www.elsevier.com/locate/epsr
Received 25 September 2002; received in revised form 11 December 2002; accepted 16 December 2002
Abstract
The interference of power transmission lines to nearby pipelines and other metallic structures has been a research subject over the
past 20 years. Especially during fault conditions, large currents and voltages are induced on the pipelines. Several methods have been
proposed over the years and more recently one utilizing finite element calculations. The last method has the disadvantage that if it
considers the pipeline to have a perfect coating, which is rarely the case as defects appear on the coating soon after the pipeline is
buried in the ground. In this work a hybrid method employing finite element calculations along with Faraday’s law and standard
circuit analysis is discussed. The method is used in order to calculate the induced voltages and currents on a pipeline with defects,
running in parallel to a faulted line and remote earth. Non-parallel exposures are converted to parallel ones and dealt with similarly.
The defects are modeled as resistances, called leakage resistances. The fault is assumed to be a single earth-ground one and outside
the exposure so that conductive interference is negligible. A sample case is analyzed and discussed. The results show that although
the pipeline defects act in a way as to reduce the levels of induced voltages and currents, large currents can flow to earth through the
defects that may damage the pipeline.
# 2003 Elsevier Science B.V. All rights reserved.
Keywords: Finite element method; Gas pipelines; Inductive interference; Power line faults
resistances are negligible. The earth is assumed to be and relative permeabilities respectively, v is the angular
homogeneous with a resistivity ranging from r /30 to frequency, J̄ sz is the source current density in the z-
1000 Vm. In spite of that, the proposed method may direction and Ī i is the rms value of the current flowing
deal with situations with non-homogeneous earth also. through conductor i of cross-section Si .
The pipeline has an inner radius of 0.195 m, while its It is shown [16] that the finite-element formulation of
outer radius is 0.2 m and its coating thickness is s/0.1 Eqs. (1a), (1b) and (1c) leads to a matrix equation,
m. The conductivity and relative permeability of the which can be solved utilizing the Crout variation of the
pipeline’s metal are sm /3.522 /106 S/m and mr,m /250 Gauss elimination. Using the solution of this matrix
respectively. equation, the MVP values in every node of the
The fault impedance is considered all resistance (Rf). discretization domain, as well as the unknown source
In the case of an arc phase-to-ground fault, the fault current densities, are calculated. Therefore, for a ran-
resistance is not linear having a typical value of 1 or 2 V dom element e, the eddy-current density J̄ eez is calculated
for about 0.5 s, with peaks of 25 /50 V later. Since we using the relation:
consider steady state condition, the parametric analysis e
J̄ eez (x; y)jvsĀz (x; y) (2a)
of Rf may give an indication of the calculated para-
meters at each value of the fault resistance. and the total element current density J̄ ez ; being the sum
of the conductor-i source current density J̄ szi and of the
element eddy current density J̄ eez of Eq. (2a), is obtained
3. The proposed method by the following equation:
J̄ ez (x; y) J̄ eez (x; y) J̄ szi (2b)
The proposed method combines FEM calculations,
Faraday’s law and standard circuit analysis in order to Integrating Eq. (2b) over a conductor cross-section, the
calculate the influence of a single phase-to-earth fault on total current flowing through this conductor is obtained.
a nearby parallel pipeline. The required input data for The FEM package [20], developed at the Power
the method are: Systems Laboratory of the Aristotle University of
Thessaloniki during the last 15 years, has been used
1) Power line and pipeline geometrical configuration for the finite element formulation of the case under
2) Physical characteristics of conductors and pipeline investigation. A local error estimator, based on the
3) Location and value of the leakage resistances discontinuity of the instantaneous tangential compo-
4) Air and earth characteristics nents of the magnetic field, has been chosen as in Ref.
5) Power system terminal parameters [20] for an iteratively adaptive mesh generation.
