EXAMPLES ON DESIGN OF FLEXURAL MEMBERS
1. A simply supported beam 7.00 m span is laterally supported at the third points and carries un factored
uniform loads of 18.5 kN/m and 9.4 kN/m permanent load. In addition the beam carries at mid span un
factored concentrated load of 50 kN permanent load and 50 kN imposed load. Find a universal beam of
grade Fe 430.
Solution:
Geometry, materials and loads.
Factored loads:
Imposed loads: q = 1.6 x 18.50 = 29.60 kN/m
Q = 1.6 x 50.00 = 80.00 kN.
Permanent loads: g = 1.3 x 9.40 = 12.20 kN/m
G = 1.3 x 50.00 = 65.00 kN.
Fe 430; fy = 275 N/mm2 (assume t ≤ 40 mm)
Step 1. Maximum bending moment and shear force.
max M
29.6 12.2 x7 2 80 65 x7
509.8 kN m
8 4
max V
29.6 12.2 x7 80 65 218.8 kN
2 2
Step 2. Required plastic modulus.
M 509.8 x10 2 (kN cm)
W pl 2039 cm3 . Tray 533 x 210 x 92 UB.
f y M1 2
27.5 ( kN / cm ) 1.1
Step 3. Selection of the profile.
The relevant section properties are:
h = 533.1 mm w = 0.92 kN/m It = 76.2 cm4
d = 476.5 mm A = 118 cm2 Iw = 1.6 x 106 cm6
tf = 15.6 mm Iy = 55400 cm4
w = 10.2 mm Iz = 2390 cm4
b = 209.3 mm Wel,y = 2080 cm3
Wpl,y = 2370 cm3
1| Flexural members (2016/17)
209.3 2 6.70 11x0.92 OK
Class of section.
235
0.92 .
15.6 The section is Class 2 at
275 476.5 46.7 83x0.92 OK
10.2
least.
Step 4. Resistant moment. (for class 2 section).
W pl f y 2370 x 275 x103
M pl , Rd 592.5 kN m
Mo 1.1
Check of self-weight of the beam. (w = 0.92 kN/m)
Factored weight: 1.3 x 0.92 = 1.2 kN/m
Additional moment: (1.2 x 72)/8 = 7.35 kN-m.
Total moment: 509.8 + 7.35 = 517 kN-m < 592.5 kN-m OK.
Step 5: Check for shear.
Maximum shear force, VSd = 218.8 + (1.2 x 7)/2 = 223 kN.
Shear resistance of section.
d 476.5
46.7 69 x0.92 63.5 OK . Shear buckling resistance must not be verified.
tw 10.2
V pl , Rd
AV f y 3 1.04x533.1x10.2 275 3 x10 3
816.4 kN 233 kN OK .
Mo 1.1
VSd 233
and 0.27 0.5 Therefore, no reduction of design resistance moment is required.
V pl , Rd 816.4
Step 6: Check for deflection.
5wL4
For uniformly distributed load:
384 EI y
PL3
For concentrated load: 5 14 14 2
and EI y 2.1x10 x55400 x10 1.1634 x10 N mm .
48 EI y
5 x9.4 x 70004 50 x103 x70003
Dead load deflection: LL 5.59 mm.
385x1.1634 x1014 48 x1.1634x1014
5 x18.5 x70004 50 x103 x70003
Imposed load deflection: IL 8.04 mm .
384 x1.1634 x1014 48 x1.1634 x1014
L 7000
Allowable deflection for imposed load 20 mm. 8.04 mm OK .
350 350
Total deflection max 5.59 8.04 13.63 mm .
L 7000
Allowable total deflection 28 mm 13.63 mm OK .
250 250
Step 7: Check for lateral – torsional buckling.
2| Flexural members (2016/17)
LT wWol , y f y c
M b, Rd . 209.3 6.70 10 x0.92 9.2 .
M1 tf 15.6
The section is Class 1 and w 1 .
Determination of Mcr.
Lateral support to the beam is provided at the ends at the third points. Therefore the effective buckling length is
L = span/3 = 7000/3 = 2333 mm.
The critical moment for lateral-torsional buckling is:
2 EI z I w L2GIt
M cr C1 2 . C1 = 1.132 for the worse condition; G = 80 Gpa
L I z 2 EI z
G 80000
and 2 0.039
E x 210000
2
1.132 2 x 2.1x105 x 2390x104 1.6 x1012 0.39 x 23332 x76.2 x104
M cr 2.67 x109 N mm
23332 2390x10 4
2390x10 4
.
2 EW pl , y 2 x 2.1x105 x 2370 x103
LT 42.9
M cr 2.67 x109
42.9
1 93.9 93.9 x0.92 86.8 and LT 0.4942 0.4
86.8
For rolled section curve a is used. Therefore LT 0.9250
0.9250x1x 2370x103 x 275
M b , Rd x10 6 548 kN m 517 kN m
1 .1
Therefore, resistance of the member is adequate in bending.
