You are on page 1of 8

© 2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Journal Vol.

49, Jan. 2006. For personal use only.


Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.

By George J. Berbari, Member ASHRAE; Sleiman Shakkour, Member ASHRAE; & Fadi Hashem, Associate Member ASHRAE

T
 he United Arab Emirates (UAE) has one of the highest wet- overall efficiency but also proved effec-
tive for controlling the indoor conditioned
bulb design temperatures in the world (87°F [30.56°C]), space relative humidity.
The increased supply of outdoor air
making it one of the most challenging places for controlling needed for ventilation to achieve those
acceptable indoor air quality levels rec-
indoor relative humidity. Around 20% of the total building ommended in ANSI/ASHRAE Standard
62-1989, Ventilation for Acceptable In-
cooling load and annual energy consumption is used for the door Air Quality, significantly increases
the cooling and heating loads that the
treatment of the fresh air supply needed for ventilation. For HVAC equipment needs to handle, result-
ing in higher initial and operating system
those reasons, we are always challenged to look for better costs. To compensate, system designers
look for innovative ways to reduce the
and more efficient ways to treat the fresh air supply. energy consumption associated with the
In 1993 in a seminar held in the UAE, recovery unit, which after investigating treatment of the supply of fresh air.
a cooling coil with runaround coil was thoroughly and having been convinced An analysis based on a 20-year life
presented as one possible solution. Since of its merits, introduced one of the first
then the authors have helped introduce such system in the Middle East in 1999.
Since then, we have promoted the benefits About the Authors
thousands of such systems into the local
George J. Berbari is CEO at DC PRO Engineering
market and demonstrated in practice the of using this method to treat the fresh air
in the UAE. Sleiman I. Shakkour is district energy
effectiveness of this method of control- and hundreds of units have been installed specialist at FVB Energy in Woodbridge, ON, Canada.
ling the indoor relative humidity.1 and specified in our area. The use of this Fadi Hashem is assistant mechanical engineering
Later, we discovered the double heat system has resulted not only in improved manager at DC PRO Engineering in the UAE.

34 ASHRAE Journal ashrae.org January 2007


cycle for six different types of supply air-handling units was surface area to transfer moisture and heat between the
made to evaluate the available system design options to com- two airstreams having different temperatures, and vapor
pare the impact of each method of treatment on capital costs pressures as the driving force for energy transfer.
and energy costs. This was used to establish the individual During the cooling season, this precools and dehu-
system merits for use as a guide when considering options for midifies the fresh air prior to entering the main cooling
optimizing performance. coil, reducing the cooling load demand. The cooling
This article offers practical design guidelines based on our coil dehumidifies the air to a constant 56°F (13.3°C)
experience installing and maintaining fresh air makeup systems dew point. Leaving the cooling coil, this dehumidi-
that include energy recovery. fied fresh air enters a second sensible-only wheel
(sensible effectiveness = 70%), where it absorbs heat
Six Fresh Air-Handling Units from the exhaust airstream and is reheated to a neutral
The six units use different air-to-air energy transfer technolo- air condition of 70°F (21.1°C) dry bulb. During this
gies and are used to precondition outdoor air before it is mixed last stage, by releasing heat to the supply airstream,
with return air from the conditioned space (Figure 1). exhaust air is precooled prior to entering the first
A. Conventional fresh air-handling unit with cooling coil enthalpy wheel, which further enhances cooling the
and supply fan. The cooling coil dehumidifies the air to fresh airstream.
a constant 56°F (13.3°C) dew point, which is equivalent C. Fresh air-handling unit with total energy wheel and
to the desired indoor condition of 76°F (24.4°C) dry bulb runaround coils. In this unit, a total energy wheel
and 50% RH, without reheating it to a “neutral” dry-bulb is placed in series with a runaround recovery coils
temperature. (sensible effectiveness = 70%) placed between supply
B. Double wheel energy recovery unit with a total recovery and exhaust air ducts. A pump circulates water that is
wheel and a sensible heat recovery wheel. This unit has used as a sensible energy transfer medium between
two energy transfer stages between adjacent fresh air sup- the airstreams.
ply duct and exhaust air duct, with air flowing at opposite D. Fresh air-handling unit with total energy wheel and heat
directions, creating a counterflow heat exchange arrange- pipe coils. In this unit, heat pipe coils (sensible effective-
ment. In the first recovery phase, total energy exchange ness = 63%) are placed between the supply and exhaust
combining both latent and sensible energy transfer is air ducts using refrigerant as the energy transfer medium,
achieved by virtue of a revolving enthalpy wheel (total eliminating the need for a circulating pump.
effectiveness = 80%) having an aluminum backbone E. Fresh air-handling unit with total energy wheel only. In
structure with a desiccant coating and large internal this unit, an enthalpy wheel (total effectiveness = 80%)

