You are on page 1of 14

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/273451377

Impact of Photovoltaic (PV) Systems on Distribution Networks

Article  in  International Review on Modelling and Simulations (IREMOS) · February 2014

CITATIONS READS

5 2,974

3 authors:

Wadhah Esmaeel Chin Kim Gan


Baaquba Technical Institute Technical University of Malaysia Malacca
2 PUBLICATIONS   5 CITATIONS    133 PUBLICATIONS   1,365 CITATIONS   

SEE PROFILE SEE PROFILE

Mohd Ruddin Ab Ghani


Technical University of Malaysia Malacca
117 PUBLICATIONS   1,263 CITATIONS   

SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Optimum Distributed Generation Allocation Using PSO in order to Reduce Losses and Voltage Improvement View project

renewable energy View project

All content following this page was uploaded by Wadhah Esmaeel on 16 October 2018.

The user has requested enhancement of the downloaded file.


International Review on Modelling and Simulations (I.RE.MO.S.)

Impact of Photovoltaic (PV) Systems on Distribution Networks


Wadhah Esmaeel Ibraheem 1, Chin Kim Gan 2, Mohd Ruddin Ab. Ghani3
Faculty of Electrical Engineering
Universiti Teknikal Malaysia Melaka (UTeM)1, 2,3
Department of Electrical Engineering, University of Diyala, Iraq1

Abstract – Traditionally, power systems are designed to operate in a unidirectional power flow.
In the past few years, solar Photovoltaic (PV) systems have grown rapidly driven by its potential
technical and economic benefits. These include higher network utilization, enhanced reliability
and loss reduction. However, the PV generation depends directly to the sun's radiation. Thus, the
intermittent fluctuations may potentially cause problems to the network operation especially in
high penetration levels. In addition, the voltage fluctuation and power quality issues may limit the
PV penetration level and hence mitigation measures are needed to alleviate the potential
problems. In this paper, the impact of PV on the distribution network in term of voltage
performance and losses has been investigated by using the OpenDss simulator tool. Mitigation
strategy has also been proposed to control the voltage fluctuation that caused by the PV plants.
IEEE 13-bus test system was used to perform the case study.

Keywords: Photovoltaic (PV), distribution network, loss reduction, OpenDss

Nomenclatures I. Introduction
These days the demand for electrical energy is
RES Renewable Energy System increasing to meet the load expansion in the electrical
PV Photovoltaic power system. The rise of the world weather temperature
DG Distributed Generation and the depletion of fossil fuel and the price of the fuel
OPENDSS Open Distribution System Simulator had motivated more researches and development in
COM Component Object Model renewable energy system (RES). This is to reduce the
VBA Visual Basic Applications CO2 emission. Many countries have engaged in
DLL Dynamic Link Library renewable electricity and they have set ambitious target
Yprim Primitive y Matrix for producing power from green sources to meet the
I0 Diode's reverse saturation current expected demand in the coming years.
q Electron charge
A Curve fitting factor Photovoltaic (PV) solar energy is one of the important
K The Boltzmann constant sources of the renewable energy; it has grown in many
T The absolute temperature in Ko countries steadily in the last few years. In Europe, the
Np Number of the parallel connected panels combined target yield a total expected PV power
Ki The temperature coefficient of short circuit generation capacity is 84.4 GW by 2020, where the
 Solar radiation measured by (W/m2) maximum projected PV target is in Germany which is
around 51.8 GW from solar energy [1]. In Malaysia
Tr Reference temperature of the cell according to the 10th Malaysian plan (2011-2015) the PV
Ego The energy of band gab generation in the country will reach 65 MW in 2015 and
IL The line current it is projected to be 190 MW by 2020 [2]. U.S. imports
IPV The PV current of PV products from South Korea are small, but the
Vd Voltage drop country has a stated goal to capture 10% of the global PV
Voc Open circuit voltage market by 2020 [3].
Isc Short circuit current
PV systems generation is not different of other
renewable energy resources (naturally replenished). Solar
energy is comparatively clean by owning a lower effect
on the environment as well as it saves the depletion of
fossil fuel and coal. But the variability in the output of
Wadhah Esmaeel Ibraheem, Chin Kim Gan, Mohd Ruddin Ab. Ghani

