FEATURES
INNOVATIVE DESIGN & PROTOTYPE TESTING are key components of
¡ SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION.
¡
GENERAC’S success in “IMPROVING POWER BY DESIGN.” But it This state-of-the-art power maximizing regulation system is standard on
doesn’t stop there. Total commitment to component testing, reliability all Generac models. It provides optimized FAST RESPONSE to changing
testing, environmental testing, destruction and life testing, plus testing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by
to applicable CSA, NEMA, EGSA, and other standards, allows you to electronically torque-matching the surge loads to the engine. Digital
choose GENERAC POWER SYSTEMS with the confidence that these voltage regulation at ±1%.
systems will provide superior performance.
SINGLE SOURCE SERVICE RESPONSE from Generac’s extensive dealer
¡
network provides parts and service know-how for the entire unit, from the
engine to the smallest electronic component.
¡ TEST CRITERIA:
3 PROTOTYPE TESTED 3 NEMA MG1-22 EVALUATION
G ENERAC TRANSFER SWITCHES. Long life and reliability are
¡
3 SYSTEM TORSIONAL TESTED 3 MOTOR STARTING ABILITY synonymous with GENERAC POWER SYSTEMS. One reason for this
confidence is that the GENERAC product line includes its own transfer
systems and controls for total system compatibility.
ISO
9 0 0 1:
2008
Protector™ Series
®
GENERATOR SPECIFICATIONS
Type Synchronous
Rotor Insulation Class H (15 & 20 kW) or F (30, 48 & 50 kW)
Stator Insulation Class H
2 of 6
Telephone Interference Factor (TIF) <50
Alternator Output Leads 1-Phase 3 wire
Alternator Output Leads 3-Phase 6 wire
Bearings Single Sealed Cartridge
Coupling Direct, Flexible Disc
Excitation System Direct
VOLTAGE REGULATION
Type Electronic
Sensing Single Phase
Regulation ± 1%
Features Adjustable Voltage & Gain
GOVERNOR SPECIFICATIONS
Type Electronic Isochronous
Steady State Regulation ± 0.25%
ELECTRICAL SYSTEM
Battery Charge Alternator 50 Amp (15 & 20 kW) or 70 Amp (30, 48 & 50 kW)
Static Battery Charger 2 Amp
Recommended Battery (battery not included) Group 27F, 700 CCA
System Voltage 12 Volts
GENERATOR FEATURES
Revolving field heavy duty generator
Directly connected to the engine
Operating temperature rise 120°C above a 40°C ambient
Class H insulation is NEMA rated
Class F insulation is NEMA rated
All models fully prototype tested
ENCLOSURE FEATURES
Ensures protection against mother nature. Electrostatically applied textured
Aluminum weather protective enclosure
epoxy paint for added durability.
Enclosed critical grade muffler Quiet, critical grade muffler is mounted inside the unit to prevent injuries
and maximize sound dampening.
Small, compact, attractive Makes for an easy, eye appealing installation.
SAE Sound attenuated enclosure ensures quiet operation.
Protector™ Series
®
Dimensions
62 x 31 x 49/158 x 78 x 124 77 x 35 x 55/195 x 89 x 141
(LxWxH) (in/cm)
Protector™ Series
®
15 • 20 • 30 • 48 • 50 kW operating data
GENERATOR OUTPUT VOLTAGE/kW - 60 Hz
kW (Standby) Amp (Standby) kW (Prime) Amp (Prime) CB Size
120/240 V, 1Ø, 1.0 pf 15 62 12 50 70
RD015 120/208 V, 3Ø, 0.8 pf 15 52 12 42 60
120/240 V, 3Ø, 0.8 pf 15 45 12 36 50
4 of 6
120/240 V, 1Ø, 1.0 pf 20 83 16 67 100
RD020 120/208 V, 3Ø, 0.8 pf 20 69 16 56 80
120/240 V, 3Ø, 0.8 pf 20 60 16 48 70
120/240 V, 1Ø, 1.0 pf 30 125 24 100 150
120/208 V, 3Ø, 0.8 pf 30 104 24 83 125
RD030
120/240 V, 3Ø, 0.8 pf 30 90 24 72 100
277/480 V, 3Ø, 0.8 pf 30 45 24 36 50
120/240 V, 1Ø, 1.0 pf 48 200 38.4 183 200
RD048 & 120/208 V, 3Ø, 0.8 pf 50 173 40 153 200
RD050 120/240 V, 3Ø, 0.8 pf 50 150 40 132 175
277/480 V, 3Ø, 0.8 pf 50 75 40 66 90
STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There
is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.
