Professional Documents
Culture Documents
RR
TYYMM DD TT NN Page
T9834 XX XX XX 1 of 3
ﭘﺮوژه اﺣﺪاث ﭼﻨﺪ راھﮫ اﻗﻤﺎری در واﺣﺪ ﺑﮭﺮه ﺑﺮداری ﻣﺎرون 5
RR
TYYMM DD TT NN Page
T9834 XX XX XX 2 of 3
Maroon P1 Tender (Electrical MTO)
Description Quantity
Deiesel genetartor
DIESEL GENERATOR, 3 PHASE ,400 VOLTS, 1500 RPM, 350KVA FOR CONTINIOUS USE(S1) @55℃, ACCORDING TO LATEST VERSION OF IPS-M-EL-138, IPS-E-EL-100, IEC 60034, IEC 60085, IEEE
112, IPS-M-PM-290(2), ISO 8528, BS 5514, IPS-M-EL-174 & Document NO: 971009-P01-EL-SP-002-0 AND WITH LOW VOLTAGE PANEL WITH ALL PROTECTION ACCORDING TO LATEST VERSION
Nos 1
IPS-M-EL-143, BATTERY CHARGER AND NI-CD BATTRY ACCORDING TO LATEST VERSION IPS-M-EL-174 (WITH STANDARD AND ORIGINAL SUPPORT STANDING FOR BATTERIES) AND ALL
ACCESSORIES
Power Transformer
POWER TRANSFORMERS, HERMITICALY OIL IMMERSE SEALD TYPE, (33 KV/ 0.4 KV) , 250 KVA,50 HZ,DYn11,AMBIENT TEMP 60℃ ,SHORT CIRCUIT IMPEDANCE 4%, SYSTEM SHORT CIRCUIT
POWER PRIMERY(25KA)/SECONDARY(50KA),OFF CIRCUIT TAP CHANGER( 5 POSITIONS (± 2 x 2.5)%),WITH ALL PROTECTION, IP55,ACCORDING TO LATEST VERSION OF IPS-M-EL-152, IPS-E-EL- Nos 1
100, IEC 60076 & Document NO: 971009-P01-EL-SP-001-0
OUTDOOR LOCAL CONTROL STATION WITH THE MINIMUM ENCLOSURE BODY OF SS 316 L SUITABLE FOR ZONE 1 OR ZONE 2, GAS GROUP IIB & T3 CLASSIFIED AREA WITH THE FOLLOWING
SPECIFICATIONS EEX 'E', COLUMN MOUNTED WITH START/ STOP AMP METER , EMERGENCY MUSHROOM PUSH BUTTON , CABLE GLANDS AND WITH A MINIMUM OF TWO ISO METRIC TYPE
Nos 3
CABLE ENTRIES, SUITABLE FOR BOTTOM ENTRY OF 19C X 2.5 SQ.MM. CABLE. CLIP-ON TYPE TERMINAL BLOCKS SHALL BE PROVIDED FOR ALL INCOMING AND OUTGOING CABLES. A MINIMUM
OF 20% SPARE TERMINALS SHALL BE PROVIDED WITHIN EACH ENCLOSURE. AII CABLE GLANDS ENTERING INTO THE ENCLOSURE SHALL DO SO THROUGH THREADED ENTRIES.
