Professional Documents
Culture Documents
Renewable Energy
journal homepage: www.elsevier.com/locate/renene
Technical note
a r t i c l e i n f o a b s t r a c t
Article history: Photovoltaic (PV) systems are the most promising renewable energy sources in Malaysia because of its
Received 6 July 2013 location being around the equatorial region where sunlight is available throughout the year. However,
Accepted 28 October 2013 the country is warm and surrounded by the South China Sea and Malacca Straits. A large amount of
Available online 20 November 2013
clouds is created and passed over the region. The impacts of the passing clouds on the PV power outputs
and voltage magnitude have to be studied thoroughly. Therefore, an experimental low-voltage network
Keywords:
integrated with a PV system is set up. The experimental results show that the passing clouds result in the
Photovoltaic system
frequent and rapid fluctuations of PV power outputs, hence producing a large amount of flickers to the
Cloud
Flicker
distribution networks. Some of the flickers are actually greater than the statutory limits. To mitigate this
Load controller power quality issue, a dynamic load controller is proposed to be the solution because its components are
cheap. The load controller is made of a number of 200 W power resistors and solid-state relays. A central
controller switches the resistors on and off very rapidly based on the fluctuations of the network voltage.
The experimental results show that the dynamic load controller is able to reduce the flickers effectively
on the distribution networks. The studies and solution presented in this paper are very valuable to
different parties, such as the government, policy makers, utility companies and owners of the PV sys-
tems, in order to ensure an effective growth of the PV systems without compromising the quality of
electricity supply to the customers.
Ó 2013 Elsevier Ltd. All rights reserved.
1. Introduction However, the country is warm and surrounded by the South China
Sea and Malacca Straits. Therefore, a large amount of clouds is
Malaysia is one of the tropical countries in Southeast Asia. It is created and passed over the country. Fig. 2 shows the frequency of
divided into West and East Malaysia by the South China Sea as completely clear sky occurrences at various regions around the
shown in Fig. 1. Malaysia depends highly on fossil fuels for elec- world [7]. Malaysia does not have a single day with a completely
tricity generation. Electricity generation from renewable energy clear sky. As tabulated in Table 1, the average amount of clouds in
sources was about 1% or less [1]. However, extreme reliance on Malaysia is about 77% which is the highest in the world [8,9].
fossil fuels has created much controversy because of its excessive With a large amount of clouds passing over Malaysia, the
GHG emissions [2,3]. Also the reserves of oil and gas are depleting incident solar irradiance is therefore highly scattered and fluctu-
very rapidly [4]. Therefore, the government has promoted the usage ating, hence making the power output of the photovoltaic systems
of renewable energy sources by launching renewable energy pro- to be very intermittent. Highly intermittent power output from PV
grammes, such as Main Building Integrated Photovoltaic Project in systems causes the voltage at the point of connection to be fluc-
2005, new feed-in-tariffs for RE in 2012 and the new forward tuating sharply and frequently, hence generating a large number of
looking RE policy in 2012 [5,6]. voltage fluctuations and flickers to the low-voltage distribution
Photovoltaic (PV) systems are the most promising renewable networks.
energy sources in Malaysia because of its location being around the At present, little attention is placed on the flicker emissions by
equatorial region where sunlight is available over the year. the PV systems because the majority of the countries is free from
cloudy skies at the most of the time. Flickers introduced by wind
turbines have been studied by the authors in [10e13]. There are a
* Corresponding author. Tel.: þ60 126399520.
number of methods used to reduce flickers generated from the
E-mail addresses: yslim@utar.edu.my (Y.S. Lim), tangjh8@1utar.com (J.H. Tang). wind turbines. The most common solution is to use a power
1
Tel.: þ60 126399520. electronic-based device, namely static synchronous compensator
0960-1481/$ e see front matter Ó 2013 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.renene.2013.10.043
62 Y.S. Lim, J.H. Tang / Renewable Energy 64 (2014) 61e70
Fig. 2. World map showing the frequency of completely clear sky occurrence (%).