January 2007 ASHRAE Journal 35


Chilled Water

A B 2 in. Bag
45°F/55°F

Supply
1 Prefilter Filter
2 Fresh Air
Fresh Treated
Fresh Air Air
Air
3
4

Purge Purge
Air Air

1 – Prefilter 2 – Bag Filter Exhaust Return


3 – Cooling Coil 4 – Supply Fan Air Air
Total Energy Cooling Coil Sensible 2 in.
Fresh Air-Handling Unit Recovery Energy Filter
Wheel Recovery
Optional Wheel
Variable Speed
Control
Fresh Air-Handling Unit With Double Recovery Wheels

Chilled Water

C D
Chilled Water
45°F/55°F 45°F/55°F
2 in. Bag 2 in. Bag
Prefilter Filter Fresh
Fresh Prefilter Filter
Fresh Fresh Air Duct
Air Air Duct
Air

Exhaust Exhaust
Exhaust Air
Exhaust Air
Air Duct Purge Optional Three-
Purge Air Way Valve Duct
Air Air

Runaround 2 in.
Total Energy
Coil Filter Total Energy Cooling Coil Heat Pipe 2 in.
Recovery
Recovery Filter
Wheel
Optional Wheel
Variable Speed Optional Optional
Control Three-Way Variable Speed
Valve Control
Fresh Air-Handling Unit With Total Energy Fresh Air-Handling Unit With Total Energy
Recovery Wheel and Runaround Coil Recovery Wheel and Heat Pipe

Chilled Water Chilled Water

E 2 in. Bag
45°F/55°F
F 2 in. Bag
45°F/55°F

Prefilter Filter Prefilter Filter

Supply Supply
Fresh Fresh
Air Air
Air Air

Cooling Coil With Horseshoe Heat Pipe


Exhaust Purge Exhaust Return
Return Purge
Air Air Air Air
Air Air

2 in.
Total Energy Cooling Coil 2 in. Total Energy
Filter
Recovery Wheel Filter Recovery Wheel
Optional Variable Optional Variable
Speed Control Speed Control
Fresh Air-Handling Unit With Energy Wheel Only Fresh Air-Handling Unit With Total Energy Wheel
And Horseshoe Heat Pipe

Figure 1: Different arrangements for fresh air-handling units.

is added to precool and dehumidify the air entering the horseshoe heat pipe wrapped around the main cooling
conventional fresh air-handling unit. Again, the cooling coil. In this arrangement, a precooling heat pipe coil
coil dehumidifies the air to a constant 56°F (13.3°C) (sensible effectiveness = 54%) is placed at the inlet to
dew point, without reheating it to a “neutral” dry-bulb the main cooling coil to further precool the on-coil fresh
temperature. air and reheat heat pipe coil is placed at the outlet to
F. Fresh air-handling unit with total energy wheel and a reheat fresh air to the desired condition.