Lighting fixture
Fluorescent light, 2x36W, bi-pin type, suitable for use in Zone 2 Nos 12
LV Switchgear
LV MCC SWITCHGEAR PANEL, WITHDRAWABLE, MOTOR CONTROL CENTERS SWITCHGEAR PANEL , 2 NO.S INCOMERS, 1 NO BUS SECTION 400VOLTS, 3 PHASE, 800A ,(IP=42), ACCORDING TO
Nos 1
LATEST VERSION IPS-M-EL-143 & Documents NO: 971009-P01-EL-DW-001-0 & 971009-P01-EL-SP-003-0
BATTERY CHARGER 110VDC, INDUSTRIAL TYPE, DUAL UNIT SET WITH DISTRIBUTION PANEL, IP42 , INPUT :THREE PHASE, 380/400/440 VOLTS ±10%, OUT PUT: 110 VOLTS DC, 10KW, FULL
THYRISTOR CONTROL 12 PULSE WITH NICKEL CADMIUM BATTERIES 184(2×92) NO,INPUT THD% <5% , SBLE TYPE , AGING FACTOR 1.25 & DESIGN MARGINE1.15 AND FINALL VOLTAGE 1.14
Nos 1
PER CELL AND WITH 8 HOURS BACKUP TIME, ACCORDING TO LATEST VERSION IPS-M-EL-174 & , IPS-E-EL-100 (WITH STANDARD AND ORIGINAL SUPPORT STANDING FOR BATTERIES) &
Document NO: 971009-P01-EL-SP-004-0 & 971009-P01-EL-DW-005-0
DC UPS 24 VDC
BATTERY CHARGER 24VDC, INDUSTRIAL TYPE, DUAL UNIT SET WITH DISTRIBUTION PANEL, IP42 , INPUT :THREE PHASE, 380/400/440 VOLTS ±10%, OUT PUT: 24 VOLTS DC, 2KW, FULL
THYRISTOR CONTROL 12 PULSE, WITH NICKEL CADMIUM BATTERIES 40(2×20) NO , INPUT THD% <5% , SBLE TYPE , AGING FACTOR 1.25& DESIGN MARGINE1.15 , FINALL VOLTAGE 1.14 PER
Nos 1
CELL AND WITH 24 HOURS BACKUP TIME, ACCORDING TO LATEST VERSION IPS-M-EL-174 & , IPS-E-EL-100 (WITH STANDARD AND ORIGINAL SUPPORT STANDING FOR BATTERIES ) &
Document NO: 971009-P01-EL-SP-004-0 & 971009-P01-EL-DW-005-0
AC UPS 110VAC, INDUSTRIAL TYPE, TRUE ONLINE DOUBLE CONVERSION WITH DISTRIBUTION PANEL, FLOOR MOUNTED ,IP42 ,INPUT THREE PHASE , 380/400/440 VOLTS ±10%,VOLTS ,
OUTPUT SINGLE PHASE 110 VAC, 5KVA ,FULL THYRISTOR CONTROL 12 PULSE, WITH NICKEL CADMIUM BATTERIES 184(2×92) NO , INPUT THD% <5% , SBM TYPE , AGING FACTOR 1.25& DESIGN
Nos 1
MARGINE1.15 , FINALL VOLTAGE 1.14 PER CELL AND WITH 2 HOUR BACK UP TIME, WITH SUPPORT STANDING AND ALL ACCESSORIES ACCORDING TO LATEST VERSION IPS-E-EL-100, IPS-M-EL-
176(WITH STANDARD AND ORIGINAL SUPPORT STANDING FOR BATTERIES ) & Document NO: 971009-P01-EL-SP-005-0 & 971009-P01-EL-DW-006-0
DC MCCB
DC DISCONNECTOR SWITCH BOXIES WITH 2 NO SWITCHE FUSES , 2 POLE FOR UPS AND 110 VDC BATTERY CHARGER , 24 VDC , 110 UPS (EXD IIC T3) Nos 6
DISTRIBUTION BOARD
EXD TYPE DISTRIBUTION BOARD, DISTRIBUTION FUSE BOARD AND MOTOR STARTER WALL MOUNTED, EXD IIB,T3 ,400 VOLTS ,3PH+N, IP=54 AND IP42, ACCORDING TO IPS-E-EL-100(1) Nos 2
AUTOMATIC CAPACITOR BANK PANEL WITH CAPACITORS & AUTOMATIC REGULATOR RELAY ,75 KVAR, 400 VOLTS , 3PH, ACCORDING TO LATEST VERSION IPS-M-EL-181 & Document NO:
Nos 1
971009-P01-EL-SP-006-0
3 POLE OUTDOOR MOTORIZED ON LOAD BREAK SWITCHES WITH EARTH BLADE, 36KV, WITH THREE POLE FUSES , ISC=25KA FOR 3 SEC, In=1250 AMPS WITH ALL REQUIREMENTACCESSORIES Nos 8
DISCONNECTOR SWITCHES MV
3POLE OUTDOOR DISCONNECTOR SWITCHES WITH EARTH BLADE, 36 KV , Isc=25KA FOR 3 SEC ,In=1250 AMPS WITH MANUAL EARTHING SWITCH AND ALL REQUIRED ACCESSORIES Nos 4
GANTRY MV
GALVANIZED STEEL STRUCTURE GANTRIES, 9 METER HIGH , 6 METER WIDE , SUITABLE FOR INSTALATION OF 36 KV ON LOAD BREAK SWITCHES OR 36KV DISCONNECTOR SWITCHES, WITH ALL
Nos 7
REQUIREMENT ACCESSORIES.