Protector™ Series
®
15 • 20 • 30 • 48 • 50 kW operating data
ENGINE COOLING
15 kW 20 kW 30 kW 48 & 50 kW
Air flow (inlet air including alternator and combustion air in cfm/cmm) 2824/80 2824/80 3038/86 2824/80
System coolant capacity (gal/liters) 2.8/10.6 2.8/10.6 2.8/10.6 2.8/10.6
5 of 6
Heat rejection to coolant (BTU per hr/MJ per hr) 63,535/67 63,535/67 111,000/117.1 135,900/143.4
Maximum operation air temperature on radiator (°C/°F) 50/122
Maximum ambient temperature (°C/°F) 50/122
COMBUSTION REQUIREMENTS
Flow at rated power (cfm/cmm) 84.76/2.4 84.76/2.4 90/2.55 190/5.38
SOUND EMISSIONS
Sound output in dB(A) at 23 ft (7 m) with generator in exercise mode* 65
Sound output in dB(A) at 23 ft (7 m) with generator operating at normal load* 70
*Sound levels are taken from the front of the generator. Sound levels taken from other sides of the generator may be higher depending on installation parameters.
EXHAUST
Exhaust flow at rated output (cfm/cmm) 98.88/2.8 98.88/2.8 230/6.51 448/12.7
Exhaust temperature at rated output (°C/°F) 510/950 510/950 454.4/850 604.4/1120
ENGINE PARAMETERS
Rated Synchronous RPM 1800
HP at rated kW 26.4 33.5 49 85
CONTROLLER FEATURES
2-Line Plain Text Multilingual LCD Display......................................................................................................................Simple user interface for ease of operation.
Mode Buttons: Auto..................................................................................................................... Automatic Start on Utility failure. Programmable 7 day exerciser.
Manual........................................................................................ Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Off..........................................................................................................................Stops unit. Power is removed. Control and charger still operate.
Ready to Run/Maintenance Messages................................................................................................................................................................................. Standard
Engine Run Hours Indication............................................................................................................................................................................................... Standard
Programmable start delay between 2-1500 seconds ..........................................................................................................Standard (programmable by dealer only)
Utility Voltage Loss/Return to Utility Adjustable..................................................................................................................................... From 140-171 V/190-216 V
Future Set Capable Exerciser/Exercise Set Error Warning..................................................................................................................................................... Standard
Run/Alarm/Maintenance Logs .................................................................................................................................................................................. 50 Events Each
Engine Start Sequence .................................................................................................................... Cyclic cranking: 16 sec on, 7 rest (90 sec maximum duration).
Starter Lock-out ................................................................................................................................Starter cannot re-engage until 5 sec after engine has stopped.
Smart Battery Charger ........................................................................................................................................................................................................ Standard
Charger Fault/Missing AC Warning...................................................................................................................................................................................... Standard
Low Battery/Battery Problem Protection and Battery Condition Indication ............................................................................................................................ Standard
Automatic Voltage Regulation with Over and Under Voltage Protection ................................................................................................................................ Standard
Under-Frequency/Overload/Stepper Overcurrent Protection.................................................................................................................................................. Standard
Safety Fused/Fuse Problem Protection................................................................................................................................................................................ Standard
Automatic Low Oil Pressure/High Oil Temperature Shutdown .............................................................................................................................................. Standard
Overcrank/Overspeed (@ 72 Hz)/RPM Sense Loss Shutdown ............................................................................................................................................ Standard
High Engine Temperature Shutdown ................................................................................................................................................................................... Standard
Internal Fault/Incorrect Wiring Protection ............................................................................................................................................................................ Standard
Common External Fault Capability ...................................................................................................................................................................................... Standard
Field Upgradable Firmware................................................................................................................................................................................................. Standard
6 of 6
Protector™ Series
AIR INTAKE OIL DIP STICK RIGHT SIDE GENERATOR AS SHOWN 555 [1224] 1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1092 (43") WIDE X 1887 (74.3") LONG.