(STATCOM), integrated with capacitors. STATCOM is installed on a networks because the line reactance is larger than the resistance.
point of concern to supply reactive power actively to the trans- Another method is to control actively the supply of real power from
mission network to reduce the flickers [14]. However, this solution the converter of the wind turbines so that the flickers can be
is effective if the wind turbines are placed on the transmission minimised [10,16]. This approach is effective if the wind turbines
are installed on the distribution networks because the line resis-
Table 1 tance is larger than the reactance.
Average amount of cloud and frequency of clear sky occurrence in several regions. The general technical issues caused by the distributed genera-
tion have also been studied by the researchers in [17e19]. Although
Regions Europe US South South America Malaysia
Africa near near equator some researchers have investigated the impacts of photovoltaic
equator systems on the voltage levels [20e23], they use simulation ap-
Average amount of 53.29 56.44 60.44 62.81 76.86 proaches to carry out the studies. Experimental studies on the
cloud (%) power quality issues caused by the PV systems are not very
Frequency of 22.95 16.87 11.37 13.10 0.71 common.
clear sky The objective of this paper is to present the findings on the
occurrence (%)
flicker emissions by the photovoltaic systems on Malaysia. An
Y.S. Lim, J.H. Tang / Renewable Energy 64 (2014) 61e70 63
Usually, the main sources of voltage fluctuations and flickers on modules are divided into four strings. Each string has the capacity
HV and MV networks are arcing furnaces, welding machines, roll- of 1.84 kW and is detachable from the solar inverter such that the
ing mills, mine winders, large capacitor bank for reactive power capacity of the PV system can be fixed at 1.84, 3.68, 5.52 and
compensation and electric boilers. The main sources of voltage 7.36 kW.
fluctuations and flickers on the low voltage networks are starting of The rating of the solar inverter is 3.0 kW. Two inverters are used
large electrical motors, X-ray, pumps, refrigerators and electric to accommodate the 7.36 kW PV modules. The technical specifi-
cookers [24]. cations of the solar inverter are given in Appendix A. The inverter is
The flickers cause electrical motors to change in their starting a well-recognised solar device that complies with all the technical
torques and power consumption, hence causing the increase in the standards. Therefore, the quality of the device and AC output
temperature and the deterioration of the efficiencies of the ma- voltage are well within the permissible tolerance.
chines. The lifespan of the motors are then shortened. Air condi- The PV modules are mounted on the car park area surrounded
tioners are very common appliances in Malaysia. The motors being by trees and buildings. The nearest building is more than 30 m
used in the air conditioners can fail prematurely. Therefore, the cost away from the PV modules. The building is too far away from the PV
associated with the repair and maintenance of the air conditioners panel and should not shade the PV panel. The trees are the only
may increase substantially. Also rapid changes in voltage supply can possible object to shade the PV panel. The shortest distance from
make the motors to run at the varying speeds with vibration, hence the PV modules to the nearest tree is about 15.8 m. The PV panel is
leading to the poor quality of products in any manufacturing fac- alighted with the tree in a straight line pointing towards the East.
tories [25]. The trees may shade the PV panel early in the morning. The heights
The voltage fluctuations and flickers can cause the light sources, of the PV mounting structure and the tree are 3.3 and 6.6 m
such as incandescent lamps, to vary their luminous of light flux. respectively. The angle made between the PV plane and the solar
Anyone who is affected by light flickering can suffer headaches, radiation just before the PV panel receives the direct sunlight in the
migraines and eye discomfort. In addition, unstable voltage supply morning is calculated to be 12.4 . This inclination angle can happen
causes electronic equipment malfunction, unwanted triggering of approximately at 8 am as determined by using PSA algorithm [27].
