You are on page 1of 7

Project no.

Project :
Your contact :
23/10/2019

On integrated frame construction


Double wall panelling with standard 50 mm insulation
Outside wall with lacquered paint
Taking into account recommendation of norm EN 13053
Classification as per European standard EN 1886
EUROVENT performances (M) :
Casing strength class D2
Casing tightness class (-400 Pa / +700 Pa ) : L1/L1
Filter bypass leakage : F9
Thermal transmittance class : T2
Thermal bridge factor class : TB2

EUROVENT certification 16.04.011

EUROVENT CERTIFIED PERFORMANCE


CARRIER participates in the ECC program for: Air Handling Unit
Check ongoing validity of certificate online:
www.eurovent-certification.com

ISO 16890 Ready

Price per unit


Description Quantity Without taxes

AHU 39CZ HE 400 1 73.409,00 EUR

Damper
- Damper blades driven via linkage 1 546,00 EUR

Filter
- Door contact switch (factory fitted) 1 31,00 EUR
- Additional filters set (1st row) 1 132,00 EUR
- Additional filters set (2nd row) 1 296,00 EUR

Filter
- Door contact switch (factory fitted) 1 31,00 EUR
- Additional filters set 1 132,00 EUR

Filter
- Door contact switch (factory fitted) 1 31,00 EUR
- Additional filters set 1 132,00 EUR

Damper
- Damper blades driven via linkage 1 546,00 EUR
Based on our general terms and conditions of sale in your possession.
As part of our policy of continual improvement, we reserve the right to make any technical modifications we feel necessary without prior notice.
Validity of prices: 1 month.

1 AHU 39CZ HE 400


Flow rate : SUPPLY UNIT 19.000 m3/h / EXTRACT UNIT 19.000 m3/h (Frontal speed : 1.33 / 1.33 m/s)
(Filtration surface area / Filtration surface area)
Speed class V1 EN13053
AHU Assembly Delivery : Double stacked / Ext. unit with internal coil connections
Altitude : 200 m
Reference air conditions supply unit : 20 °C / 50 %(RH) / 1,17 kg/m3
Reference air conditions extract unit : 20 °C / 50 %(RH) / 1,17 kg/m3
Specific Fan Power v : 2.204 W/(m3/s), 0,61 W/(m3/h)

Winter fresh air reference temperature EUROVENT -18 °C


Mixing ratio 0,00
Designed for wet conditions
ERV_2016, Subgroup 1 Energy class A+
EN 1886-2007 CAL(R) -400 Pa / +400 Pa = 0,99 / 0,36 %
CLIMGIW 13.00.10-A20 05/2019 Page : 1 / 7
Project no. :

Project :
Your contact :
23/10/2019

Internal leak flow rate = 8,6 % of supply air flow rate


PED 2014/68/UE Article 4.3

ECODESIGN 1253-2014 / 2018


Typology : NRVU BVU
SUPPLY UNIT : ΔPint : 153,9 Pa
EXTRACT UNIT : ΔPint : 89,3 Pa
SFPint : 418 W/(m3/s)
SRC efficiency: 80.4 % in accordance with EN308 (Minimum efficiency: 73.0 %)

SUPPLY UNIT : Ancillaries


Doors : right in air flow direction
Piping : right in air flow direction

EXTRACT UNIT : Ancillaries


Doors : left in air flow direction

Cut-out : Automatic

EXTRACT UNIT : Position 2HH

Block A1 627 kg with


1 Baseframe B401179
13 Polyester powder coated external skin (C3) B401191
12 Polyester powder coated internal skin (C3) B401209
Mounted block

1 filtration section B401628


Slides assembly 1, lift off panel B401741
8 Cells type F2 B372132
Filtration Class (EN 779-2012) : G4
Filtration Class (ISO16890) : Coarse 60%
Air pressure drops (Dirty point) : 90 Pa
Pressure drop on the 3 fouling levels : Clean point 45 / Mid point 68 / Dirty point 91 Pa
With pressure valves
All filters must be equipped with a visual device or monitoring by the control
Left face access in the direction of air
Pressure tappings (fitted) B371554

