Professional Documents
Culture Documents
Submitted by:
Cereño, Adrianne
Apa-ap, Kimberly
Rebojo, Garyl
Pagaran, Natalie
Dacanay, Rubyen
c. Side View
d. Top View
e. Structural View
V. COOLING LOAD ESTIMATE
a. Sensible and Latent Heat Load
For the Cooling Load Calculation, it is important to set the parameters
of building, wall type, window type, inside and outside temperature.
Level: 1st and Second WALL COMPONENTS
Floor
Wall: 200mm concrete
block
with 15mm EXTERIOR
gypsum Concrete 0.18
(samples shown are just snips from the excel file attached in the Appendices)
TRANSMISSION
A rea ∗ (Outs ide Tem p. − Ins ide Tem
Cooling Load (Wall) = p.) Wall Resistance
SOLAR
(samples shown are just snips from the excel file attached in the Appendices)
Cooling Load (Wall) = Wall Overall Heat Load (Window) = Shading Coefficient *
Heat Transfer * CLTD * Sunlit Area SHGF * CL Factor * Area
For the CLTD, please refer to Stoecker and Jones, Refrigeration and Air Conditioning,
page 82 Table 4-15
For the SHGF, refer to Instantaneous Calculator (see References)
INTERNAL
(samples shown are just snips from the excel file attached in the Appendices)
APPLIANCES USED
For the Heat Gain of each appliances, refer to ASHRAE Handbook 2017, Chapter 18
For the Heat Gain of each appliances, refer to ASHRAE Handbook 2017, Chapter 18
LIGHTING
From the www.archtoolbox.com
PRESSURE LOSS
(samples shown are just snips from the excel file attached in the Appendices)
Equivalent Volume Flow ∆P Duct a, b, Velocit
Length, m Rate, m3/s Diameter mm mm y
,m
Room 1 6
Room 2 9
hma = 70.304
hsupply = 30.76
m= 6.078219
Total AHU Capacity,
Q = 252.9856 kW 1 Ton of refrigeration = 3.517 kW
= 71.93222 ToR
VI. COMMERCIAL COOLING LOAD ESTIMATE FORM
Design Conditions:
Dry-Bulb Wet-Bulb
Temperature (C) Temperature
Outside 30 27.09
Inside 24 17.07
Difference (Use this value to determine applicable factors.) 6 10.02
BTU/HR
ITEM Area FACTOR (Area x
(sq. ft.) (Circle the Factors applicable) Factor)
1. (a) WINDOWS. Gain from sun For glass block, reduce factors by
(Figure for all windows for each 10%: for storm windows or double-
exposure. But use only the hlass, reduce factor by 15% Load for Each
exposure with largest No Inside Outside exposure
load.) Shading Shades Awnings (Area x factor)
For calculating gain from sun though windows under overhanging roofs, see example given in Instruction
DESIGN DRY-BULB TEMPERATURE DIFFERNCE
(as computed at top of form)
10 F 12F 15F 17F 20F 22F 25F 30F 35F
(b) WINDOWS, Heat Gain
(Total of all windows)
Single- glass 13 15 19 22 25 27 30 36 42
Double-glass or glass block 6321.854 7 8 9 10 11 12 13 16 19 56896.68
2. WALLS
No insulation (brick veseer,
frame, stucco, etc.) 8852.339 4 4 5 6 6 7 8 9 10 44261.69
1 in. insulation or 25/32 in.
insulation sheathing 3 3 4 4 5 5 6 7 9
2 in. or more insulation 2 2 2 2 3 3 3 4 4
3. Partitions
(Between Conditioned and un-
conditioned space)
4. Roofs
(a ) pitched or flat with vented
airspace, and:
No insulation 18 18 19 20 21 21 22 24 25
No insulation, with attic fan 9 11 12 14 16 17 19 22 15
2 in. insulation 5 5 5 5 6 6 6 7 7
4 in. insulation 3 3 4 4 4 4 4 5 5
(b) Flat with no air space, and :
No insulation 16145.63 28 29 30 31 33 34 35 38 40 484369
1 in. or 25/32 in. insualtion 14 14 15 16 16 17 18 19 20
1 1/2 in. insulation 8 9 9 9 10 10 11 11 12
3 in insulation 6 6 6 6 7 7 7 8 8
5. Ceiling
(Under unconditioned rooms
6. Floors
(Omit if ever basement, en-
closed crawl space, or slab.)
Over unconditioned rooom 2 2 2 3 3 4 4 5 6
over open crcawl space 3 3 4 5 5 6 7 8 9
7. Outside Air
Total sqft of floor area 15404.22 2 2 2 2 3 3 4 4 5 30808.43
8. PEOPLE
(Use minimum of 5 people) 383 (number of people) x 200 76600
9. SUB-TOTAL 773046.7
10. LATENT HEAT ALLOWANCE 30% of Item 9 231914
11. TOTAL Sum of Item 9 and 10 1004961
Copyright 1957 by Air-Conditioning and Refrigeration Institute
SI (kW)
Latent Heat allowance 67.96727249
Sensible Heat 226.557575
Total 294.5248474
VII. AIR DISTRIBUTION AND DUCTING SYSTEM
A. Equal Friction Method
Parameters:
FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
FOURTH FLOOR
Features
Units are design in accordance
with ARI Standard for coils (ARI 410).
Double wall with 1” & 2”
40kg/m³ CFC-Free PU insulation (HCFC
141b). Isolates insulation exposure to the
air stream.
Wide range of coil offering – 4,
5, 6, 7, 8 rows and 8, 10, 12, 14 FPI for
chilled water. Optimized coil circuiting.
DX Coil (4, 6 rows) and Hot Water Coil
(1, 2 rows) are also available.
All chilled water, DX and Hot
Water coils are factory pressure tested at
400 psig as standard.
Coil tracks enable easy coil removal for complete cleaning and assurance of a dry
unit interior.
Powder painted sloped galvanized steel drain pan with bottom drainage.
Stainless steel marine double drain pan provides positive drainage under pitch and
roll conditions.
Forward curved, Backward curved and Airfoil fan.
oForward curved – sizes 160 to 1000mm diameter.
oBackward curved / Airfoil blade – sizes 225 to 1000mm diameter.
Low leak construction with hex socket compression, type latch and nitrile gasket on
mating panel parameter.
Factory installed unit base of 100mm height, constructed of 14 gauge galvanized steel.
b. Ducting Design
XII. RECOMMENDATION
For future design and re-installment, it is recommended that duct sizes must be
adjusted to a much larger cross-sectional area. This is because there are some
duct sections where air velocity is very high which can cause noise that can
affect the comfort of the occupants. It is also highly recommended that the VAV box
will be transferred to a more remote area in order to avoid disturbances from the noise
it will generate.