uninterruptible power supply (UPS) units to switch to battery mode After 8 am, the PV panel receives direct sunlight throughout the day
and reduce the operational efficiency [26]. without being shaded by any surrounding objects. Therefore, the
measurement of the voltage and current from the PV is set to take
3. Set up of the experimental low-voltage distribution place after 8 am.
network with a photovoltaic system
To study the characteristics of PV power output and voltage 4. Characterisation of the PV power output
magnitude at the point of the PV connection, a low-voltage three-
phase distribution network is set up as shown in Fig. 3. A photo- A case study is carried out to characterise the power output of
voltaic (PV) system and a controllable load bank are connected to the PV system in the experimental network. The two PV systems
the distribution network. Either the utility grid or a 15 kW gener- are connected to phase A of the distribution network. The terminal
ator can be used as the supply source to the distribution network. voltage and the current output of the PV systems are measured by
The 15 kW generator is used to study the flickers purely generated using two national instrument modules, namely NI 9225 voltage
by the photovoltaic system. The technical details of the 15 kW module and NI 9227 current module. Labview is used as a pro-
generator are given in Appendix A. gramming platform to read the readings from the NI modules and
The type of solar cells in the modules is polycrystalline. The store them in a Microsoft excel file. The PV systems are monitored
technical specifications of the PV modules are shown in Appendix over a period of 9 months. The result of a particular day is shown in
A. The PV modules are commercial products that comply with all Fig. 5. The PV power output fluctuates very rapidly, causing the
the technical standards. Therefore, the quality of the PV modules voltage magnitude to change frequently throughout the day. Three
and their power outputs are well trusted. unique characteristics of the PV power outputs are observed as
Each PV module has a maximum capacity of 230 W. There are 32 listed below.
modules being mounted on the car park area to produce the
maximum capacity of 7.36 kW as shown in Fig. 4. These 32 PV 1. Many high PV power outputs happen within short durations.
64 Y.S. Lim, J.H. Tang / Renewable Energy 64 (2014) 61e70
2. Some of the high power outputs drop down suddenly instead of 5 min. This is because Thailand is close to Malaysia, making this
gradually. For example, the high power output of 2.7 kW that region to be vulnerable to much passing clouds.
happens between 12.00 and 12.22 pm drops immediately to
1.2 kW after 12.22 pm.
3. The magnitude of reduction in the PV power output is signifi- 5. Quantification of voltage fluctuations and flickers
cant, about 63% of reduction in the PV power output. produced by the photovoltaic system
Many high PV power outputs happen within short durations To quantify the voltage fluctuation and flickers produced by the
because of the high frequency of the passing clouds over the PV photovoltaic systems, standard formulas are adopted from [11,32].
panels. The sudden reductions in the PV power outputs are caused The method described in this paper to calculate the short-term
by the thick clouds that reduce the total solar irradiation arriving at flickers is an estimation approach as described in IEC 61000-3-3
the solar panels. Some of the thick clouds can reduce the solar [33] as well as the handbook of power quality [34]. It is a simplified
irradiation substantially, hence making a significant reduction in assessment technique for estimating the short-term flicker severity
the PV power output. caused by equipment at the low voltage networks. It is also known
A collection of PV power outputs over a period of 9 months is as the unity flicker severity curve approach. This method makes use
characterised to derive a chart as shown in Fig. 6. This chart shows of the fact that the short-term flicker severity is a linear parameter
the frequency of various PV power outputs and the corresponding to the magnitude of the voltage changes that causes it. It provides
duration. It is noticed that the majority of the high PV power out- good indication of the flicker severity and has been used in the past
puts happen for less than 5 min. as described in [11,32,35]
A comprehensive PV monitoring data from Thailand, China, This method is chosen and incorporated into the control algo-
Hong Kong and the UK are collected from the sources of [28e31]. rithm of the load controller because it is a quick and simple
Fig. 7 shows the characteristics of PV power outputs in Thailand, assessment approach which creates a very little delay in the
China Hong Kong and the UK. It is shown that the majority of the PV execution of the load controller. The approach defined in IEC
power outputs in China, Hong Kong and the UK happen for more 61000-4-15 [6] calculates the short-term flicker accurately. How-
than 30 min which is much longer than that in Malaysia. Further- ever, this approach needs more computation effort than the flicker
more, the PV power outputs reduce gradually. Therefore, the curve method. If it is used in the control algorithm, the execution of
magnitudes of flickers produced by the photovoltaic systems are the programme can slow down the response of the load controller
significantly less than that in Malaysia. It is noticed that the lifespan towards voltage fluctuations substantially.
of some high PV power outputs in Thailand are short, less than The steps of the flicker curve method are described as follows:-
Fig. 5. Fluctuation in PV output and voltage magnitude. Fig. 6. Characteristic of PV output in Kuala Lumpur.