1 Fan section (free wheel) B403525


Number of fan(s) : 2
Air flow rate : 19.000 m3/h 5,2778 m3/s
Duct available pressure : 350 Pa
K-factor : 308
Requires a controller delivering a 0/10 V signal
Diameter of fan impeller : 0,56 m
Motor and fan efficiency : 67%
Impeller rotation speed : 1.393 rpm
Impeller rotation maximum speed : 1.800 rpm
Power input : 4.791 W
Specific Fan Power : 842 W/(m3/s), 0,23 W/(m3/h)
2 x Single motor
Unit specifications:
Rated current : 8,00 A
Motor EC : 5,2 kW
Voltage : TRI_400V_50HZ
Control voltage : 7,74 V
Left face access in the direction of air
Hinged door, Max handles B401128
Epoxy paint on cross rails and fan partition B401293
Pressure pick-up for air flow control B506379

Block A2 2.781 kg with


1 Baseframe B401179
6 Polyester powder coated external skin (C3) B401191
6 Polyester powder coated internal skin (C3) B401209
Mounted block

Rotary heat exchanger with speed regulator and safety management sensible
B402371
RR21 - Sensible - Standard
Delivery in 6 parts

CLIMGIW 13.00.10-A20 05/2019 Page : 2 / 7


Project no. :

Project :
Your contact :
23/10/2019

*** Performance WINTER ***


Efficiency: fresh air / Hygrometric : 87,0 % / 56,6 %
Efficiency in accordance with EN308 : 80,4 %
Recovery class H1 EN13053
Recovery capacity : 265,1 kW
Supply side
- Compute on air flow :16.470 m3/h (-18 °C / 90 %(RH))
- air inlet t° / rh % : -18 °C / 90 %(RH)
- air outlet t° / rh % : 15,1 °C / 41,6 %(RH)
- Air pressure drops : 73 Pa
Extraction side
- Compute on air flow :19.000 m3/h (20 °C / 50 %(RH))
- air inlet t° / rh % : 20 °C / 50 %(RH)
- Air pressure drops : 89 Pa
*** Performance SUMMER ***
Efficiency: fresh air / Hygrometric : 75,3 % / 0,0 %
Recovery capacity : 43,99 kW
Supply side
- Compute on air flow :19.990 m3/h (34,3 °C / 37 %(RH))
- air inlet t° / rh % : 34,3 °C / 37 %(RH)
- air outlet t° / rh % : 27,3 °C / 55,2 %(RH)
- Air pressure drops : 107 Pa
Extraction side
- Compute on air flow :19.350 m3/h (25 °C / 50 %(RH))
- air inlet t° / rh % : 25 °C / 50 %(RH)
- Air pressure drops : 102 Pa
Right face access in the direction of air
Epoxy painted internal air path separating plates B401314
Pressure tappings installed (Exhaust) B371554
Pressure tappings installed (Supply) B371554

Block A3 104 kg with


1 Baseframe B401179
2 Polyester powder coated external skin (C3) B401191
2 Polyester powder coated internal skin (C3) B401209
Mounted block

Damper inside B401461


Airtight damper box B401407
Opposed dampers with gaskets on the thin plates extremities
Cog wheel drive
External spindle (actuator by others) B401620
Left face access in the direction of air
Commands on the left in the direction of air

1 Hood with bird mesh on fresh air sup. sect REP2 B401161
Droplets eliminator for large opening B401164

ACOUSTIC OUTPUT SPECTRUM


Frequencies (Hz) / Levels per octave band (dB Lin) Overall
63 125 250 500 1000 2000 4000 8000 dB (A)
Radiated 63 75 63 57 49 43 33 26 61
Ducted air inlet 71 82 82 78 74 73 69 68 81
Ducted discharge 72 86 85 83 79 76 72 70 85
Tolerance on the global spectrum: +/- 3dB
Tolerance on the octave spectrum : +/-5 dB @ 63-125 Hz
Tolerance on the octave spectrum : +/-3 dB @ 250-8000 Hz