RADIATOR/EXHAUST (BOTH SIDES) REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES.
OIL FILTER RIGHT SIDE WITH WODDEN SHIPPING SKID 594 [1310]
DISCHARGE AIR 2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
OIL DRAIN HOSE RIGHT SIDE AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
(BOTH SIDES) WEIGHT: KG [LBS]
RADIATOR DRAIN HOSE LEFT SIDE DIMENSIONS: MM [INCH] APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
735 [28.9] STATE, AND LOCAL CODES.
110 CENTER OF GRAVITY COOLANT RECOVERY BOTTLE LEFT SIDE
3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
Drawing #0K7394-A (1 of 2)
[4.3] (SEE NOTE 5) RADIATOR FILL CAP ACCESS ROOF TOP - SEE SPECIFICATION SHEET OR OWNERS MANUAL
AIR CLEANER ELEMENT EITHER SIDE - ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR.
212 MUFFLER FRONT 4. REMOVE THE REAR STUB-UP AND REAR ENCLOSURE COVER PANEL TO ACCESS
[8.3] THE STUB-UP AREAS AS FOLLOWS:
FAN BELT EITHER SIDE - HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION,
BATTERY LEFT SIDE NEUTRAL CONNECTION, AND BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
- LOW VOLTAGE CONNECTION INCLUDING TRANSFER SWITCH CONTROL WIRES
REFERENCE OWNERS MANUAL FOR PERIODIC AND ACCESSORY RELAY CONNECTION (QTY 4)
2" O.D. EXHAUST REPLACEMENT PART LISTINGS. 5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
OUTLET 6. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
B RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW. B
7. EXHAUST SYSTEM MAXIMUM BACK PRESSURE: 24 INCHES H2O.
8. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
9. MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5
(USE STANDARD SAE TORQUE SPECS)
10. MUST ALLOW FREE FLOW OF INTAKE AIR, DISCHARGE AIR AND EXHAUST. SEE SPEC
REMOVE COVER SHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS.
FOR ACCESS TO BATTERY 12 VOLT 11. GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE
RADIATOR FILL CAP TOP VIEW NEGATIVE GROUND AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED.
REAR ENCLOSURE
COVER PANEL
SEE NOTE 4
TITLE
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
INSTALL PROTECTOR D2.3L G16
APPLIED TO SOLID MODEL ONLY. SINGLE WALL TANK
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS. ISSUE DATE: 06/2014
c GENERAC POWER SYSTEMS 2013
SIZE CAGE NO DWG NO REV
ELECTRONICALLY APPROVED B N/A 0K7394 A
INSIDE WINDCHILL
SCALE 0.050 WT-KG SEE ABOVE SHEET 1 of 2
4 3 2 1
installation layout
®
SH REV WINDCHILL VERSION
4 3 2/2 A A.1 1
15 & 20 kW
1120 [44.1]
FUEL FILL
1007 [39.7] (2" NPT FEMALE)
B B
CIRCUIT BREAKER 674
NEUTRAL AND CUSTOMER [26.5]
CONNECTION OPENING STUB-UP
625 AREA
[24.6]
TYP 105
[4.1]
19 9
[.7] [.4]
51
100 [2.0]
[3.9]
1582 [62.3]
TITLE
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
INSTALL STUB-UP VIEW PROTECTOR D2.3L
APPLIED TO SOLID MODEL ONLY. SINGLE WALL TANK
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS. ISSUE DATE: 06/2014
c GENERAC POWER SYSTEMS 2013
SIZE CAGE NO DWG NO REV
ELECTRONICALLY APPROVED B N/A 0K7394 A
INSIDE WINDCHILL
SCALE 0.080 WT-KG SEE SHEET 1 SHEET 2 of 2
installation layout
Drawing #0K7394-A (2 of 2)
4 3 2 1
®
7 of 6
Protector™ Series
8 of 6
Protector™ Series
30 kW
SH REV WINDCHILL VERSION
4 3 1/2 B B.1 1
SERVICE ITEM 2.4L WEIGHT DATA WITH EMPTY BASETANK
OIL FILL CAP RIGHT SIDE (SEE NOTE 5)
AIR CLEANER ELEMENT LEFT SIDE REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT
REMOVE COVER FOR CONCRETE PAD GUIDELINES
FOR ACCESS TO MUFFLER FRONT
2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
RADIATOR FILL CAP AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
FAN BELT EITHER SIDE
APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
BATTERY LEFT SIDE STATE, AND LOCAL CODES.
