15 - TECHNICAL INFORMATION

Motor Protection - general information 488

Motor full load currents 489

DOL Starting
Fuse links 490
Circuit Breakers 491

Assisted Starting
Fuse links 492
GE Circuit Breakers 493
GE Contactors 494

Auto Transformer Starting


GE Contactors 495

Fire Pump Starting


Fuse Links 496
Circuit Breakers 497

Type 2 Coordination
DOL Class 10 498
DOL Class 20 500
Star Delta 501

Transformers & Capacitors


General Information 502
Capacitor Protection Circuit Breakers 504
Capacitor Protection Fuse Links 505
Fuse Links TRx 503

Back Up Protection
MCCB & Switch 506
Fuses & MCB’s 506
Circuit Breakers 507

Discrimination & Selectivity


Fuses & Fuses 509
Circuit Breakers 510

Enhanced Discrimination & Selectivity


Circuit Breakers 516

Fuse Link Temperature De-rating 522

Protection of Cables with Fuse Links 523

GE Contactors for Lighting Circuits 524

Relay Equivalent Selection Chart 526


TECHNICAL

15
IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au
Product Catalogue 2013 487
MOTOR PROTECTION

General
In a circuit that provides power to a motor a number of protective & Control devices are normally present. The combination of these devices must be coordinated to
ensure the efficiency & optimal protection of the motor. Here, the protection of such circuits strongly depends on the operational requirements, as the application for
which the motor is used, the required starting frequency, required service level & applicable safety standards.

Category Load type Ir setting


(min)
AC1 Non Inductive motor Energization
AC2 Slip ring motor Starting
Switching off while running
Regenerative breaking
Inching
AC3 Squirrel-cage motor Energization
Switching off while running
AC4 Squirrel-cage motor Starting
(Cos phi = 0.45 <= 100A) Switching off while running
(Cos phi = 0.35 > 100A) Regenerative breaking
Pluging
Inching

Required
tripping time at
Trip Class 1.2 x In 1.5 x In 7.2 x In
10A t < 2 hours t < 2 min. 2 <= t <= 10sec.
10 t < 2 hours t < 4 min. 4 <= t <= 10sec.
20 t < 2 hours t < 8 min. 6 <= t <= 10sec.
30 t < 2 hours t < 12 min. 8 <= t <= 10sec.

COORDINATION TYPE 2 TEST SEQUENCE


Co ordination
The standards require tests to define the co ordination between the protective & switching devices within the motor circuit.
Depending on the state of the components after the test two coordination.
Classes, 1 & 2 have been defined.
The unique properties of the Record Plus breakers allow GE to offer solutions to meet the highest standard. Type 2 co ordination.

Motor current Test with


ie (AC3) current “r”
Ie <= 16A 1kA
16 < Ie <= 63A 3 kA
63 < Ie <= 125A 5 kA
125 < Ie <= 315A 10 kA
315 < Ie <= 630A 18 kA
After this test the original characteristics of the contactor
and thermal relay MUST remain unchanged.
After this test the short-circuit protection must trip within
10 ms at a fault current >= 15 x In

Type 2 - Short-circuit test with current “Iq”


<= 50kA
This value which is generally 15kA is used to check the coordination of
the device used in the motor starter circuit. For each combination with
Record Plus™ breakers this value is mentioned in the following tables.
After test with this current the following conditions must be met.
No or minor welding of the contactors after testing; contact separation is
simple and easy.
The switchgear and controlgear are fully operational after test.

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


488 Product Catalogue 2013
MOTOR PROTECTION

MOTOR RATED OUTPUTS AND FULL LOAD CURRENTS


Motor Rating Full Load Current (A)
kW HP At 415V At 440V At 1000V
0.09 1/8 0.4 0.38 -
0.12 1/6 0.5 0.47 -
0.18 1/4 0.6 0.56 -
0.25 1/3 0.8 0.75 -
0.37 0.5 1.1 1 0.46
0.55 0.75 1.5 1.4 0.63
0.75 1 1.8 1.7 0.76
1.1 1.5 2.6 2.4 1.1
1.5 2 3.4 3.2 1.5
2.2 3 4.8 4.5 2
3.7 5 7.6 7.2 2.7
5.5 7.5 11 10.3 4.6
7.5 10 14 13.2 5.9
11 15 21 19.8 8.8
15 20 28 26.4 11.8
18.5 25 34 32 14.3
22 30 40 38 17
30 40 55 52 23
37 50 66 62 28
45 60 80 75 33
55 75 100 94 42
75 100 135 127 57
90 125 160 150 67
110 150 200 188 84
132 175 230 216 97
150 200 260 245 108
160 220 280 264 116
185 250 320 301 134
200 270 350 329 147
220 300 380 357 160
250 350 430 404 181
300 400 510 479 214
Notes:
1. Full load current values are nominal for standard squirrel-cage induction motors of rated
speed 1500 rpm (4 pole).
Possible deviation of FLC values ±10% depending on type and manufacturer.
TECHNICAL

15
IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au
Product Catalogue 2013 489
MOTOR PROTECTION

FUSE SELECTION FOR DIRECT-ON-LINE MOTOR STARTING


Motor FLC (A) Recommended GEC,
GE or IPD Fuse-Link Rating (A)
From To Type T ‘gG’ Type T ‘gM’ DIN Type ‘gL’ - ‘gG’
0 0.7 2 - 4
0.8 1.4 4 - 4
1.5 2 6 - 6
2.1 3 10 - 10
3.1 6.1 16 - 16
6.2 9 20 - 20
9.1 11 25 20M25† 25
11.1 14.4 32 20M32† 32
14.5 15.4 35 32M35 35
15.5 18 40 32M40 40
18.1 22 50 32M50 50
22.1 28 63 32M63 63
28.1 45 80 63M80 80
45.1 58 100 63M100 100
58 80 125 100M125 125
80.1 99 160 100M160 160
99.1 128 200 - 200
128.1 180 250 200M250 250
180.1 216 315 200M315* 315
216.1 270 355 315M355 355
270.1 328 400 - 400
328.1 385 450 400M450 500
385.1 430 500 - 500
430.1 500 560 - 630
500.1 560 630 - 630
560.1 620 670 630M670 800
620.1 645 710 - 800
645.1 680 750 - 1000

† Type NIT for 415V or less.


* Type TF, if motor FLC does not exceed 200A and voltage is 500V or less.

Notes:
1. Assumed starting conditions: Motor Rating Run-Up
Up to 1kW 5 x FLC for 5 secs.
1.1 to 7.5kW 6 x FLC for 10 secs.
7.6 x 75kW 7 x FLC for 10 secs.
Greater than 75kW 6 x FLC for 15 secs.
Operating cycle of 2 starts in rapid succession and up to 8 starts per hour.

2. Suitable adjustments to the recommended rating may be necessary for:


(a) Starting conditions in excess of the assumed starting conditions.
(b) High enclosure (fluid environment) temperatures, refer to fuse de-rating information
indicated on page 522.

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


490 Product Catalogue 2013
MOTOR PROTECTION

GE CIRCUIT BREAKER GUIDE FOR DIRECT-ON-LINE MOTOR STARTING 415V APPLICATIONS


Motor Rating Circuit Breaker Types and Ratings (A)
MCB MCCB Type
kW FLC Series G FD FD FE FE FG FG FK FK FK
(A) (Curve C) 63 160 160 250 400 630 800 1250 1600
0.37 1.1 2
0.55 1.5 4
0.75 1.8 6
1.1 2.6 10
1.5 3.4 10
2.2 4.8 16
3.7 7.6 20 16
5.5 11 25 20 20
7.5 14 32 32 32
11 21 50 40 40
15 28 50 50
18.5 34 63 64 63
22 40 80 80
30 55 100 100 100 100
37 66 125 125 125 125
45 80 160 160 160 160
55 100 200 200
75 135 250 250 250
90 160 300 300
110 200 400 400 400 400
132 230 450 450 450
150 250 500 500 500
160 270 550 550 550
185 320 630 630 630 640
200 350 700 700 700
220 380 800 800 800
250 430 900 900
300 510 1050 1050
315 550 1200 1200
335 590 1250 1250
375 660 1400
400 700 1500
Notes:
1. FLC values are nominal for standard squirrel-cage induction motors of rated speed 1500 rpm (4 poles). Possible deviation of FLC
values ± 10% depending on type and manufacturer.

2. Circuit breaker ratings are based on carrying 100% FLC continuous and 600% FLC for 10 seconds. Operating cycle 2 starts in
rapid succession and up to 8 starts per hour.

3. Suitable adjustments to the indicated ratings may be necessary for:


a) Starting conditions in excess of the above conditions.
b) High enclosure (fluid environment) temperatures.
TECHNICAL

15
IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au
Product Catalogue 2013 491
MOTOR PROTECTION

FUSE SELECTION FOR ASSISTED MOTOR STARTING


(Star-Delta, Autotransformer, Resistor or Reactor)
Motor FLC (A) Recommended GEC,
GE or IPD Fuse-Link Rating (A)
From To Type T ‘gG’ Type T ‘gM’ DIN Type ‘gL’ - ‘gG’
0 1.4 2 - 4
1.5 2.1 4 - 4
2.2 3.1 6 - 6
3.2 5.5 10 - 10
5.6 10 16 - 16
10.1 14 20 - 20
14.1 18 25 20M25 25
18.1 22 32 - 32
22.1 28 35 32M35 35
28.1 32 40 32M40 40
32.1 40 50 - 50
40.1 51 63 - 63
51.1 80 80 - 80
80.1 100 100 - 100
100.1 125 125 - 125
125.1 160 160 - 160
160.1 200 200 - 200
200.1 250 250 - 250
250.1 315 315 - 315
315.1 355 355 - 355
355.1 400 400 - 400
400.1 450 450 - 500
450.1 500 500 - 500
500.1 560 560 - 630
560.1 630 630 - 630
630.1 670 670 - 800
670.1 710 710 - 800
710.1 750 750 - 800
Notes:
1. Assumed starting conditions: Motor Rating Run-Up
Up to 1kW 2.5 x FLC for 20 secs.
1.1 to 7.5kW 3.5 x FLC for 20 secs.
Greater than 75kW 3.5 x FLC for 15 secs.
Operating cycle of 2 starts in rapid succession and up to 8 starts per hour.

2. Suitable adjustments to the recommended ratings may be necessary for:


(a) Starting conditions in excess of the assumed starting conditions.
(b) High enclosure (fluid environment) temperatures more than 35°C. Some fuses need
to be derated as indicated on page 522.

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


492 Product Catalogue 2013
MOTOR PROTECTION

GE CIRCUIT BREAKER GUIDE FOR ASSISTED MOTOR STARTING


(STAR-DELTA, 415V APPLICATIONS)
Motor Rating Circuit Breaker Types and Ratings (A)
MCB MCCB Type
kW FLC Series G FD FD FE FE FG FG FK FK
(A) (Curve C) 63 160 160 250 400 630 800 1250
0.37 1.1 2
0.55 1.5 4
0.75 1.8 4
1.1 2.6 6
1.5 3.4 6
2.2 4.8 10
3.7 7.6 16
5.5 11 20 16
7.5 14 25 20 20
11 21 40 32 32
15 28 50 40 40
18.5 34 50 50
22 40 63 64 63
30 55 80 80
37 66 90 90
45 80 100 100 100 100
55 100 125 125 125 125
75 135 160 160 160 160
90 160 200 200
110 200 250 250 250
132 230 280 280
150 250 300 300
160 270 320 320 320
185 320 380 380 380
200 350 400 400 400 400
220 380 450 450 450
250 430 550 550 550
300 510 630 650 650
315 550 700 700
335 590 750 750
375 660 800 850
400 700 950
Notes:
1. FLC values are nominal for standard squirrel-cage induction motors of rated speed 1500 rpm (4 poles). Possible
deviation of FLC values ± 10% depending on type and manufacturer.

2. Circuit breaker ratings are based on carrying 100% FLC continuous and 600% FLC for 10 seconds. Operating cycle 2
starts in rapid succession and up to 8 starts per hour.

3. Suitable adjustments to the indicated ratings may be necessary for:


a) Starting conditions in excess of the above conditions.
b) High enclosure (fluid environment) temperatures.
TECHNICAL

15
IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au
Product Catalogue 2013 493
MOTOR PROTECTION

GE CONTACTOR GUIDE FOR STAR-DELTA MOTOR STARTING


415V APPLICATIONS
Motor Rating Contactor Types
kW FLC (A) Line and Delta Star TOL Relay Types
0.37 1.1 MCO MCO MT03D
0.55 1.5 MCO MCO MT03E
0.75 1.8 MCO MCO MT03F
1.1 2.6 MCO MCO MT03G
1.5 3.4 MCO MCO MT03H
2.2 4.8 MCO MCO MT03J
3.7 7.6 MCO MCO MT03K
5.5 11 MC1 MCO MT03M
5.5 11 CL00 CL00 RT1L
7.5 14 MC1 MCO MT03N
7.5 14 CL00 CL00 RT1M
11 21 CL02 CL00 RT1P
15 28 CL02 CL01 RT1S
18.5 34 CL25 CL01 RT1T
18.5 34 CL03 CL01 RT1T
22 40 CL25 CL02 RT1U
22 40 CL03 CL02 RT1U
30 55 CL04 CL25 RT1V
30 55 CL04 CL03 RT1V
37 66 CL45 CL25 RT1W
37 66 CL45 CL03 RT1W
45 80 CL06 CL04 RT2G
55 100 CL07 CL45 RT2H
75 135 CL08 CL06 RT2J
90 160 CL09 CL07 RT2L
110 200 CK75C CL08 RT3D
132 230 CK75C CL08 RT3E
150 250 CK75C CL09 RT3F
160 270 CK08C CL09 RT3F
185 320 CK08C CK75C RT3F
200 350 CK85B CK75C RT4P
220 380 CK09B CK75C RT4P
250 430 CK09B CK75C RT4P
300 510 CK95B CK08C RT4R
315 550 CK10C CK08C RT5C
335 590 CK10C CK85B RT5C
375 660 CK10C CK09B RT5D
400 700 CK10C CK09B RT5D
Notes:
1. FLC values are nominal for standard squirrel-cage indication motors of rated speed
1500 rpm (4 poles).
Possible deviation of FLC values ± 10% depending on type and manufacture.

2. Contactor types based on the following conditions:


a) Starting duration not more than 20 seconds.
b) Starting frequency of 2 starts in rapid succession and up to 8 starts per hour.

