Maroon P1 Tender (Electrical MTO)
Description Quantity
Deiesel genetartor

DIESEL GENERATOR, 3 PHASE ,400 VOLTS, 1500 RPM, 350KVA FOR CONTINIOUS USE(S1) @55℃, ACCORDING TO LATEST VERSION OF IPS-M-EL-138, IPS-E-EL-100, IEC 60034, IEC 60085, IEEE
112, IPS-M-PM-290(2), ISO 8528, BS 5514, IPS-M-EL-174 & Document NO: 971009-P01-EL-SP-002-0 AND WITH LOW VOLTAGE PANEL WITH ALL PROTECTION ACCORDING TO LATEST VERSION
Nos 1
IPS-M-EL-143, BATTERY CHARGER AND NI-CD BATTRY ACCORDING TO LATEST VERSION IPS-M-EL-174 (WITH STANDARD AND ORIGINAL SUPPORT STANDING FOR BATTERIES) AND ALL
ACCESSORIES

Power Transformer

POWER TRANSFORMERS, HERMITICALY OIL IMMERSE SEALD TYPE, (33 KV/ 0.4 KV) , 250 KVA,50 HZ,DYn11,AMBIENT TEMP 60℃ ,SHORT CIRCUIT IMPEDANCE 4%, SYSTEM SHORT CIRCUIT
POWER PRIMERY(25KA)/SECONDARY(50KA),OFF CIRCUIT TAP CHANGER( 5 POSITIONS (± 2 x 2.5)%),WITH ALL PROTECTION, IP55,ACCORDING TO LATEST VERSION OF IPS-M-EL-152, IPS-E-EL- Nos 1
100, IEC 60076 & Document NO: 971009-P01-EL-SP-001-0

Local control station and Junction box

OUTDOOR LOCAL CONTROL STATION WITH THE MINIMUM ENCLOSURE BODY OF SS 316 L SUITABLE FOR ZONE 1 OR ZONE 2, GAS GROUP IIB & T3 CLASSIFIED AREA WITH THE FOLLOWING
SPECIFICATIONS EEX 'E', COLUMN MOUNTED WITH START/ STOP AMP METER , EMERGENCY MUSHROOM PUSH BUTTON , CABLE GLANDS AND WITH A MINIMUM OF TWO ISO METRIC TYPE
Nos 3
CABLE ENTRIES, SUITABLE FOR BOTTOM ENTRY OF 19C X 2.5 SQ.MM. CABLE. CLIP-ON TYPE TERMINAL BLOCKS SHALL BE PROVIDED FOR ALL INCOMING AND OUTGOING CABLES. A MINIMUM
OF 20% SPARE TERMINALS SHALL BE PROVIDED WITHIN EACH ENCLOSURE. AII CABLE GLANDS ENTERING INTO THE ENCLOSURE SHALL DO SO THROUGH THREADED ENTRIES.

Lighting fixture
Fluorescent light, 2x36W, bi-pin type, suitable for use in Zone 2 Nos 12

LV Switchgear

LV MCC SWITCHGEAR PANEL, WITHDRAWABLE, MOTOR CONTROL CENTERS SWITCHGEAR PANEL , 2 NO.S INCOMERS, 1 NO BUS SECTION 400VOLTS, 3 PHASE, 800A ,(IP=42), ACCORDING TO
Nos 1
LATEST VERSION IPS-M-EL-143 & Documents NO: 971009-P01-EL-DW-001-0 & 971009-P01-EL-SP-003-0

DC UPS 110 VDC

BATTERY CHARGER 110VDC, INDUSTRIAL TYPE, DUAL UNIT SET WITH DISTRIBUTION PANEL, IP42 , INPUT :THREE PHASE, 380/400/440 VOLTS ±10%, OUT PUT: 110 VOLTS DC, 10KW, FULL
THYRISTOR CONTROL 12 PULSE WITH NICKEL CADMIUM BATTERIES 184(2×92) NO,INPUT THD% <5% , SBLE TYPE , AGING FACTOR 1.25 & DESIGN MARGINE1.15 AND FINALL VOLTAGE 1.14
Nos 1
PER CELL AND WITH 8 HOURS BACKUP TIME, ACCORDING TO LATEST VERSION IPS-M-EL-174 & , IPS-E-EL-100 (WITH STANDARD AND ORIGINAL SUPPORT STANDING FOR BATTERIES) &
Document NO: 971009-P01-EL-SP-004-0 & 971009-P01-EL-DW-005-0