SUPPLY UNIT : Position 1HH

1 Hood with bird mesh on fresh air sup. sect REP2 B401161
Droplets eliminator for large opening B401164

Block A4 323 kg with


1 Baseframe B401179
9 Polyester powder coated external skin (C3) B401191
8 Polyester powder coated internal skin (C3) B401209

CLIMGIW 13.00.10-A20 05/2019 Page : 3 / 7


Project no. :

Project :
Your contact :
23/10/2019

Mounted block

Damper inside B401461


Airtight damper box B401407
Opposed dampers with gaskets on the thin plates extremities
Cog wheel drive
External spindle (actuator by others) B401620
Right face access in the direction of air
Commands on the right in the direction of air

1 filtration section B401658


Slides assemblies 1+2, hinged door B401747
8 Cells type F2 B372132
Filtration Class (EN 779-2012) : G4
Filtration Class (ISO16890) : Coarse 60%
Air pressure drops (Dirty point) : 90 Pa
Pressure drop on the 3 fouling levels : Clean point 45 / Mid point 68 / Dirty point 91 Pa
With pressure valves
8 Cells type HPS2C B372144
Filtration Class (EN 779-2012) : F7
Filtration Class (ISO16890) : ePM1 60% - ePM2.5 70%
Air pressure drops (Dirty point) : 161 Pa
Pressure drop on the 3 fouling levels : Clean point 81 / Mid point 121 / Dirty point 161 Pa
With pressure valves
All filters must be equipped with a visual device or monitoring by the control
Right face access in the direction of air
Pressure tappings (fitted) B371554

Block A2 2.781 kg with


1 Baseframe B401179
6 Polyester powder coated external skin (C3) B401191
6 Polyester powder coated internal skin (C3) B401209
Mounted block

Rotary heat exchanger with speed regulator and safety management sensible
B402371
See EXTRACT UNIT.

Block A5 1.678 kg with


1 Baseframe B401179
15 Polyester powder coated external skin (C3) B401191
14 Polyester powder coated internal skin (C3) B401209
Mounted block

1 Heating Coil B401799


2 Row(s), Fin space 2,1 mm Imposed
Copper tubes / Aluminium fins
Heating capacity : 94 kW
Heating fluid : Water
inlet t° / outlet t° : 60 °C / 40 °C
air inlet t° / rh % : 15 °C / 80 %(RH)
air outlet t° / rh % : 30 °C / 32,1 %(RH)
Water flow : 4,1 m3/h
Fluid pressure drop : 1.520 Pa
Air pressure drops : 21 Pa
Air speed : 1,71 m/s
Slide mounting
Diameters of bosses Circuit (1) : Male threaded connection 2"
Fluid content : 33,1 l
Right face access in the direction of air
Pipings on the right in the direction of air
Epoxy painted slide rails B401260
Panel with frost protection drawer 12_1 B401898

Headers and internal connections directed toward

For an anti-frost coil for which outlet temperature is below 15°C, use a constant flow control to avoid anti-frost fault or frost upon the coil

1 Cooling Coil B401814


12 Row(s), Fin space 2,5 mm Imposed
Copper tubes / Aluminium fins
Cooling capacity : 104 kW
Refrigerant :35% Mono-Ethylene-Glycol solution

CLIMGIW 13.00.10-A20 05/2019 Page : 4 / 7


Project no. :

Project :
Your contact :
23/10/2019

inlet t° / outlet t° : 5 °C / 10 °C
air inlet t° / rh % : 27 °C / 40 %(RH)
air outlet t° / rh % : 11,7 °C / 98,7 %(RH)
Water flow : 19,9 m3/h
Fluid pressure drop : 14.210 Pa
Air pressure drops : 117 Pa
Air speed : 1,71 m/s
High speed droplet eliminator
Air pressure drops : 11 Pa
Slide mounting
connection Circuit (1) : Male threaded steel 3"
Fluid content : 163 l
Right face access in the direction of air
Pipings on the right in the direction of air
Epoxy painted slide rails B401269
Hygienic stainless steel drain tray B401937
Hinged door 400 mm B401113