the PV panels is a natural behavior of these resources and platforms as a component object model (COM) server
it is a significant issue. The rising and setting of the sun DLL. By the (COM) interface, researchers have the
leads to a regular variation of the PV panel generation ability to run the solution modes from external programs
over the daily time period. In addition, the output can be that can handle COM. Commonly, the DSS can be driven
decreased to 50%-80% when the clouds pass over PV by the MS office tool through VBA, C#, MATLAB and
plants [4]. In this case a backup power will be required to other languages. This is providing wide capability of
cover the output variation to maintain the operation analysis and excellent graphics for exploring results and
voltage under the limit. If the response of the backup solutions in power flow, energy efficiency, harmonics,
elements is too slow to cover the problem, power quality smart grids and other studies.
can adversely affect. Despite these difficulties, solar PV
plants still have the fastest growing of renewable energy The power flow is a most common popular problem
technology in 2012. The power was almost 150% has which can be solved by OpenDss program. The largest
increased of the installed capacity of 2010 bringing the advantage of this simulator is the unique and powerful
total generation about 100 GW [5]. As the rapid capabilities of performing all aspects of (DG), distributed
increasing of the PV integration, it could potentially bring generation, including harmonic analysis. The program is
problems in terms system operation where a reverse designed to execute a basic distribution style power flow.
power can be introduced by higher penetration levels However, OpenDss varies from other radial system
resulted a rise in buses voltages and feeder loses [6]. solvers where it solves the meshed distribution networks
easily. Thus, it can be utilized to perform small to
The injected power by the PV plant modules at the medium sized system's power flow execution. Number of
load side buses will decrease the demand of the local load solution models can be implemented by power flow in the
which leads to a loss reduction and voltage profile program including the standard snapshot mode, daily
improvement [7],[8]. Obviously, this case is true as long mode, duty cycle mode and several modes in the case of
as the real power flows from the substation to the the load is changing with the time. Commonly, 24-hour a
customer side (when the load is less that PV power). If day, a month, a year time period is used for planning
the PV generation is more than the load downstream of purposes. The power flow solution can be divided into
the PV location, the power flow may be reversed towards two types; Iterative Power flow solution and Direct
the substation. Consequently, a voltage rise can be solution. In Iterative power flow the treatment of DGs
expected along the distribution system feeder as a result and Loads model is considering them as an injection
of the reverse power flow. The rise of the voltage at the sources where Direct solution is a direct solution without
end-user limits the amount of the penetration level which iterations through the system admittance matrix.
wanted to be installed in the distribution network. The
natural behavior of the solar source makes the generation In this research OpenDss will be used in modeling of
of the PV plant systems in fluctuated profile. The rapid each of distribution network circuits and PV time series
variation of the PV power introduces a voltage generation to execute the grid connected PV system and
fluctuation along the PV working time and hence its evaluate the PV impact on the distribution grid [9]. The
effects on the voltage regulation in some cases. All these architecture of the program to model the circuit and PV
issues will be evaluated and mitigation control will be plant will be as:
proposed in this paper to mitigate the voltage rise which
caused by PV interconnection and to investigate the
II.1 Distribution Network Model
regulation benefits in term of daily time.
The main object simulation engine of OpenDss has a
II. Open Distribution system Simulator structure consist of executive program that control the
(OpenDss) simulation. The different distribution components are
classified into five objects classes which are:
The Open Distribution System Simulator (OpenDss) is • Power delivery elements.
an inclusive tool for the electrical distribution system • Power conversation elements.
simulation. It supports the frequency domain analysis • Control.
usually performed for distribution analysis and planning. • Meters.
Furthermore, many features in this simulator were • General.
intended for backing distribution generation analysis All those components of the architecture of the
needs, it has been designed as flexible to expand which OpenDss engine as shown in Figure 1. Power delivery
can easily to amend for supporting a several analysis that elements are the components that transfer the electrical
meet the future studies. OpenDss is executed by the power from node to another. They can be either single or
solution engine through a basic text-based interface to multi phased elements including transformers and
assist the researchers in developing scripts and exploring transmission lines. Electrical energy is converted to
solutions. The program can be implemented either stand- another form once achieve the power conversation
alone program or driven by other existing software elements. Load and generators are considered common
Wadhah Esmaeel Ibraheem, Chin Kim Gan, Mohd Ruddin Ab. Ghani

power delivery elements are modeled by introducing their Eff.


impedances or injected currents. The other circuit P
Pmpp
elements are assistance elements that associated with the 1kW/m2 I
main objects to achieve solutions; some of them will be T
AC
used in this research. Irradiance V
DC
P*Eff.
Irradiance, Yearly
Temperature
DSS Executive loadshapes Daily

Pmpp kV Conn. Kvar PF


T
0 100C
Solution
Circuit
V | [Y] | I
Figure 2 Block diagram of the PVsystem model [9]

PDElement PCElement Controls Meters General

Line Load RegControler Monitor LineCode


III. Data Gathering
Transformer Generator CapControl Energy Meter LineGeometry
Capacitor Vsource Relay Sensor Wiredata In any kind of study, data preparation is very important
Reactor Isource Reclose LoadShape
Storage Fuse GrowthShape to assess and evaluate the case studies. In this paper, load
Spectrum
TCCcurve
profile, irradiance, temperatures and distribution test
XfmrCode system have been selected to execute the impact study
and evaluate the results. Following are the types of
Figure 1 OpenDss Architecture of Models [9] selected data and their description.

III.1 Distribution Network


All elements in the architecture of the program and
system bus bars are managed as a creation and To determine the impact of photovoltaic (PV) system
modification of (Yprim) primitive Y matrices. The results on of distribution grids. A 13-bus system test feeder has
collection will be through meter components. The system been used which includes the most of the important
Y matrix is constructed according to feeding the spars electrical components that are commonly used to analyse
matrix solver by Yprim matrices. voltage impact in case of grids-connected PV system.
The single line diagram in Figure 3 illustrates the 13-bus
distribution system which had been suggested by IEEE
II.2 PV Panel Model Power and Energy Society (PES) [10].The test feeder
OpenDss has implemented PV model as a combination contains:
of PV array modeling and the PV inverter into one model
to be utilized for distribution grids impact studies. Figure • Different levels of voltages that are transformed by 2
2 shows the structure of the PV system model which connected transformers (115 kV, 4.16 kV and 0.48
presents the circuit of the PV panel as a generator. The kV).
output generation power, P, will be as a function of: • 9 node-connected loads with 2 capacitors at 2 bus
bars (611,675), the loads are unbalanced.
Irradiance: the net outdoor irradiance applied as a load • 3 voltage regulators are connected to the 3 phases of
with a certain time step resolution. the main sub-transformer.
Temperature: the net weather temperature which applied 650
as a load with a certain time step Voltage
resolution. Regulator