3. TOL relays selected for direct connection to the line contactor, in the delta branch of the
motor starter circuit.

4. Suitable adjustments to the indicated types may be necessary for:


a) Starting conditions in excess of the above conditions.
b) High enclosure (fluid environment) temperatures.

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


494 Product Catalogue 2013
MOTOR PROTECTION

GE CONTACTOR GUIDE FOR AUTOTRANSFORMER MOTOR


STARTING 415V APPLICATIONS
Motor Rating Contactor Types
kW FLC (A) Line Transformer Star TOL Relay Types
0.37 1.1 MCO MCO MCO MT03F
0.55 1.5 MCO MCO MCO MT03G
0.75 1.8 MCO MCO MCO MT03H
1.1 2.6 MCO MCO MCO MT03J
1.5 3.4 MCO MCO MCO MT03K
2.2 4.8 MCO MCO MCO MT03L
3.7 7.6 MC1 MCO MC0 MT03M
3.7 7.6 CL00 CL00 CL00 RT1N
5.5 11 MC2 MC1 MC0 MT03P
5.5 11 CL01 CL00 CL00 RT1N
7.5 14 CL02 CL00 CL00 RT1P
11 21 CL25 CL01 CL01 RT1T
15 28 CL04 CL02 CL02 RT1V
18.5 34 CL45 CL25 CL02 RT1W
22 40 CL45 CL04 CL25 RT1W
30 55 CL07 CL45 CL25 RT2G
30 55 CL07 CL45 CL03 RT2G
37 66 CL08 CL06 CL04 RT2J
45 80 CL08 CL07 CL45 RT2J
55 100 CL10 CL07 CL06 RT2M
75 135 CK75C CL09 CL07 RT3E
90 160 CK08C CL10 CL08 RT3F
110 200 CK85B CK75C CL09 RT4P
132 230 CK09B CK75C CL10 RT4P
150 250 CK09B CK08C CK75C RT4P
160 270 CK95B CK08C CK75C RT4P
185 320 CK10C CK85B CK75C RT5C
200 350 CK10C CK09B CK08C RT5C
220 380 CK10C CK09B CK08C RT5C
250 430 CK11C CK95B CK85B RT5D
300 510 CK11C CK10C CK09B RT5E
315 550 CK11C CK10C CK09B RT5E
335 590 CK12B CK10C CK95B RT5E
375 660 CK12B CK11C CK95B RT5E
400 700 CK12B CK11C CK10C RT5E
Notes:
1. FLC values are nominal for standard squirrel-cage indication motors of rated speed
1500 rpm (4 poles). Possible deviation of FLC values ± 10% depending on type and
manufacture.

2. Contactor types based on the following conditions:


a) Starting duration not more than 20 seconds.
b) Starting frequency of 2 starts in rapid succession and up to 8 starts per hour.
c) Auto-transformer tap at 80%.

3. Suitable adjustments to the indicated types may be necessary for:


a) Starting conditions different to the above conditions.
b) High enclosure (fluid environment) temperatures.
TECHNICAL

15
IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au
Product Catalogue 2013 495
MOTOR PROTECTION

FUSE SELECTION FOR FIRE PUMP MOTOR STARTING


Motor FLC (A) Recommended GEC,
GE or IPD Fuse-Link Rating (A)
kW FLC (A) Type T ‘gG’ Type T ‘gM’ DINType ‘gL’ - ‘gG’
0.37 1.1 4 - 4
0.55 1.5 6 - 4
0.75 1.8 6 - 6
1.1 2.6 10 - 6
1.5 3.4 16 - 10
2.2 4.8 16 - 16
3.7 7.6 20 - 20
5.5 11 32 20M32 25
7.5 14 35 20M35 32
11 21 50 32M50 40
15 28 63 32M63 50
18.5 34 80 63M80 63
22 40 80 63M80 80
30 55 100 63M100 100
37 66 125 100M125 125
45 80 160 100M160 160
55 100 160 - 160
75 135 250 200M250 200
90 160 250 200M250 250
110 200 315 - 315
132 230 355 315M355 315
150 250 355 315M355 355
160 270 400 - 400
185 320 450 400M450 500
200 350 450 400M450 500
220 380 500 - 630
250 430 560 - 630
300 510 630 - 800
Notes:
1. FLC values are nominal for standard squirrel-cage induction motors of rated speed 1500 rpm
(4 pole).
Possible deviation of FLC values ±10% depending on type and manufacturer.

2. Recommend fuse ratings are based on carrying 125% FLC continuously and operating in not less
than 20 seconds at 600% FLC, in accordance with Clause 7.2.9.2 of AS/NZS 3000:2007.

3. Suitable adjustments to the recommended ratings may be necessary for high enclosure (fluid
environment) temperatures, refer to de-rating information indicated on page 522.

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


496 Product Catalogue 2013
MOTOR PROTECTION

GE CIRCUIT BREAKER GUIDE FOR FIRE PUMP MOTOR STARTING 415V APPLICATIONS
Motor Rating Circuit Breaker Types and Ratings (A)
MCB MCCB Type
kW FLC Series G FD FD FE FE FG FG FK FK FK
(A) (Curve C) 63 160 160 250 400 630 800 1250 1600
0.37 1.1 4
0.55 1.5 6
0.75 1.8 6
1.1 2.6 10
1.5 3.4 16
2.2 4.8 16 16
3.7 7.6 25 20 20
5.5 11 40 32 32
7.5 14 50 40 40
11 21 63 50 50
15 28 64 63
18.5 34 80 80
22 40 100 100 100 100
30 55 125 125 125 125
37 66 140 140 140 140
45 80 180 180
55 100 220 220 220
75 135 300 300 320
90 160 400 400 400 400
110 200 450 450 450
132 230 500 500 500
150 250 550 550 550
160 270 580 580 580
185 320 700 700 700
200 350 750 750 750
220 380 800 800 800
250 430 1000 1000
300 510 1250 1250
315 550 1300
335 590 1400
375 660 1500
400 700 1600
Notes:
1. FLC values are nominal for standard squirrel-cage induction motors of rated speed 1500 rpm (4 poles). Possible deviation of FLC
values ± 10% depending on type and manufacturer.

2. Circuit breaker ratings are based on carrying 125% FLC continuously and opening in not less than 20 seconds at 600% FLC, in
accordance with clause 7.2.9.2 of AS/NZS 3000:2007.

3. Suitable adjustments to the indicated ratings may be necessary for high enclosure (fluid environment) temperatures.
TECHNICAL

15
IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au
Product Catalogue 2013 497
MOTOR PROTECTION

TYPE 2 COORDINATION
CLASS 10 PROTECTION @ 415V AC

For type 2 Coordination @ other voltage, please refer to product catalogues of your local representative.

Upstream Record Plus Breakers selection


Type N H L
IIcc values in kA Ue= 400/415V AC
FD63/160 50kA 80kA 130kA
FE160/250 50kA 80kA 130kA
FG 400/630 50kA 80kA 130kA
FK 800/1250 50kA 80kA 100kA

SELECTION OF ASSOCIATED COMPONENTS (1)


Motor Breaker details Contactor
P(kW) In Type Ie Im Type + O.R.
0.75 2 FD63 /FE160 3 (2) 35 CL25+RT1J
1.1 2.6 FD63 /FE160 3 (2) 35 CL25+RT1K
1.5 3.6 FD63 /FE160 7 70 CL03+RT1K
2.2 5 FD63 /FE160 7 80 CL03+RT12L
3 7 FD63 /FE160 7 86 CL03+RT1M
4 8.3 FD63/FE160 12.5 125 CL06+RT2AN
5.5 11.5 FD63/FE160 12.5 150 CL06+RT2AN
7.5 16.1 FD63/FE160 20 200 CL06+RT2B
10 21 FD63 /FE160 30 300 CL06-RT2C
11 22 FD63 /FE160 30 300 CL06-RT2C
15 30 FD63 /FE160 30 390 CL06-RT2D
18.5 37 FD63/FE160 50 478 CL06+RT2E
22 43 FD63/FE160 50 561 CL06+RT2G
25 49 FD63/FE160 50 635 CL06+RT2G
30 58 FD/FE160 80 800 CL09+RT2H
37 72 FD/FE160 80 934 CL09+RT2J
45 86 FD/FE160 100 1121 CK75C+RT2L
55 104 FE160 125 1346 CK85B+RT3E
75 144 FE160 160 1869 CK85B+RT3F
90 179 FE250 250 2500 CK95B+RT4N
110 207 FE250 250 2691 CK10B+RT4P
132 247 FE250 250 3214 CK10B+RT4R
160 300 FG400 350 3900 CK10B+RT5C
200 360 FG630 500 4680 CK12B+RT5C
220 400 FG630 500 5200 CK12B+RT5D
250 462 FG630 500 6004 CK12B+RT5D
300 560 FK800 800 6720 CK13B+RT5E
315 582 FK800 800 6985 CK13B+RT5C
335 619 FK800 800 6810 CK13B+RT5C

Notes:
(1) The contactor has a breaking capacity that is sufficient to operate the specified motor up to the specified magnetic setting of the breaker.
(2) The 3 AMP device is designed to operate AA current level up to 3.5 Amps.

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


498 Product Catalogue 2013
MOTOR PROTECTION

TYPE 2 COORDINATION
CLASS 10 AND PROTECTION
(WITH SMR2 OTHER CLASSES POSSIBLE)

Upstream Record Plus Breakers selection


Type N H L
IIcc values in kA Ue= 400/415V AC
FE160/250 50kA 80kA 130kA
FG400/630 50kA 80kA 130kA

SELECTION OF ASSOCIATED COMPONENTS (1)

Motor Breaker details Contactor


P(kW) In Type Ie Im Type + O.R.
5.5 11.5 FE160 25 150 CL08
7.5 16.1 FE160 25 200 CL08
10 21 FE160 25 300 CL08
11 22 FE160 25 300 CL08
15 30 FE160 63 390 CL09
18.5 37 FE160 63 478 CL09
22 43 FE160 63 561 CL09
25 49 FE160 63 635 CL09
30 58 FE160 63 800 CL09
37 72 FE160 125 934 CK85B
45 86 FE160 125 1121 CK85B
55 104 FE160 125 1346 CK85B
75 144 FE160 160 1869 CK85B
90 179 FE250 250 2500 CK95B
110 207 FE250 250 2691 CK95B
132 247 FE250 250 2967 CK95B
160 300 FG400 350 3900 CK10C
200 360 FG630 500 4680 CK12B
220 400 FG630 500 5200 CK12B
250 462 FG630 500 6004 CK12B

Notes:
(1) The contactor has a breaking capacity that is sufficient to operate the specified motor up to the specified magnetic setting of the breaker.
(2) The 3 AMP device is designed to operate AA current level up to 3.5 Amps.
TECHNICAL

15
IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au
Product Catalogue 2013 499
MOTOR PROTECTION

TYPE 2 COORDINATION
CLASS 20(3) PROTECTION

Upstream Record Plus Breakers selection


Type N H L
IIcc values in kA Ue= 400/415V AC
FD63/160 50kA 80kA 130kA
FE160/250 50kA 80kA 130kA
FG 400/630 50kA 80kA 130kA
FK 800/1250 50kA 80kA 100kA

SELECTION OF ASSOCIATED COMPONENTS (1)

Motor Breaker details Contactor


P(kW) In Type Ie Im Type + O.R.
0.75 2 FD63/FE160 3 (2) 35 CL25+RT12J
1.1 2.6 FD63/FE160 3 (2) 35 CL25+RT12K
1.5 3.6 FD63/FE160 7 70 CL03+RT12K
2.2 5 FD63/FE160 7 80 CL03+RT12L
3 6.6 FD63/FE160 7 86 CL03+RT12M
4 8.3 FD63/FE160 12.5 125 CL06+RT2AN
5.5 11.5 FD63/FE160 12.5 150 CL06+RT2AN
7.5 16.1 FD63/FE160 20 200 CL06+RT2B
10 21 FD63/FE160 30 300 CL06-RT2C
11 22 FD63/FE160 30 300 CL06-RT2C
15 30 FD63/FE160 30 390 CL06-RT22D
18.5 37 FD63/FE160 50 478 CL06+RT22E
22 43 FD63/FE160 50 561 CL06+RT22G
25 49 FD63/FE160 50 635 CL06+RT22G
30 58 FD/FE160 80 800 CL09+RT22H
37 72 FD/FE160 80 934 CL09+RT22J
45 86 FD/FE160 100 1121 CK75C+RT22L
55 104 FE160 125 1346 CK85B+RT32E
75 144 FE160 160 1869 CK85B+RT32F
90 179 FE250 250 2500 CK95B+RT32F
110 207 FE250 250 2691 CK10B+RT5LB
132 247 FE250 250 3214 CK10B+RT5LB
160 300 FG400 350 3900 CK10B+RT5LB
200 360 FG630 500 4680 CK12B+RT52LC
220 400 FG630 500 5200 CK12B+RT52LD
250 462 FG630 500 6004 CK12B+RT52LD
300 560 FK800 800 6720 CK13B+RT5LE
315 582 FK800 800 6985 CK13B+RT5LE
335 619 FK800 800 6810 CK13B+RT5LE

Notes:
(1) The contactor has a breaking capacity that is sufficient to operate the specified motor up to the specified magnetic setting of the breaker.
(2) The 3 AMP device is designed to operate AA current level up to 3.5 Amps.