Y.S. Lim, J.H. Tang / Renewable Energy 64 (2014) 61e70 65
Step 1: Determine the magnitude of every voltage changes over The long-term flicker index, PLT, is the average of PST evaluated
the specified minute using the following equation. over 2 h using the cubic law as defined below.
vffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
u 3
u N i
Vmax Vmin u
3 X PST
DV ¼ *100 (1) PLT ¼ t (3)
Vnom N
i¼1
d d
PST ¼ PST0 ¼ (2)
d0 d0
Fig. 8. Unity flicker curve at PST0 ¼ 1.
66 Y.S. Lim, J.H. Tang / Renewable Energy 64 (2014) 61e70
5.1. Case study 1: study flicker emission on the network with the
15 kW generator
Table 2
The values of voltage fluctuation index, short- and long-term flickers.
Fig. 11. Short-term and long-term flicker indices on phase A with respect to various Fig. 13. Short-term and long-term flicker indices on Phase C with respect to various
capacity of PV. capacity of PV.
Hence, the photovoltaic systems can be an unattractive renewable The load controller is implemented in the experimental
energy source in Malaysia. In order to keep the cost of the photo- network as shown in Fig. 3. It consists of 6 units of 200 W power
voltaic systems as low as possible, the mitigation methods must be resistors with solid state relays to switch on and off the power
cheap and yet effective enough to reduce the indices of voltage resistors. The resistance of each resistor is 288 U. A simple control
fluctuation and flickers. algorithm is developed using LabVIEW as a programming platform
It is proposed to use dynamic load controllers to mitigate the in a computer. Fig. 14 shows the flow chart of the control algorithm.
voltage fluctuations and flickers. Dynamic load controllers are a The control algorithm uses the voltage magnitude at the point of
form of demand side management usually used to control the level the common coupling to determine whether the voltage is within
of power consumption on the electrical grid. They can reduce the the required tolerance or not. The nominal value of the low-voltage
peak demand to avoid any power interruptions on the grid or distribution network is 240 V. The tolerance with the upper and
maintain the frequency of standalone power systems due to the lower limits of 243 and 238 V is established in the control algo-
limited capacity of the power generation as described in Refs. [35e rithm. If the network voltage is detected to be outside the toler-
39]. Demand side management is also proved to be an effective ance, the control algorithm can immediately switch on or off the
approach for reducing the distribution losses and hence cutting resistors to reduce the voltage fluctuation or flickers. The algo-
down the electricity bills for customers [40,41]. It is also used to rithm is very simple and therefore the resistors can be switched on
solve voltage rise issues on distribution networks integrated with a and off very rapidly.
large number of distributed generation (DG) [42]. Using the load The cost of a STATCOM with the use of capacitors is at least US$
controllers to mitigate flickers caused by the photovoltaic systems 5000.00 [43]. The cost of the dynamic load controller is estimated
may not be studied thoroughly. to be Ringgit Malaysia (RM) 1000.00 or US$ 314.00 based on the
The proposed load controller is made of a number of resistors and exchange rate of 0.31 USD/RM. It is shown that the cost of the dy-
solid-state relays which are cheap components. The load controller namic load controller is very much lower than that of STATCOM.
makes use of the real power to correct the network voltage on the An experiment is carried to investigate the effectiveness of using
distribution network because the line resistance is bigger than the the load controllers to mitigate flickers. In this experiment, a
reactance. Furthermore, the amount of real power required by the 1.84 kW PV system is connected to the laboratory network with the
load controller is small. Therefore, only a small amount of PV power is 15 kW generator being the supply source. The short-term flickers are
dissipated as heat in the resistors. This amount can be used to heat up then calculated and shown in Fig. 15. It is noticed that all the short-
water for washing purposes. term flicker indices are reduced when the load controllers are used.