36 ASHRAE Journal ashrae.org January 2007


Outdoor Conditions Total Energy Wheel Cooling Coil Sensible Wheel
Supply Exhaust Supply Air Sensible Total Supply Exhaust Exhaust
Air Outlet Air Inlet Outlet Capacity Capacity Air Outlet Air Inlet Air Outlet
Tdb Twb BIN Tdb Twb Tdb Twb Tdb Twb Ton Ton Tdb Twb Tdb Twb Tdb Twb
°F °F Hours °F °F °F °F °F °F °F °F °F °F °F °F
95 87 Abu-Dhabi 68.6 65.5 62.3 58.5 56.3 56.1 11.6 25.6 70 61.3 76 63.4 62.3 58.5
94 86 Dubai 68.4 65.2 62.3 58.5 56.3 56.1 11.4 24.7 70 61.3 76 63.4 62.3 58.5
110.4 76.3 33 71.5 62.4 62.3 58.5 56.3 56.1 14.4 16.4 70 61.3 76 63.4 62.3 58.5
106.6 76.7 91 70.8 62.5 62.3 58.5 56.3 56.1 13.7 16.7 70 61.3 76 63.4 62.3 58.5
102.1 77.7 333 69.9 62.8 62.3 58.5 56.3 56.1 12.9 17.5 70 61.3 76 63.4 62.3 58.5
97.2 78.8 687 69.0 63.1 62.3 58.5 56.3 56.1 12.0 18.4 70 61.3 76 63.4 62.3 58.5
92.3 79.1 992 68.1 63.2 62.3 58.5 56.3 56.1 11.1 18.7 70 61.3 76 63.4 62.3 58.5
87.5 77.6 1,375 67.1 62.8 62.3 58.5 56.3 56.1 10.2 17.5 70 61.3 76 63.4 62.3 58.5
82.6 73.6 1,203 66.2 61.8 62.3 58.5 56.3 56.1 9.4 14.7 70 61.3 76 63.4 62.3 58.5
75.0 67.2 2,061 64.7 60.3 62.3 58.5 56.3 56.1 8.0 10.6 70 61.3 76 63.4 62.3 58.5
65.7 60.5 1,712 62.9 58.9 62.3 58.5 56.3 56.1 6.3 6.8 70 61.3 76 63.4 62.3 58.5
57.6 54.3 279
49.1 44.2 1
Total 8,767
Ton-Hours Per Year 67,026 114,193
Table 1a: Double wheel heat recovery with total energy wheel and sensible energy wheel (10,000 cfm supply/exhaust model).

Outdoor Conditions Total Energy Wheel Horseshoe Heat Pipe Cooling Coil Horseshoe Heat Pipe
(Precooling) (Reheating)
Supply Air Exhaust Air Supply Air Supply Air Supply Air
Outlet Outlet Outlet Outlet Sensible Total Outlet
Tdb Twb BIN Tdb Twb Tdb Twb Tdb Twb Tdb Twb Capacity Capacity Tdb Twb
°F °F Hours °F °F °F °F °F °F °F °F Btu/h Btu/h °F °F
95 87 79.6 69.0 76.0 63.4 67.1 65.3 56.3 56.1 116,640 284,800 68.7 60.3
110.4 76.3 33 82.6 66.2 76.0 63.4 68.5 61.3 56.3 56.1 131,760 151,300 70.4 60.8
106.6 76.7 91 81.9 66.2 76.0 63.4 68.1 61.3 56.3 56.1 127,440 151,300 70.1 60.8
102.1 77.7 333 81.0 66.5 76.0 63.4 67.6 61.8 56.3 56.1 122,040 169,100 69.7 60.4
97.2 78.8 687 80.1 66.8 76.0 63.4 67.2 62.4 56.3 56.1 117,720 186,900 69.2 60.2
92.3 79.1 992 79.1 66.9 76.0 63.4 66.7 62.7 56.3 56.1 112,320 195,800 68.7 60
87.5 77.6 1,375 78.2 66.5 76.0 63.4 66.3 62.6 56.3 56.1 108,000 195,800 68.2 59.9
82.6 73.6 1,203 77.3 65.5 76.0 63.4 65.6 61.5 56.3 56.1 100,440 160,200 68 60
75.0 67.2 2,061 75.8 63.9 76.0 63.4 64.5 60.2 56.3 56.1 88,560 120,150 66.8 59.5
65.7 60.5 1,712 74.0 62.8 76.0 63.4 64.6 59.5 56.3 56.1 89,424 97,900 65.8 59.2
57.6 54.3 279
49.1 44.2 1
Total 8,767
Ton-Hours Per Year 71,155 106,243
Table 1b: Total energy wheel with horseshoe arrangement (10,000 cfm supply/exhaust model).