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


500 Product Catalogue 2013
MOTOR PROTECTION

TYPE 2 COORDINATION
START DELTA STARTERS

Upstream Record Plus Breakers selection


Type N H L
IIcc values in kA Ue= 400/415V AC
FD63/160 50kA 80kA 130kA
FE160/250 50kA 80kA 130kA
FG400/630 50kA 80kA 130kA
FK800/1250 50kA 80kA 130kA

Motor Breaker details Contactor Delta Star


P(kW) In Type Ie Im Type + O.R. Cont. Cont.
2.2 5.0 FD63/FE160 7 80 CL03+RT12L CL03 CL03
3 6.6 FD63/FE160 7 86 CL03+RT1M CL03 CL03
4 8.3 FD63/FE160 12.5 125 CL06+RT2AN CL04 CL04
5.5 11.5 FD63/FE160 12.5 150 CL06+RT2AN CL04 CL04
7.5 16.1 FD63/FE160 20 200 CL06+RT2B CL45 CL45
10 21 FD63/FE160 30 300 CL06-RT2C CL45 CL45
11 22 FD63/FE160 30 300 CL06-RT2C CL45 CL45
15 30 FD63/FE160 30 390 CL06-RT2D CL45 CL45
18.5 37 FD63/FE160 50 478 CL06+RT2E CL06 CL06
22 43 FD63/FE160 50 561 CL06+RT2G CL06 CL06
25 49 FD63/FE160 50 635 CL06+RT2G CL06 CL06
30 58 FD/FE160 80 800 CL09+RT2H CL09 CL09
37 72 FD/FE160 80 934 CL09+RT2J CL09 CL09
45 86 FD160 100 1121 CL09+RT2L CL09 CL09
45 86 FE160 100 1121 CK75C+RT2L CL10 CL10
55 104 FE160 125 1346 CK85B+RT3E CK75C CL10
75 144 FE160 160 1869 CK85B+RT3F CK08C CL10
90 179 FE250 250 2500 CK95B+RT4N CK85B CK75C
110 207 FE250 250 2691 CK10B+RT4P CK95B CK75C
132 247 FE250 250 3214 CK10B+RT4R CK95B CK75C
160 300 FG400 350 3900 CK10B+RT5C CK95B CK85B
200 360 FG630 500 4680 CK12B+RT5C CK10C CK10C
220 400 FG630 500 5200 CK12B+RT5D CK10C CK10C
250 462 FG630 500 6004 CK12B+RT5D CK10C CK10C
300 560 FK800 800 6720 CK13B+RT5E CK12C CK12C
315 582 FK800 800 6985 CK13B+RT5C CK12C CK12C
335 619 FK800 800 6810 CK13B+RT5C CK12C CK12C
TECHNICAL

15
IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au
Product Catalogue 2013 501
TRANSFORMER RATINGS

GUIDE TO LOW VOLTAGE FAULT LEVEL


mVA Current (I) Current (I) Typical Z1 @ 433V PSC @ 433V
kVA kVA/1000 @ 11kV @ 433V %Z in Ohms in kA
15 0.015 0.79 20 4.75 0.5937 0.421
25 0.025 1.31 33.33 4.5 0.3375 0.741
50 0.050 2.62 66.67 4.5 0.1687 1.482
100 0.100 5.25 133.34 4.75 0.0891 2.807
150 0.150 7.87 200.01 4.75 0.0594 4.211
200 0.200 10.5 266.67 4.75 0.0445 5.614
300 0.300 15.75 400.01 4.75 0.0297 8.421
315 0.315 16.53 420.01 5 0.0298 8.400
400 0.400 20.99 533.35 4.75 0.0223 11.228
500 0.500 26.24 666.69 4.75 0.0178 14.035
600 0.600 26.24 666.69 4.75 0.0148 16.843
750 0.750 39.36 1000.03 4.75 0.0119 21.053
750 0.750 39.36 1000.03 6.25 0.0156 16.000
800 0.800 41.99 1066.70 4.75 0.0111 22.457
1000 1.000 52.49 1333.37 4.75 0.0089 28.071
1200 1.200 62.98 1600.05 5 0.0078 32.001
1350 1.350 70.86 1800.05 5.25 0.0073 34.287
1500 1.500 78.73 2000.06 5.5 0.0069 36.365
2000 2.000 104.97 2666.74 5.5 0.0052 48.486
2500 2.500 131.22 3333.43 6 0.0045 55.557

Note:
The attached calculations are based on zero source impendance and are intended as a guide only.
Example: Fault level for 400kA Sub:

Ohms = KV Line Voltage2 x %Z = (433)2 


  
MVA 0.4x106 100

KA = KV Line Voltage = 433 = 11.228 KA


    

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


502 Product Catalogue 2013
TRANSFORMER PROTECTION

FUSE SELECTION FOR 3-PHASE TRANSFORMER


PRIMARIES AT 415VAC
Transformer Recommended GEC,
Rating English Electric
GE or IPD Fuse-Link
Rating (A)
kVA Primary FLC (A) Type T ‘gG’ DIN Type ‘gL’-’gG’
0.5 0.8 4 4
1 1.5 6 4
2 3.1 10 6
3 4.6 16 10
4 6.1 16 10
5 7.7 16 16
6 9.2 20 16
7 10.7 20 16
8 12.2 20 16
10 15 25 20
12 18 32 25
15 23 35 32
20 31 40 40
25 38 50 50
30 46 63 63
40 61 80 80
50 77 80 80
75 115 125 125
100 153 160 160
125 191 200 200
150 230 250 250
200 306 315 315
250 383 400 400
300 459 500 500
400 612 630 630
500 765 800 800
630 964 1250 1000
750 1148 1250 -
Notes:
1. FLC values are typical only. Possible deviation of FLC values ±5%
depending on manufacturer.
2. Recommended fuse ratings allow for transformer magnetising inrush current
of 12 times FLC for 0.1 seconds.
3. Suitable adjustments to the recommended ratings may be necessary for
high enclosure (fluid environment) temperatures, refer to de-rating information
indicated on page 522.
TECHNICAL

15
IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au
Product Catalogue 2013 503
TRANSFORMERS & CAPACITOR PROTECTION

Maximum crest
inrush values
Transformer 1st Period 2nd Period 3rd Period
value 5 ms. 25 ms. 45 ms.
< 50 kvA 25 x In 12 x In 5 x In
>= 50 kvA 15 x In 8 x In 3.5 x In

Transformer ratings Record Plus breaker


1ph 240V 3ph 400/415V Type Trip unit Ist
kVA In kVA In type & rating*
2.5 10 6.3 9 FD160N, FD160H or L LTMD-25 250
4 11 8 12 FD160N, FD160H or L LTMD-25 250
5 17 10 14 FD160N, FD160H or L LTMD-32 320
12.5 18 FD160N, FD160H or L LTMD-32 320
6.3 27 16 23 FD160N, FD160H or L LTMD-40 400
8 34 20 28 FD160N, FD160H or L LTMD-50 500
10 42 25 35 FD160N, FD160H or L LTMD-63 630
12.5 53 31.5 44 FD160N, FD160H or L LTMD-80 800
40 56 FD160N, FD160H or L LTMD-100 1000
16 68 50 70 FD160N, FD160H or L LTMD-125 1250
20 84 FD160N, FD160H or L LTMD-125 1250
63 89 FE160N, H or L SMR1-125
25 105 80 113 FE160N, H or L SMR1-125
31.5 133 100 141 FE160N, H or L SMR1-160
40 169 125 176 FE250N, H or L SMR1-250
50 211 160 225 FE250N, H or L SMR1-250
63 266 200 287 FG400N, H or L SMR1-350
80 338 250 352 FG400N, H or L SMR1-350
100 422 315 444 FG630N, H or L SMR1-500
125 528 400 563 FG630N, H or L SMR1-630
160 675 500 704 FK800N or H SMR1-800
630 887 FK1250N or H SMR1-1000
800 1126 FK1250N or H SMR1-1250
1000 1408 FK1600N or H SMR1-1600

PROTECTION OF CAPACITOR BANKS


Un = 400/415V
(phase to phase voltage)
Capacitor rating Record Plus Ir setting
(kVAr) breaker (min)
10 FD160N, FD160H or L 21 A
15 FD160N, FD160H or L 31 A
20 FD160N, FD160H or L 41 A
25 FD160N, FD160H or L 52 A
30 FD160N, FD160H or L 62 A
35 FD160N, FD160H or L 72 A
40 FD160N, FD160H or L 83 A
45 FD160N, FD160H or L 93 A
50 FD160N, FD160H or L 103 A
60 FD160N, FD160H or L 124 A
70 FD160N or FE160N, H or L 144 A
80 FE250N, H or L 165 A
90 FE250N, H or L 186 A
100 FE250N, H or L 206 A
120 FE250N, H or L 248 A
140 FG400N, H or L 289 A
160 FG400N, H or L 330 A
180 FG400N, H or L 372 A
200 FG630N, H or L 413 A
250 FG630N, H or L 516 A
300 FG630N, H or L 619 A
350 FK800N, H or H 722 A

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


504 Product Catalogue 2013
CAPACITOR PROTECTION

FUSE SELECTION FOR 3-PHASE CAPACITOR BANKS AT 415VAC


Capacitor Bank Recommended GEC,
Rating GE or IPD Fuse-Link
Rating (A)
kVAr FLC (A) Type T ‘gG’ DIN Type ‘gL’-’gG’
5 6.9 16 16
7.5 10.4 16 16
10 13.9 25 25
15 20.9 32 32
20 27.8 50 50
25 34.8 63 63
30 41.7 63 63
35 48.7 80 80
40 55.6 100 100
50 69.6 125 125
60 83.5 125 125
75 104 160 160
90 125 200 200
100 139 250 250
110 153 250 250
120 167 250 250
135 188 315 315
150 209 315 315
160 223 355 355
180 250 400 400
190 264 400 400
200 278 450 500
225 313 500 500
240 334 500 500
275 383 630 630
300 417 630 630
360 501 750 800
400 557 1000 1000
Notes:
1. Recommended fuse ratings allow for a capacitor manufacturing tolerance of +10% on the kVAr
values and the possibility of up to 30% constant overload of a capacitor bank due to harmonic
currents.

2. Suitable adjustments to the recommended ratings may be necessary for high enclosure (fluid
environment) temperatures, refer to de-rating information indicated on page 522. TECHNICAL

15
IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au
Product Catalogue 2013 505
BACKUP PROTECTION

MCCB AND SWITCH DISCONECTOR BACKUP PROTECTION


Record Plus™ circuit breakers excel in their characteristics as current and energy limiting devices. This allows one to use lighter and more economical downstream
busbar systems and switchgear.
A frequently used combination is that of a Record Plus™ breaker, used as a protection and switching device in the mains switchboard, and a Dilos load break switch,
as an incomer, in a downstream, secondary switchboard. In this application the Dilos needs to be able to withstand the current and energy values on a short-circuit
event, this taking the limiting effects of the upstream breaker into account.
The table indicates the maximum prospective short-circuit that the combination of an upstream Record Plus™ and a downstream Dilos or Record Plus™ in its switch
disconnect variant (type Y) can withstand.

Protection of Switch Disconectors (Dilos or Record PlusTM) -


Valid for 400/415V AC
Upstream Breaking Downstream Maximum Downstream Maximum
capacity, allowable allowable
Record Plus™ Icu = Ics Dilos switch short-circuit Record Plus™ short-circuit
circuit breaker (kA eff.) (kA eff.) switch (kA eff.)
FD160S 30 1 & 1H 18 FD63Y 30
FD160S 30 2 18 FD160Y 30
FD160N 50 1 & 1H 25 FD63Y 50
FD160N 50 2 25 FD160Y 50
FD160H 80 1 & 1H 30 FD63Y 80
FD160N 80 2 30 FD160Y 80
FD160L 150 1 & 1H 36 FD63Y 150
FD160L 150 2 36 FD160Y 150
FE160N 50 1 & 1H 25 FE63Y 50
FE160N 50 2 25 FE160Y 50
FE160H 80 1 & 1H 30 FE63Y 80
FE160H 80 2 30 FE160Y 80
FE160L 150 1 & 1H 36 FE63Y 150
FE160L 150 2 36 FE160Y 150
FE250N 50 3 50 FE250Y 50
FE250H 80 3 80 FE250Y 80
FE250L 150 3 150 FE250Y 150
FG400N 50 4 50 FG400Y 50
FG400H 80 4 80 FG400Y 80
FG400L 150 4 150 FG400Y 150
FG630N 50 4 50 FG630Y 50
FG630H 80 4 80 FG630Y 80
FG630L 150 4 150 FG630Y 150
FK800N 50 6 50 FK800Y 50
FK800H 80 6 80 FK800Y 80
FK1250N 50 6 50 FK1250Y 50
FK1250H 80 6 80 FK1250Y 80
FK1600N 50 7 50 FK1600Y 50
FK1600H 80 7 80 FK1600Y 80

FAULT-CURRENT LIMITER FUSES SELECTION FOR


MINIATURE CIRCUIT BREAKERS AT 415VAC 50kA
PROSPECTIVE
Miniature Minimum Maximum Fuse Rating (A)
Circuit Fuse For For
Breaker Rating GE Series Ge Series
Rating (A) (A) G60 G100
4 20 200 250
6 25 200 250
10 40 200 250
16 50 200 250
20 63 200 250
25 80 200 250
32 100 200 250
40 125 200 250
50 160 200 250
63 160 200 250
Note: Fuses are type ‘T’, ‘gG’ or DIN type ‘gL’ - ‘gG’

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


506 Product Catalogue 2013
BACKUP PROTECTION

Record Plus Moulded Case Circuit Breakers (at 400/415V AC; table B2 ed. 2c)

Upstream Record PlusTM type


FD63/160E FD63/160S FD63/160N FD63/160H FD63/160L FE160N FE160H FE160L FE250V FE250N FE250H FE250L FG400N
Icu 25 36 50 80 150 50 80 150 36 50 80 150 50
in kA
Downstream Icu of the combination in kA
Redline
G60 & GT10 10 22 25 30 36 42 30 36 42 22 30 36 36 16
G100 15 25 30 36 42 50 36 42 50 25 30 36 36 22
GT25 <=25A 25 -- 36 42 50 65 42 50 65 -- 36 42 42 --
GT25; 32 & 40A 20 -- 30 36 42 50 36 42 50 -- 36 42 42 --
GT25; 50 & 63A 15 25 30 36 42 50 36 42 50 25 30 36 36 --
Surion
GPS1B/MS <=10A 100 -- -- -- -- 150 -- -- 150 -- -- -- 150 --
GPS1B/MS 12.5A 50 -- -- -- 80 150 -- 80 150 -- -- 80 150 --
GPS1B/MS >=16A 25 -- -- 42 50 65 42 50 65 -- 42 50 65 --
GPS1B/MH <=12.5A 100 -- -- -- -- 150 -- -- 150 -- -- -- 150 --
GPS1B/MH >12.5A 50 -- -- -- 80 150 -- 80 150 -- -- 80 150 --
GPS2B/MS 10A 100 -- -- -- -- 150 -- -- 150 -- -- -- 150 --
GPS2B/MS >10A 25 -- -- 42 50 65 42 50 65 -- 42 50 65 --
GPS2B/MH 10A 100 -- -- -- -- 150 -- -- 150 -- -- -- 150 --
GPS2B/MH >10A 50 -- -- -- 80 150 -- 80 150 -- -- 80 150 --
TM
Record Plus
FD63/160C 18 22 25 30 36 42 30 36 42 22 30 36 42 30
FD63/160E 25 -- 30 36 42 50 36 42 50 -- 36 42 50 36
FD63/160S 36 -- -- 42 50 65 42 50 65 -- 42 50 65 42
FD63/160N 50 -- -- -- 80 150 -- 80 150 -- -- 80 150 --
FD63/160H 80 -- -- -- -- 150 -- -- 150 -- -- -- 150 --
FE160N 50 -- -- -- -- -- -- 80 150 -- -- 80 150 --
FE160H 80 -- -- -- -- -- -- -- 150 -- -- -- 150 --
FE250N 50 -- -- -- -- -- -- -- -- -- -- 80 150 --
FE250H 80 -- -- -- -- -- -- -- -- -- -- -- 150 --
FG400N 50 -- -- -- -- -- -- -- -- -- -- -- -- --
FG400H 80 -- -- -- -- -- -- -- -- -- -- -- -- --
FG630N 50 -- -- -- -- -- -- -- -- -- -- -- -- --
FG630H 80 -- -- -- -- -- -- -- -- -- -- -- -- --
FK800N 50 -- -- -- -- -- -- -- -- -- -- -- -- --
FK800H 80 -- -- -- -- -- -- -- -- -- -- -- -- --
FK1250N 50 -- -- -- -- -- -- -- -- -- -- -- -- --
FK1250H 80 -- -- -- -- -- -- -- -- -- -- -- -- --