DC UPS 24 VDC

BATTERY CHARGER 24VDC, INDUSTRIAL TYPE, DUAL UNIT SET WITH DISTRIBUTION PANEL, IP42 , INPUT :THREE PHASE, 380/400/440 VOLTS ±10%, OUT PUT: 24 VOLTS DC, 2KW, FULL
THYRISTOR CONTROL 12 PULSE, WITH NICKEL CADMIUM BATTERIES 40(2×20) NO , INPUT THD% <5% , SBLE TYPE , AGING FACTOR 1.25& DESIGN MARGINE1.15 , FINALL VOLTAGE 1.14 PER
Nos 1
CELL AND WITH 24 HOURS BACKUP TIME, ACCORDING TO LATEST VERSION IPS-M-EL-174 & , IPS-E-EL-100 (WITH STANDARD AND ORIGINAL SUPPORT STANDING FOR BATTERIES ) &
Document NO: 971009-P01-EL-SP-004-0 & 971009-P01-EL-DW-005-0

AC UPS 230 VAC

AC UPS 110VAC, INDUSTRIAL TYPE, TRUE ONLINE DOUBLE CONVERSION WITH DISTRIBUTION PANEL, FLOOR MOUNTED ,IP42 ,INPUT THREE PHASE , 380/400/440 VOLTS ±10%,VOLTS ,
OUTPUT SINGLE PHASE 110 VAC, 5KVA ,FULL THYRISTOR CONTROL 12 PULSE, WITH NICKEL CADMIUM BATTERIES 184(2×92) NO , INPUT THD% <5% , SBM TYPE , AGING FACTOR 1.25& DESIGN
Nos 1
MARGINE1.15 , FINALL VOLTAGE 1.14 PER CELL AND WITH 2 HOUR BACK UP TIME, WITH SUPPORT STANDING AND ALL ACCESSORIES ACCORDING TO LATEST VERSION IPS-E-EL-100, IPS-M-EL-
176(WITH STANDARD AND ORIGINAL SUPPORT STANDING FOR BATTERIES ) & Document NO: 971009-P01-EL-SP-005-0 & 971009-P01-EL-DW-006-0

DC MCCB

DC DISCONNECTOR SWITCH BOXIES WITH 2 NO SWITCHE FUSES , 2 POLE FOR UPS AND 110 VDC BATTERY CHARGER , 24 VDC , 110 UPS (EXD IIC T3) Nos 6

DISTRIBUTION BOARD

EXD TYPE DISTRIBUTION BOARD, DISTRIBUTION FUSE BOARD AND MOTOR STARTER WALL MOUNTED, EXD IIB,T3 ,400 VOLTS ,3PH+N, IP=54 AND IP42, ACCORDING TO IPS-E-EL-100(1) Nos 2

CAPACITOR BANK PANEL

AUTOMATIC CAPACITOR BANK PANEL WITH CAPACITORS & AUTOMATIC REGULATOR RELAY ,75 KVAR, 400 VOLTS , 3PH, ACCORDING TO LATEST VERSION IPS-M-EL-181 & Document NO:
Nos 1
971009-P01-EL-SP-006-0

MOTORIZED ON LOAD BREAKER MV

3 POLE OUTDOOR MOTORIZED ON LOAD BREAK SWITCHES WITH EARTH BLADE, 36KV, WITH THREE POLE FUSES , ISC=25KA FOR 3 SEC, In=1250 AMPS WITH ALL REQUIREMENTACCESSORIES Nos 8

DISCONNECTOR SWITCHES MV

3POLE OUTDOOR DISCONNECTOR SWITCHES WITH EARTH BLADE, 36 KV , Isc=25KA FOR 3 SEC ,In=1250 AMPS WITH MANUAL EARTHING SWITCH AND ALL REQUIRED ACCESSORIES Nos 4

GANTRY MV

GALVANIZED STEEL STRUCTURE GANTRIES, 9 METER HIGH , 6 METER WIDE , SUITABLE FOR INSTALATION OF 36 KV ON LOAD BREAK SWITCHES OR 36KV DISCONNECTOR SWITCHES, WITH ALL
Nos 7
REQUIREMENT ACCESSORIES.

DOUBLE MV LINE TOWER

DOUBLE CIRCUIT 36 KV OVER HEAD LINE TOWER AND ACCESSORIES, STEEL LATICE TOWERS,16 Km ACSR CONDUCTOR FOR 12 MW,EARTH WIRE GALVANIZED STEEL, TENSION/SUSPENTION
INSULATOR SET (AT LAST 4 INSOULATOR PER STRING ), STUB SETTING TEMPLATE,STOCKBRIDGE VIBRATION DAMPER,PARALLEL GROOVE CALAMP ,STRAIN CALAMP , PIN INSULATOR ,SHACKLE
Nos 70
,OVER-BALL , SOCKET EYE , SUSPENSION CALAMP SET, Y-BALL , MID SPAN JOINT , POST INSULATOR , TOWER( PHASE,NUMBER,DANGER )PLATE,DEAD END CALAMP, LIGHTNING ARRESTERS
WITH ALL REQUIREMENT ACCESSORIES ACCORDING TO LATEST VERSION IPS-M-EL-160
‫ ﻣﺨﺰن ﻣﻨﺘﺨﺐ ﺷﺮﮐﺖ ﻣﻠﯽ ﻣﻨﺎﻃﻖ ﻧﻔﺖ ﺧﯿﺰ ﺟﻨﻮب‬27 ‫ ﻧﮕﻬﺪاﺷﺖ ﺗﻮﻟﯿﺪ‬/ ‫ در ﻗﺎﻟﺐ ﯾﮏ ﺑﺴﺘﻪ ﯾﮑﭙﺎرﭼﻪ از ﻃﺮح ﻋﻤﻠﯿﺎت ﻣﺤﻮر اﻓﺰاﯾﺶ‬25 ‫ﻃﺮح ﻣﺎرون آﺳﻤﺎري‬

