Contents
1. What’s is Aquator?..................................................................................................................................... 4
2. What requirement need for CAD drawing? ............................................................................................... 5
3. Aquator Ribbon & Dock Panel ................................................................................................................... 5
4. Aquator Setup Dialog ................................................................................................................................. 8
4.1 General Setup .................................................................................................................................... 8
5. Aquator Pressure Type. ........................................................................................................................... 10
5.1 Pressure Type Setup ........................................................................................................................ 11
6. Aquator Design Mode .............................................................................................................................. 11
6.1 Design Mode Setup .......................................................................................................................... 12
7. Aquator Project Case ............................................................................................................................... 12
7.1 Project Case Setup ................................................................................................................................. 13
8 Aquator Water Network .......................................................................................................................... 14
8.1 Water Network Modeling ...................................................................................................................... 14
8.1.2 Water Network Modeling at CAD (AutoCAD, ZWCAD etc.) ................................................................ 15
8.2 Delete Necessary Water Network ......................................................................................................... 16
9. Aquator Tapping Point & Pressure Head (Intake).................................................................................... 16
9.1 How to Get the Pressure Head for AQ? ........................................................................................... 17
10. Aquator Pipe ........................................................................................................................................ 17
10.1 Pipe Parameter Setup ...................................................................................................................... 17
10.2 Pipe Setup ........................................................................................................................................ 19
10.3 Pipe Color Setup............................................................................................................................... 19
10.4 How to Manually Changed Pipe Type or Diameter?........................................................................ 20
10.5 How to Change Length of Pipe?....................................................................................................... 21
11. Aquator Domestic Water Demand, QD. ............................................................................................... 21
11.1 Unit flow for QD .................................................................................................................................... 22
11.2 How to Insert Q inside Aquator? ......................................................................................................... 22
11.2.1 Table......................................................................................................................................... 23
11.2.2 Properties Input ............................................................................................................................ 24
11.2.3 Node Input ............................................................................................................................... 24
12 Aquator Hydrant Water Demand, QH .................................................................................................. 24
12.1 Hydrant Flow Setup ............................................................................................................................. 25
12.2 QH Case Factor Setup ........................................................................................................................... 25
12.3 How to Insert QH? ................................................................................................................................ 26
Page 1 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Page 3 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
1. What’s is Aquator?
Aquator (AQ) is a water supply network application that use the Hardy Cross Method or junction method. It
works in either loop system, branched system or both system.
i) Branched System
Junction equation
Qin - Qout = Qe
Qin = Inflow
Qout = Outflow
Qe =External flow into the system
Figure 1.1: Branched system sketch.
Currently the application is analysed by Hazen Williams’s equation. The working units in AQ are SI or imperial
unit. Therefore, user has the flexibility on data input.
Page 4 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Scale
Always ensure your drawing scale 1:1 (meter)
Page 5 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
ii) Water
Data Ribbon
Computation Ribbon
Page 6 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Option Ribbon
Tools Ribbon
To renumber node.
To renumber pipe.
iii) Report
Page 8 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Parameter Description
Default Data
Pipe Name Default pipe name.
Refer Topic 10.2: Pipe Setup.
Hydrant Flow I Unit The fire flow value and unit of flow.
Refer Topic 12.1: Hydrant Flow Setup
Length Interval I Unit The tolerance value to be used in pipe adding command and unit.
Example; user may add pipe with length of 12.63m with interval value of
0.5m the length added shall be 12.50m.
Alert
Max Head Loss The alert value of maximum head loss
Head Max I Min I Unit The maximum and minimum head allowed in application and unit.
V Max I Min I Unit The maximum and minimum velocity allowed in application and unit.
Tolerance
Node I Pipe The minimum distance between node/pipe for adding a new node/pipe.
Page 9 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Parameter Description
Design Data
Design Mood The design mode of AQ.
Refer Topic 6.1: Design Mode Setup
No decimal point for Loop Number of decimal point used in loop analysis.
convergence Use lesser decimal point for loop convergence. Example: below 5.
Aqua Motion
Bubble Size The diameter of bubble in AQ motion.
Report
Hide node without draw To disable unused node, select “True”.
off
Page 10 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Step b Step a
Step c
Step d
Notes:
If design in HSL, Required Head parameter must be 0.
Refer Topic 16: Design for HSL
ii) Manual
Pipe determined by user.
If failed in design, AQ will mention it at “Error List” dock panel.
Step b Step a
Step c
Step c
Page 12 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Step a
Step b
Step c
Parameter Description
Name Case name.
Can be change.
Page 13 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
The sign is positive value. When it negative value, it means that it flow from upper node number to lower
node number.
Step b
Step a
Step d
Diagram 4.1: Modeling icon
Step i & ii
Step iii
Step iv & v
Step vii
Page 14 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
c) To add node only, just left click one time, then right click it.
Step i
Step ii
Recommendation:
*Only keep the necessary layers.