Upstream Record PlusTM type


FG400H FG400L FG630N FG630H FG630L FK800N FK800H FK800L FK1250N FK1250H FK1250L FK1600N FK1600H
Icu 80 150 50 80 150 50 80 100 50 80 100 50 80
in kA
Downstream Icu of the combination in kA
Redline
G60 & GT10 10 16 16 12 12 12 -- -- -- -- -- -- -- --
G100 15 22 22 16 16 16 -- -- -- -- -- -- -- --
GT25 <=25A 25 -- -- -- -- -- -- -- -- -- -- -- -- --
GT25; 32 & 40A 20 -- -- -- -- -- -- -- -- -- -- -- -- --
GT25; 50 & 63A 15 -- -- -- -- -- -- -- -- -- -- -- -- --
Surion
GPS1B/MS <=10A 100 -- -- -- -- -- -- -- -- -- -- -- -- --
GPS1B/MS 12.5A 50 -- -- -- -- -- -- -- -- -- -- -- -- --
GPS1B/MS >=16A 25 -- -- -- -- -- -- -- -- -- -- -- -- --
GPS1B/MH <=12.5A 100 -- -- -- -- -- -- -- -- -- -- -- -- --
GPS1B/MH >12.5A 50 -- -- -- -- -- -- -- -- -- -- -- -- --
GPS2B/MS 10A 100 -- -- -- -- -- -- -- -- -- -- -- -- --
GPS2B/MS >10A 25 -- -- -- -- -- -- -- -- -- -- -- -- --
GPS2B/MH 10A 100 -- -- -- -- -- -- -- -- -- -- -- -- --
GPS2B/MH >10A 50 -- -- -- -- -- -- -- -- -- -- -- -- --
TM
Record Plus
FD63/160C 18 36 42 30 36 42 -- -- -- -- -- -- -- --
FD63/160E 25 42 50 36 42 50 -- -- -- -- -- -- -- --
FD63/160S 36 50 65 42 50 65 -- -- -- -- -- -- -- --
FD63/160N 50 80 150 -- 80 150 -- 80 100 -- 80 100 -- 80
FD63/160H 80 -- 150 -- -- 150 -- -- 100 -- -- 100 -- --
FE160N 50 80 150 -- 80 150 -- 80 100 -- 80 100 -- 80
FE160H 80 -- 150 -- -- 150 -- -- 100 -- -- 100 -- --
FE250N 50 80 150 -- 80 150 -- 80 100 -- 80 100 -- 80
FE250H 80 -- 150 -- -- 150 -- -- 100 -- -- 100 -- --
FG400N 50 80 150 -- 80 150 -- 80 100 -- 80 100 -- 80
FG400H 80 -- 150 -- -- 150 -- -- 100 -- -- 100 -- --
FG630N 50 -- -- -- 80 150 -- 80 100 -- 80 100 -- 80
FG630H 80 -- -- -- -- 150 -- -- 100 -- -- 100 -- --
FK800N 50 -- -- -- -- -- -- 80 100 -- 80 100 -- 80
TECHNICAL

FK800H 80 -- -- -- -- -- -- -- 100 -- -- 100 -- --


FK1250N
FK1250H
50
80
--
--
--
--
--
--
--
--
--
--
--
--
80
--
100
100
--
--
80
--
100
100
--
--
80
-- 15
IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au
Product Catalogue 2013 507
NOTES

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


508 Product Catalogue 2013
DISCRIMINATION & SELECTIVITY

Supply
Source

Up-Stream
Fuse

Down-Stream
Fuse

Fault Point

DISCRIMINATION BETWEEN FUSES AT 415VAC


Down-Stream Minimum Up-Stream
Fuse Rating (A) Fuse Rating (A)
Type T ‘gG’ Type T ‘gM’ DIN Type ‘gL’-’gG’ Type T ‘gG’ DIN Type ‘gL’-’gG’
2 - - 4 4
4 - 4 6 6
6 - 6 10 10
10 - 10 16 16
16 - 16 25 25
20 - 20 32 32
25 20M25 25 40 40
32 20M32 - 40 40
32 - 32 50 50
35 32M35 35 50 50
40 32M40 40 63 63
50 32M50 50 80 80
63 32M63 - 125 125
63 - 63 125 100
80 63M80 80 160 125
100 63M100 100 160 160
125 100M125 125 200 200
160 100M160 160 250 250
200 100M200 200 315 315
250 200M250 250 400 400
315 200M315 315 500 500
355 315M355 - 560 630
400 - - 630 800
400 - 400 630 630
450 400M450 - 670 800
500 - 500 750 800
560 - - 800 1000
630 - 630 1000 1000
670 630M670 - 1250 -
710 - - 1250 -
750 - - 1250 -
800 - 800 1250 -
Notes:
1. Fuses must be GE or IPD brands of fuse-links only. Not applicable for other manufacturers’ fuses.

2. The selected fuse ratings achieve discrimination for overload conditions and short-circuit currents up
to 80kA.

3. This discrimination ensures that the down-stream fuse operates and the up-stream fuse remains
unaffected.

4. Where the up-stream fuse supplies more than one down-stream fuse, the minimum up-stream fuse
TECHNICAL

rating should be increased to allow for load biasing effects.

15
IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au
Product Catalogue 2013 509
DISCRIMINATION & SELECTIVITY

SELECTIVITY DISCRIMINATION TABLES


Selectivity Discrimination tables: Where discrimination is partial the selectivity limits in kA Is are listed. Where ‘T’ is found in the tables, this indicates total discrimination
up to the highest breaking capacity of the devices.
These discrimination/selectivity limits are only valid if the ratio between the current settimes, ranks or time settings of upstream & downstream breakers are equal or
higher than the factor indicated below.

TM
L

TM

TM
1.6
20

TM

Terminology
LTM Thermal Magnetic Trip Unit
Ir = Overload setting Im = Magnetic setting
LTMD Selective Thermal Magnetic Trip Unit
Ir = Overload setting Im = Magnetic setting
Mag. Break™ Magnetic Only Trip Unit
Im = Magnetic setting
SMR1 & SMR1e Selective Electronic Trip Unit
Ir = Setting on LT device Ist = Setting on ST device
SMR1s, g and SMR2 Enhanced Electronic trip Unit
MPRO 17, 20, 30 & 40 Mpact Electronic Trip Unit
Ir = Setting on LT device Ist = Setting on ST device

LTD class, time setting at 7.2 x Ir STD Delay setting on ST device


A2S Cropped short time delay setting
Inst. = Setting on I ( Instantaneous ) device

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


510 Product Catalogue 2013
DISCRIMINATION & SELECTIVITY

SELECTIVE TABLES
(RECORD PLUS MOULDED CASE CIRCUIT BREAKERS; TABLE D1 ED. 2C)

Upstream FDC & FDE 63/160 LTM FDS 63/160 LTMD FDN, H & L 63/160 LTMD
In in A In in A In in A
In 40 50 63 80 100 125/160 40 50 63 80 100 125/ 160 40 50 63 80 100 125/160
Downstream (A) Selectivity limit in kA*
16 0.6kA 2.5kA 6kA 6kA T T T T T T T T T T T T T T
20 0.6kA 2.5kA 3kA 6kA 8kA T 3.5kA T T T T T 3.5kA T T T T T
25 - 0.8kA 1.2kA 6kA 6kA T 1.6kA 3.5kA T T T T 1.6kA 3.5kA T T T T
32 - - 1.2kA 3kA 6kA 8kA - - 10kA T T T - - 10kA T T T
40 - - - 3kA 4kA 6kA - - 3.5kA T T T - - 3.5kA T T T
50 - - - 1.2kA 1.5kA 6kA - - - 3.5kA T T - - - 3.5kA T T
63 - - - - 1.5kA 2kA - - - - 8kA T - - - - 8kA T
16 0.6kA 2.5kA 6kA 6kA 10kA T 10kA 10kA T T T T 10kA 10kA T T T T
20 0.6kA 2.5kA 3kA 6kA 8kA T 3.5kA 10kA T T T T 3.5kA 10kA T T T T
25 - 0.8kA 1.2kA 6kA 6kA T 1.6kA 3.5kA T T T T 1.6kA 3.5kA T T T T
32 - - 1.2kA 3kA 6kA 8kA - - 10kA 10kA T T - - 10kA 10kA T T
40 - - - 3kA 4kA 6kA - - 3.5kA 10kA T T - - 3.5kA 10kA T T
50 - - - 1.2kA 1.5kA 6kA - - - 3.5kA 10kA T - - - 3.5kA 10kA T
63 - - - - 1.5kA 2kA - - - - 8kA T - - - - 8kA T
16 0.6kA 2.5kA 6kA 6kA 10kA T 10kA 10kA T T T T 10kA 10kA T T T T
20 0.6kA 2.5kA 3kA 6kA 8kA T 3.5kA 10kA T T T T 3.5kA 10kA T T T T
25 - 0.8kA 1.2kA 6kA 6kA T 1.6kA 3.5kA 15kA T T T 1.6kA 3.5kA 15kA T T T
32 - - 1.2kA 3kA 6kA 8kA - - 10kA 10kA T T - - 10kA 10kA T T
40 - - - 3kA 4kA 6kA - - 3.5kA 10kA 15kA T - - 3.5kA 10kA 15kA T
50 - - - 1.2kA 1.5kA 6kA - - - 3.5kA 10kA T - - - 3.5kA 10kA T
63 - - - - 1.5kA 2kA - - - - 8kA T - - - - 8kA T
Redline 80 - - - - - 1.9kA - - - - - 2.5kA - - - - - 2.5kA
HTI C curve 100 - - - - - 1.9kA - - - - - 2.5kA - - - - - 2.5kA
GPS1BS & 20 0.6kA 2.5kA 6kA 6kA 10kA T 10kA 10kA T T T T 10kA 10kA T T T T
GPS1MS 25 - 1kA 1.2kA 6kA 6kA T - 3.5kA 15kA 15kA T T - 3.5kA 15kA 15kA T T
GPS2BS & 32 - - 1.2kA 3kA 6kA 10kA - - 6kA 6kA T T - - 6kA 6kA T T
GPS2MS
40 - - - 3kA 4kA 6kA - - - 6kA T T - - - 6kA T T
50 - - - 1.2kA 1.6kA 6kA - - - 3.5kA T T - - - 3.5kA T T
63 - - - - 1.6kA 2kA - - - - 8kA T - - - - 8kA T
20 T T T T T T T T T T T T T T T T T T
25 - 2.5kA 15kA 15kA T T - 3.5kA T T T T - 3.5kA T T T T
32 - - 6kA 6kA 8kA T - - T T T T - - T T T T
40 - - - 6kA 8kA T - - T T T T - - T T T T
50 - - - - 6kA T - - - 3.5kA T T - - - 3.5kA T T
63 - - - - - T - - - - 8kA T - - - - 8kA T
25 0.4kA 0.5kA 0.6kA 0.8kA 1kA 1.3kA 0.6kA 0.8kA 0.9kA 1.2kA 1.5kA 3.5kA 0.6kA 0.8kA 0.9kA 1.2kA 1.5kA 3.5kA
- 0.5kA 0.6kA 0.8kA 1kA 1.3kA - 0.8kA 0.9kA 1.2kA 1.5kA 3.5kA - 0.8kA 0.9kA 1.2kA 1.5kA 3.5kA
Record Plus

32
40 - - - 0.8kA 1kA 1.3kA - - - 1.2kA 1.5kA 3.5kA - - - 1.2kA 1.5kA 3.5kA
50 - - - 0.8kA 1kA 1.3kA - - - 1.2kA 1.5kA 3.5kA - - - 1.2kA 1.5kA 3.5kA
63 - - - - 1kA 1.3kA - - - - 1.5kA 3.5kA - - - - 1.5kA 3.5kA
80 - - - - - 1.3kA - - - - - 3.5kA - - - - - 3.5kA

Remark; For MCB’s with D type Curve assume a C curve type with a one step higher rating.
E.G. Selectivity FD160 80Amp LTM with downstream C Curve 40A MCB = 3kA, for D curve 40A, take the value mentioned for 50A C curve, here 1.2kA

*Where T is mentioned Selectivity is full up until the Icu of the downstream device
TECHNICAL