Cost and Energy Consumption Comparison Based on these selections, and by computing the air conditions
To compare these units and decide which is the most ad- at different sections of each unit, the annual cooling energy and
vantageous to use, it is necessary to consider the cost of the electrical energy consumption were calculated using the Abu
equipment and its impact on the associated chiller plant cost, Dhabi bin hour data that were computed using weather data
and the annual energy consumption cost. For this purpose, a covering a span of 10 years, which were provided by the Abu
10,000 cfm (4720 L/s) model was chosen for comparison, and Dhabi Ministry of Communications—Meteorological Depart-
it was assumed that the fan brings this amount of outdoor air ment for the period 1985 – 1994.
for 24 hours/day, every day of the year. Different selections and Tables 1a and 1b show an example of a calculation for the cool-
quotations were obtained from various major manufacturers. ing energy demand of the double-wheel energy recovery unit and

38 ASHRAE Journal ashrae.org January 2007


Supply Supply Exhaust Exhaust Energy Sensible Runaround Total
Equipment Fan Fan Fan Fan Wheel Wheel Coil Pump Power
kW kWh kW kWh kWh kWh kWh kWh
Outdoor Air Handling Unit 6.38 54,163 4.23 35,916 90,079
Total Energy Recovery Only 7.93 69,534 5.79 50,786 5,092 125,413
Total Energy Wheel With
10.29 90,181 5.79 50,786 5,092 146,060
Horseshoe Heat Pipe
Double Wheel Energy Recovery 8.91 78,078 7.64 66,981 5,092 5,092 155,244
Energy Recovery With Runaround
8.88 77,888 7.44 65,184 5,092 2,033 150,197
Coil (1.6 m/s Face Velocity)
Energy Recovery
With Runaround Coil 10.67 93,504 9.34 81,893 5,092 2,033 182,521
(2.6 m/s Face Velocity)
Energy Recovery
With Heat Pipe Coil 9.12 80,000 7.69 67,444 5,092 152,537
(1.6 m/s Face Velocity)
Energy Recovery
With Heat Pipe Coil 11.14 97,657 9.85 86,337 5,092 189,086
(2.6 m/s Face Velocity)
Double Wheel Energy Recovery
8.31 72,857 6.63 58,096 5,092 5,092 141,137
(Exhaust = 90% Supply Fresh Air)
Total Energy Wheel With
Horseshoe Heat Pipe 10.29 90,181 5.25 46,040 5,092 141,314
(Exhaust = 90% Supply Fresh Air)
Notes: Purge air is included. Fan static pressure includes pressure drop in wheels, cooling coil, runaround coils, heat pipe coils, filters and external pressure drop.

Table 2: Electrical consumption for 10,000 cfm model.