P-T Factor: this factor is applied as a curve to base the


Pmpp at different degree of temperature. 632

Efficiency: this curve is a number of efficiencies of the


646 645 633 634
inverter based on the operating power.
Other functions are needed in the model such as rated
voltage and power, as well as an average Pmpp for the 671

panel at 1kW/m2 irradiance at constant panel temperature


as 25Co.(see Figure 2) 611 684 692 675

652 680

Figure 3 IEEE 13-Node Distribution Network without PV System


Wadhah Esmaeel Ibraheem, Chin Kim Gan, Mohd Ruddin Ab. Ghani

This system contains a comination of three phases and


two phases feeders. Some of bus bars are connected with
one or two phases, thus, the PV installation in this case
study will be only on buses that are supplied by three
phases feeders.

III.2 Irradiance and Temperature Data

In this research PV power generation module requires


a variability of the irradiance time history and load data.
Commonly, utilities records a data for the historical load
time series in term of 1 hour resolution, but this type of
Figure 5 Daily Load Profile
time resolution is too poor to analyze some important
aspects in impact studies on grid-connected. Therefore All the previously mentioned data are used to perform
high resolution in order to 15 minute term has been the impact study analysis by using Open Distribution
collected to drive the time series of power flow and Simulation Software (OpenDss) program in several
voltage profile simulation. The current paper assumes scenarios
that the location of the grids connected PV system is in
Loughborough city in United Kingdom at latitude and
IV. PV Power Generation Model
longitude, 52.8 N and 1.2 W respectively. The global
outdoor irradiance and weather temperature are shown in The electrical specification data sheet for the
the Figure 4. Integrated High-resolution Modeling of photovoltaic panel module in table 1 provides the
Domestic Electricity Demand and Low Voltage electrical characteristics of SolarWorld SW 255 (mono)
Electricity Distribution Networks tool has been used for type. Commonly, the important characteristics are
irradiance modeling in any orientation at any location in maximum generated power (Pmax), voltage and current
the world [11]. 16th of June 2012 is the collected date for at maximum power point (Vmp) and (Imp) respectively,
the historical temperature data at PV installation site [12]. open circuit voltage (Voc) and short circuit current (Isc).
Those data will be used in time series power generation All these parameters are under Standard Test Condition
model of PV system by OpenDss simulator. (STC),1000 W/m2 and 25 Co, but the ecological weather
always changes with time in general real life [14]. Thus,
Data sheets provide other parameters in order to accurate
the calculation; these parameters are represented by
Nominal Operating Cell Temperature (NOCT) with the
temperature coefficients for each (Voc) and (Isc). The
following table represents to the simulation parameters of
the collected PV model under (STC) conditions,
irradiation 1KW/m2, spectrum of 1.5 air mass and cell
temperature equal to 25Co.
Figure 4 Global Outdoor Irradiance and Temperature at Selected Site
TABLE I THE ELECTRICAL CHARACTERISTICS DATA OF SOLARWORLD
SW 255 PV PANEL

III.3 Daily Demand (Load Profiles) Parameter Value


Rated Power 255 W
A typical load profile has been used in this research as
shown in Fig 5. The considered load in the case studies is Voltage at Maximum power (Vmp) 37.8 V
normalized to the maximum load during the daily Current at Maximum power (Imp) 8.66 A
demand. It is worth to mention, generally, the load starts Open circuit voltage (Voc) 31.4 V
to increase during the night. As can be noted from the Short circuit current (Iscr) 8.15 A
figure the The load drops to its minimum demand during
Total number of cells in series, parallel
the time from 8:00 AM to 5:00 PM and starts to increase 60
(NS, Np)
to its peak value at 7:00 PM until midnight. This
behavior can be understood by mentioning that the daily
Mathematically, photovoltaic has been modeled
consumption of the customers is low at noon time
according to equations from (1) to (4). In view of the PV
because most of the people are in their work. On the
cell equivalent circuit in Figure 6, the mathematical
other hand the load becomes high at the night because all
model of output current has formed by equation (1)
adult and children in the homes at that time [13].
[15],[16]:
Wadhah Esmaeel Ibraheem, Chin Kim Gan, Mohd Ruddin Ab. Ghani

  q(V  Rs )   and Figure 8. Power is multiplying VPV with the Iph and
I PV  Np  I ph  Np  I o exp    1 (1) it has been found current and voltage are scaled based on
  AKT   solar irradiation and temperature, where the generated
Where, I0: diode's reverse saturation current. current has recorded 8.6 A at the times with 1kW/m2 of
q: electron charge (1.602×10-19 C). irradiance value and 1.7 A with 0.2kW/m2 of irradiance.
A: curve fitting factor normally greater than 1. The parameters magnitude will be increased according to
K is the Boltzmann constant (1.38×10-23 J/K) and T is connecting parallel and series PV cells to meet the set up
the absolute temperature of the solar cell. requirements.
Np: number of parallel connected panels (in this section
Np is 1). Because of the fixed temperature in this case the power
increases with irradiation rising (the voltage has not
significant change with decreasing on irradiance).
Conversely it the power has inversely proportional with
temperature due to the lessening of the voltage with
temperature rising and fixed irradiation as shown Figure
9. The validation of these results has been investigated
through comparing them with the manufactured I-V
Figure 6 Equivalent circuit of a single solar cell [17]
curves of SolarWorld SW 255 (mono) which provided in
[19]. Those results have been modeled by using
As mentioned before the output voltage is very MATLAB/SIMULINK toolbox based on the equations
small to use, thus the PV array should be assembled as a that has been provided in this section.
collection of series and parallel panels to generate a
usable voltage and current. Therefore, the photovoltaic
model in this research has been used is a string of 255W
in series or parallel connection to get the require power.
Radiation and temperature from the most important and
effective factors in calculation of PV modeling, the
changes consideration of these factors is given by
following equation:



