurable icons
Hardware Requirements z Visualises device alarms and status of in- and outputs
Communication RS232, Modem and/or TCP/IP z Event texts retrieval from the panel
Display SVGA or higher resolution
Hard Disk 2 GB with 650 MB free space z Configurator and operator contol levels
Keyboard Required
Pointing Device Required
z Navigation buttons allowed
Printer System printer required for printing z Event logs with reporting facilities
Processor 1 GHz or higher Pentium III-compatible CPU
RAM 256 Mb or more z Basic drawing package included
Removable Media 1.44 Mb stiffy and CD-ROM or DVD drive
z Imports bmp & drw format graphics
Software Requirements
Operating System Windows ‘98 or Windows 2000

Ordering Information

PCG-Graphic102 Graphic Software for KSA700/FP1500 Fire Systems (1 panel-2 loops)


Software
Page 56

Graphic Software for KSA700 Fire Systems (1 panel-5 loops) PCG-Graphic105

The PCG-Config series consists of 3 software applications. The individual


software formats allows the graphic package to grow with the installation.
PCG-Config105 supports a single panel up to 5 loops. z Bi-directional communication with single panels and networked
fire systems
Technical Data z Local or remote connection via modem or TCP/IP

Hardware Requirements
z Large selection of user configurable icons
Communication RS232, Modem and/or TCP/IP z Visualises device alarms and status of in- and outputs
Display SVGA or higher resolution
Hard Disk 2 GB with 650 MB free space z Event texts retrieval from the panel
Keyboard Required
z Configurator and operator contol levels
Pointing Device Required
Printer System printer required for printing z Navigation buttons allowed
Processor 1 GHz or higher Pentium III-compatible CPU
RAM 256 Mb or more z Event logs with reporting facilities
Removable Media 1.44 Mb stiffy and CD-ROM or DVD drive z Basic drawing package included
Software Requirements
Operating System Windows ‘98 or Windows 2000 z Imports bmp & drw format graphics

Ordering Information

PCG-Graphic105 Graphic Software for KSA700/FP1500 Fire Systems (1 panel-5 loops)

Graphic Software for KSA700 Fire Systems (multi-panel) PCG-GraphicNW

The PCG-Config series consists of 3 software applications. The individual


software formats allows the graphic package to grow with the installation.
PCG-ConfigNW allows for monitoring on networked systems with multiple z Bi-directional communication with single panels and networked
panels. fire systems
z Local or remote connection via modem or TCP/IP
Technical Data z Large selection of user configurable icons
Hardware Requirements z Visualises device alarms and status of in- and outputs
Communication RS232, Modem and/or TCP/IP z Event texts retrieval from the panel
Display SVGA or higher resolution
Hard Disk 2 GB with 650 MB free space z Configurator and operator contol levels
Keyboard Required
Pointing Device Required
z Navigation buttons allowed
Printer System printer required for printing z Event logs with reporting facilities
Processor 1 GHz or higher Pentium III-compatible CPU
RAM 256 Mb or more z Basic drawing package included
Removable Media 1.44 Mb stiffy and CD-ROM or DVD drive
z Imports bmp & drw format graphics
Software Requirements
Operating System Windows ‘98 or Windows 2000

Ordering Information

PCG-GraphicNW Graphic Software for KSA700/FP1500 Fire Systems (multi-panel)