RR
TYYMM DD TT NN Page
T9834 XX XX XX 3 of 3
Maroon P1 Tender (Electrical MTO)
Description Quantity
SINGLE MV LINE TOWER

SINGLE CIRCUIT 36 KV OVER HEAD LINE TOWER AND ACCESSORIES, STEEL LATICE TOWERS,1 Km ACSR CONDUCTOR FOR 2 MW,EARTH WIRE GALVANIZED STEEL,
TENSION/SUSPENTION INSULATOR SET (AT LAST 4 INSOULATOR PER STRING ), STUB SETTING TEMPLATE,STOCKBRIDGE VIBRATION DAMPER,PARALLEL GROOVE
Nos 5
CALAMP ,STRAIN CALAMP , PIN INSULATOR ,SHACKLE ,OVER-BALL , SOCKET EYE , SUSPENSION CALAMP SET, Y-BALL , MID SPAN JOINT , POST INSULATOR , TOWER(
PHASE,NUMBER,DANGER )PLATE,DEAD END CALAMP, LIGHTNING ARRESTERS WITH ALL REQUIREMENT ACCESSORIES ACCORDING TO LATEST VERSION IPS-M-EL-160

LIGHTING TOWER

LIGHTING TOWERS GALVANIZED 50 ft , WITH EXD LOOPING BOX, TERMINAL BOX ,LED FLOODLIGHT (AT LAST 4 FLOODLIGHT FOR EACH TOWER), ACCORDING TO IPS-D-
Nos 7
EL-321

LIGHTNING SYSTEM

LIGHTNING PROTECTION SYSTEM STRUCTURE WITH ALL ACCESSORIES (LIGHTNING ARESTER, … ) Nos 4

Control Room Distribution Board


Installation Indoor/ Zone 2
Nominal System Voltage v 400
Frequency Hz 50
No. of Phases 3
Mounting Wall mounted
Bus bar material copper
Incomer/Outgoing : Incommer Outgoing
a) Frequency 50 Hz 50 Hz
b) Voltage available 400 Volt,3 ph 230 Volt,1 ph 230 Volt,1 ph
c) Switch type MCCB (4 pole) MCB (2 pole) MCB (2 pole)
d) Rating 32 A 16 A 25 A
e) No. of Outgoing Circuits 1 13 2
Electrical building Distribution Board
Installation Indoor/ Zone 2
Nominal System Voltage v 400
Frequency Hz 50
No. of Phases 3
Mounting Wall mounted
Bus bar material copper
Incomer/Outgoing : Incommer Outgoing
a) Frequency 50 Hz 50 Hz
b) Voltage available 400 Volt,3 ph 230 Volt,1 ph 230 Volt,1 ph
c) Switch type MCCB (4 pole) MCB (2 pole) MCB (2 pole)
d) Rating 25 A 16 A 25 A
e) No. of Outgoing Circuits 1 13 2
Guard House Distribution Board
Installation Indoor/ Zone 2
Nominal System Voltage v 400
Frequency Hz 50
No. of Phases 3
Mounting Wall mounted
Bus bar material copper
Incomer/Outgoing : Incommer Outgoing
a) Frequency 50 Hz 50 Hz
b) Voltage availa 400 Volt,3 ph 230 Volt,1 ph
c) Switch type MCCB (4 pole) MCB (2 pole)
d) Rating 25 A 16 A
e) No. of Outgoi 1 5
Air Compresor House Distribution Board
Installation Indoor/ Zone 2
Nominal System Voltage v 400
Frequency Hz 50
No. of Phases 3
Mounting Wall mounted
Bus bar material copper
Incomer/Outgoing : Incommer Outgoing
a) Frequency 50 Hz 50 Hz
b) Voltage availa 400 Volt,3 ph 230 Volt,1 ph
c) Switch type MCCB (4 pole) MCB (2 pole)
d) Rating 25 A 16 A
e) No. of Outgoi 1 5
Out of list

PRE-COMMISSIONING, COMMISSIONING, START UP & TWO YEARS SPARE PARTS FOR ALL ABOVE ITEMS -