The maximum flicker is lower than the statutory limit. The long-
term flicker is also reduced to 0.458. This experiment shows that
the load controller is an effective means of mitigating voltage fluc-
tuation and flickers. The load controller consumes about 10% of the
total electricity generated by the 1.84 kW PV system. Therefore, the
electricity consumed by the resistors is 0.65 kWh per day. The fre-
quency of switching the load controller varies depending on the
intermittency of the PV power outputs. It is noticed that the
switching frequency can vary ranging from 100 to 150 times per day.
7. Conclusion
The PV power output and the voltage magnitude have been coupling enables any severe flickers on one phase to propagate to
measured and characterised to show the frequency and the dura- the other two phases of the network. Therefore, the effects of the
tion of the high power output. The majority of the high PV power flickers can be widely spread out across the distribution network.
outputs happen within short durations. The changes in the power A load controller is proposed to be the mitigation method
outputs happen very rapidly. These are due to the large number of because its components are cheap. It consists of several resistors and
clouds passing over the PV panel. Some of the clouds are very thick, solid state relays. It can switch the resistors on and off very rapidly to
hence reducing the solar irradiation substantially. reduce severity of flickers caused by the photovoltaic system. The
The collection of voltage magnitudes is used to calculate the load controller is an effective approach on the distribution network
short and long-term flickers with respect to various PV capacities. because the line resistance is larger than the reactance. Furthermore,
The experimental results show that the severity of the flickers the amount of real power required by the load controller is small.
grows with the PV capacity. Some of the short-term flickers exceed Therefore, only a small amount of PV power is dissipated as heat.
the statutory limits. In addition, the presence of the mutual
Appendix A. Specifications of the laboratory distribution
network
PV module Specifications
Table A2 DV ¼ Z DI (B1)
Technical specifications of photovoltaic inverter.
Photovoltaic inverter Specifications where Z is the impedance of the transmission line where the PV
Type Single-phase grid-connected solar inverter
system is connected to. The change in PV power output (DP) is
DC input related to DI by the following equation.
Max. input voltage 500 V
MPPT voltage range 150e450 V DP ¼ ðV þ DVÞ DI (B2)
Max. input current 2*12 A
AC output DI is related to DV by the following equation.
Nominal power 3000 W
Nominal voltage 230 V DV
Voltage range 184e264 V DI ¼ (B3)
Z
Max. output current 14 A
Nominal frequency 50/60 Hz Substituting Eq. (B2) into Eq. (B3) gives the following.
Frequency range 49e51 Hz
Temperature range 20 to 50 DV
DP ¼ ðV þ DVÞ (B4)
Z
V is the nominal voltage and is much greater than DV. Therefore,
Table A3
V
Some of the technical specifications of the generator DPz DV (B5)
Z
15 kW generator Specifications
The change of the voltage magnitude depends on two factors
Type Three phase synchronous generator
Voltage (V) 415 based on Eq. (B5). It depends on the change of the PV power output
Rating power (kVA) 17 and the impedance (Z) of the cable where the PV system is con-
Efficiency (%) at 0.8 PF 85.4 nected to. If the impedance of the cable (Z) is high, then the change
Phase resistance 0.94
of the voltage magnitude is reduced.
(ohms) at 20 C
Voltage regulation accuracy 1% in steady state condition
Compliance with Standards IEC 60034-1; CEI 2-3, BS 4999-5000;
VDE 0530; NF 51-100, 111; OVE M-10, References
NEMA MG 1.22
[1] Che Khalib MN. Nuclear energy as an option for Malaysia, Kuala Lumpur;
2012.
[2] Choi TW. PM pledges conditional reduction of GHG emission by 2020 [Online].
Available from: www.thestar.com.my; 18 March 2012 [accessed 01.05.12].
[3] Douglas UE. Malaysia second national communication to the UNFCCC. Putra-
Appendix B. Relationship between the change in PV power jaya; 2012.
output and voltage magnitudes [4] Gan P. An econometric study on long-term energy outlook and the implica-
tions of renewable energy utilisation in Malaysia. Energy Policy Feb 2008:
890e9.