Fire Panels ......................................................................................................................................
1
Conventional fire alarm panel with 2 zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NKB602 . . . . . . . . . . . . . . . . . . . . . . . . . 1
Conventional fire alarm panel with 4 zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NKB604 . . . . . . . . . . . . . . . . . . . . . . . . . 2
Conventional fire alarm panel with 6 zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NKB606 . . . . . . . . . . . . . . . . . . . . . . . . . 3
Conventional fire panel with 2 fire alarm zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NK702 . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Conventional fire panel with 4 fire alarm zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NK704 . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Conventional fire panel with 8 fire alarm zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NK708 . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Conventional fire panel with 12 fire alarm zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NK712 . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Conventional fire panel with 16 fire alarm zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NK716 . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Conventional extinguishing control panel with 3 zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NK703 . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Extinguishing Panels .....................................................................................................................
9
Conventional extinguishing control panel with 5 zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NK706 ...........................
10
Relay module, 4 supervised relays for NK700/Fx400 fire panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SB404 ...........................
11
Relay module, 4 potential free relays for NK700/Fx400 fire panels . . . . . . . . . . . . . . . . . . . . . . . . . . . RB404 ...........................
11
Expansion Modules .......................................................................................................................
11
Analogue addressable fire detection panel - 1 loop ..............................................
KSA701/1 .......................
12
Fire Panels ......................................................................................................................................
12
Analogue addressable fire detection panel - 2 loops . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KSA701/2 . . . . . . . . . . . . . . . . . . . . . . . 13
Analogue addressable fire panel (expandable to 5 loops) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KSA705 . . . . . . . . . . . . . . . . . . . . . . . . . 14
Analogue addressable fire panel with printer (expandable to 5 loops) . . . . . . . . . . . . . . . . . . . . . . . KSA705P . . . . . . . . . . . . . . . . . . . . . . . . 15
KSA700 Series LCD Repeater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KSA701R . . . . . . . . . . . . . . . . . . . . . . . 16
Repeater Panels ............................................................................................................................
16
GSM Modem for Kilsen Fire Panels .................................................................
MODGSM .......................
17
Expansion Modules .......................................................................................................................
17
RS232 communications module for KSA702/5 control panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KAL732 . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Loop driver module for KSA702/705 control panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KAL701 . . . . . . . . . . . . . . . . . . . . . . . . . . 18
RS485 expansion kit for KSA701/FP1500 fire panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NC785 . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
RS485 communications module for KSA702/5 control panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KAL785 . . . . . . . . . . . . . . . . . . . . . . . . . . 19
CO detection control panel - 4 Zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KM260/4-ING . . . . . . . . . . . . . . . . . . 20
CO detection control panel - 5 Zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KM260/5-ING . . . . . . . . . . . . . . . . . . 20
CO detection control panel - 3 Zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KM260/3-ING . . . . . . . . . . . . . . . . . . 20
CO detection control panel - 2 Zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KM260/2-ING . . . . . . . . . . . . . . . . . . 20
CO detection control panel - 1 Zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KM260/1-ING . . . . . . . . . . . . . . . . . . 20
CO Detection .................................................................................................................................
20
CO detection expansion module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KM260-ING . . . . . . . . . . . . . . . . . . . . 21
CO detector with base and mounting supplement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KM170 . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Detectors ........................................................................................................................................
23
Aspiration Smoke Detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASD20 ...........................
23
Power supply unit with battery charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FC252 ...........................
24
Power supply unit with battery charger 0.8A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FC251 ...........................
24
Power Supplies ..............................................................................................................................
24
Illuminated warning sign (No text) 24VDC .........................................................
KR24B ...........................
25
Fire indicators ................................................................................................................................
25
Ionisation detector, conventional .....................................................................
KL700 ...........................
26
Fire Detectors ................................................................................................................................
26
Temperature detector (fixed and rate-of-rise), conventional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KL710 ...........................
27
Optical detector, conventional (with field exchangeable optical block) . . . . . . . . . . . . . . . . . . . . . . . KL731 ...........................
28
KL731/DP331I Calibration Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KCT731 .........................
29
Test and Service Equipment ......................................................................................................
29
Analogue addressable ionisation sensor ...........................................................
KL700A ..........................
30
Fire Detectors ................................................................................................................................
30
Analogue addressable temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KL710A ..........................
31
Analogue addressable optical sensor (with field exchangeable chamber) . . . . . . . . . . . . . . . . . . . KL731A ..........................
32
Analogue addressable dual (optical and thermal) sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KL735A ..........................
33
Fire sensor programmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PG700 ...........................
34
Accessories ....................................................................................................................................
34
Surface mount supplement for KL300 detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S300 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Fire Detector base for KL300 series devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KZ300 . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Bases ...............................................................................................................................................
35
Conventional fire detector base with diode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KZ705D . . . . . . . . . . . . . . . . . . . . . . . . . 36
Surface mount accessory for KZ700/DB304 and KZ700 series bases . . . . . . . . . . . . . . . . . . . . . . . S700 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Universal fire detector base with earth connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KZ705 . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Universal fire detector base (for KL700 and KL700A series detectors) . . . . . . . . . . . . . . . . . . . . . . KZ700 . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Active end-of-line device for use with FP400/KL700 fire panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . EOL-ACT . . . . . . . . . . . . . . . . . . . . . . . . 38
Analogue fire detector base with isolator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KZ705I . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Conventional fire detector base with relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KZ705R . . . . . . . . . . . . . . . . . . . . . . . . . 39
Analogue fire detector base with sounder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KZ705AS . . . . . . . . . . . . . . . . . . . . . . . . 40
Analogue fire detector base with isolator and sounder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KZ705IAS . . . . . . . . . . . . . . . . . . . . . . . 41
Conventional Zone Monitor Unit - 1 Zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KAL410 . . . . . . . . . . . . . . . . . . . . . . . . . . 42
I/O Modules .....................................................................................................................................
42
Conventional Zone Monitor Unit - 4 Zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KAL414/4 . . . . . . . . . . . . . . . . . . . . . . . 43
Extinguishing Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KAL426 . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Relay Module - 1 Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KAL430 . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Supervised Relay Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KAL440 . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Relay Module - 4 Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KAL434/4 . . . . . . . . . . . . . . . . . . . . . . . 47
Addressable Manual Call Point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KAL450 . . . . . . . . . . . . . . . . . . . . . . . . . . 48
KAL450 accessory for flush mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KAL450E . . . . . . . . . . . . . . . . . . . . . . . . 49
Spare glasses (10-pack) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DM715 . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Accessories ....................................................................................................................................
49
Anti-tamper plastic cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DM782 ..........................
50
Surface mount back box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DM787 ..........................
50
Digital Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KAL460 ..........................
51
I/O Modules .....................................................................................................................................
51
Isolator Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KAL470 . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Retention Module - 1 Input / 1 Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KAL490 . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Addressable loop powered siren . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SK07A . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Graphic Software for KSA700 Fire Systems (1 panel-2 loops) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PCG-Graphic102 . . . . . . . . . . . . . . 55
KSA700 Configuration software kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PCC-Config . . . . . . . . . . . . . . . . . . . . . 55
Software .........................................................................................................................................
55
Graphic Software for KSA700 Fire Systems (multi-panel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PCG-GraphicNW ..............
56
Graphic Software for KSA700 Fire Systems (1 panel-5 loops) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PCG-Graphic105 ..............
56

You might also like