*The less data keep, the less error it might trigger.
*Stop at any intersection pipe to avoid pop up error “Not intake detect” inside AQ.
Page 15 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
To delete any selected node, the pipe must be delete first. Then delete that node.
Step a & b
Step d
Step e
Step d
Step b
Step a
Step c
Topic 9: (Please refer Diagram 5.1: Tapping point and tapping pressure head)
a) Select node to add as tapping point and pressure head.
b) Go to properties (left hand side), change as “True” at “7.Tapping Point”.
c) Arrow will pop up at layout mark as tapping.
d) Add pressure head in meter unit at “7-Tapping Pressure Head”
Page 16 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
ODL=83.79 m , GL=23.5 m
To add tapping pressure head, Original Datum Level (ODL) must be minus with Ground Level (GL).
It is because, inside AQ calculation, application will plus with GL for pressure head.
Using Design Mode as Auto, AQ will determine the diameter of pipe. However, user still can changed it
manually (Refer topic 8.3).
Using Design Mode as Manual, user need to determine your own the diameter to use.
Step a
Step b
Page 17 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Parameter Description
Name The pipe name.
Can be changed any name.
Parameter Description
C Hazen William Coefficient.
Can be change here based on authority required
Parameter Description
Page 18 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Step c
Step d
Step e
Topic 10.2: (Please refer Diagram 7.2: Pipe setup for type and diameter)
a) At “Option” ribbon.
Page 19 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
ii. By Diameter
Color of pipe will follow diameter color.
Setup Diameter Color Diameter and Pipe Color
i. Pipe Type
Step b Step a
Step c
Step d
Diagram 7.4: Change pipe type manually.
Topic 10.4: (Please refer Diagram 7.4: Change pipe type manually)
a) Select pipe at layout. (highlight in yellow colour after selected)
b) Go to properties (left hand side)
c) At “Input”, change at “Type Name”.
d) Can select any pipe type to used (pipe type will based on parameter at Pipe Setup)
Step b
Step a
Step c
Step e
Page 20 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Step b
Step a
Step c
Topic 10.5: (Please refer Diagram 7.6: Change pipe length manually)
a) Select pipe at layout.
b) Go to properties (left hand side)
c) At “2-Calculation”, change it at “Length”.
Step a
Step b
Topic 11: (Please refer Diagram 8.1: Water demand setup table based on guideline selected)
Page 21 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Step a
Step b
Step c
Method i
i) Table
ii) Properties Input
iii) Node Input.
Page 22 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
11.2.1 Table
Step a
Step b
Step c
Step f Step g
Step d
Step e
Step h
Step i
Diagram 8.5: Q Table of Node
Page 23 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Step b
Step a
Step c
Step d
Step d Step a
Step c
Page 24 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Hydrant shall be placed at intersections, branches and generally at a spacing interval of not more than 180
meters. High fire risk installations shall have hydrants placed not more than 90 meters walking distance from
the installation.
Step b
Step c
Step d
Step b
Step a
Step c
Page 25 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Step b
Step a
Step c Step d
Step b
Step c
Step d
Page 26 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Method i
Method iii
Method ii
ii) Properties GL
Manually insert GL by select node by node.
13.2.1 PL Read
Step a
Step b
Step e
Step f
Topic 13.2.1: (Please refer Diagram 10.3: Import the whole GL)
a) Select “CAD” tab. (Please refer condition required for PL read at topic 11.2)
h) Next box will pop up, “Import PL”. Select “OK” button also.
Page 28 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
13.2.2 Properties GL
Step b
Step c Step a
Step b
Step d
Step a
Step c
Topic 13.2.3: (Please refer Diagram 10.5: manually insert GL at node properties)
a) Click “Node Input” at right hand side.
b) Node input table will sliding out.
c) At “4-GL”, insert GL for node required.
d) Node will be highlight in yellow at layout once select any item at that table.
14 Aquator Fitting
These fittings mainly for calculate the minor losses. The valves supported are allowed SYABAS guideline.
Page 29 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Step f Step c
Step a
Step d
Step e
Step b
15 Aquator Layout
AQ provides a graphical UI that allows user to input nodes and pipes in graphical way.
User can visualize the water supply layout. Qin and Qout show in graphical mode.
It has simple CAD features such as pan view, Zoom window, Zoom all, Zoom in and Zoom out.
Item Description
Tapping point (intake).
Refer Topic 9: Aquator Tapping Point & Tapping Pressure Head (Intake)
Node
To add any QD or QH.
Can also not insert any Q.
Refer Topic 11.2: How to Insert Q Inside Aquator? Or Topic 12.3: How
to Insert QH?
Pipe
Refer Topic 10: Aquator Pipe
Item Description
Branched system
Refer Topic 1: What’s is Aquator?
Loop system.
Clockwise flow.
Refer Topic 1: What’s is Aquator?