I ph  I scr  K i T  298  
1000
(2)

Where Ki is the temperature coefficient of short circuit


and  is solar radiation measured by (W/m2). Reverse
saturation current and its variation with temperature can
be calculated and modeled by equation (4) and equation
(3) respectively.
Figure 7 I-V characteristics of SolarWorld SW 255 (mono)
photovoltaic cell (25 Co)
I scr
I rs 
expqVoc / N s kAT   1 (3)

3
T   q  E go 1 1 
I o  I rs   exp    (4)
 Tr   Bk Tr T 

Tr is a reference temperature of the cell. Some of


modeling parameters not obtainable in the photovoltaic
manufacture’s datasheets like curve fitting and the energy
of band gab (Ego). These parameters are considered
different from type to another of semi-conductors
materials as mentioned in [18]. The obtained results in
this section are I-V and P-V characteristics of
photovoltaic (PV) panel modeling with different Figure 8 P-V characteristics of SolarWorld SW 255 (mono)
irradiation at constant temperature as shown in Figure 7 photovoltaic cell (25 Co)
Wadhah Esmaeel Ibraheem, Chin Kim Gan, Mohd Ruddin Ab. Ghani

morning compared with the middle of the day. As shown


in the power Fig 10, the PV generation is reduced to the
zero from 6:20 AM until 7:40 AM due to the high density
of clouds that occurred at that time, but PV power has
been generated at maximum at midday from 11 AM until
12.30 AM. After midday until 7 PM thin and thick clouds
had obscured PV panel introduced a generation power
from 25% to 90% at time of heavy and light clouds
respectively. This fluctuation will impact the customer's
voltages in some cases with higher penetration levels as
would be shown later.
The voltage in Figure 11 has the same impact by
irradiation with current and power but with very small
values of volts as proven in section V-I characteristics.
The generating voltage is fluctuating in a range of 1.5
Figure 9 P-V Characteristics of SolarWorld SW 255 (mono) hotovoltaic volts.
cell (1000 kW/m2)
Current Voltage
9 242
As shown in the previous results, The PV power output 8
241
generation is varied with temperature of the panel surface 7
and the change of solar irradiation. For the impact study Current (A) 6 241
purpose, the hourly generation of PV system as a function 5
240
of solar irradiation at different values can be estimated. 4
From the collected data regarding to the irradiance and 3 240
temperature, the OpenDss software has been used to 2
239
model the daily time series PV generation. The explored 1
results showed that the clearing index which varies from 0 239
time to time introduced a fluctuation in global irradiance.

205
109
121
133
145
157
169
181
193

217
229
241
253
265
277
1

73
13
25
37
49
61

85
97
Figure 11 PV Panel Daily Voltage and Current Profiles
Thus the PV current will be affected by that; thus again
Daily Time (5-minutes)
PV power generation will be in oscillation profile.
V. Impact of the PV Plants on Network’s
A three phase of photovoltaic system with 6.12 kW
power and has been tested by DSS with time series Voltage and losses
execution. The obtained results in figures below are PV plant systems have some unique characteristics
based on applying the temperature and irradiance profiles which have to be considered when connecting a high
to the program; they are the daily generating AC penetration of such distributed generators into the
voltages, currents and three phase power at each 5 distribution system. For preferable investigation of the
minutes in the selected day. impacts that are accompanied with connecting the PV
system into the distribution grids; a simulation of IEEE
test feeders has been done by OpenDss simulator. The
13-bus IEEE test systems has been considered with
specific load profile data to evaluate the effect of
photovoltaic system on distribution grids in terms of
losses and voltage issues with penetration level as well.

V.1 Voltage Assessment of Grid-connected PV Systems


This section identifies the improvement of voltage
which has been occurred due to connect solar PV system
in distribution grids. For this purpose a program code has
been developed to execute the power flow study and
record the voltage improvement through different levels
Figure 10 PV Power Generation Profile (10%-50%) of penetration. Penetration level has been
calculated as the percentage of installed power by PV to
The capacity of generating power from the solar PV the total load which is supplied by the system. The solar
system at sunny time is greater than a cloudy time. PV system has been connected to the 13-bus IEEE
Obviously, photovoltaic panels have not electricity distribution network at buses (671, 675 and 680). The
generation at night and less in the evening with early expected results have been obtained and the voltage
Wadhah Esmaeel Ibraheem, Chin Kim Gan, Mohd Ruddin Ab. Ghani

improvement has been investigated as shown in Figure 12


which shows the variation of the 3 phases of buses
voltages along the feeder as PV penetration increasing.
From the graphs below, it can be seen the impact of PV
generation on regulation zone, where PV installation with
high penetration levels has increased voltages the end
point of the feeder. The regulator has been excited by that
to return back to lower settings which are required to
maintain system voltages within limits. It can be noticed
the voltages at regulator bus in three phases are reduced
at lower than base case (without PV) due to increasing
the PV penetration level which mean regulator changed
the tap position to lower settings as shown in Figure ‎5.13.