DOUBLE CIRCUIT 36 KV OVER HEAD LINE TOWER AND ACCESSORIES, STEEL LATICE TOWERS,16 Km ACSR CONDUCTOR FOR 12 MW,EARTH WIRE GALVANIZED STEEL, TENSION/SUSPENTION
INSULATOR SET (AT LAST 4 INSOULATOR PER STRING ), STUB SETTING TEMPLATE,STOCKBRIDGE VIBRATION DAMPER,PARALLEL GROOVE CALAMP ,STRAIN CALAMP , PIN INSULATOR ,SHACKLE
Nos 70
,OVER-BALL , SOCKET EYE , SUSPENSION CALAMP SET, Y-BALL , MID SPAN JOINT , POST INSULATOR , TOWER( PHASE,NUMBER,DANGER )PLATE,DEAD END CALAMP, LIGHTNING ARRESTERS
WITH ALL REQUIREMENT ACCESSORIES ACCORDING TO LATEST VERSION IPS-M-EL-160
ﻣﺨﺰن ﻣﻨﺘﺨﺐ ﺷﺮﮐﺖ ﻣﻠﯽ ﻣﻨﺎﻃﻖ ﻧﻔﺖ ﺧﯿﺰ ﺟﻨﻮب27 ﻧﮕﻬﺪاﺷﺖ ﺗﻮﻟﯿﺪ/ در ﻗﺎﻟﺐ ﯾﮏ ﺑﺴﺘﻪ ﯾﮑﭙﺎرﭼﻪ از ﻃﺮح ﻋﻤﻠﯿﺎت ﻣﺤﻮر اﻓﺰاﯾﺶ25 ﻃﺮح ﻣﺎرون آﺳﻤﺎري
RR
TYYMM DD TT NN Page
T9834 XX XX XX 3 of 3
Maroon P1 Tender (Electrical MTO)
Description Quantity
SINGLE MV LINE TOWER
SINGLE CIRCUIT 36 KV OVER HEAD LINE TOWER AND ACCESSORIES, STEEL LATICE TOWERS,1 Km ACSR CONDUCTOR FOR 2 MW,EARTH WIRE GALVANIZED STEEL,
TENSION/SUSPENTION INSULATOR SET (AT LAST 4 INSOULATOR PER STRING ), STUB SETTING TEMPLATE,STOCKBRIDGE VIBRATION DAMPER,PARALLEL GROOVE
Nos 5
CALAMP ,STRAIN CALAMP , PIN INSULATOR ,SHACKLE ,OVER-BALL , SOCKET EYE , SUSPENSION CALAMP SET, Y-BALL , MID SPAN JOINT , POST INSULATOR , TOWER(
PHASE,NUMBER,DANGER )PLATE,DEAD END CALAMP, LIGHTNING ARRESTERS WITH ALL REQUIREMENT ACCESSORIES ACCORDING TO LATEST VERSION IPS-M-EL-160
LIGHTING TOWER
LIGHTING TOWERS GALVANIZED 50 ft , WITH EXD LOOPING BOX, TERMINAL BOX ,LED FLOODLIGHT (AT LAST 4 FLOODLIGHT FOR EACH TOWER), ACCORDING TO IPS-D-
Nos 7
EL-321
LIGHTNING SYSTEM
LIGHTNING PROTECTION SYSTEM STRUCTURE WITH ALL ACCESSORIES (LIGHTNING ARESTER, … ) Nos 4
PRE-COMMISSIONING, COMMISSIONING, START UP & TWO YEARS SPARE PARTS FOR ALL ABOVE ITEMS -