Headers and internal connections directed toward

Cooling coil | Cooling coil B402276


Length : 200 mm
Right face access in the direction of air

1 Heating Coil B401799


1 Row(s), Fin space 2,1 mm Imposed
Copper tubes / Aluminium fins
Heating capacity : 43,8 kW
Heating fluid : Water
inlet t° / outlet t° : 60 °C / 40 °C
air inlet t° / rh % : 12 °C / 95 %(RH)
air outlet t° / rh % : 19 °C / 60,6 %(RH)
Water flow : 1,91 m3/h
Fluid pressure drop : 3.795 Pa
Air pressure drops : 10 Pa
Air speed : 1,71 m/s
Slide mounting
Diameters of bosses Circuit (1) :Male threaded connection 1"1/2
Fluid content : 15,6 l
Right face access in the direction of air
Pipings on the right in the direction of air
Epoxy painted slide rails B401260

Headers and internal connections directed toward

Block A6 781 kg with


1 Baseframe B401179
17 Polyester powder coated external skin (C3) B401191
16 Polyester powder coated internal skin (C3) B401209
Mounted block

1 Fan section (free wheel) B403525


Number of fan(s) : 3
Air flow rate : 19.000 m3/h 5,2778 m3/s
Duct available pressure : 350 Pa
K-factor : 308
Requires a controller delivering a 0/10 V signal
Diameter of fan impeller : 0,56 m
Motor and fan efficiency : 57%
Impeller rotation speed : 1.538 rpm
Impeller rotation maximum speed : 1.800 rpm
Power input : 9.008 W
Specific Fan Power :1.362 W/(m3/s), 0,38 W/(m3/h)
3 x Single motor
Unit specifications:
Rated current : 8,00 A
Motor EC : 5,2 kW
Voltage : TRI_400V_50HZ
Control voltage : 8,55 V
Right face access in the direction of air
Hinged door, Max handles B401128
Epoxy paint on cross rails and fan partition B401293
Pressure pick-up for air flow control B506379

CLIMGIW 13.00.10-A20 05/2019 Page : 5 / 7


Project no. :

Project :
Your contact :
23/10/2019

1 filtration section B401697


Front withdrawal frame assembly 3, hinged door B401750
8 Cells type F2 B372132
Filtration Class (EN 779-2012) : G4
Filtration Class (ISO16890) : Coarse 60%
Air pressure drops (Dirty point) : 90 Pa
Pressure drop on the 3 fouling levels : Clean point 45 / Mid point 68 / Dirty point 91 Pa
With pressure valves
All filters must be equipped with a visual device or monitoring by the control
Right face access in the direction of air
Pressure tappings (fitted) B371554

Accessories
6 Weaterproof roof B401140
1 Clean unit, Procedure for Clean Room and Healthcare B402051

ACOUSTIC OUTPUT SPECTRUM


Frequencies (Hz) / Levels per octave band (dB Lin) Overall
63 125 250 500 1000 2000 4000 8000 dB (A)
Radiated 77 84 67 59 51 46 36 29 69
Ducted air inlet 72 81 76 68 59 54 38 35 72
Ducted discharge 89 97 90 87 83 81 77 75 90
Tolerance on the global spectrum: +/- 3dB
Tolerance on the octave spectrum : +/-5 dB @ 63-125 Hz
Tolerance on the octave spectrum : +/-3 dB @ 250-8000 Hz

CLIMGIW 13.00.10-A20 05/2019 Page : 6 / 7


Project no. :

Project :
Your contact :
23/10/2019

1 AHU 39CZ HE 400

Doors, Cells, Space Allowance = 660 mm


Components: Space Allowance = Air handling unit width
Canopy overhang: See technical brochure
DIMENSIONS AND WEIGHT
Length : 5.930 mm Width : 2.812 mm Height : 3.332 mm
Weight 6.534 kg (+/-10%)
All weights are dry weights

CLIMGIW 13.00.10-A20 05/2019 Page : 7 / 7