Figure 13 Tap-changer Position According to Penetration level

The previous results were modeled by considering that


the system loads are a full load and the meet the full
generation of the PV power output. But in the real life,
the improvement of the voltage of the PV system is
during the daytime where starts with working time of the
PV power generation. In this task the same test system
has been executed with daily time series power flow with
5 minute resolution control mode. A random load profile
is shown in Fig 5 has been selected and applied to the
program after normalization. The injected PV generation
has been modeled by the OpenDss program as shown in
Fig 10 . In this system a monitor has been installed beside
(a) Phase A bus bar 671 and the regulator bus to record the voltage at
each 5 minutes at customer end. The execution includes
two scenarios, the first of them is voltage performance of
the customers voltage at bus 671 and on the regulator bus
without PV installation. The second one was with 1800
kW of PV power divided into 3 plants (each one has 600
kWp) at buses (671, 675 and 680). Fig shows the voltage
behavior before and after PV penetration.

(b) Phase B

Figure 14 Voltage Profile of Bus-Bar 671

As shown in the previous figure, generally, the voltage


of the system has a directly proportional to the amount of
PV power and the improvement starts with working of
PV system from 7AM to 6:30 PM. The peak voltage on
(c) Phase C the profile without PV system during that time was 1.02
Figure 12 Three Phase Voltages at 13-bus Feeder with PV pu at the bus 671. The 50% of penetration level has
Wadhah Esmaeel Ibraheem, Chin Kim Gan, Mohd Ruddin Ab. Ghani

increased the voltages to 1.033 pu at bus 671. But the


voltage of the substation is decreased by PV penetration
due to tap setting which had set the baseline of the
substation voltage in the range of 1.0 pu to 1.0625 pu as
shown in Figure 15. The regulator by this range trying to
maintain the voltage work within the acceptable limit of
standards (+5, -5 pu voltage), but in the night in this case
the voltage drops to minimum due to the full load
consumption. It is worth to mention, the negative impact
may occur due to the voltage fluctuation which is caused
by PV system. Voltage behavior acts the response of the
demand profile with PV integration including a local
oscillation at each minute of irradiation. This fact may
effects the system in case of higher penetration on PV Figure 16 Percentage of Losses at Various PV Locations
installations through violating the voltage constrains or
may impacts the tap changer operation by increasing the From that, it can be understood that the place of PV
number of position changes. In this thesis a mitigation of connection which supplies more loads than others will
voltage fluctuation as a control strategy has been introduce more reduction of losses in the system. But it
investigated and will be explored later. should be far from the main source because it will
compensate the demand current that would come from
the main source and would be loosed by line parameters.
Thus, the amount of the current which is compensated by
PV system in case of bus 632 connections, is only the
currents that flow from buses 650 to 632, but in case of
bus 671 installation a large loosed current has been
compensated, thus again a lowest losses had been
recorded by that.
From hour to another throughout the daily time, the
losses change with a variation of the load demand. The
time step load flow by OpenDss simulator has applied on
the 13-bus IEEE test feeder to calculate the hourly losses
that occur based on the local load profile. It has
calculated each individual interval losses in the feeder,
Figure 15 Voltage Profile of Main Substation the time step interval in this case is one hour. In this task,
3 plants of PV systems, each one is rated with 600 kWp.
V.2 Losses Impact on Grid-connected PV Systems Figure 17 shows the hourly demand profile of the loads
that are supplied by 1800 kWp PV system. Solar
The feeder losses in distribution systems with PV generation based on the irradiation at the collected site.
integration have been reduced. In this section, the three
phase power flow has been executed in 13-bus IEEE test
feeder system to show the loss reduction by connecting
1800 kW PV system. The results have shown that the
percentage of loss reduction differs with the changing of
PV system location. The maximum reduction of system
losses has been obtained with this capacity of PV
installation is when the PV connection at bus 671 and
675, where it is decreased until 1.37% from total losses
before PV injection which was equal to 3.21%. Figure
‎5.18 illustrates the percentage of system losses at
different connection buses in 13-bus IEEE system.

Figure 17 The Load Demand and the PV Generation Profile

As it can be seen, a part of demand load will be served


by the PV power from 7AM until 6PM by a range of
(500kW - 1000kW) power consumption. Thus a loss
reduction will be recorded at that time due to decreasing
Wadhah Esmaeel Ibraheem, Chin Kim Gan, Mohd Ruddin Ab. Ghani

of the demand currents that are needed from the main


source. The previous figure illustrates the reverse power
has been occurred by installing this capacity of the PV
power. This power will flow through the system feeders.
In the highest penetration levels, if it will not be
consumed from other loads, it will introduce power losses
in the system.