3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
REFERENCE OWNERS MANUAL FOR PERIODIC
- SEE SPECIFICATION SHEET OR OWNERS MANUAL
REPLACEMENT PART LISTINGS.
- ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF
B GENERATOR B
4. REMOVE THE REAR TANK AND REAR ENCLOSURE COVER PANEL TO ACCESS
THE STUB-UP AREAS AS FOLLOWS:
- HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION
NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
- LOW VOLTAGE CONNECTIONS INCLUDING TRANSFER SWITCH CONTROL WIRES
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
6. ENGINE SERVICE CONNECTIONS
173 OIL DRAIN: 3/8" NPT
[6.8] EXHAUST OUTLET: 2" O.D.
7. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
AND RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
146 8. EXHAUST SYSTEM MAXIMUM BACK PRESSURE: 35 INCHES H2O.
[5.8] BATTERY 12 VOLT
9. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
NEGATIVE GROUND
10. MOUNTING BOLTS OR STUDS TO CONCRETE PAD SHALL BE 5/8-11 GRADE 5
TOP VIEW (USE STANDARD SAE TORQUE SPECS)
CIRCUIT BREAKER
SEE NOTE 3
1407 [55.4]
OVERALL
HEIGHT
CUSTOMER ACCESS LIFTING PROVISIONS
ASSEMBLY, CONTROL PANEL (4 PLACES)
ACCESS, BATTERY CHARGER SEE NOTE 9 AND
LOCATED WITHIN CENTER OF GRAVITY
SEE NOTE 4 DIMENSIONS
302 [11.9]
REAR TANK COVER
SEE NOTE 4
38
[1.5] 51
[2.0]
828 [32.6]
923 [36.4]
112 [4.4]
1429 [56.2]
1554 [61.2]
1764 [69.4] 187 [7.3]
STUB-UP
AREA
353
[13.9]
16.7 [.66]
MOUNTING HOLES
(8 PLACES)
112 [4.4]
19 851 [33.5]
A 712 [28.0] [.7] TYP A
1242 [48.9] 888
1842 [72.5] [35.0]
TITLE
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY. INSTALL CPL PROT D2.4L SW
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS. ISSUE DATE:
c GENERAC POWER SYSTEMS 2013
SIZE CAGE NO DWG NO REV
ELECTRONICALLY APPROVED B 0K7002A B
INSIDE WINDCHILL
SCALE 0.075 WT-KG SEE ABOVE SHEET 2 of 2
installation layout
Drawing #0K7002A-B (2 of 2)
4 3 2 1
®
9 of 6
Protector™ Series
Protector™ Series
10 of 6
SH REV WINDCHILL VERSION
4 3 1/2 A A.4 1
48 & 50 kW
(BOTH SIDES) AIR CLEANER ELEMENT RIGHT SIDE STATE AND LOCAL CODES.
FOR ACCESS TO
RADIATOR FILL CAP MUFFLER FRONT 3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
- SEE SPECIFICATION SHEET OR OWNERS MANUEL
FAN BELT EITHER SIDE
- ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR
BATTERY LEFT SIDE 4. REMOVE THE REAR TANK AND REAR ENCLOSURE COVER PANEL TO ACCESS THE
STUB-UP AREAS AS FOLLOWS:
REFERENCE OWNERS MANUAL FOR PERIODIC
-HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION
REPLACEMENT PART LISTINGS.
NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
-LOW VOLTAGE CONNECTIONS INCLUDE TRANSFER SWITCH CONTROL WIRES
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
6. ENGINE SERVICE CONNECTIONS
OIL DRAIN: 3/8" NPT
B EXHAUST OUTLET: 2" O.D.
B
7. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
TOP VIEW 8. EXHAUST SYSTEM MAXIMUM BACK PRESSURE: 35 INCHES H20.
9. REFERNCE OWNERS MANUAL FOR LIFTING WARNINGS.
173 [6.8] 10. MOUNTING BOLTS OR STUDS TO CONCRETE PAD SHALL BE 5/8-11 GRADE 5
RADIATOR/EXHAUST
DISCHARGE AIR
VISE ACTION LATCH,
758 [29.8] ONE PER DOOR, ONE LIFT-OFF
DOOR TYP DOOR PER SIDE OF GENERATOR
REAR ENCLOSURE COVER
PANEL
SEE NOTE 4
CIRCUIT BREAKER
SEE NOTE 3
LIFTING PROVISIONS
CUSTOMER ACCESS (4 PLACES)
ASSEMBLY, CONTROL PANEL 1408 SEE NOTE 10 AND CENTER
ACCESS, BATTERY CHARGER [55.4] OF GRAVITY DIMENSIONS
LOCATED WITHIN OVERALL
SEE NOTE 4 HEIGHT
302
[11.9]
REAR TANK COVER
FRONT TANK SEE NOTE 4
COVER EXHAUST MUFFLER ENCLOSED WITHIN
GENERATOR ENCLOSURE 888 [35.0] 182 1322 [52.0]
A OVERALL WIDTH [7.2] 1954 [76.9]
A
OVERALL LENGTH
TITLE
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY. INSTALL CPL PROT D3.4L SW
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS. ISSUE DATE:
c GENERAC POWER SYSTEMS 2013
SIZE CAGE NO DWG NO REV
ELECTRONICALLY APPROVED B 0K6968A A
INSIDE WINDCHILL
SCALE 0.050 WT-KG SEE ABOVE SHEET 1 of 2
4 3 2 1
installation layout
®
SH REV WINDCHILL VERSION
4 3 2/2 A A.4 1
48 & 50 kW
B B
CIRCUIT BREAKER,
757 [29.8] NEUTRAL AND CUSTOMER 786 [30.9]
TYP CONNECTION OPENING STUB-UP
AREA
621 [24.5]
TYP
REMOVABLE STUB-UP
COVER
REMOVABLE COVER
353 [13.9]
16.7 [.66] MOUNTING HOLES
(8 PLACES)
TITLE
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY. INSTALL CPL PROT D3.4L SW
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS. ISSUE DATE:
c GENERAC POWER SYSTEMS 2013
SIZE CAGE NO DWG NO REV
ELECTRONICALLY APPROVED B 0K6968A A
INSIDE WINDCHILL
SCALE 0.075 WT-KG SEE ABOVE SHEET 2 of 2
installation layout
4 3 2 1
Drawing #0K6968A-A (2 of 2)
®
Protector™ Series
11 of 6
Protector™ Series
®
15 • 20 • 30 • 48 • 50 kW available accessories
Model # Product Description
006505-0 - 15 & 20 kW Tank risers are required in some municipalities to help avoid potential base tank
Tank Risers
006506-0 - 30, 48 & 50 kW corrosion caused by mounting on rough surfaces.
12 of 6 The cast iron, lockable fuel cap provides the ability to lock the fuel system to
006512-0 Lockable Fuel Cap
prevent unwanted fuel tampering or fuel siphoning.
006572-0 - 15 & 20 kW
The Protector Maintenance Kits offer all the hardware necessary to perform
006571-0 - 30 kW Maintenance Kits
complete maintenance on Ottomotores Protector generators.
006570-0 - 48 & 50 kW
Wireless Remote Recommended for use with the Wireless Remote on units up to 60 kW, required
006665-0
Extension Harness for use on units 70 kW or greater.
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2015 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0K4730-H Printed in U.S.A. 07/21/15