total energy wheel with horseshoe arrangement. Design condi- Table 4 shows a comparison between the units considered.
tions are shown in the first row according to ASHRAE climatic For comparison, the cost of the air-cooled chiller plant being
design conditions. Air conditions are obtained at each section of considered was estimated at $1,200/ton ($341/kW), including
the unit, and the total annual cooling energy consumption was civil, mechanical, electrical, and utility connection costs. The
determined in that manner. It is assumed that the unit is cycled equipment costs were obtained from manufacturers’ quotations.
off when the ambient temperature drops below that required for Electrical consumption was assumed to be 1.7 kW/ton (6 kW/
indoor comfort conditions in accordance with ANSI/ASHRAE kW) for the total chilled water plant (including chillers, pumps
Standard 55-1992, Thermal Environmental Conditions for Hu- and auxiliaries). The electric power cost was determined based
man Occupancy, at 76°F (24.4°C) and 50% RH. on a flat rate of $0.0543/kWh. The total capital and operating
Electrical energy was calculated taking into account the power costs were calculated, for a 20-year period. The net present value
consumption of the supply fan, the exhaust fan, the runaround was determined using an 11.75% discount rate.
pump, and the total energy and sensible wheel’s energy. Total As shown on Table 4, the fresh air-handling unit resulted in
energy was calculated based on the operating hours for each the highest life-cycle cost. This value was reduced by 58% when
unit. the total energy wheel with the horseshoe heat pipe arrangement
Table 2 shows a summary for the electrical energy consump- was used, which resulted in the lowest life-cycle cost. However,
tion calculation. Two cases were considered for the dual energy the drawback when using this unit is the difficulty of controlling
recovery units with runaround coils and heat pipe options: the temperature and moisture content of the supply air, which
1. Face velocity through the coils 315 fpm (1.6 m/s); and will vary depending on the ambient conditions.
2. Face velocity through the coils 510 fpm (2.6 m/s). The life-cycle cost of the system with the dual energy re-
Because of the large size of the energy wheel, enough cross- covery unit, compared closely with that having the lowest life-
sectional area is available for the coils, which helps reduce the cycle cost, but having the added advantage of supplying air at
face velocity and consequently the energy consumption of the constant temperature and humidity levels year-round regardless
fan, but for the cost of a bigger coil. Thus, these two options of the outdoor conditions. This results in a better control of the
were considered to study the feasibility of increasing the coil’s indoor humidity levels.
size for reducing energy consumed. The higher coil face velocity resulted in an increase of the
Table 3 shows a summary of results for the cooling coil life-cycle cost by about 8%. This lead into concluding that
design load, annual cooling energy and electrical energy exceeding a coil face velocity of 400 fpm (2 m/s) is not rec-
required for each unit. ommended.

January 2007 ASHRAE Journal 39


Design FAHU Coil Total Coil Additional Additional AHU Electric
Condition Cooling Capacity Cooling Energy Cooling Effect Cooling Effect Power & Exhaust
Equipment
Fan Power
db/wb, °F Tons Ton-Hours/Year Tons Ton-Hours/Year kWh/Year
Fresh Air Handling Unit 95/87 101.0 362,139 18 150,480 90,079
Total Energy Wheel Only Recovery 95/87 34.6 195,220 18 150,480 125,413
Total Energy Wheel
95/87 23.7 106,243 7 64,357 146,060
With Horseshoe Heat Pipe
Double Heat Recovery AHUs
95/87 25.6 114,193 5 45,831 155,244
Double Wheel Energy Recovery
Total Energy Wheel
And Runaround Coil 95/87 25.3 116,385 6 54,234 150,197
(1.6 m/s Face Velocity)
Total Energy Wheel
And Runaround Coil 95/87 26.2 124,014 8 63,858 182,521
(2.6 m/s Face Velocity)
Total Energy Wheel
And Heat Pipe 95/87 24.7 111,299 5 44,609 152,537
(1.6 m/s Face Velocity)
Total Energy Wheel
And Heat Pipe 95/87 25.9 121,471 7 55,609 189,086
(2.6 m/s Face Velocity)
Double Wheel Energy Recovery
95/87 30.5 130,349 5 45,831 141,137
(Exhaust = 90% Supply Fresh Air)
Total Energy Wheel
With Horseshoe Heat Pipe 95/87 26.3 124,785 6 63,224 141,314
(Exhaust = 90% Supply Fresh Air)
Notes: All above AHUs have a chilled water coil for cooling and dehumidification. Additional cooling effect is measured as: 1.08 × cfm × (76°F – Ts,o)/12,000
where Ts,o is the supply temperature entering the space.

Table 3: Comparison of different AHU types (10,000 cfm supply/exhaust model).