The provided results in the Figure 18 have shown that


the losses have been reduced during the working time of
PV system. The results have shown that the system was
consuming 1518.7kW/day before PV penetration where a
50% of penetration level has decreased the energy
consumption to 1121.4kW/day. The energy saving in this Figure 19 U-shape Trajectory of The Loses Behavior in IEEE 13-bus
case was 397.3kW/day. When the penetration level System
increased to 70% the losses was still less than the base
case (before PV connection) but the daily energy saving V.3 Penetration Level Evaluation
decreased to 383.5kW/day. That means the reverse power Although solar photovoltaic systems are considered
as shown in Fig 17 has introduced line losses entire the green energy have a wide ranges of positive benefits
system. For this purpose, losses corresponding to the applications, there is a limit in penetration level in case of
penetration level has been prepared and it showed that grid-connected. Maximum penetration level is a
the U-shape trajectory had been obtained, where the maximum solar power allowable to inject into the
behavior of losses falls until minimum at 90% and 100% distribution grids without any acceding in voltage or add
penetration, that because, at that level there is no power extra system equipment. IEEE 1547-2003 recommends
flowing inside the system, power of PV is equal to load that the penetration level want to not violate electrical
power. After 100% the losses starts again to rise due to system voltage (Normal system should be inside range of
the revers power from the bus tied PV. Figure 19 (0.95 pu – 1.05 pu) voltage), and the electrical system
illustrates that the benefit of the PV system connection is equipment must not be overloaded [20]. In this paper, the
until 170% of penetration level, where the losses after sensitivity of the voltage magnitude is the way to
that, will be more than that before PV installation. calculate the maximum allowable penetration level can be
applied on 13-bus IEEE test system. As has been shown,
the generation power of the connecting PV has reversed
to the grid during the daylight. The reverse power is
introduced when the load downstream is less than PV
plant power generation. This power associates in a
voltage rise in the system [21]. This rise of the voltage
will limit the penetration level in the system. The
penetration level is different from system to another, in
some cases the penetration level is more than 100%
without causing any voltage violation [13]. In this case
also the penetration level can be achieved more than
100% without voltage violation. But it can be calculated
by monitoring the system losses. The injected power at
which the losses of the system would be more than the
Figure 18 System Losses with and wthout PV Instalation base case in Figure 18 is considered as a maximum
penetration level. The maximum penetration level in this
system is 90% (3150 kWp as total capacity of three
plants) where at above this value, losses have been
occurred at 12:00 PM as shown in Figure 20 below. This
case has not violated the voltage where it was still under
limit but it will introduce an extra operation cost.
Wadhah Esmaeel Ibraheem, Chin Kim Gan, Mohd Ruddin Ab. Ghani

That means the voltages with PV interconnection


behaves according systems design and topologies. In this
case, the voltage violation will be obtained at higher
penetration level. Thus, the maximum penetration level
can be connected in this system is 3000 kWp which equal
to 86% of total load connected to the grid. The voltage
profile behavior with this capacity of PV power is shown
in Fig 22.

Figure 20 System Losses without and with Maximum Penetration Level


of PV

Voltage rise depend on the voltage regulation in the


system, where the voltage drop is a function of feeder
length [22]. For this purpose, the length of the feeder
633-671 has been increased from 2000 ft to 6000ft. It has
been found the difference between the voltage profile Figure 22 Voltage Profile with Maximum Penetration Level
(see Figure 21 ) with PV connection and voltage profile
without PV in case of 6000ft length is higher than that in VI. Mitigation of Voltage Fluctuation by
case of 2000ft length (see Figure 14). This case has been STATCOM Compensation
evaluated by (5) and (6) [22].
The current research considered the reactive power
(5)
Vd withoutPV  I L. ( R cos( )  X sin( ))
compensation by STATCOM as control approach to
mitigate the voltage fluctuations. Generally, this device
(6) provides a capacitive or reactive power in cases of under
. .
Vd withPV  ( I L  R cos( )  I PV )  I L  X sin( ) or upper voltage limit respectively. But in this research it
has been used to ramp the voltage dips that produced by
where is Vd is voltage drop PV power fluctuation and mitigate the over voltage
IL, IPV are the line and PV currents causes. MATLAB environment has been interfaced with
OpenDss simulator to develop a strategy of voltage
and: control. The methodology of this part is taking a
Difference = VdwithoutPV  VdwithPV reference (mean) voltage between the upper and lower
value in the voltage profile. IEEE 13-bus system has been
According to the equations and Figure 21the base case used as a case study for the voltage mitigation with 5
(without PV) voltage is dropped by increasing the length. minutes daily PV generation data, the load demand data
But when connecting the 1800 kWp of PV penetration, were assumed for the test requirements. This method has
the voltage has been increased with percentage more than been applied to test the system by connecting a 20
before if compared with Fig 14. MVAR of compensation to ramp the voltage profile that
is caused by installing three PV plants with 3000 kW
solar system at bus 671,675 and 680, the mitigation on
voltage violation and fluctuation has been obtained

The installing of reactive power compensators in


distribution systems is according to its exigency in system
and operation economics. This study has used
STATCOM after considering that the main requirement
is to regulate feeder voltage with power fluctuation which
is produced by connected solar systems. The expected
result is the compensator will mitigate the voltage
fluctuation and the number of Tap changing positions
will be reduced as well. The penetration level of this case
will be increased by using STATCOM mitigation. The
Figure 21 Voltage Profile with and without PV in Case of Longer steps of the block diagram in Fig 23 represent the
Feeder
Wadhah Esmaeel Ibraheem, Chin Kim Gan, Mohd Ruddin Ab. Ghani

mitigation approach of voltage fluctuation in this


research.