Step a Step b
Page 31 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
16 Aquator Result
Result will be generated after select “Integrity” and then “Run” icon.
Result for pipe and node can be view at dock panel (bottom);
i. Pipe
Pipe Result Average Flow or Peak Flow
Calculation for total head loss (Pipe), and residual head (node) can be viewed by select “Calc” icon.
Step a
Step b
Step h
Step c
Step g
Step d Step f
Step e
Topic 16.1: (Please refer Diagram 13.3: Calculation for pipe or node)
Page 32 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
c) For pipe, click “Select all” button if to view all calculation or tick any pipe to view it.
d) Click “Show” button.
e) Calculation pipe selected will be show.
16.2 Report
Step a Step e
Step c Step f
Step g
Step h
ii. Water
To generate report.
c) Select “Setup” at “Report” ribbon. “Report Setup” table will pop up.
d) Select “OK” for “Report Setup” after insert all information required.
Page 33 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
17 Aquator Section
The plotted sections view will be display.
It generally for setup section plotting. User can control how the section data to present in section plot such
as scale for section, change datum value or etc.
Step a
Step b
Step c
Step d
Page 34 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Topic 17.1.1: (Please refer Diagram 14.2: Additional data to add at section)
d) Click “Add row” to insert into “Selected section row for view”.
e) Select “OK” button to exit.
Button Description
Add Row To add any new data than at default section row.
(Add Empty Row)
Add All To add all Default Section Row.
Remove added row To remove any selected section row for draw.
Page 35 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Step b Step e
Step c Step f
Step d
Step g
g) To amendments setup required, select ”Setup” button (shortcut for CAD Section)
Step a
Step c
Step b
Step d
Step f
Step e
Step g
Page 36 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
ODL: 21.35m
Ground Level: 3.35m
Page 37 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Step a
Step d
Step c Step e
Step 2: (Please refer Diagram 1.1: Setup parameter before Import CAD)
a) Select Setup icon.
b) At “General”, go to “Check Pressure Type” and “Default Data”.
c) Change pressure type at “Check Pressure type” as HSL.
d) At “Default Data” change “Required Head” as 0 and set parameter require such as;
i. Pipe Name
ii. Hydrant Flow
iii. Diameter
Step a
Step b
Page 38 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
e) “Water Supply Guideline” will pop up. Select guideline to design which is SYABAS.
Step c
Step i
Step ii
Step b
Page 39 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Step c
Step e
Step d
Step f Step b
Step a
Step 5: (Please refer Diagram 5.1: Add tapping point and pressure head)
a) Select node for intake.
b) Once select required node, node will be highlight in yellow colour.
c) Go to properties (left hand side) at “1-Input” table.
d) At “7.Tapping Point” change as “True”.
e) After change “True”, layout at required node will appear arrow (means that Intake point)
f) Other number 7, “7-Tapping Pressure Head”, add pressure head required as 18 m.
ODL=21.35m , GL=3.35m
Pressure Head = 21.35 – 3.35
= 18.0 m
Step b
Step c
Step a
Step d
Step 6: (Please refer Diagram 6.1: Add HSL and Q at node required)
a) Select node that contain Q. (will be highlight in yellow colour after select)
b) Go to properties at “1-Input” again.
Page 40 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Step b
Step a
Step c
Step d
Step b
Step c
Step a
Page 41 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Step a Step b
Notes:
If after “Integrity” show as Integrity FAILED, kindly check
the caused failed at Error List and fix it to proceed.
Step a
Step b
Notes:
To RE-SAVE same project, select Save or Save icon.
Please save every project into different folder.
Step b
Step f
Step c
Step e
Step d
Diagram 11.1: Default Section
e) To change section or datum, select “Setup” button. (Shortcut for section from Setup
icon)
f) To save, select “Save” Icon at section part. Section will save inside the folder created
in .dwg format.
Page 43 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
11.2 3D View
Step a
Step b
11.3 Calculation
Step a Step f
Step b Step d
Step c Step e
Page 44 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
11.4 Report
Step a
Step b
Step c
Step d
Step e
Page 45 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
ODL: 21.35m
Ground Level: 15.0 m
Page 46 of 47
Infravera Engineering Software.(2335278-U)
No 6-3, JalanPuteri 2/4, Bandar PuteriPuchong, 47100 Puchong, Selangor.Website: www.infravera.com
Tel: 03-8063 5733 Fax: 03-8051 4637 Email: sales@infravera.com (Sales) support@infravera.com (Tech. Support)
Step d
Step c
Step 2: (Please refer Diagram 11.6: Setup parameter before Import CAD)
a) Select Setup icon.
b) At “General”, go to “Check Pressure Type” and “Default Data”.
c) Change pressure type at “Check Pressure type” as Required Head.
d) At “Default Data”, set parameter require such as;
i. Pipe Name
ii. Hydrant Flow
iii. Diameter
iv. Required Head
Page 47 of 47