Step 8.1. Check for web crushing (at the support).
R y , Rd S s S y t w f yw / M 1 ; Where Ss = 75 mm; Sy – is the length over which the applied force is effectively
distributed.
2
1 b f f yf f , Ed
Sy 2t f 1 at the end S y is half .
2 t w f yw f yf
Check if bf < 25 tf ; 209.3 < 25 x 15.6 = 390 OK.
f , Ed 0 at the sup port .
1
75 70.6610.2 x275 x103
Then S y 2 x15.6 209.3 10.2 70.66 mm and R y , Rd
2 1.1
R y , Rd 371.3 kN 223 kN OK
8.2 Check for web crippling.
Crippling resistance:
Ss = 75 mm < 0.2 d = 0.2 x 476.5 = 95.22 mm. OK.
3| Flexural members (2016/17)
tf t S
Ra , Rd 0.5t w2 Ef yw 3 w s / M 1
tw t f d
Ra , Rd
0.5 x10.2 210000x 275 15.6 10.2 310.2 15.6 75 476.5 103
660.6 kN 233
1.1
kN
Interaction at mid-span. Where the member is also subjected to bending moments, the following criteria should be
satisfied.
FSd M Sd
1 ; Substituting the value of Mc,Rd = 592.5 kN-m
Ra , Rd M c , Rd
80 65 517 1.09 1.5 OK .
660.6 592.5
8.3 Check for web buckling (at the support). Ss = 75 mm.
Ss 75
beff 0.5 h 2 S s2 0.5 533.12 752 306.7 mm
2 2
I beff t w3 tw
i
A 12beff hw 12
assuming that l = o.7 d = 0.7 x 476.5 = 333.6 mm.
tw 10.2
Radius of gyration of the web is: i 2.94 mm
12 12
333.6 235 113.5
113.5; 1 93.9 93.9 86.8; and 1.31
2.94 275 86.8
h 533.1
2.55 1.2 and t f 15.6 mm 40 mm
b 208.7
Using buckling curve c for solid section χ = 0.3848.
The buckling resistance of the web is: Rb , Rd A Af y / M 1; A 1; and A beff t w
A 306.7 x10.2 3124 mm.
0.3848 x1x3124 x 275
Rb, Rd x10 3 300.5 kN 223 kN . OK .
1.1
Step 9. Check for flange induced buckling.
4| Flexural members (2016/17)
d E Aw
k
tw f yf A fc
c 209.3 2
6.7 10 ; therefore , the fange is class 1; k 0.3
tf 15.6
d
tw
476.5
10.2
46.7 0.3 210000
275
533.1x10.2
209.3 x15.6
296 ok .
Step 10. Check for transverse force on the web.
In the absence of shear force the web of a member subject to transverse force in the plane of the web shall also
satisfy the following condition:
2 2
x , Ed z , Ed x , Ed z , Ed
1
f yd f yd f yd f yd
x, Ed Is the design value of the local longitudinal stress due to moment and axial force at the point.
z, Ed Is the design value of the stress at the same point due to the transverse force.
fy
f y,d
Mo
x, Ed and z , Ed shall be taken as positive for compression and negative for tension.
The point to be considered is the joint between flange and web.
x, Ed
M
Sd
h 2 t 517 x10
fl
6
533.1 2 15.6
x 234 N / mm 2
Wel h 2980 x103
533.1 2
2
z , Ed
FSd
80 65 x103 134 N / mm2 ; assume S 75 mm
S s t fl t w 75 15.6 x10.2
s
Therefore:
2 2
234 134 234 134
250 250 250 250 0.66 1 OK .
2. Design a simple supported beam of F e 430 steel grade. The span of the beam is 5.00 m. The top flange is
embedded in a reinforced concrete floor providing sufficient restraint against lateral-torsional buckling.
The beam carries a uniformly distributed load of 20 kN/m permanent load and 20 kN/m imposed load.
solution
5| Flexural members (2016/17)
The factored loads are: Imposed load: 1.6 x 20 = 32 kN/m
Permanent load: 1.3 x 20 = 26 kN/m.
6| Flexural members (2016/17)
7| Flexural members (2016/17)
8| Flexural members (2016/17)
EXERCISE
1.The beam shown in Figure-1 below is fully laterally restrained along its length and
has bearing lengths of 50 mm at the unstiffened supports and 75 mm under the
point load. For S275 steel and t < 16 mm. Use 533 x 210 x 92 UKB in S275.
Consider the self-weight of the beam. F 2d, F1d represents factored resultant forces
for concentrated and uniformly distributed loads respectively(fig-1). Design the
beam in S275 steel for the loading shown below. Assume any missed datas.
Loadings:
1.1. Permanent loads:
Uniformly distributed load (including self weight) g1 = 15 kN/m
Concentrated load G2 = 40 kN
1.2. Variable loads:
Uniformly distributed load q1 = 30 kN/m
Concentrated load Q2 = 50 kN
fig-1
9| Flexural members (2016/17)