Start
Network parameter
· Transformers
· Regulators
OpenDss
· Lines
Circuit Model
· Capacitors
· Meters
· Load profile
PV model
PV System
Generation
Installation
Profile
Figure 24 Voltage Profile Before and After Mitigation

STATCOM By this way, the over voltage has been reduced and the
Installation under voltage has been increased as shown in Fig 24. The
voltages limits in this research are according to Wills,
they are -5% and +5% [23]. Introducing by that a profile
Time Series of tap-changer with less tap positions compared with
Power Flow before mitigation. The curried out results of tap-changer
before and after mitigation showed that the numbers of
tap changing before mitigation was 12 times but after
Voltage Profile mitigation it is reduced to 11 times during the day. This
at Customer Bus reduction of the mechanical movements will increase the
Switch ON Switch ON
life time of transformer regulator resulting economic
Inductor Capacitor
benefits in the power system.
Calculate the Vreference Then, according to the analysis above, the STATCOM
Value of Voltage Profile can increase the penetration level of the grid-connected
PV systems. Therefore within STATCOM control can
install extra capacity of the PV panels without violating
Yes
If Voltage < Vreference the system constraints. In this case 200 kW at each plant
has been added to the system. The PV system capacities
No
have become 1200 kW at each plant where the obtained
results showed that the voltage with that amount of PV
Yes generation is still under the limit and also the tap
If Voltage < V limit
changing reduction has been obtained as shown the Fig
25. The tap changer movement also has been reduced
Switch OFF from 14 to 11 tap position per day.
STATCOM

Voltage Profiles Before/After


Mitigation
With Tap positions

End

Figure 23 Flow Chart of STATCOM Compensation Methodology


Figure 25 Voltage Profiles with Mitigation Control and 1200 kW
installation

According to the methodology the results of installing


3000 kW solar PV system at three locations in the IEEE
13-bus test system with a certain load profile indicated to
there are a fluctuation of the voltage at the customers’
buses and out of the limit as shown below.
Wadhah Esmaeel Ibraheem, Chin Kim Gan, Mohd Ruddin Ab. Ghani