We noticed that Unit A (conventional fresh air-handling unit) capital costs can be used (supply temperature was found
and Unit E (fresh air-handling unit with total-energy wheel to vary between 66°F and 70°F [18.9°C to 21.1°C] and
only) both dehumidify the outdoor air to the same dew point RH between 59% and 67%). The recommended spacing
as the other systems, but they deliver it cold—56.3°F (13.5°C) between the heat pipe coils is 4.6 ft (1.4 m) for easier
dry bulb—rather than reheating it to a neutral 70°F (21.1°C). cooling coil’s maintenance, although this leads to having
In these two systems, this cold air is able to offset a portion of a slightly longer unit.
the space sensible cooling loads. • Double energy recovery systems resulted in a better hu-
However, many designers don’t take into consideration the midity control with a constant fresh air supply temperature
cooling effect for sizing the secondary (local) HVAC systems and RH year-round regardless of fresh ambient conditions
nor is it used to reduce the chilling plant size. In this case, it has (70°F [21°C] and 61% RH). Although costs are higher,
no impact on the capital cost. In off peak hours, when the room they are recommended for use when constant supply tem-
temperature condition is satisfied and the secondary system perature and humidity are necessary.
is turned off, this cool, conditioned outdoor air may overcool Of course, the results of the analysis may differ with climate,
the space. At such time, the dehumidified outdoor air should operating hours, utility costs, and installed costs.
be reheated or the local HVAC equipment needs to add heat
to avoid overcooling the space. For this analysis, we decided Design Guide for Fresh Air-Handling Unit
to list the cooling energy in the tables but to ignore its impact. The following are summarized design parameters recom-
The reader may choose otherwise. mended based on the preceding analysis and our experience
installing and maintaining these systems.
Recommendations • Total energy or sensible wheel to have a maximum air face
Based on the results and assumptions of this specific analysis: velocity of 600 fpm (3 m/s). This limits the pressure drop,
• When no need exists for a constant supply temperature blower power and cross leakage to modest levels.
and RH, the total energy wheel with a horseshoe heat pipe • Heat pipe and runaround coil to have a maximum air face
arrangement with the lowest energy consumption costs and velocity of 400 fpm (2 m/s):

40 ASHRAE Journal ashrae.org January 2007


Equipment FAHU Chilled Outdoor Air Total Total Annual 20 Years
Cooling Water Plant AHU & Exhaust Capital Consumption Life Cycle
Capacity Capital Cost Fan Capital Cost Cost Cost Cost NPV
Ton
Outdoor AHU 101.0 $121,200 $15,076 $136,276 $38,354 $382,379
Total Energy Wheel Only Recovery 34.6 $41,460 $20,000 $61,460 $24,853 $223,752
Total Energy Wheel
23.7 $28,440 $27,717 $56,157 $17,754 $170,806
With Horseshoe Heat Pipe
Double Heat Recovery AHUs
Double Wheel Energy Recovery 25.6 $30,720 $26,902 $57,622 $18,988 $180,493
Total Energy Wheel
And Runaround Coil 25.3 $30,312 $27,717 $58,029 $18,916 $180,370
(1.6 m/s Face Velocity)
Total Energy Wheel
And Runaround Coil 26.2 $31,392 $26,087 $57,479 $21,377 $196,593
(2.6 m/s Face Velocity)
Total Energy Wheel
And Heat Pipe 24.7 $29,592 $33,424 $63,016 $18,573 $182,505
(1.6 m/s Face Velocity)
Total Energy Wheel
And Heat Pipe 25.9 $31,032 $29,620 $60,652 $21,499 $200,259
(2.6 m/s Face Velocity)
Double Wheel Energy Recovery
30.5 $36,600 $26,902 $63,502 $19,714 $190,685
(Exhaust = 90% Supply Fresh Air)
Total Energy Wheel
With Horseshoe Heat Pipe 26.3 $31,560 $27,717 $59,277 $19,209 $183,478
(Exhaust = 90% Supply Fresh Air)
Notes: Total consumption assumed is 1.7 kW/ton. Electricity cost considered is U.S. 5.43 cents/kWh. Air cooled chiller plant is based on $1,200/ton including
mechanical, electrical, civil and utility connections works. Discount rate for net present value calculation = 11.75%.

Table 4: Capital cost and life-cycle analysis (air-cooled chiller plant).