15
IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au
Product Catalogue 2013 511
DISCRIMINATION & SELECTIVITY

SELECTIVE TABLES
(RECORD PLUS MOULDED CASE CIRCUIT BREAKERS; TABLE D2 ED. 2C)
Upstream FE160N, H & L LTM FE160N, H & L LTMD FE160N, H & L SMR1 FE250V LTM FE250N, H & L LTMD FE250N, H & L SMR1
63A 80A 100A 125A 160A 100A 125A 160A 63A 125A 160A 160A 200A 250A 125A 160A 200A 250A 125A 160A 250A
Downstream
In (A) Selectivity limit in kA*
Redline <= 20A 6kA 6kA 8kA T T T T T T T T T T T T T T T T T T
25A 1.2kA 6kA 6kA T T T T T T T T T T T T T T T T T T
DME100 32A 1.2kA 3kA 6kA 8kA T T T T T T T T T T T T T T T T T
B/C curve 40A -- 3kA 4kA 6kA 6kA T T T T T T T T T T T T T T T T
50A -- -- 1.5kA 6kA 6kA T T T -- T T T T T T T T T T T T
63A -- -- 1.5kA 2kA 2kA T T T -- T T T T T T T T T T T T
Redline <= 20A 6kA 6kA 8kA T T T T T T T T T T T T T T T T T T
G60 & DM100 25A 1.2kA 6kA 6kA T T T T T T T T T T T T T T T T T T
B/C curve 32A 1.2kA 3kA 6kA 8kA T T T T T T T T T T T T T T T T T
40A -- 3kA 4kA 6kA 6kA T T T T T T T T T T T T T T T T
50A -- 1.2kA 1.5kA 6kA 6kA T T T -- T T T T T T T T T T T T
63A -- -- 1.5kA 2kA 2kA T T T -- T T T T T T T T T T T T
Redline <= 20A 6kA 6kA 8kA T T T T T T T T T T T T T T T T T T
G100 & GT25 25A 1.2kA 6kA 6kA T T T T T T T T T T T T T T T T T T
B/C curve 32A 1.2kA 3kA 6kA 8kA T T T T T T T T T T T T T T T T T
40A -- 3kA 4kA 6kA 6kA T T T T T T T T T T T T T T T T
50A -- -- 1.5kA 6kA 6kA T T T -- T T T T T T T T T T T T
63A -- -- 1.5kA 2kA 2kA T T T -- T T T T T T T T T T T T
Redline 80A -- -- 1.5kA 2kA 2kA -- T T -- T T 1.9kA 2.5kA 3kA T T T T T T T
HTI 100A -- -- -- -- 2kA -- -- T -- -- T 1.9kA 2.5kA 3kA -- T T T -- T T
C curve 125A -- -- -- -- -- -- -- -- -- -- -- -- -- 3kA -- T T T -- T T
Surion <= 20A 6kA 6kA 10kA T T T T T T T T T T T T T T T T T T
GPS1BS & 25A 1.2kA 6kA 6kA T T T T T T T T T T T T T T T T T T
GPS1MS 32A 1.2kA 3kA 6kA 10kA 10kA T T T T T T 10kA T T T T T T T T T
GPS2BS & 40A -- -- 4kA 6kA 6kA T T T T T T 6kA 10kA T T T T T T T T
GPS2MS 50A -- -- 1.6kA 6kA 6kA T T T -- T T 6kA 6kA 10kA T T T T T T T
63A -- -- -- 2kA 2kA -- T T -- T T 2kA 6kA 6kA T T T T T T T
Surion <= 20A T T T T T T T T T T T T T T T T T T T T T
GPS1BH & 25A 15kA 15kA T T T T T T T T T T T T T T T T T T T
GPS1MH 32A 6kA 6kA 8kA T T T T T T T T T T T T T T T T T T
GPS2BH & 40A -- 6kA 8kA T T T T T T T T T T T T T T T T T T
GPS2MH 50A -- -- 6kA T T T T T -- T T T T T T T T T T T T
63A -- -- -- T T -- T T -- T T T T T T T T T T T T
Record Plus <= 40A -- 0.8kA 1kA 1.2kA 1.6kA T T T T T T 1.6kA 2kA 2.5kA T T T T T T T
FD63/160E 50A -- -- 1kA 1.2kA 1.6kA T T T -- T T 1.6kA 2kA 2.5kA T T T T T T T
LTM/MO/GTM 63A -- -- -- 1.2kA 1.6kA T T T -- T T 1.6kA 2kA 2.5kA T T T T T T T
80A -- -- -- 1.2kA 1.6kA -- T T -- -- T 1.6kA 2kA 2.5kA T T T T T T T
100A -- -- -- -- 1.6kA -- -- T -- -- T 1.6kA 2kA 2.5kA -- T T T -- T T
125A -- -- -- -- -- -- -- -- -- -- -- -- 2kA 2.5kA -- -- T T -- -- T
160A -- -- -- -- -- -- -- -- -- -- -- -- -- 2.5kA -- -- -- T -- -- T
Record Plus <= 40A 0.6kA 0.8kA 1kA 1.2kA 1.6kA 30kA 30kA 30kA 36kA 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA
FD63/160S, N 50A -- 0.8kA 1kA 1.2kA 1.6kA 30kA 30kA 30kA -- 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA
H&L 63A -- -- 1kA 1.2kA 1.6kA 30kA 30kA 30kA -- 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA
LTMD 80A -- -- -- 1.2kA 1.6kA -- 30kA 30kA -- 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA
100A -- -- -- -- 1.6kA -- -- 30kA -- -- 36kA 1.6kA 2kA 2.5kA -- 42kA 42kA 42kA -- 50kA 50kA
125A -- -- -- -- -- -- -- -- -- -- -- -- 2kA 2.5kA -- -- 42kA 42kA -- -- 50kA
160A -- -- -- -- -- -- -- -- -- -- -- -- -- 2.5kA -- -- -- 42kA -- -- 50kA
Record Plus <= 40A 0.6kA 0.8kA 1kA 1.2kA 1.6kA 30kA 30kA 30kA 36kA 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA
FE160 N, H & L 50A -- 0.8kA 1kA 1.2kA 1.6kA 30kA 30kA 30kA -- 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA
LTM/MO/GTM 63A -- -- 1kA 1.2kA 1.6kA 30kA 30kA 30kA -- 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA
80A -- -- -- 1.2kA 1.6kA -- 30kA 30kA -- 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA
100A -- -- -- -- 1.6kA -- -- 30kA -- -- 36kA 1.6kA 2kA 2.5kA -- 42kA 42kA 42kA -- 50kA 50kA
125A -- -- -- -- -- -- -- -- -- -- -- -- 2kA 2.5kA -- -- 42kA 42kA -- -- 50kA
160A -- -- -- -- -- -- -- -- -- -- -- -- -- 2.5kA -- -- -- 42kA -- -- 50kA

*Where T is mentioned Selectivity is full up until the Icu of the downstream device.

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


512 Product Catalogue 2013
DISCRIMINATION & SELECTIVITY

SELECTIVE TABLES
(RECORD PLUS MOULDED CASE CIRCUIT BREAKERS; TABLE D3 ED. 2C)
Upstream FE160N, H & L SMR1 FE250N, H & L LTMD FE250N, H & L SMR1 FG400N, H & L SMR1 & 2 FG630N, H & L SMR1 & 2
63A 125A 160A 125A 160A 200A 250A 125A 160A 250A 250A 350A 400A 400A 500A 630A
Downstream
In (A) Selectivity limit in kA*
Redline <= 16A T T T T T T T T T T T T T T T T
20A T T T T T T T T T T T T T T T T
G60 25A T T T T T T T T T T T T T T T T
G100 & G25 32A T T T T T T T T T T T T T T T T
DM100 & 40A -- T T T T T T T T T T T T T T T
DME100 50A -- T T T T T T T T T T T T T T T
B/C curve 63A -- T T T T T T T T T T T T T T T
Redline 80A -- T T -- T T T T T T T T T T T T
HTI 100A -- -- T -- T T T -- T T T T T T T T
C curve 125A -- -- T -- -- T T -- T T T T T T T T
Surion <= 25A T T T T T T T T T T T T T T T T
GPS1BS & 32A T T T T T T T T T T T T T T T T
GPS1MS 40A -- T T T T T T T T T T T T T T T
GPS2BS & 50A -- T T T T T T T T T T T T T T T
GPS2MS 63A -- T T T T T T T T T T T T T T T
Surion <= 25A T T T T T T T T T T T T T T T T
GPS1BH & 32A T T T T T T T T T T T T T T T T
GPS1MH 40A -- T T T T T T T T T T T T T T T
GPS2BH & 50A -- T T T T T T T T T T T T T T T
GPS2MH 63A -- T T T T T T T T T T T T T T T
Record Plus <= 40A T T T T T T T T T T T T T T T T
FD63/160E 50A -- T T T T T T T T T T T T T T T
LTM/MO/GTM 63A -- T T T T T T T T T T T T T T T
80A -- -- T -- T T T T T T T T T T T T
100A -- -- T -- -- T T -- T T T T T T T T
125A -- -- -- -- -- T T -- -- T T T T T T T
160A -- -- -- -- -- -- T -- -- T T T T T T T
Record Plus <= 40A 36kA 36kA 36kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA T T T T T T
FD63/160S, N 50A -- 36kA 36kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA T T T T T T
H&L 63A -- 36kA 36kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA T T T T T T
LTMD/MO/GTM 80A -- -- 36kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA T T T T T T
100A -- -- 36kA -- 42kA 42kA 42kA -- 50kA 50kA T T T T T T
125A -- -- -- -- -- 42kA 42kA -- -- 50kA T T T T T T
160A -- -- -- -- -- -- 42kA -- -- 50kA T T T T T T
Record Plus <= 40A 36kA 36kA 36kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA T T T T T T
FE160 N, H & L 50A -- 36kA 36kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA T T T T T T
LTM/MO/GTM 63A -- 36kA 36kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA T T T T T T
80A -- 36kA 36kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA T T T T T T
100A -- -- 36kA -- 42kA 42kA 42kA -- 50kA 50kA T T T T T T
125A -- -- -- -- -- 42kA 42kA -- -- 50kA T T T T T T
160A -- -- -- -- -- -- 42kA -- -- 50kA T T T T T T
Record Plus <= 40A 0.8kA 1.8kA 2.2kA 1.3kA 1.6kA 2.5kA 2.5kA 1.8kA 2.2kA 3.5kA T T T T T T
FE160 N, H & L 63A -- 1.8kA 2.2kA 1.3kA 1.6kA 2.5kA 2.5kA 1.8kA 2.2kA 3.5kA T T T T T T
LTMD/SMR1 80A -- 1.8kA 2.2kA 1.3kA 1.6kA 2.5kA 2.5kA 1.8kA 2.2kA 3.5kA T T T T T T
100A -- -- 2.2kA -- 1.6kA 2.5kA 2.5kA -- 2.2kA 3.5kA T T T T T T
125A -- -- -- -- -- 2.5kA 2.5kA -- -- 3.5kA T T T T T T
160A -- -- -- -- -- -- 2.5kA -- -- 3.5kA T T T T T T
Record Plus 125A -- -- -- -- -- -- -- -- -- -- 3.5kA 10kA 15kA T T T
FE250 N, H & L 160A -- -- -- -- -- -- -- -- -- -- 3.5kA 10kA 15kA T T T
LTMD/SMR1 200A -- -- -- -- -- -- -- -- -- -- -- 10kA 15kA T T T
250A -- -- -- -- -- -- -- -- -- -- -- 10kA 15kA T T T
Record Plus
FG400 N, H & L 250A -- -- -- -- -- -- -- -- -- -- -- 5kA 6kA 5kA 7kA 7kA
SMR1/SMR2 400A -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- 7kA

*Where T is mentioned Selectivity is full up until the Icu of the downstream device.
TECHNICAL

15
IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au
Product Catalogue 2013 513
DISCRIMINATION & SELECTIVITY

SELECTIVE TABLES
(RECORD PLUS MOULDED CASE CIRCUIT BREAKERS; TABLE D4 ED. 2C)
Upstream FK800N, H FK1250N, H & FK1600N, H &
& L SMR1 L SMR1 L SMR1
800A 1000A 1250A 600A
Downstream In (A) Selectivity limit in kA*
Redline
G60, G100, G25, DM60,
DME60, DM100 & DME100 B/C curve ALL T T T T T
Surion
GPS1BS, GPS1MS, GPS2BS, GPS2MS
GPS1BH, GPS1MH, GPS2BH & GPS2MH ALL T T T T T
Record Plus
FD63/160E, S N & L types
LTM/LTMD/MO/GTM Trip Units ALL T T T T T
Record Plus
FE160 N, H & L types
LTM/LTMD/MO/GTM/SMR1 Trip Units ALL T T T T T
Record Plus
FE250 V, N, H & L types
LTM/LTMD/MO/GTM/SMR1 Trip Units ALL T T T T T
Record Plus
FG400 N, H & L types
SMR1/SMR2 Trip Units ALL T T T T T
Record Plus
FG630 N, H & L types
SMR1/SMR2 Trip Units 400A 15kA T T T T
500A 15kA T T T T
630A 15kA T T T T
Record Plus
FK800 N, H & L types
LTM/MO/SMR1e, s & g Trip Units ALL -- 15kA 15kA 25kA 25kA
Record Plus
FK1250 N, H & L types
LTM/MO/SMR1e, s & g Trip Units 1000A -- -- -- 25kA 25kA
1250A -- -- -- 25kA 25kA
* Where T is mentioned Selectivity is full up untilthe Icu of the downstream device

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


514 Product Catalogue 2013
DISCRIMINATION & SELECTIVITY

SELECTIVE TABLES
(RECORD PLUS MOULDED CASE CIRCUIT BREAKERS; TABLE D4 ED. 2C)
Upstream Mpact + Frame 1 Mpact + Frame 2 Mpact + Frame3
400A 630A 800A 1000A 1250A 1600A 2000A 2500A 1000A 1250A 1600A 2000A 2500A 3200A 4000A 5000A 6300A
Downstream

In (A) Selectivity limit in kA*


Redline
G60,G100,G25, DM60,
DME60, DM100 & DME100 B/C curve ALL T T T T T T T T T T T T T T T T T
Surion
GPS1BS, GPS1MS, GPS2BS, GPS2MS
GPS1BH, GPS1MH, GPS2BH & GPS2MH ALL T T T T T T T T T T T T T T T T T
Record Plus
FD63/160E, S N & L types
LTM/LTMD/MO/GTM Trip Units ALL T T T T T T T T T T T T T T T T T

FE160 N, H & L types


LTM/LTMD/MO/GTM/SMR1 Trip Units ALL T T T T T T T T T T T T T T T T T
Record Plus
FE250 V, N, H & L types
LTM/LTMD/MO/GTM/SMR1 Trip Units ALL T T T T T T T T T T T T T T T T T
Record Plus
FG400 N, H & L types
SMR1/SMR2 Trip Units 250A T T T T T T T T T T T T T T T T T
400A -- -- T T T T T T T T T T T T T T T
Record Plus
FG630 N, H & L types
SMR1/SMR2 Trip Units 400A -- -- T T T T T T T T T T T T T T T
500A -- -- -- T T T T T T T T T T T T T T
630A -- -- -- T T T T T T T T T T T T T T
Record Plus
FK800 N, H & L types
LTM/MO/SMR1e, s & g Trip Units ALL -- -- -- -- T T T T T T T T T T T T T
Record Plus
FK1250 N, H & L types
LTM/MO/SMR1e, s & g Trip Units 1000A -- -- -- -- -- T T T -- -- T T T T T T T
1250A -- -- -- -- -- -- T T -- -- -- T T T T T T
Mpact Plus
Frame 1 & Frame 2
MPRO plus 17, 18, 30 & 40 Trip Units 400A -- T T T T T T T T T T T T T T T T
630A -- -- -- T T T T T T T T T T T T T T
800A -- -- -- -- T T T T -- T T T T T T T T
1000A -- -- -- -- -- T T T -- -- T T T T T T T
1600A -- -- -- -- -- -- -- T -- -- -- -- T T T T T
2000A -- -- -- -- -- -- -- -- -- -- -- -- -- T T T T
2500A -- -- -- -- -- -- -- -- -- -- -- -- -- -- T T T
* Where T is mentioned Selectivity is full up until the Icu of the downstream device
TECHNICAL

