You are on page 1of 4

#4U BLR Safety Valve Trevitest Result

Valve Design Pressure (Barg) Holding Pressure Result


Approx. Load Popping
No Name Name Tag Popping Reset Min 60% (Barg) Fixing Pressure Max 80% (Barg)
Gross/net (MW) (Bar)
185.3
1 4MS-SFV501 185.10 177.2 110 130 148 485/450
SH Outlet 185.5
SV 185.1
2 4MS-SFV502 185.10 177.2 110 130 148 485/450
185.2

199.9
3 4BDW-SFV601 200 192.05 120 150 160 535/500
201.6

204.3
4 4BDW-SFV602 206 197.8 120 150 160 535/500
204.6

206.1
5 4BDW-SFV603 206 197.8 120 150 160 535/500
205.5

STEAM DRUM 205.0


6 4BDW-SFV604 206 197.8 120 150 160 535/500
SV 205.7

206.0
7 4BDW-SFV605 206 197.8 120 150 160 535/500
206.6

206.1
8 4BDW-SFV606 206 197.8 120 150 160 535/500
206.9

205.3
9 4BDW-SFV607 206 197.8 120 150 160 535/500
206.7

43.5
10 4HRH-SFV501 43.90 42.17 26 32 35 620/585
RH Outlet 43.9
SV 44.0
11 4HRH-SFV502 43.90 42.17 26 32 35 620/585
43.9

46.3
12 4CRH-SFV501 46 44.2 27 34 36 610/575
12 4CRH-SFV501 46 44.2 27 34 36 610/575
46.2

47.3
13 4CRH-SFV502 47.30 45.42 27 34 36 610/575
47.1

47.5
14 4CRH-SFV503 47.30 45.42 27 34 36 610/575
47.5

RH Inlet 47.3
15 4CRH-SFV504 47.30 45.42 27 34 36 610/575
SV 47.4

47.3
16 4CRH-SFV505 47.30 45.42 27 34 36 610/575
47.3

47.2
17 4CRH-SFV506 47.30 45.42 27 34 36 610/575
47.4

46.8
18 4CRH-SFV507 47.30 45.42 27 34 36 610/575
46.7
29.7
19 Soot Blower SV 4AI-SFV501 29.4 - 17 28 23 29.4
29.7
Valve Trevitest Result
Result
Reset Date Time Priority
(Bar)
184.2
09:00 ~ 09:30 1
180.0

182.1
10:00 ~ 10:30 2
182.2

195.2
13:00 ~ 13:30 3
195.0

203.6
14:00 ~ 14:30 4
202.3

199.5
15:00 ~ 15:30 5
193.9

202.9
16:00 ~ 16:30 6
205.0

204.9
17:00 ~ 17:30 7
203.3

204.3
18:00 ~ 18:30 8
204.8

204.3
19:00 ~ 19:30 9
205.7
24-Sep-18
42.6
09:00 ~ 09:30 10
41.7

43.3
10:00 ~ 10:30 11
43.0

45.3
11:00 ~ 11:30 12
11:00 ~ 11:30 12
45.8

46.8
12:00 ~ 12:30 13
46.4

46.0
13:00 ~ 13:30 14
46.4

46.0
14:00 ~ 14:30 15
45.8

46.6
15:00 ~ 15:30 16
46.5

46.0
16:00 ~ 16:30 17
45.9

45.8
17:00 ~ 17:30 18
45.8
29.1
28.9 19:30 ~ 20:00 19
29.1

You might also like