VII. Conclusion [10] PES-Power and Energy Society, “IEEE Distribution Test
Feeders,” Winter Power Meeting, 2009. [Online]. Available:
This paper studied the impact of the PV plants http://ewh.ieee.org/soc/pes/dsacom/testfeeders/.
[11] I. Richardson and M. Thomson, “Integrated domestic electricity
installation on the distribution networks in term of demand and PV micro-generation model.” Loughborough, UK,
voltages and feeder losses. The case studies claimed that 2011.
there is a positive and negative impact of the PV [12] Wunderground, “Weather History for East Midlands, United
interconnection, that’s where the interest lies in the Kingdom,” Weather Underground, 2013. [Online]. Available:
http://www.wunderground.com/history/airport/EGNX/2012/6/16
voltage improvement at loads buses and the reduction in /DailyHistory.html?req_city=NA&req_state=NA&req_statenam
the system losses which can save the energy of the main e=NA&theprefset=SHOWMETAR&theprefvalue=1. [Accessed:
source, but nevertheless, there are some concerns that 15-Dec-2013].
accompany this in terms of voltages fluctuation and [13] C. H. Tie and C. K. Gan, “Impact of Grid-Connected Residential
PV Systems on the Malaysia Low Voltage Distribution
overvoltage conditions. The impact of the PV on the grid Network,” 2013 IEEE 7th Int. Power Eng. Optim. Conf., no.
connected depends on the PV size, install location, and June, pp. 670–675, 2013.
system topology. This report proved that the penetration [14] R. Bharti, J. Kuitche, and M. G. TamizhMani, “Nominal
level calculations are very important in installation design Operating Cell Temperature (NOCT): Effects of module size,
loading and solar spectrum,” 2009 34th IEEE Photovolt. Spec.
to determine the maximum allowable PV power can be
Conf., pp. 001657–001662, Jun. 2009.
installed in certain system. This study suggested a control [15] R. M. Pandiarajan, “Development of Power Electronic Circuit-
method to mitigate the voltage fluctuation which may Oriented Model of Photovoltaic Module,” Int. J. Adv. Eng.
effect on the regulation and hence on the regulator. Technol., vol. II, no. Iv, pp. 118–127, 2011.
Voltage mitigation can give the opportunity to increase [16] H. Andrei, T. Ivanovici, E. Diaconu, M. R. Ghita, O. Marin, and
P. C. Andrei, “Analysis and experimental verification of the
the PV penetration level in some cases by damping the sensitivity of PV cell model parameters,” 2012 Int. Conf. Synth.
overvoltage conditions during the PV generation Model. Anal. Simul. Methods Appl. to Circuit Des., pp. 129–
working. 132, Sep. 2012.
[17] K. Ding, X. Bian, and H. Liu, “Matlab-Simulink Based
Modeling to Study the Influence of Nonuniform Insolation
Photovoltaic Array,” 2011 Asia-Pacific Power Energy Eng.
Acknowledgements Conf., no. 1, pp. 1–4, Mar. 2011.
The authors would like to gratefully acknowledge the [18] P. Hsiao and C. Chang, “Accuracy Improvement of Practical PV
Model,” SICE Annu. Conf. 2010, pp. 2725–2730, 2010.
funding support provided by the Ministry of Education [19] SolarWorld, “Sunmodule SW 255 mono,” USA, 2012.
Malaysia under the research grant NO.MTUN [20] R. A. Shayani, S. Member, M. Aurélio, G. De Oliveira, and S.
/2012/UTEM-FKE/7 M00015. Member, “Photovoltaic Generation Penetration Limits in Radial
Distribution Systems,” IEEE Trans. Power Syst., vol. 26, no. 3,
pp. 1625–1631, 2011.
References [21] Y. Liu, J. Bebic, B. Kroposki, J. De Bedout, and W. Ren,
“Distribution System Voltage Performance Analysis for High-
[1] N. M. Pearsall, “PV research and development in Europe — A Penetration PV,” IEEE Energy2030, no. November, pp. 1–8,
view from the Technology Platform,” 2011 37th IEEE 2008.
Photovolt. Spec. Conf., pp. 200–205, Jun. 2011. [22] G. K. A. and Y. Baghzouz, “Impact of High PV Penetration on
[2] A. H. Shamsuddin, “Development of Renewable Energy in Voltage Regulation in Electrical Distribution Systems,” Clean
Malaysia-Strategic Initiatives for Carbon Reduction in the Power Electr. Power (ICCEP), 2011 Int. Conf., pp. 744–748, 2011.
Generation Sector,” Procedia Eng., vol. 49, pp. 384–391, Jan. [23] E. Liu and J. Bebic, “Distribution System Voltage Performance
2012. Analysis for High-Penetration Photovoltaics,” Oak Ridge, TN,
[3] M. D. Platzer, “U . S . Solar Photovoltaic Manufacturing : United States, 2008.
Industry Trends , Global Competition , Federal Support,” United
State, 2012. AUTHORS’ INFORMATION
[4] J. Kleissl, M. Lave, M. Jamaly, and J. Bosch, “Aggregate solar 1,2,3
variability,” 2012 IEEE Power Energy Soc. Gen. Meet., pp. 1–3,
Faculty of Electrical Engineering, Universiti Teknikal
Jul. 2012. Malaysia Melaka, 76100 Durian Tunggal, Melaka,
[5] D. Mcginn, D. Green, R. Hinrichs-rahlwes, S. Sawyer, M. Malaysia
Sander, R. Taylor, I. Giner-reichl, S. Teske, H. Lehmann, and D. 1
Department of Electrical Engineering, Engineering
Hales, “Renewables 2013 Global Status Reprot 2013,” 2013.
Collage, University of Diyala, Baaquba, Iraq
[6] Y. P. Agalgaonkar, S. Member, B. C. Pal, R. A. Jabr, and S.
Member, “Distribution Voltage Control Considering the Impact
of PV Generation on Tap Changers and Autonomous Wadhah Esmaeel Ibraheem received
Regulators,” IEEE Trans. Power Syst., vol. PP, no. 99, pp. 1–11, his master of electrical engineering
2013.
from Universiti Teknikal Malaysia
[7] N. Diabi, R.; Belizidia, “Distributed generation influence on the
electric network voltage level,” Int. Rev. Electr. Eng., vol. 3, no. Melaka (UTeM) in 2014. Prior to this
2, pp. 248–252, 2008. he had graduated his first degree from
[8] S. Porkar, S.; Poure, P.; Abbaspour-Tehrani-fard, A.; Saadate, Department of Electrical Engineering,
“Distributed Generation Planning for Losses, Voltage Profile, University of Diyala in Iraq (2005-
Line Congestion and Total System Cost Improvement,” Int. Rev.
Electr. Eng., vol. 4, no. 3, pp. 434–440, 2009. 2009). His research interests lie predominantly in the area
[9] R. C. Dugan, “The Open Distribution System Simulator ( of renewable sources of energy and the impact of PV
OpenDSS ),” California, 2012. system in distribution grids.
Wadhah Esmaeel Ibraheem, Chin Kim Gan, Mohd Ruddin Ab. Ghani

Email: wii_eng2012@yahoo.com

Chin Kim Gan received his B.Eng


and M.Sc degrees both in electrical
engineering from the Universiti
Teknologi Malaysia (UTM) and PhD
degree from the Imperial College
London, UK. He is currently a Senior
Lecturer at the Universiti Teknikal
Malaysia Melaka (UTeM). His research interests are
distribution network design, integration of renewable
energy and smart grid.
Email: ckgan@utem.edu.my

Mohd Ruddin Ab. Ghani is a


professor and the Rector of the
Universti Teknikal Malaysia Melaka
(UTeM). Before coming to UTeM,
He was professor and the dean of the
Faculty of Electrical Engineering at
Univesiti Teknologi Malaysia
(UTM). Prof. Mohd. Ruddin Ab. Ghani obtained his
Ph.D. in Systems Engineering and Control from the
University of Manchester Institute of Science and
Technology in 1989. His current research interests
include: dynamic economic load dispatch, unit
commitment, distribution automation, optimization of
large scale power systems, system identification, expert
system applications and advanced control techniques to
power systems. He has published over 100 papers and
articles in the related fields. Besides actively involved in
research and publications, he is also a committee member
of various distinguished boards such as: committee
member of Malaysian International Electro-technical
Commission (IEC), Intensification of Research in Priority
Areas (IRPA) and IEEE Malaysian chapter. He is also
member of Advisory Council Member of Malaysian
Armed Forces Academy and a member of Energy
Technology under Economic planning unit.
Email: dpdruddin@utem.edu.my

View publication stats

You might also like