15
IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au
Product Catalogue 2013 515
DISCRIMINATION & SELECTIVITY

SELECTIVE PLUS TABLES


(RECORD PLUS MOULDED CASE CIRCUIT BREAKERS; TABLE DB1 ED. 2C)
Upstream FDC 63/160 LTM FDE 63/160 LTM FDS 63/160 LTMD

63A 80A 100A


125A 63A 80A 100A 125A 63A 80A 100A 125A
Downstream 160A 160A 160A
In (A) Selectivity limit in kA / Icu of combination in kA at 400-415V AC
Redline <= 16A 6/18 6/18 10/18 18/18 6/22 6/22 10/22 22/22 25/25 25/25 25/25 25/25
G60 &GT10 20A 3/18 6/18 8/18 18/18 3/22 6/22 8/22 22/22 25/25 25/25 25/25 25/25
B/C curve 25A -- 6/18 6/18 18/18 -- 6/22 6/22 22/22 15/25 15/25 25/25 25/25
32A -- 3/18 6/18 18/18 -- 3/22 6/22 22/22 10/25 10/25 25/25 25/25
40A -- 3/18 4/18 18/18 -- 3/22 4/22 22/22 3.5/25 10/25 15/25 25/25
50A -- -- 1.5/18 6/18 -- -- 1.5/22 6/22 -- 3.5/25 10/25 22/25
63A -- -- -- -- -- -- -- -- -- -- 8/25 22/25
Redline <= 16A 6/18 6/18 10/18 18/18 6/25 6/25 10/25 25/25 30/30 30/30 30/30 30/30
G100 20A 3/18 6/18 8/18 18/18 3/25 6/25 8/25 25/25 30/30 30/30 30/30 30/30
B/C curve 25A -- 6/18 6/18 18/18 -- 6/25 6/25 25/25 15/30 30/30 30/30 30/30
32A -- 3/18 6/18 18/18 -- 3/25 6/25 25/25 10/30 10/30 30/30 30/30
40A -- 3/18 4/18 18/18 -- 3/25 4/25 25/25 3.5/30 10/30 15/30 25/30
50A -- -- 1.5/18 6/18 -- -- -- 6/25 -- 3.5/30 10/30 22/30
63A -- -- -- 2/18 -- -- -- 2/25 -- -- 8/30 22/30
Redline <= 20A -- -- -- -- -- -- -- -- 36/36 36/36 36/36 36/36
GT25 25A -- -- -- -- -- -- -- -- 15/36 15/36 30/36 30/36
B/C curve 32A -- -- -- -- -- -- -- -- 10/30 10/30 36/30 30/30
40A -- -- -- -- -- -- -- -- 3.5/30 10/30 15/30 25/30
50A -- -- -- -- -- -- -- -- -- 3.5/30 10/30 22/30
63A -- -- -- -- -- -- -- -- -- -- 8/30 22/30
Surion <= 10A -- -- -- -- -- -- -- -- -- -- -- --
GPS1BS & 12.5A -- -- -- -- -- -- -- -- -- -- -- --
GPS1MS 16/20A -- -- -- -- -- -- -- -- 36/36 36/36 36/36 36/36
25/32A -- -- -- -- -- -- -- -- 36/36 36/36 36/36 36/36
40A -- -- -- -- -- -- -- -- -- 36/36 36/36 36/36
50/63A -- -- -- -- -- -- -- -- -- -- 36/36 36/36
Surion <= 10A -- -- -- -- -- -- -- -- -- -- -- --
GPS2BS & 12.5A -- -- -- -- -- -- -- -- 36/36 36/36 36/36 36/36
GPS2MS 16/20A -- -- -- -- -- -- -- -- 36/36 36/36 36/36 36/36
25/32A -- -- -- -- -- -- -- -- 36/36 36/36 36/36 36/36
40A -- -- -- -- -- -- -- -- -- 36/36 36/36 36/36
50/63A -- -- -- -- -- -- -- -- -- -- 36/36 36/36
Surion <= 10A -- -- -- -- -- -- -- -- -- -- -- --
GPS1BH & 12.5A -- -- -- -- -- -- -- -- -- -- -- --
GPS1MH 16/20A -- -- -- -- -- -- -- -- -- -- -- --
GPS2BH & 25/32A -- -- -- -- -- -- -- -- -- -- -- --
GPS2MH 40A -- -- -- -- -- -- -- -- -- -- -- --
50/63A -- -- -- -- -- -- -- -- -- -- -- --

Upstream FDN 63/160 LTMD FDH 63/160 LTMD FDL 63/160 LTMD

63A 80A 100A 125A 63A 80A 100A 125A 63A 80A 100A 125A
Downstream 160A 160A 160A
In (A) Selectivity limit in kA / Icu of combination in kA at 400-415V AC
Redline <= 16A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/42 36/42 36/42 36/42
G60 &GT10 20A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/42 36/42 36/42 36/42
B/C curve 25A 15/30 15/30 30/30 30/30 15/36 15/36 30/36 30/36 15/42 15/42 30/42 30/42
32A 10/30 10/30 30/30 30/30 10/36 10/36 36/36 30/36 10/42 10/42 36/42 30/42
40A 3.5/30 10/30 15/30 25/30 3.5/36 10/36 15/36 25/36 3.5/42 10/42 15/42 25/42
50A -- 3.5/30 10/30 22/30 -- 3.5/36 10/36 22/36 -- 3.5/42 10/42 22/42
63A -- -- 8/30 22/30 -- -- 8/36 22/36 -- -- 8/42 22/42
Redline <= 16A 36/36 36/36 36/36 36/36 36/42 36/42 36/42 36/42 36/50 36/50 36/50 36/50
G100 20A 36/36 36/36 36/36 36/36 36/42 36/42 36/42 36/42 36/50 36/50 36/50 36/50
B/C curve 25A 15/36 36/36 30/36 30/36 15/42 36/42 30/42 30/42 15/50 15/50 30/50 30/50
32A 10/36 10/36 30/36 30/36 10/42 10/42 30/42 30/42 10/50 10/50 30/50 30/50
40A 3.5/36 10/36 15/36 25/36 3.5/42 10/42 15/42 25/42 3.5/50 10/50 15/50 25/50
50A -- 3.5/36 10/36 22/36 -- 3.5/42 10/42 22/42 -- 3.5/50 10/50 22/50
63A -- -- 8/36 22/36 -- -- 8/42 22/42 -- -- 8/50 22/50
Redline <= 20A 36/42 36/42 36/42 36/42 36/50 36/50 36/50 36/50 36/65 36/65 36/65 36/65
GT25 25A 15/42 15/42 30/42 30/42 15/50 15/50 30/50 30/50 15/65 15/65 30/65 30/65
B/C curve 32A 10/36 10/36 36/36 30/36 10/42 10/42 36/42 30/42 10/50 10/50 36/50 30/50
40A 3.5/36 10/36 15/36 25/36 3.5/42 10/42 15/42 25/42 3.5/50 10/50 15/50 25/50
50A -- 3.5/36 10/36 22/36 -- 3.5/42 10/42 22/42 -- 3.5/50 10/50 22/50
63A -- -- 8/36 22/36 -- -- 8/42 22/42 -- -- 8/50 22/50
Surion <= 10A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150
GPS1BS & 12.5A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150
GPS1MS 16/20A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65
25/32A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65
40A -- 42/42 42/42 42/42 -- 50/50 50/50 50/50 -- 65/65 65/65 65/65
50/63A -- -- 42/42 42/42 -- -- 50/50 50/50 -- -- 65/65 65/65
Surion <= 10A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150
GPS2BS & 12.5A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65
GPS2MS 16/20A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65
25/32A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65
40A -- 42/42 42/42 42/42 -- 50/50 50/50 50/50 -- 65/65 65/65 65/65
50/63A -- -- 42/42 42/42 -- -- 50/50 50/50 -- -- 65/65 65/65
Surion <= 10A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150
GPS1BH & 12.5A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150
GPS1MH 16/20A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150
GPS2BH & 25/32A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150
GPS2MH 40A -- -- -- -- -- 80/80 80/80 80/80 -- 150/150 150/150 150/150
50/63A -- -- -- -- -- -- 80/80 80/80 -- -- 150/150 150/150

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


516 Product Catalogue 2013
DISCRIMINATION & SELECTIVITY

SELECTIVE PLUS
TABLE DB1A ED 2C
Upstream FDC 63/160 LTM FDE 63/160 LTM FDS 63/160 LTMD

63A 80A 100A 125A 63A 80A 100A 125A 63A 80A 100A 125A
Downstream 160A 160A 160A
In (A) Selectivity limit in kA / Icu of combination in kA at 240V AC
Redline <= 16A 6/18 6/18 10/18 18/18 6/22 6/22 10/22 10/22 25/25 25/25 25/25 25/25
DME100 20A 3/18 6/18 8/18 18/18 3/22 6/22 8/22 10/22 25/25 25/25 25/25 25/25
B/C curve 25A -- 6/18 6/18 18/18 -- 6/22 6/22 10/22 15/25 25/25 25/25 25/25
32A -- 3/18 6/18 18/18 -- 3/22 6/22 10/22 10/25 10/25 25/25 25/25
40A -- 3/18 4/18 18/18 -- 3/22 4/22 10/22 3.5/25 10/25 15/25 25/25

Upstream FDN 63/160 LTMD FDH 63/160 LTMD FDL 63/160 LTMD

63A 80A 100A 125A 63A 80A 100A 125A 63A 80A 100A 125A
Downstream 160A 160A 160A
In (A) Selectivity limit in kA / Icu of combination in kA at 240V AC
Redline <= 16A 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25
DME100 20A 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25
B/C curve 25A 15/25 25/25 25/25 25/25 15/25 25/25 25/25 25/25 15/25 25/25 25/25 25/25
32A 10/25 10/25 25/25 25/25 10/25 10/25 25/25 25/25 10/25 10/25 25/25 25/25
40A 3.5/25 10/25 15/25 25/25 3.5/25 10/25 15/25 25/25 3.5/25 10/25 15/25 25/25

SELECTIVE PLUS
TABLE DB2A ED 2C
Upstream FE160N-LTMD/SMR1 FE160H-LTMD/SMR1 FE160L-LTMD/SMR1

63A 100A 125A 160A 63A 100A 125A 160A 63A 100A 125A 160A
Downstream
In (A) Selectivity limit in kA / Icu of combination in kA at 240V AC
Redline <= 16A 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22
DME100 20A 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22
B/C curve 25A 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22
32A 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22
40A -- 22/22 22/22 22/22 -- 22/22 22/22 22/22 -- 22/22 22/22 22/22

Upstream FE250N-LTMD/SMR1 FE250H-LTMD/SMR1 FE250L-LTMD/SMR1

125A 160A 200A 250A 125A 160A 200A 250A 125A 160A 200A 250A
Downstream
In (A) Selectivity limit in kA / Icu of combination in kA at 240V AC
Redline <= 16A 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18
DME100 20A 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18
B/C curve 25A 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18
32A 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18
40A 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18
TECHNICAL

15
IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au
Product Catalogue 2013 517
DISCRIMINATION & SELECTIVITY

SELECTIVE PLUS
TABLE DB2 ED 2C
Upstream FE160N-LTMD/SMR1 FE160H-LTMD/SMR1 FE160L-LTMD/SMR1

63A 100A 125A 160A 63A 100A 125A 160A 63A 100A 125A 160A
Downstream
In (A) Selectivity limit in kA / Icu of combination in kA at 400-415V AC
Redline <= 25A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42
G60 &GT10 32A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42
B/C curve 40A -- 30/30 30/30 30/30 -- 36/36 36/36 36/36 -- 42/42 42/42 42/42
50A -- 30/30 30/30 30/30 -- 36/36 36/36 36/36 -- 42/42 42/42 42/42
63A -- -- 30/30 30/30 -- -- 36/36 36/36 -- -- 42/42 42/42
Redline <= 25A 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50
G100 32A 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50
B/C curve 40A -- 36/36 36/36 36/36 -- 42/42 42/42 42/42 -- 50/50 50/50 50/50
50A -- 36/36 36/36 36/36 -- 42/42 42/42 42/42 -- 50/50 50/50 50/50
63A -- -- 36/36 36/36 -- -- 42/42 42/42 -- -- 50/50 50/50
Redline <= 25A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65
GT25 32A 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50
B/C curve 40A -- 36/36 36/36 36/36 -- 42/42 42/42 42/42 -- 50/50 50/50 50/50
50A -- 36/36 36/36 36/36 -- 42/42 42/42 42/42 -- 50/50 50/50 50/50
63A -- -- 36/36 36/36 -- -- 42/42 42/42 -- -- 50/50 50/50
Surion <= 10A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150
GPS1BS & 12.5A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150
GPS1MS 16/20A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65
25/32A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65
40A -- 42/42 42/42 42/42 -- 50/50 50/50 50/50 -- 65/65 65/65 65/65
50/63A -- -- 42/42 42/42 -- -- 50/50 50/50 -- -- 65/65 65/65
Surion <= 10A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150
GPS2BS & 12.5A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65
GPS2MS 16/20A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65
25/32A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65
40A -- 42/42 42/42 42/42 -- 50/50 50/50 50/50 -- 65/65 65/65 65/65
50/63A -- -- 42/42 42/42 -- -- 50/50 50/50 -- -- 65/65 65/65
Surion <= 10A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150
GPS1BH & 12.5A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150
GPS1MH 16/20A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150
GPS2BH & 25/32A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150
GPS2MH 40A -- -- -- -- -- 80/80 80/80 80/80 -- 150/150 150/150 150/150
50/63A -- -- -- -- -- -- 80/80 80/80 -- -- 150/150 150/150