The changes in the PV power output (DP) and the corresponding [5] SEDA. SEDA [Online]. Available from: www.seda.gov.my; 1 Feb 2012 [accessed
fluctuations in voltage magnitude (DV) are determined from the 21.03.12].
[6] Koh SL, Lim YS. Meeting energy demand in a developing economy without
collected measurements and plotted as shown in Fig. B1. damaging the environment e a case study in Sabah Malaysia from technical,
It is shown that DP is linearly proportional to DV with the environmental and economic perspectives. Energy Policy 2010;38:12e26.
gradient of 0.171. This result does not agree with the conventional [7] Hahn Carole J, Warren Stephen G. Climatic atlas of clouds over land and ocean.
University of Washington; August 2010 [Online]. Available from: http://www.
idea of non-linear relationship between the power flow and voltage atmos.washington.edu/CloudMap/ [accessed 23.01.13].
magnitude. To understand exactly how DP is related to DV, the [8] Warren Stephen G, Hahn Carole J. UW atmospheric sciences [Online]. Avail-
correlation between DP and DV has to be determined. It is known able from: http://www.atmos.washington.edu/CloudMap/; June 2012
[accessed 06.06.12].
that the changes in voltage magnitude (DV) and current (DI) are [9] Kushnir Y. The climate system [Online]. Available from: http://eesc.columbia.edu/
related as follows:- courses/ees/climate/lectures/gen_circ/index.html; 2007 [accessed 18.11.12].
[10] Hu W, Chen Z, Wang Y. Flicker mitigation by active power control of variable-
speed wind turbines with full-scale back-to-back power converters. IEEE
Trans Energy Convers Sept 2009:640e9.
[11] Nambiar A, Kiprakis A, Wallace A. Quantification of voltage fluctuations
caused by a wave farm connected to weak, rural electricity networks. In: 14th
international conference on harmonics and quality of power, 2010 26e29
Sept 2010. Bergamo, Italy.
[12] Ammar M. Flicker emission of distributed wind power: a review of impacts,
modeling, grid codes and mitigation techniques. In: 2012 IEEE power and
energy society general meeting, San Diego, CA, USA 2012.
[13] Jakus D, Goic R, Krstulovic J. The impact of wind power plants on slow voltage
variations in distribution networks. Electr Power Syst Res 2011;81:589e98.
[14] Ferdous MJ, Arafat Y, Azam MA. Flicker level mitigation of weak grid con-
nected wind turbine with DFIG by injecting optimum reactive power using
STATCOM, 2013 International Conference on Informatics. Electronics and
Vision 17e18 May 2013:1e5.
[16] Ali H, Alaboudy Kasem, Daoud Ahmed A, Desouky Sobhy S, Salem Ahmed A.
Converter controls and flicker study of PMSG-based grid connected wind
turbines. Ain Shams Eng J March 2013;4(1). ISSN: 2090-4479:75e91. http://
dx.doi.org/10.1016/j.asej.2012.06.002.
[17] Ortega MJ, Hernandez J, Garcia OG. Measurement and assessment of power
quality characteristics for photovoltaic systems: harmonics, flicker, unbalance
and slow voltage variations. Electr Power Syst Res 2013:23e35.
[18] Hernandez JC, Ortega MJ, Vidal PG. Procedure for the technical measurement
Fig. B1. Correlation between DP and DV.
of harmonic, flicker and unbalance emission limits for photovoltaic-
70 Y.S. Lim, J.H. Tang / Renewable Energy 64 (2014) 61e70
distributed generation. In: Proceedings of the 2011 international conference [30] Danny HWL, Gary HWC. Analysis of the operation performance and efficiency
on power engineering, energy and electrical drives, Malaga, Spain 2011. characteristic for photovoltaic system in Hong Kong. Energy Convers Manag
[19] Passey R, Spooner T, MacGill L, Watt M, Syngellakis K. The potential impacts of 2005:1107e18.
grid-connected distributed generation and how to address them: a review of [31] More solar PV goodness [Online]. Available from: http://blog.darrenscott.com/
technical and non-technical factors. Energy Policy 2011;39:6280e90. 2012/05/27/more-solar-pv-goodness/; 2012 [accessed 16.01.13].