 As the area defined by the wheel allows larger rectan- of the wheel as well as the exhaust air intake for proper
gular coil area; wheel operation and for reducing the need for frequent
 Heat pipe and runaround coils typically have lower ef- cleaning and maintenance.
fectiveness than sensible wheel at same face velocity, • The wheel purge system should be field adjusted to get
for runaround coil or heat pipe (typically eight rows or the design purge air based on actual field differential air
less); and pressure between fresh air and exhaust airstream. The
 Life-cycle analysis justifies use of lower face velocity. consultant or designer should specify air pressure taps
• Wheels and heat pipes should be tested and rated according extended to the unit’s outer panel to allow measurement
to the following: of differential air pressure between upstream fresh air and
 ANSI/ARI Standard 1060-2001, Performance Rating upstream exhaust air of the wheel.
of Air-to-Air Heat Exchangers for Energy Recovery • An optional speed detector with alarm function and inter-
Ventilation Equipment; and face to the building management system is recommended
 ANSI/ASHRAE 84-1991, Method of Testing Air-to-Air to guard against motor or belt failure.
Heat Exchangers.
• Recommended maximum air duct velocity to be 1,200 fpm Controls for Fresh Air-Handling Unit
(6 m/s) and total external air static pressure drop should not Necessary Controls
exceed 1.5 in. w.g. (380 Pa) for each of the fresh air and • It is necessary to control the leaving air temperature
exhaust air ductwork. It is recommended to use the static from the cooling coil to a dry-bulb temperature of 56.3°F
regain method for duct sizing. (13.5°C), which corresponds to the absolute humidity
• Recommended maintenance spacing between wheel, coils, level of the comfort indoor condition of 76°F (24.4°C)
heat pipe and fans is 1.7 ft to 2 ft (500 to 600 mm). and 50% RH.
• The energy wheel edges should be protected with an epoxy • Fresh air fan motors start/stop, exhaust air fan start/stop ,
coating (or equivalent) to eliminate edge corrosion. total energy wheel motor start/stop, sensible wheel motor
• Proper filtration should be provided at the fresh air intake start/stop or runaround pump start/stop with necessary

January 2007 ASHRAE Journal 41


electric protection and allowance for local as well as remote tion to minimize leakage rate to a range of 0.05% to 0.2%.
controls and communication. Seals require field adjustment.
• Ambient dew point (or grains transmitter) sensor to shut off • Wheel media cleaning can be done annually using
the cooling coil motorized valve and enthalpy wheel motor vacuum or pressurized air (hot water is accepted by some
when the ambient dew point is below 56°F (13.3°C). manufacturers). The wheel is designed for laminar flow
and resists plugging and accumulation of dust particles
Optional Control because of the back-flushing done by the incoming and
• Should the occasional need arise to control the final leaving outgoing of airstreams, which help minimize the need for
supply fresh air temperature (which, if the component is frequent wheel cleaning.
properly selected, should be achieved automatically), then • Other wheel components requiring routine maintenance
the consultant or designer can opt to control the capacity involve bearing lubrication, motor and gear reducer
via a variable speed drive of the sensible wheel motor, a lubrication, verifying bearing bolt and sheave tight-
solenoid valve for the heat pipe and a three-way bypass ness, belt condition, rotor runout and flatness, media
valve at the runaround coil. tightness, etc.
• Variable speed drives for both fresh air and exhaust air can • Coils and heat pipe require minimum maintenance such as
be adopted for variable occupancy applications such as scheduled cleaning and runaround pump maintenance.
office buildings, theaters, conference rooms, sport arenas,
restaurants and others that are possible to control via CO2 References
1. Berbari, G.J. 1998. “Fresh air treatment in hot and humid cli-
sensors located in the exhaust air ducts.
mates.” ASHRAE Journal 40(10):64–70.

Installation and Maintenance Bibliography


• Adjust the purge to actual site conditions. 2001 ASHRAE Handbook—Fundamentals.
• Multipass labyrinth seals or adjustable brush seals are Selection and Pricing Software from SEMCO Inc. Heat Pipe and
important elements for effective and efficient wheel opera- SPC Inc. and Bry-Air.

Advertisement formerly in this space.

42 ASHRAE Journal ashrae.org January 2007

You might also like