Upstream FE250N-LTMD/SMR1 FE250H-LTMD/SMR1 FE250L-LTMD/SMR1

125A 160A 200A 250A 125A 160A 200A 250A 125A 160A 200A 250A
Downstream
In (A) Selectivity limit in kA / Icu of combination in kA at 400-415V AC
Redline <= 25A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36
G60 &GT10 32A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36
B/C curve 40A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36
50A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36
63A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36
Redline <= 25A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36
G100 32A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36
B/C curve 40A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36
50A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36
63A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36
Redline <= 25A 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 42/42 42/42 42/42 42/42
GT25 32A 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 42/42 42/42 42/42 42/42
B/C curve 40A 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 42/42 42/42 42/42 42/42
50A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36
63A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36
Surion <= 10A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150
GPS1BS & 12.5A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150
GPS1MS 16/20A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65
25/32A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65
40A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65
50/63A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65
Surion <= 10A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150
GPS2BS & 12.5A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65
GPS2MS 16/20A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65
25/32A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65
40A 42/42 42/42 42/42 42/42 -- 50/50 50/50 50/50 -- 65/65 65/65 65/65
50/63A 42/42 42/42 42/42 42/42 -- -- 50/50 50/50 -- -- 65/65 65/65
Surion <= 10A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150
GPS1BH & 12.5A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150
GPS1MH 16/20A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150
GPS2BH & 25/32A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150
GPS2MH 40A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150
50/63A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


518 Product Catalogue 2013
DISCRIMINATION & SELECTIVITY

SELECTIVE PLUS
TABLE DB3 ED 2C
Upstream FE160N-LTMD FE160H-LTMD FE160L-LTMD

In (A) 100A 125A 160A 100A 125A 160A 100A 125A 160A
Downstream Type & In
Selectivity limit in kA / Icu of combination in kA at 400 - 415V AC
Record Plus FDC63 30/30 30/30 30/30 30/36 30/36 30/36 30/42 30/42 30/42
LTM. LTMD, FDE63 30/36 30/36 30/36 30/42 30/42 30/42 30/50 30/50 30/50
GTM & MO FDS63 30/42 30/42 30/42 30/50 30/50 30/50 30/65 30/65 30/65
FDN63 30/50 30/50 30/50 30/80 30/80 30/80 30/150 30/150 30/150
FDH63 -- -- -- 30/80 30/80 30/80 30/150 30/150 30/150
Record Plus FDC160 <= 100A -- -- 30/30 -- -- 30/36 -- -- 30/42
LTM. LTMD, FDE160 <= 100A -- -- 30/36 -- -- 30/42 -- -- 30/50
GTM & MO FDS160 <= 100A -- -- 30/42 -- -- 30/50 -- -- 30/65
FDN160 <= 100A -- -- 30/50 -- -- 30/80 -- -- 30/150
FDH160 <= 100A -- -- -- -- -- 30/80 -- -- 30/150
Record Plus FDC160 125A -- -- -- -- -- -- -- -- --
LTM. LTMD, FDE160 125A -- -- -- -- -- -- -- -- --
& GTM FDS160 125A -- -- -- -- -- -- -- -- --
FDN160 125A -- -- -- -- -- -- -- -- --
FDH160 125A -- -- -- -- -- -- -- -- --
Record Plus FDC160 160A -- -- -- -- -- -- -- -- --
LTM. LTMD, FDE160 160A -- -- -- -- -- -- -- -- --
& GTM FDS160 160A -- -- -- -- -- -- -- -- --
FDN160 160A -- -- -- -- -- -- -- -- --
FDH160 160A -- -- -- -- -- -- -- -- --

Upstream FE250N-LTMD FE250H-LTMD FE250L-LTMD

In (A) 125A 160A 200A 250A 125A 160A 200A 250A 125A 160A 200A 250A
Downstream Type & In
Selectivity limit in kA / Icu of combination in kA at 400 - 415V AC
Record Plus FDC63 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42
LTM. LTMD, FDE63 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 42/50 42/50 42/50 42/50
GTM & MO FDS63 42/42 42/42 42/42 42/42 42/50 42/50 42/50 42/50 42/65 42/65 42/65 42/65
FDN63 42/50 42/50 42/50 42/50 42/80 42/80 42/80 42/80 42/150 42/150 42/150 42/150
FDH63 -- -- -- -- 42/80 42/80 42/80 42/80 42/150 42/150 42/150 42/150
Record Plus FDC160 <= 100A -- 30/30 30/30 30/30 -- 36/36 36/36 36/36 -- 42/42 42/42 42/42
LTM. LTMD, FDE160 <= 100A -- 36/36 36/36 36/36 -- 42/42 42/42 42/42 -- 42/50 42/50 42/50
GTM & MO FDS160 <= 100A -- 42/42 42/42 42/42 -- 42/50 42/50 42/50 -- 42/65 42/65 42/65
FDN160 <= 100A -- 42/50 42/50 42/50 -- 42/80 42/80 42/80 -- 42/150 42/150 42/150
FDH160 <= 100A -- -- -- -- -- 42/80 42/80 42/80 -- 42/150 42/150 42/150
Record Plus FDC160 125A -- -- 30/30 30/30 -- -- 36/36 36/36 -- -- 42/42 42/42
LTM. LTMD, FDE160 125A -- -- 36/36 36/36 -- -- 42/42 42/42 -- -- 42/50 42/50
& GTM FDS160 125A -- -- 42/42 42/42 -- -- 42/50 42/50 -- -- 42/65 42/65
FDN160 125A -- -- 42/50 42/50 -- -- 42/80 42/80 -- -- 42/150 42/150
FDH160 125A -- -- -- -- -- -- 42/80 42/80 -- -- 42/150 42/150
Record Plus FDC160 160A -- -- -- 30/30 -- -- -- 36/36 -- -- -- 42/42
LTM. LTMD, FDE160 160A -- -- -- 36/36 -- -- -- 42/42 -- -- -- 42/50
& GTM FDS160 160A -- -- -- 42/42 -- -- -- 42/50 -- -- -- 42/65
FDN160 160A -- -- -- 42/50 -- -- -- 42/80 -- -- -- 42/150
FDH160 160A -- -- -- -- -- -- -- 42/80 -- -- -- 42/150 TECHNICAL

15
IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au
Product Catalogue 2013 519
DISCRIMINATION & SELECTIVITY

SELECTIVE PLUS
TABLE DB4 ED 2C
Upstream FE160N-SMR1 FE160H-SMR1 FE160L-SMR1

In (A) 63A 125A 160A 63A 125A 160A 63A 125A 160A
Downstream Type & In
Selectivity limit in kA / Icu of combination in kA at 400 - 415V AC
Record Plus FDC63 -- 30/30 30/30 -- 30/36 30/36 -- 36/42 36/42
LTM. LTMD, FDE63 -- 36/36 36/36 -- 30/42 30/42 -- 36/50 36/50
GTM & MO FDS63 -- 36/42 36/42 -- 30/50 30/50 -- 36/65 36/65
FDN63 -- 36/50 36/50 -- 30/80 30/80 -- 36/150 36/150
FDH63 -- -- -- -- 30/80 30/80 -- 36/150 36/150
Record Plus FDC160 <= 100A -- -- 30/30 -- -- 30/36 -- -- 36/42
LTM. LTMD, FDE160 <= 100A -- -- 36/36 -- -- 30/42 -- -- 36/50
GTM & MO FDS160 <= 100A -- -- 36/42 -- -- 30/50 -- -- 36/65
FDN160 <= 100A -- -- 36/50 -- -- 30/80 -- -- 36/150
FDH160 <= 100A -- -- -- -- -- 30/80 -- -- 36/150
Record Plus FDC160 125A -- -- -- -- -- -- -- -- --
LTM. LTMD, FDE160 125A -- -- -- -- -- -- -- -- --
& GTM FDS160 125A -- -- -- -- -- -- -- -- --
FDN160 125A -- -- -- -- -- -- -- -- --
FDH160 125A -- -- -- -- -- -- -- -- --
Record Plus FDC160 160A -- -- -- -- -- -- -- -- --
LTM. LTMD, FDE160 160A -- -- -- -- -- -- -- -- --
& GTM FDS160 160A -- -- -- -- -- -- -- -- --
FDN160 160A -- -- -- -- -- -- -- -- --
FDH160 160A -- -- -- -- -- -- -- -- --

Upstream FE250N-SMR1 FE250H-SMR1 FE250L-SMR1

In (A) 125A 160A 200A 250A 125A 160A 200A 250A 125A 160A 200A 250A
Downstream Type & In
Selectivity limit in kA / Icu of combination in kA at 400 - 415V AC
Record Plus FDC63 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42
LTM. LTMD, FDE63 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50
GTM & MO FDS63 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 50/65 50/65 50/65 50/65
FDN63 50/50 50/50 50/50 50/50 50/80 50/80 50/80 50/80 50/150 50/150 50/150 50/150
FDH63 -- -- -- -- 50/80 50/80 50/80 50/80 50/150 50/150 50/150 50/150
Record Plus FDC160 <= 100A -- 30/30 30/30 30/30 -- 36/36 36/36 36/36 -- 42/42 42/42 42/42
LTM. LTMD, FDE160 <= 100A -- 36/36 36/36 36/36 -- 42/42 42/42 42/42 -- 50/50 50/50 50/50
GTM & MO FDS160 <= 100A -- 42/42 42/42 42/42 -- 50/50 50/50 50/50 -- 50/65 50/65 50/65
FDN160 <= 100A -- 50/50 50/50 50/50 -- 50/80 50/80 50/80 -- 50/150 50/150 50/150
FDH160 <= 100A -- -- -- -- -- 50/80 50/80 50/80 -- 50/150 50/150 50/150
Record Plus FDC160 125A -- -- 30/30 30/30 -- -- 36/36 36/36 -- -- 42/42 42/42
LTM. LTMD, FDE160 125A -- -- 36/36 36/36 -- -- 42/42 42/42 -- -- 50/50 50/50
& GTM FDS160 125A -- -- 42/42 42/42 -- -- 50/50 50/50 -- -- 50/65 50/65
FDN160 125A -- -- 50/50 50/50 -- -- 50/80 50/80 -- -- 50/150 50/150
FDH160 125A -- -- -- -- -- -- -- -- -- -- 50/150 50/150
Record Plus FDC160 160A -- -- -- 30/30 -- -- -- 36/36 -- -- -- 42/42
LTM. LTMD, FDE160 160A -- -- -- 36/36 -- -- -- 42/42 -- -- -- 50/50
& GTM FDS160 160A -- -- -- 42/42 -- -- -- 50/50 -- -- -- 50/65
FDN160 160A -- -- -- 50/50 -- -- -- 50/80 -- -- -- 50/150
FDH160 160A -- -- -- -- -- -- -- 50/80 -- -- -- 50/150

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


520 Product Catalogue 2013
DISCRIMINATION & SELECTIVITY

SELECTIVE PLUS
TABLE DB5 ED 2C
Upstream FG400N-SMR1 FG400H-SMR1 FG400L-SMR1 FG630N-SMR1 FG630H-SMR1 FG630L-SMR1

In (A) 250A 400A 250A 400A 250A 400A 400A 500A 400A 500A 400A 500A

Downstream Type & In 630A 630A 630A

Selectivity limit in kA / Icu of combination in kA at 400-415V AC

Record Plus FDC63 30/30 30/30 36/36 36/36 42/42 42/42 30/30 30/30 36/36 36/36 42/42 42/42
LTM. LTMD, FDE63 36/36 36/36 42/42 42/42 50/50 50/50 36/36 36/36 42/42 42/42 50/50 50/50

GTM & MO FDS63 42/42 42/42 50/50 50/50 65/65 65/65 42/42 42/42 50/50 50/50 65/65 65/65

FDN63 50/50 50/50 80/80 80/80 150/150 150/150 50/50 50/50 80/80 80/80 150/150 150/150
FDH63 -- -- 80/80 80/80 150/150 150/150 -- -- 80/80 80/80 150/150 150/150

Record Plus FDC160 30/30 30/30 36/36 36/36 42/42 42/42 30/30 30/30 36/36 36/36 42/42 42/42

LTM. LTMD, FDE160 36/36 36/36 42/42 42/42 50/50 50/50 36/36 36/36 42/42 42/42 50/50 50/50

GTM & MO FDS160 42/42 42/42 50/50 50/50 65/65 65/65 42/42 42/42 50/50 50/50 65/65 65/65
FDN160 50/50 50/50 80/80 80/80 150/150 150/150 50/50 50/50 80/80 80/80 150/150 150/150

FDH160 -- -- 80/80 80/80 150/150 150/150 -- -- 80/80 80/80 150/150 150/150

Record Plus FEN160 50/50 50/50 80/80 80/80 150/150 150/150 50/50 50/50 80/80 80/80 150/150 150/150
LTM.LTMD,GTM FEH160 -- -- 80/80 80/80 150/150 150/150 -- -- 80/80 80/80 150/150 150/150
MO & SMR1 FEN250 -- -- 80/80 80/80 150/150 150/150 50/50 50/50 80/80 80/80 150/150 150/150

FEH250 -- -- 80/80 80/80 150/150 150/150 -- -- 80/80 80/80 150/150 150/150

SELECTIVE PLUS
TABLE DB6 ED 2C
Upstream FK800N-SMR FK800H-SMR FK800L-SMR FK1250N-SMR FK1250H-SMR FK1250L-SMR FK1600N-SMR FK1600H-SMR

In (A) 800A 800A 800A 1000A 1250A 1000A 1250A 1000A 1250A 1600A 1600A
Downstream Type&In

Selectivity limit in kA / Icu of combination in kA at 400-415V AC


Record Plus
LTM. LTMD, FDN63 50/50 80/80 100/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80

GTM & MO FDH63 50/50 80/80 100/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80

Record Plus
LTM. LTMD, FDN160 50/50 80/80 100/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80

GTM & MO FDH160 50/50 80/80 100/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80

Record Plus FEN160 50/50 80/80 100/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80
LTM. LTMD, FEH160 50/50 80/80 100/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80

GTM, MO FEN250 50/50 80/80 100/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80
& SMR1 FEH250 -- 80/80 100/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80

Record Plus FGN400 50/50 80/80 100/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80

SMR1 & FGH400 50/50 80/80 100/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80
SMR2 FGN630 15/50 15/80 15/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80