[20] Woyte A, Thong VV, Belmans R. Voltage fluctuations on distribution level [32] Sanjay AD, Waghmare LL. Induction motor voltage flicker analysis and its
introduced by photovoltaic systems. IEEE Trans Energy Convers 2006;21(1): mitigation meassures using custom power devices: a case study. Int J Eng Sci
202e9. Technol 2010:7626e40.
[21] Widen J, Wackelgard E, Paatero J, Lund P. Impacts of distributed photovoltaics [33] Roger CD, Mark FM, Surya SH, Wayne B. Electrical power system quality. The
on network voltages: stochastic simulations of three swedish low-voltage McGraw-Hill; 2002.
distribution grids. Electr Power Syst Res 2010;80:1562e71. [34] Woyte A, Bodach M, Belmans R, Nijs J. Power fluctuations in micro-grids
[22] Wong J, Lim YS, Taylor P, Morris S. Optimal utilisation of small scale introduced by photovoltaics: analysis and solutions. In: 2nd European PV-
embedded generators in a developing country - a case study in Malaysia. hybrid and mini-grid conference, Kassel, Germany 2003.
Renew Energy 2011;36:2562e72. [35] Eto J. The past, present, and future of U.S. utility demand side management pro-
[23] Trichakis P, Taylor PC, Lyons P, Hair R. Predicting the technical impacts of high grams. California: Ernrst Orlando Lawrence Berkeley National Laboratory; 1996.
level of small scale embedded generators on low voltage network. IET Renew [36] Strbac G. Demand side management: benefits and challenges. Energy Policy
Power Gener 2008:249e62. 2008;36:4419e26.
[24] Hanzelka Z, Bien A. Copper development association [Online]. Available from: [37] Gellings CW. The smart grid: enabling energy efficiency and demand
http://www.copperinfo.co.uk/power-quality/voltage-disturbances/flicker- response. The Fairmont Press; 2009.
measurement.shtml; October 2005 [accessed 19.11.12]. [38] Sinha A. Role of demand side management for power distribution utility in
[25] Waghmare SA. Induction motor voltage flicker analysis and its mitigation India. In: Power and energy society general meeting 2011.
Measures using custom power devices: a case study. Int J Eng Sci Technol [39] Han J, Piette M. Solutions for summer electric power shortages: demand
2010:7626e40. response and its application in air conditioning and refrigerating system.
[26] International Electrotechnical Commssion. Electromagnetic compatibility (EMC) USA; 2008.
- part 3: limits - section 3: limitation of voltage fluctuations and flicker in low- [40] Hedrick K. Demand side management: why utility-directed load management
voltage supply systems for equipment with rated current <¼ 16 A; 1994. programs make more sense than ever before; 2011 [Online]. [accessed 18.11.12].
[27] Muriel B. Plataforma Solar de Almerya [Online]. Available from: http:// [41] Zhang N, Ochoa LF, Kirschen DS. Investigating the impact of demand side
pvcdrom.pveducation.org/SUNLIGHT/sunPSA.HTM; 2012 [accessed 22.01.13]. management on residential customers. In: 2nd IEEE PES international con-
[28] Chokmaviroja S, Wattanapongb R, Suchartc Y. Performance of a 500 kWP grid ference and exhibition 2011.
connected photovoltaic system at Mae Hong Son Province, Thailand. Renew [42] Lim YS, Taylor P. Innovative application of demand side management to po-
Energy 2006:19e28. wer systems. In: First international conference on industrial and information
[29] Zou X. Performance of a grid-connected BIPV system at Jiangsu Province, systems, Sri Lanka 2006.
China. In: Power and energy engineering conference (APPEEC), 2012 Asia- [43] Static Synchronous Compensator e STATCOM. Source: http://www.alibaba.
Pacific, Shanghai 27e29 March 2012. com/showroom/statcom.html, [accessed 14.10.13].