VHP Alarms Shutdown Setpoints S 8382 02 PDF

You might also like

You are on page 1of 2

GE Energy

Gas Engines Control Systems


VHP*
JACKET WATER OUTLET TEMPERATURE: 1
a. Standard Cooling System:
Normal: 180°F (82°C) for continuous rating.
200°F (93°C) for intermittent rating.
Alarm: 10°F (5.5°C) above normal / design temperature.2
Shutdown: 20°F (11°C) above normal / design temperature.2
b. Waukesha Power Systems – Standard:
Alarm: 205°F (96°C)
Shutdown: 215°F (102°C)
Note: Alarm and Shutdown differ because of the 10% overload for 2 hours in 24.
c. Elevated Temperature Solid Water Cooling System (All Applications):
Normal: 210 – 235°F (99 – 113°C) for solid water.
Alarm: 5°F (3°C) above normal / design operating temperature.2, 3
Shutdown: 10°F (5.5°C) above normal / design operating temperature.2, 3
d. Ebullient Cooling System (All Applications):
Normal: 212 – 250°F (100 – 121°C)
Alarm: See Note 4.
Shutdown: See Note 4.
LUBE OIL HEADER TEMPERATURE:
Normal: 180°F (82°C)
Alarm: 195°F (91°C) 2
Shutdown: 205°F (96°C) 2
a. Naturally Aspirated Standby Rating with auxiliary cooling connected to jacket cooling:
Alarm: 200°F (93°C)
Shutdown: 205°F (96°C)
b. Waukesha Code 1107:
Alarm: 200°F (93°C)
Shutdown: 205°F (96°C)
LUBE OIL HEADER PRESSURE:
a. Six and Twelve Cylinder Models:
Normal: 50 – 60 psi (345 – 415 kPa)
Alarm: 35 psi (241 kPa) 2, 5
Shutdown: 30 psi (207 kPa) 2, 5
b. Sixteen Cylinder Models:
Normal: 30 – 50 psi (207 – 345 kPa)
Alarm: 30 psi (207 kPa) 5
Shutdown: 25 psi (172 kPa) 5
LUBE OIL FILTER DIFFERENTIAL PRESSURE:
Normal: 2 – 15 psi (14 – 103 kPa differential)
Alarm: 15 psi (103 kPa differential) 2

Page 5 of 13

EN: 153106
Ref.
Recommended Alarm And Shutdown Setpoints S
DATE: 3/11
8382-2
GE Energy
Gas Engines Control Systems
VHP (CONTINUED)
INTAKE MANIFOLD TEMPERATURE 2
Normal: Up to 10°F (5.5°C) above design intercooler water inlet temperature.
Alarm: 15°F (8.5°C) above design intercooler water inlet temperature.2
Shutdown: 20°F (11°C) above design intercooler water inlet temperature.2
INTAKE MANIFOLD PRESSURE:
Contact Waukesha Sales Engineering.
MAIN BEARING TEMPERATURE:
Shutdown: 250°F (121°C)
Note: Waukesha* Code 6010, Eutectic alloy melting pint is 252°F. Oil pressure switch pressure
setting is 20 Psig. 5
OVERSPEED:
Shutdown: Not to exceed 10% over governed speed. 2
a. Waukesha Power Systems:
Shutdown: 10 – 15% over governed speed, not to exceed 1320 RPM.
Caution: When setting engine overspeed shutdown, do not exceed the lesser of engine or driven equipment’s
speed limits. To avoid equipment damage, consult the driven equipment manufacturer for maximum
overspeed value.
FUEL PRESSURE:
Alarm: The minimum fuel pressure at the regulator (from Tech Data Book).
Shutdown: 85% of the alarm value.
NOTES:
1. For engines equipped with ESM, refer to ECU calibration and limits from the F11 advanced function screen.
2. Alarm and shutdown functionality provided on engines equipped with ESM engines.
3. Waukesha Power Systems Engomatic Control Model 1105, 1105A, or equivalent shutdown system is recommended
when jacket water temperature exceeds 210°F (99°C).
4. Waukesha Power Systems Engomatic Control Model 1106, 1106A, or equivalent shutdown system is recommended
for ebulliently cooled engines.
5. Waukesha Power Systems Control is required to have an 8 second delay after engine start.

Page 6 of 13

EN: 153106
Ref.
Recommended Alarm And Shutdown Setpoints S
DATE: 3/11
8382-2

You might also like