FGH630 -- 15/80 15/100 -- -- 80/80 80/80 100/100 100/100 50/50 80/80

Record Plus FKN800 -- -- -- 15/50 15/50 15/80 15/80 15/100 15/100 25/50 25/80
SMR1 FKH800 -- -- -- -- -- 15/80 15/80 15/100 15/100 25/50 25/80
FKN1250 -- -- -- -- -- -- -- -- -- 25/50 25/80
TECHNICAL

15
IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au
Product Catalogue 2013 521
FUSE LINK TEMPERATURE DERATING

FUSE DE-RATING WITH HIGH ENCLOSURE TEMPERATURES


In accordance with the relevant Standards, the rated current of fuses is determined
by tests conducted at 35°C ambient air temperature. When fuses are installed within
enclosures, it is the temperature within the enclosure (fluid enviroment temperature)
which determines whether de-rating is necessary.
The effect of high enclosure temperatures on IPD Type T fuses is indicated by the
table below.
Fuse Nominal Maximum Load Current (A)
Rating (A) Versus Fluid Environment
Temperature
55°C 60°C 65°C 70°C 75°C
63 or less
80 75 70
De-rating not
100 necessary 95 90
125 120 110
160 145 135
200 190 180 170
250 235 225 210
315 300 285 270 255
355 350 330 315 295
400 390 380 360 340
450 425 405 380 360
500 475 450 425 400 380
560 540 520 495 465 440
630 600 570 540 510 480
670 650 615 585 550 520
710 700 665 630 595 560
750 725 710 670 630 590
800 760 720 680 640 600
1000 950 900 850 800 750
1250 1140 1070 1020 960 900

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


522 Product Catalogue 2013
PROTECTION OF CABLES WITH FUSE LINKS

FUSE PROTECTION OF CABLES AGAINST TRANSIENT OVERCURRENTS


In some circuits such as the motors, significant transient overcurrents are produced during switching, and it is not
economical practice to match cable and fuse-link ratings. For these cases, the cable is chosen for the circuit load
condition and the fuse-links are chosen to withstand the transient overcurrent condition.
The fuse-links provide only short-circuit current protection to the motor, associated cables and other circuits
components. The necessary overload protection is provided by other means such as the motor starter’s thermal
overload relay.
The short-circuit protection of cables is covered by Section 5 of AS/NZS 3008.1.1:1998 and the Table below shows
how fuse-links relate to these requirements in protecting V75 rated PVC insulated copper conductors.
Maximum Current-Carrying Maximum GEC,
Capacity (A) GE or IPD
Fuse-Link
Conductor Rating (A)
cross-sectional
area (mm2)
“Unenclosed” condition. “Enclosed” condition.
Ratings according to Ratings according to Type T DIN Type
Table 6, Column 6 of Table 6, Column 8 of ‘gG’ ‘gL’-’gG’
AS/NZS 3008.1.1:1998 AS/NZS 3008.1.1:1998
1 13 11 16 16
1.5 16 14 20 20
2.5 23 20 35 32
4 31 26 50 40
6 40 34 63 50
10 54 47 80 80
16 72 62 125 125
25 97 87 200 200
35 120 100 250 250
50 145 125 355 355
70 185 155 450 500
95 230 185 630 630
120 265 220 710 800
150 310 250 800 1000
185 355 285 1000 1000
240 425 340 1250 1000
300 490 390 1250 1000
400 570 455 1250 1000
500 660 530 1250 1000
630 760 620 1250 1000
Notes:
1. Selection of the above fuse-links is based on the formula I2t = K2S2 given in Clause 5.3 of AS/NZS
3008.1.1:1998 where:
I = Current which causes the fuse-link to operate in 5 seconds.
t = 5 seconds.
K = Constant of 111 for PVC insulated copper conductor, for the condition of initial.
temperature 75°C and final temperature 160°C (during overcurrent condition).
S = Cross-sectional area of the conductor in mm2.

2. For motor start fuse-links (i.e. those classified and marked ‘gM’) the larger of its dual current ratings is
applicable, e.g. 160A for TCP100M160 type.
TECHNICAL

15
IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au
Product Catalogue 2013 523
GE CONTACTOR SELECTION - LIGHTING CIRCUITS

CONTACTORS FOR CONTROL LIGHTING CIRCUITS


The characteristics of the most usual lighting systems are as follows:

Incandescent lamps
The connection current in very high -of the order of 15 times- rated current. Although this is a very short duration, it is only taken into account in order for the contactor
connection current not to be exceeded. The power factor is always maintained at 1.
Fluorescent lamps
The connection current is slightly higher than rated current. The power factor is about 0.5. To improve up to 0.9, compensating capacitors can be used. In such cases,
the connection power of the capacitor must be taken into account, the effect of which is appreciably greater on the smaller contactors.
High pressure mercury vapour lamps
The connection current varies, depending on type, between 1.6 and 2 times the rated current and will hold for between 3 and 5 minutes.
The power factor is of the order of 0.6 and this can be improved up to approximately unit value by means of compensating capacitors. In such cases, the connection
power of the capacitor must be taken into account, the effect of which is appreciably greater on the smaller contactors.
High pressure sodium vapour lamps
The connection current values varies, depending on type, between 1.3 and 1.6 times the rated current and will hold between 3 and 5 minutes.
The power factor is of the order of 0.45 and this can be improved up to apporximately unit value by means of compensating capacitors. In such cases, the connection
power of the capacitor must be taken into account, the effect of which is appreciably greater on the smaller contactors.

SELECTION TABLE
Maximum number of lamps per phase at 230V
Types W A μF MCR MC0 MC1 MC2 RL CL00 CL01 CL02 CL25

Incandescent 60 0.27 27 37 59 59 59 62 62 70 77
100 0.45 16 22 35 35 35 40 40 50 60
200 0.91 8 11 17 17 17 20 20 25 30
300 1.36 5 7 11 11 11 13 13 17 20
500 2.27 3 4 7 7 7 8 8 10 12
1000 4.5 1 2 3 3 3 4 4 5 6
2000 9.1 0 1 1 1 1 1 1 2 3
Fluorescent 15 0.23 51 61 79 79 79 88 98 126 155
Single arrangement 20 0.37 32 38 49 49 49 57 61 78 110
Without compensation 40 0.44 28 33 41 41 41 48 51 66 93
65 0.7 18 21 26 26 26 30 32 41 58
100 1.5 8 10 12 12 12 14 16 19 27
Fluorescent 15 0.23 3.5 26 32 49 49 49 61 77 94 111
Single arrangement 20 0.25 4.5 20 25 38 38 38 48 61 74 87
With compensation 40 0.3 4.5 20 25 38 38 38 48 61 74 87
65 0.45 7 13 14 25 25 25 31 39 47 56
100 0.7 18 5 6 9 9 9 11 14 17 21
High pressure mercury 250 2.13 5 5 5 6 6 6 8 10 12
vapour 400 3.25 3 3 4 4 4 4 5 6 8
Without compensation 700 5.4 2 2 2 2 2 2 3 4 5
1000 7.5 1 1 2 2 2 2 2 3 3
High pressure mercury 250 1.3 20 9 9 9 9 11 11 14 18 22
vapour 400 2.1 25 7 7 7 7 7 7 9 11 14
With compensation 700 3.6 40 5 5 5 5 4 4 5 6 8
1000 5.3 60 3 3 3 3 3 3 3 4 5
High pressure sodium 250 3 3 3 4 4 4 4 5 7 9
vapour 400 4.4 2 2 3 3 3 3 4 5 6
Without compensation 1000 10.3 1 1 1 1 1 1 2 2 2
High pressure sodium 250 1.45 40 5 5 5 5 10 10 12 16 20
vapour 400 2.5 45 4 4 4 4 6 6 7 9 11
With compensation 1000 5.5 100 2 2 2 2 3 3 3 4 5
Metal iodide 250 2,17 - 3 3 4 4 4 4 5 7 9
Without compensation 400 3,48 - 2 2 2 3 3 3 3 4 6
700 6,09 - 1 1 1 1 1 1 2 2 3
1000 8,7 - 1 1 1 1 1 1 1 2 2
2000 17,39 - 0 0 0 1 1 1 1 1 1
Metal iodide 250 1,4 32 0 6 6 7 7 7 9 11 16
With compensation 400 2,0 45 0 4 5 5 5 5 6 8 11
700 3,6 65 0 2 3 3 3 3 3 4 6
1000 5,3 85 0 2 2 2 2 2 2 3 4
2000 10,6 100 0 0 0 0 0 1 1 2 2

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


524 Product Catalogue 2013
GE CONTACTOR SELECTION - LIGHTING CIRCUITS

DIAGRAMS

Single-phase circuit 3-phase circuit, 3-phase circuit,


The total number of lamps will lamps delta-connected lamps star-connected
be as shown in the table. The total number of lamps will be The total number of lamps
as shown in the table, will be as shown in the table,
multiplied by 1.73 and distributed multiplied by 3 and distributed
in three equal quantities. in three equal quantities.

Maximum number of lamps per phase at 230V


CL03 CL04 CL45 CL06 CL07 CL08 CL09 CL10 CK75C CK08C CK09 CK95 CK10 CK11 CK12 CK13

77 85 122 156 191 222 264 284 333 410 555 820 1320 1550 1860 1860
60 66 73 95 116 133 160 170 200 246 333 490 790 930 1120 1120
30 33 36 47 58 66 79 84 99 122 165 240 390 460 550 550
20 22 24 31 38 44 53 56 66 81 110 165 260 300 370 370
12 12 14 19 23 26 31 33 39 48 66 95 155 185 220 220
6 6 7 9 11 13 16 17 20 24 33 50 80 90 110 110
3 3 3 4 5 7 8 8 10 12 16 25 40 45 55 55
177 224 237 355 390 434 496 553 790 988 1245 1770 2340 2740 3910 4890
125 139 147 221 243 270 309 344 490 614 774 1090 1460 1700 2430 3040
105 118 124 186 204 227 260 289 413 516 650 920 1220 1430 2045 2550
66 74 78 116 127 142 163 181 259 324 409 570 770 900 1280 1600
30 34 36 54 59 66 76 85 121 151 190 270 360 420 600 750
119 134 149 191 232 273 312 347 496 621 786 900 1240 1450 1740 1740
92 103 115 148 180 212 243 270 385 482 610 700 960 1120 1350 1350
92 103 115 148 180 212 243 270 385 482 610 700 960 1120 1350 1350
59 66 74 95 115 136 155 173 248 310 393 440 610 720 860 860
23 23 29 37 45 53 60 67 96 120 152 170 240 280 330 330
14 15 18 27 30 33 36 42 60 75 95 136 181 211 302 377
9 10 12 18 20 22 24 28 40 49 62 89 119 138 198 247
5 6 7 11 12 13 14 17 24 30 38 54 71 83 119 149
4 4 5 8 9 9 10 12 17 21 27 39 51 60 86 107
31 27 33 49 55 60 66 77 109 156 156 171 311 311 374 467
25 17 20 31 34 37 41 48 87 125 125 137 249 249 299 374
16 10 12 18 20 22 24 28 54 78 78 86 156 156 187 234
10 7 8 12 13 15 16 19 36 52 52 57 104 104 125 156
10 11 13 19 21 24 26 30 43 54 68 96 129 150 214 268
7 7 9 13 15 16 18 20 29 37 46 66 88 102 146 183
3 3 4 6 6 7 7 9 12 16 20 28 37 44 62 78
16 25 30 44 49 54 59 69 57 81 81 90 163 163 195 244
14 14 17 26 29 31 34 40 51 72 72 80 145 145 174 217
7 6 8 12 13 14 16 18 23 33 33 36 65 65 78 98
12 12 12 19 21 23 25 29 41 52 65 93 124 145 207 259
8 8 8 12 13 14 16 18 26 32 41 58 78 91 129 162
4 4 4 7 7 8 9 10 15 18 23 33 44 52 74 92
3 3 3 5 5 6 6 7 10 13 16 23 31 36 52 65
2 2 2 2 3 3 3 4 5 6 8 12 16 18 26 32
21 21 21 32 36 39 43 50 68 97 97 107 195 195 234 292
15 15 15 23 25 28 30 35 48 69 69 76 138 138 166 208
8 8 8 13 14 15 17 19 34 48 48 53 96 96 115 144
6 6 6 8 9 10 11 13 26 37 37 40 73 73 88 110
3 3 3 4 5 5 6 7 22 31 31 34 62 62 75 93
TECHNICAL

15
IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au
Product Catalogue 2013 525
RELAY EQUIVALENT SELECTION CHART

PANASONIC
RELAY & BASE IDEC (IPD) OMRON (National) FINDER

RJ Series Compact Miniature Relay


1 POLE Relay SPDT RJ1S G2R-1-SN AHN12 46.61
Base SJ1S-07L P2RF-05-E AHNA11P 97.01
2 POLE Relay DPDT RJ2S G2R-2-SN AHN22 46.52
Base SJ2S-07L P2RF-08-E AHNA21P 97.02

RU Series Miniature Rely


2 POLE Relay DPDT RU2S MY2 HC2/HJ2 55.32
Base SY4S-05E1G2 PYF08A-E HC2/HJ2-SFD-K 94.02
4 POLE Relay 4PDT RU4S MY4 HC4/HJ4 55.34
Base SY4S-05E1G2 PYF14A-E HC4/HJ4-SFD-K 94.04

RH Series General Purpose Relay


1 POLE Relay SPDT RH1B LY1 HL1 / HC1 -
Base SH1B-05C PTF08A-E HL2-SFD-K / HC2-SFD-S -
2 POLE Relay DPDT RH2B LY2 HL2 / HC2 56.32
Base SH2B-05C PTF08A-E HL2-SFD-K / HC2-SFD-S 96.02
3 POLE Relay 3PDT RH3B LY3 HC3 62.33
Base SH3B-05C PTF11A HC3-SFD-K 92.03
4 POLE Relay 4PDT RH4B LY4 HC4 56.34
Base SH4B-05C PTF14A-E HC4-TSF-K 96.04

RR2KP Series Latching Relay


2 POLE Relay DPDT RR2KP G2AK - -
Base SR3P-05C PYF14A(-E) - -

RF1V Series Safety Relay


4 POLE Relay RF1V - SFS2 / SFS3 -
Base SF1V-4-07L - SFS4-SFD -
6 POLE Relay RF1V - SFS4 / SFS5 / SFS6 -
Base SF1V-6-07L - SFS6-SFD -

RV8H Series Slim-Line Relay


Interface Relay + Base RV8H G2RV - 38.51

Note.
This is a guide only for relays that are similar in the market.
Consider physical size and detailed specification before making a final decision.

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


526 Product Catalogue 2013