6) Fault parameters describing fault location and type
jvsĀz J̄ sz J̄ z (1b) where F1 is the flux of the magnetic field through the
closed path E1E2H1H2 and can be expressed using
gg Si
J̄ z ds Ī i (1c) phasors as:
where s is the conductivity, mo and mr are the vacuum F1 L11 Ī p1 LF1 Ī F ; (4)
142 G.C. Christoforidis et al. / Electric Power Systems Research 66 (2003) 139 /148
with L11 being the self-inductance of the first section of voltage Uo is obtained:
the pipeline, Ip1 its current, Ī F the fault current and LF1
Ī F l
the mutual inductance of the first section of the pipeline Uo IF (RG RF ZS )
due to the fault current in phase A. Contributions to the sS
flux F1, due to the currents flowing in the other sections X
n1
of the pipeline, are neglected, because of the assumption jv LFi Ī Pi LFF Ī F ; (8)
that leakage resistances are located far from each other. 1
In addition to that, in a two-dimensional field this flux is where the first term on the right hand side of Eq. (6) is
given in the plane (x , y ) by: the voltage due to the concentrated elements RG, RF, ZS,
F1 ĀzP l1 ; (5) while s, S and LFF are the conductivity, the cross-
section and the self-inductance of the phase conductor.
where ĀzP is the z-component of the MVP on the surface Eqs. (7), (7a), (7b) and (8) form a system that can be
of the pipeline and l1 is the length of the first section. solved if the self and mutual inductances are calculated.
Using phasors, we may express (1) as follows:
Ū E1 E2 Ū E2 H2 Ū H2 H1 Ū H1 E1 jvF1 0 (6)
3.3. Calculation of self and mutual inductances
where,
For the determination of the self and mutual induc-
Ū E2 H2 (Ī P1 IP2 )R1 (6a)
tances of the problem, the FEM formulation is used. If a
Ū H2 H1 0 (6b) certain base fault current Ī Fb is imposed on the faulted
Ū H1 E1 Ī P1 RT (6c) phase, e.g. Ī Fb 1A; with the pipeline current set equal
H2 to zero, then the computed MVP on the surface of the
J̄ zP l1 Ī P1 l1
Ū E1 E2
g H1
Ēdl¯
sp
sp Sp
; (6d) pipeline can be utilised to determine the mutual
inductance LF1. In this case, combining (4) and (5),
where sp and Sp are the conductivity and the effective the following relation is obtained, since Ī p1 0:
cross-section of the pipeline’s metal respectively. ĀzPb l1 LF1 Ī Fb
Finally, Eq. (6) becomes:
and therefore the mutual inductance is:
l
Ī P1 R1 RT 1 Ī P2 R1 jv ĀzPb l1
sp Sp (7) LF1 ;
Ī Fb
(L11 Ī p1 LF1 Ī F )0
or
Using the same procedure, an equation similar to Eq.
ĀzPb
(5) may be stated for each of the (N/1) loops, resulting L?F1 ; (9)
in (N/1) equations. Therefore, for loop i the following Ī Fb
equation apply: the mutual inductance of the pipeline’s first section and
phase per unit length.
li
Ī Pi Ri Ri1 Ī Pi1 Ri Ī Pi1 Ri1 Additionally, the flux of the magnetic field of the
sp Sp
closed path ABCFGA, of Fig. 3, is given by:
jv(Ī Pii Lii Ī F LFi )
X
n1
0 (7a) F LFi Ī Pi LFF Ī F (10)
1
for i /2, N . While for loop N/1 the following relation
applies: while the same flux can be expressed as:
F Āz l (11)
lN1
Ī PN1 RN RT Ī PN RN
sp S p where Āz is the z -component of the MVP on the surface
of the phase conductor.
jv(Ī PN1 LN1N1 Ī F LFN1 )
Consequently, since the first term of the right hand
0 (7b) side of Eq. (10) is zero, we obtain:
Assuming that the geometry of the system and the Āz l
magnetic properties of both the pipeline and the phase A LFF : (12)
Ī Fb
conductor remain constant, the self and mutual induc-
tances per unit length of all sections are equal. In order to calculate the self inductances Lii (i /1:n/
Applying, as previously, Faraday’s law Eq. (3) in the 1) of the pipeline sections the same methodology is
loop ABCFGA, an equation involving the source phase followed, except that now we impose a zero fault current
G.C. Christoforidis et al. / Electric Power Systems Research 66 (2003) 139 /148 143
a2
Consequently, by knowing the length of each section of 53: (15a)
the pipeline, the self and mutual inductances of all a1
sections are computed by simply multiplying the per unit In case a2/a1 is more than 3, the section is divided, as
length inductance with the section length. shown in Fig. 4, in order that both a3/a1 and a2/a3 meet
Eq. (15a).
Fig. 8. Induced voltages on the pipeline over kA of fault current (V/ Fig. 10. Leakage currents over kA of fault current on the defects of the
kA) in the system of Fig. 1 versus distance from left terminal, for 5 V coating of the pipeline versus distance from left terminal, for 5 V
terminal resistances and 10, 25, 50, 250, 500 and 5000 V leakage terminal resistances and 10, 25, 50, 250, 500 and 5000 V leakage
resistances located at each km of the pipeline. Relative separation resistances located at each km of the pipeline. Relative separation
between pipeline and power line is 70 m. between pipeline and power line is 70 m.
146 G.C. Christoforidis et al. / Electric Power Systems Research 66 (2003) 139 /148
Fig. 11. Induced voltages on the pipeline over kA of fault current (V/
kA) in the system of Fig. 1 versus distance from left terminal, for 5 V Fig. 13. Induced voltages on the pipeline over kA of fault current (V/
terminal resistances and 50 V leakage resistances located at each km of kA) in the system of Fig. 1 versus distance from left terminal, for 50 V
the pipeline, for relative separation between pipeline and power line 25, terminal resistances and 50 V leakage resistances located at each km of
70, 200, 500 and 800 m. the pipeline, for values of earth resistivity of 30, 50, 70, 100, 500, 1000
V m. Relative separation between pipeline and power line is 25 m.
in the induced voltage on the pipeline approximately.
The value of earth resistivity mainly affects the values of resistances on the fault current is negligible comparing
self and mutual impedances calculated with the FEM with that of the fault resistance.
method. On the other hand, fault resistance is a
parameter that influences directly the fault current
calculated with the proposed method, while self and
6. Conclusions
mutual impedances remain unaffected. Fig. 15 show that
the fault current decreases almost linearly with increas-
A hybrid method for calculating the induced voltages
ing value of the fault resistance. Knowing the fault and currents on a pipeline with defects on its coating
current, one may determine the level of inductive was introduced. The method combines FEM calcula-
interference on the pipeline by utilizing the previous tions, Faraday’s law and standard circuit analysis in
graphs showing the unknown parameters over kA of order to compute the induced voltages and currents on
fault current. It must be noted that the effect of relative the pipeline as well as the current that flows to earth
power line/pipeline separation and pipeline leakage
Fig. 12. Induced currents on the pipeline over kA of fault current (A/ Fig. 14. Induced currents on the pipeline over kA of fault current (A/
kA) in the system of Fig. 1 versus distance from left terminal, for 5 V kA) in the system of Fig. 1 versus distance from left terminal, for 50 V
terminal resistances and 50 V leakage resistances located at each km of terminal resistances and 50 V leakage resistances located at each km of
the pipeline, for relative separation between pipeline and power line 25, the pipeline, for values of earth resistivity of 30, 50, 70, 100, 500, 1000
70, 200, 500, 800 m. V m. Relative separation between pipeline and power line is 70 m.
G.C. Christoforidis et al. / Electric Power Systems Research 66 (2003) 139 /148 147
Appendix (Continued )
Symbol Description
Symbol Description
References
Uo source voltage (V)
Zs source impedance (V) [1] J.R. Carson, Wave propagation in overhead wires with ground
Rf fault resistance (V) return, Bell System Technical Journal 5 (1926) 539 /554.
Rg neutral ground resistance (V) [2] H. Böcker, D. Oeding, Inducktionsspannung an pipelines in
RT terminal ground resistance of pipeline (V) Trassen von Hochspannungsleitungen, Elektrizitatswirtschaft 65
(1966) 5.
Ri leakage resistance of pipeline (V)
[3] G. Kaiser, Die Elektrischen Konstanten von Rohrleitungen und
r earth resistivity (V/m) Ihre Messung, ETZ-A 87 (1966) 792 /796.
s coating thickness (m) [4] E.D. Sunde, Earth Conduction Effects in Transmission Systems,
sm pipeline’s metal conductivity (S/m) Dover Publ, New York/USA, 1968.
148 G.C. Christoforidis et al. / Electric Power Systems Research 66 (2003) 139 /148
[5] J. Pohl, Influence of high voltage overhead lines on covered III, 1029 (9) 339 /359 (in German). French translation also
pipelines, CIGRE Paper No. 326, June, 1966. available in Revue Generale de l’ Electricite 29 (22) (1931) 851 /
[6] B. Favez, J.C. Gougeuil, Contribution to studies on problems 867.
resulting from the proximity of overhead lines with underground [14] P. Kouteynikoff, Résultats d’ une Enquete Internationale sur les
metal pipelines, CIGRE Paper No. 336, June, 1966. Régles Limitant les Pertubations Créés sur les Canalisations par
[7] Technical Recommendation No. 7, Arbitration agency for les Ouvrages électriques, ELECTRA (110) (1987).
problems of interference between installations of the German [15] Guide on the influence of high voltage AC power systems on
Federal Post Office and the Association of German power metallic pipelines, CIGRE Working Group 36.02, 1995.
utilities, Verlags und Wirtschaftsgesellschaft der Elektrizitäts- [16] K.J. Satsios, D.P. Labridis, P.S. Dokopoulos, Currents and
werke mbH */VHEW, 1982. voltages induced during earth faults in a system consisting of a
[8] J. Dabkowski, A. Taflove, A mutual design consideration for transmission line and a parallel pipeline, European Transactions
overhead AC transmission lines and gas pipelines, EPRI Report on Electrical Power (ETEP) May/June, 8 (3) (1998).
EL-904, vol. 1, 1978. [17] K.J. Satsios, D.P. Labridis, P.S. Dokopoulos, Finite-element
[9] M.J. Fraiser, Power line induced AC potential on natural gas computation of field and Eddy currents of a system consisting
pipelines for complex rights-off-way configurations, EPRI. Re- of a power transmission line above conductors buried in
port EL-3106, AGA. Cat. No. L51418, April, 1984. nonhomogeneous earth, IEEE Trans. Power Delivery, July, 13
[10] F.D. Dawalibi, R.D. Southey, Y. Malric, W. Tavcar, Power line (3) (1998).
fault current coupling to nearby natural gas pipelines, volumes 1 [18] W. von Baeckmann, W. Schwenk, W. Prinz, Handbook of
and 2, EPRI/AGA Project 742, EL-5472/PR176-510, November, Cathodic Corrosion Protection, Theory and Practice of Electro-
1987. chemical Protection Processes, 3rd ed., Gulf Publishing Co,
[11] F.P. Dawalibi, R.D. Southey, Analysis of electrical interference Houston, TX, 1997.
from power lines to gas pipelines Part I: computation methods, [19] F.P. Dawalibi, Ground fault current distribution between soil and
IEEE Trans. Power Delivery 4 (3) (1989) 1840 /1846 (July). neutral conductors, IEEE Trans. Power Apparatus Systems PAS
[12] F.P. Dawalibi, R.D. Southey, Analysis of electrical interference 99 (2) (1980) 452 /461 (March/April).
from power lines to gas pipelines Part II: computation methods, [20] D.P. Labridis, Comparative presentation of criteria used for
IEEE Trans. Power Delivery 5 (1) (1990) 415 /421 (January). adaptive finite element mesh generation in multiconductor Eddy
[13] F. Pollaczek, On the field produced by an infinitely long wire current problems, IEEE Trans. Magnetics 36 (1) (2000) 267 /280
carrying alternating current, Electrische Nachricten Technik vol. (January).